55
Telecommunications Structured Cabling System Technical Specification INTRODUCTION PURPOSE The intent of this document is to provide a standard specification that will be used for all TE Connectivity, “TE”, and facilities requiring cabling installations. This document provides the minimum performance criteria for the components and sub-systems comprising a complete cabling system that shall accommodate TE’s requirements in excess of ten years. Product specifications, general design considerations, and installation guidelines are provided in this written document. Quantities of telecommunications outlets, typical installation details, cable routing and outlet types for a specific TE facility will be provided as an attachment to this document. If the bid documents are in conflict, the written specification shall take precedence. The successful vendor shall meet or exceed all requirements for the cabling system described in this document. TE’s Cable Infrastructure Project requires a TE Connectivity Systems structured cabling system. The Category portion of the cabling system shall comply with the requirements of the latest revision of the TIA/EIA standards. The cabling system shall be backed by a TE 25-Year Performance Warranty. The contractor is required to furnish all labor, supervision, tooling, miscellaneous mounting hardware and consumables for each cabling system installed. The contractor shall maintain current status with all training requirements, for the duration of the Cable Infrastructure Project. The Contractor shall staff each installation crew with the appropriate number of trained personnel, in accordance with the warranty contract agreement, to support the 25-Year Performance Warranty requirements. After installation, the Contractor shall submit all documentation to support the warranty in accordance with the manufacturer’s warranty requirements, and to apply for said warranty on behalf of TE. The warranty will cover the components and labor associated with the repair/replacement of any failed link, within the warranty period, which is a valid warranty claim. SCOPE This document defines the cabling system and subsystem components to include cable, termination hardware, supporting hardware, and miscellany that Customer will furnish, unless otherwise specified in project documents, to install a complete telecommunications system supporting voice and data operations. The intent of this document is to provide all pertinent information to allow the vendor to bid the labor, supervision, tooling, and miscellaneous mounting hardware and consumables to install a complete system. However, it is the responsibility of the vendor to propose any and all items required for a complete system if not identified in the BOM attached to this specification.

Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

  • Upload
    haxuyen

  • View
    242

  • Download
    4

Embed Size (px)

Citation preview

Page 1: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Telecommunications Structured Cabling System Technical Specification

INTRODUCTION

PURPOSE

The intent of this document is to provide a standard specification that will be used for all TE Connectivity, “TE”, and facilities requiring cabling installations. This document provides the minimum performance criteria for the components and sub-systems comprising a complete cabling system that shall accommodate TE’s requirements in excess of ten years. Product specifications, general design considerations, and installation guidelines are provided in this written document. Quantities of telecommunications outlets, typical installation details, cable routing and outlet types for a specific TE facility will be provided as an attachment to this document. If the bid documents are in conflict, the written specification shall take precedence. The successful vendor shall meet or exceed all requirements for the cabling system described in this document. TE’s Cable Infrastructure Project requires a TE Connectivity Systems structured cabling system. The Category portion of the cabling system shall comply with the requirements of the latest revision of the TIA/EIA standards. The cabling system shall be backed by a TE 25-Year Performance Warranty. The contractor is required to furnish all labor, supervision, tooling, miscellaneous mounting hardware and consumables for each cabling system installed. The contractor shall maintain current status with all training requirements, for the duration of the Cable Infrastructure Project. The Contractor shall staff each installation crew with the appropriate number of trained personnel, in accordance with the warranty contract agreement, to support the 25-Year Performance Warranty requirements. After installation, the Contractor shall submit all documentation to support the warranty in accordance with the manufacturer’s warranty requirements, and to apply for said warranty on behalf of TE. The warranty will cover the components and labor associated with the repair/replacement of any failed link, within the warranty period, which is a valid warranty claim.

SCOPE

This document defines the cabling system and subsystem components to include cable, termination hardware, supporting hardware, and miscellany that Customer will furnish, unless otherwise specified in project documents, to install a complete telecommunications system supporting voice and data operations. The intent of this document is to provide all pertinent information to allow the vendor to bid the labor, supervision, tooling, and miscellaneous mounting hardware and consumables to install a complete system. However, it is the responsibility of the vendor to propose any and all items required for a complete system if not identified in the BOM attached to this specification.

Page 2: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

APPLICABLE DOCUMENTS:

The cabling system described in this specification is derived in part from the recommendations made in accordance with NFPA 70, state codes, and local codes. The lists of documents below are incorporated by reference: Each site will need to use the appropriate standard for the country they reside as this document covers North America directly. 1) This Technical Specification and Associated Drawings 2) Cat 6 TE MasterFormat 01 23 14 3) ANSI/TIA-568-C.0, Generic Telecommunications Cabling for Customer Premises, and its published

addenda. 4) ANSI/TIA-568-C.1, Commercial Building Telecommunications Cabling Standard, and its published

addenda. 5) ANSI/TIA-568-C.2, Copper Cabling Components Standard, and its published addenda. 6) ANSI/TIA-568-C.3, Optical Fiber Cabling Components Standard, and its published addenda. 7) ANSI/TIA/EIA-569-B, Commercial Building Standard for Telecommunications Pathways and Spaces,

and its published addenda 8) ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of

Commercial Buildings, and its published addenda 9) ANSI/J-STD-607-B, Commercial Building Grounding (Earthing) and Bonding Requirements for

Telecommunications, and its published addenda. 10) ANSI/TIA-942, Telecommunications Infrastructure Standard for Data Centers, and its published

addenda. 11) TE Connectivity Undercarpet Cabling Planning and Installation Manual 409-5566 12) TIA-1179, Healthcare Facility Telecommunications Infrastructure Standard 13) National Fire Protection Agency (NFPA) - 70, National Electrical Code (NEC) –Latest Revision 14) TE Connectivity Design and Installation Contractor Agreement (current) If a conflict exists between applicable documents, then the order in the list above shall dictate the order of precedence in resolving conflicts. This order of precedence shall be maintained unless a lesser order document has been adopted as code by a local, state or federal entity, and is therefore enforceable as law by a local, state, or federal inspection agency. If this document and any of the documents listed above are in conflict, then the more stringent requirement shall apply. All documents listed are believed to be the most current releases of the documents; the vendor is responsible to determine and adhere to the most recent release when developing the proposal for installation.

Page 3: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

TABLE OF CONTENTS 1 Structured Cabling

2 Communications Cabinets, Racks, Frames and Enclosures

3 Communications Termination Blocks and Patch Panels

4 Communications Optical Fiber Backbone Cabling

5 Communications Copper Horizontal Cabling

6 Communications Faceplates and Connectors

7 Communications Patch Cords, Station Cords, and Cross Connect Wire

8 Fire Stop

9 Grounding & Bonding

10 Documentation

11 Warranty and Services

12 Final Cabling System Acceptance

Page 4: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

SECTION 1

Structured Cabling

PART 1 GENERAL

1.00 SUMMARY

A. Communications Structured Cabling System

1. Cable Infrastructure Project requires a TE Connectivity structured cabling system. The

cabling system shall be backed by a TE Connectivity 25-year system warranty. The system warranty shall be facilitated by the contractor and be established between the customer and the cabling system manufacturer.

2. Deploy one data circuit(s) to each user outlet as a standard configuration. Data circuit(s) shall

consist of enhanced category 6 U/UTP plenum cable, patch panels, faceplates, and patch cords. The end-to-end data circuit beginning at the work area equipment shall include a work area patch cord, faceplate with jacks, horizontal cable, rack mount patch panel, and a patch cord connecting the equipment in the telecommunication room (TR).

3. Deploy one voice circuit(s) to each user outlet as a standard configuration. Voice circuit(s)

shall consist of enhanced category 6 U/UTP plenum cable(s), patch panels, faceplates, and patch cords as a standard configuration. End-to-end voice circuit beginning at the work area equipment shall include a work area patch cord, faceplate with jacks, horizontal cable, rack-mounted patch panels, and patch cords to connect to the backbone riser frames or VoIP switches within each Telecommunication Room (TR).

4. Deploy optical fiber data circuits in the backbone consisting of multi-fiber trunk cables, fiber

enclosures, and patch cords as a standard configuration. End-to-end data circuit beginning at the TR shall include a patch cord, fiber enclosure, multi-fiber trunk cable, another fiber enclosure, and another patch cord connecting the equipment in the Main Cross-connect (MC). Backbone circuits shall contain OM3 50/125 and/or single-mode fiber trunk cables and patch cords.

B. Contractor Requirements

1. Furnish all labor, supervision, tooling, miscellaneous mounting hardware and consumables for

each cabling system installed. Maintain current status with the warranting manufacturer, including all training requirements, for the duration of the cable infrastructure project. Staff each installation crew with the appropriate number of trained personnel, in accordance with the manufacturer/warranty contract agreement to support the 25-year system warranty requirements. After installation, submit all documentation to support the warranty in accordance with the manufacturer’s warranty requirements, including test results, and to apply for said warranty on behalf of the customer. The system warranty will cover the components

Page 5: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

and labor associated with the repair/replacement of any failed link as a result of a defective product when a valid warranty claim is submitted within the warranty period.

2. Maintain the customer’s facility in a neat and orderly manner during the installation of the

communications cabling system. The customer’s facilities shall be maintained in broom clean condition at the completion of work each day. At the completion of work in each area, perform a final cleaning of debris prior to moving the installation crew to the next work area.

1.01 DELIVERY, STORAGE, AND HANDLING

A. Deliver materials to site in manufacturer’s original, unopened, protective containers and

packaging, with labels clearly identifying product name and manufacturer.

1. Store materials in secure, clean, and dry area indoors in accordance with manufacturer’s instructions.

2. Protect materials and finish from damage and moisture during handling and installation. 1.02 WARRANTY GUIDELINES

A. Manufacturer Warranty 1. Facilitate a 25-year system performance warranty between the manufacturer and the owner.

An extended component warranty shall be provided which warrants functionality of all cabling and connectivity components used in the system for 25 years from the date of acceptance. The performance warranty shall warrant the installed copper and optical fiber portions of the cabling system. Copper and fiber optic drops shall be warranted to the link performance as defined in the ANSI/TIA-568-C standards.

2. Upon completion of the project, the customer’s technical representative will perform a final

inspection of the installed cabling system with the contractor’s project foreman. The final inspection will be performed to validate that all horizontal and backbone cables were installed as defined in the drawing package, and that the installation meets the aesthetic expectations of the customer.

3. Upon receipt of the test documentation, the customer reserves the right to perform spot testing

of a representative sample of the cabling system to validate test results provided in the test document. Customer testing will use the same method employed by the contractor, and minor variations will be allowed to account for differences in test equipment and test variability. If significant discrepancies are found, the contractor will be notified for resolution.

4. During the three week period between final inspection and delivery of the test and as-built

documentation, the customer will activate the cabling system. The customer will validate operation of the cabling system during this period.

Page 6: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

5. Completion of the installation, in-progress and final inspections, receipt of the test, receipt of

the as-built documentation, and successful performance of the system for a two week period will constitute acceptance of the system.

B. Special Warranty 1. Warrant the cabling system against defects in workmanship for a period of one year from the

date of system acceptance. The warranty shall cover all labor and materials necessary to correct a failed portion of the system and to demonstrate performance within the original installation specifications after repairs are accomplished. This warranty shall be provided at no additional cost to the owner.

PART 2 EXECUTION

2.00 INSTALLERS

A. Maintain current status with the warranting manufacturer, including all training requirements, for

the duration of the cable infrastructure project. Staff each installation crew with the appropriate number of trained personnel in accordance with their manufacturer/warranty contract agreement to support the 25-year system warranty requirements.

2.01 INSTALLATION A. Install all systems in accordance with manufacturer’s printed instructions.

1. Install wall plate units plumb, level, square, and free from warp or twist while maintaining

dimensional tolerance and alignment with surrounding construction [adjacent surfaces].

B. Special Techniques 1. Termination of RJ45 modular jacks shall be completed using a hand tool which employs a

fully repeatable, self-centering, non-impact mechanical termination process. This process shall simultaneously cut and terminate all 8 conductors to the modular jack.

2.02 FIELD QUALITY CONTROL A. Copper and fiber optic systems shall be installed as defined in the ANSI/TIA-568-C standards.

1. Copper and fiber optic systems shall be field tested as defined in the ANSI/TIA-568-C

standards.

Page 7: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

SECTION 2

Communications Cabinets, Racks, Frames and Enclosures

PART 1 GENERAL

1.00 SUMMARY

A. Communications Cabinets, Racks, Frames, and Enclosures

1. The telecommunication rooms shall house racks, voice termination fields, and required cable

routing hardware. Racks shall be placed in a manner that will allow a minimum of 3 feet of clearance from the front and rear mounting surfaces and on one side. If one mounting rail of the rack is placed against a wall, the mounting rail shall be no closer than 6” to the wall to allow room for vertical management. Where there is more than one rack, the racks shall be ganged with vertical management hardware to provide inter-bay management. Ganged rack frames will be placed in a manner that will allow a minimum of 3 feet of clearance from the front and rear mounting surfaces and on one side of the ganged assembly.

PART 2 PRODUCT

2.00 MANUFACTURED COMPONENTS

A. Product Options

1. Horizontal Cable Management Panels

a. Horizontal cable management panels shall be [1U, 2U, or 3U] [single or double] sided, [5.5” or 8”] deep.

b. Management fingers shall be black UL 94V-0 polycarbonate. c. Management front and rear covers shall be 5052-H32 2.29 mm [0.09 in] aluminum with a

flat black polyester powder coating finish (1F59126). d. Management spacers and uprights shall be 6063-T6 Aluminum with a flat black

polyester powder coating finish (1F59126) e. Horizontal Management Panels shall be TE Connectivity product part number(s) [see

Table [1].]

Page 8: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Description Part Number Horizontal 1U management panel, single sided, 5.5” deep 1933530-1 Horizontal 1U management panel, double sided, 5.5” deep front and rear 1933531-1

Horizontal 2U management panel, single sided, 5.5” deep 1933532-1 Horizontal 2U management panel, double sided, 5.5” deep front and rear 1933533-1

Horizontal 3U management panel, single sided, 5.5” deep 1933561-1 Horizontal 3U management panel, double sided, 5.5” deep front and rear 1933562-1

Horizontal 1U management panel, single sided, 8” deep 1933564-1 Horizontal 1U management panel, double sided, 8” deep front and rear 1933565-1

Horizontal 2U management panel, single sided, 8” deep 1933566-1 Horizontal 2U management panel, double sided, 8” deep front and rear 1933567-1

Horizontal 3U management panel, single sided, 8” deep 1933568-1 Horizontal 3U management panel, double sided, 8” deep front and rear 1933569-1

TABLE [1]

Horizontal Cable Management Part Numbers

2. Vertical Cable Management

a. Vertical cable managers shall be 84” high, double sided, [6”, 10”, or 12”] wide with [8.5” deep standard fingers] front side and [8.5” deep standard fingers or 8.5” open fingers] rear side.

b. Management fingers shall be black UL 94V-0 polycarbonate. c. Management front and rear covers shall be 5052-H32 2.29 mm [0.09 in] aluminum with a

flat black polyester powder coating finish (1F59126). d. Management spacers and uprights shall be 6063-T6 Aluminum with a flat black polyester

powder coating finish (1F59126). e. Vertical cable managers shall be TE Connectivity product part number(s) [see Table 1].

Page 9: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Description Part Number

Vertical cable managers, 84”, double sided, 6” W, 8.5” deep front and rear, Standard fingers front and rear

1933534-1

Vertical cable managers, 84”, double sided, 10” W, 8.5” deep front and rear, Standard fingers front and rear

1933535-1

Vertical cable managers, 84”, double sided, 12” W, 8.5” deep front and rear, Standard fingers front and rear

1933536-1

Vertical cable managers, 84”, double sided, 12” W, 11” deep front and rear, Extended fingers front and rear

1933539-1

Vertical cable managers, 84”, double sided, 6” W, 8.5” deep front and rear, Standard fingers front, Open fingers rear

1933540-1

Vertical cable managers, 84”, double sided, 10” W, 8.5” deep front and rear, Standard fingers front, Open fingers rear

1933541-1

Vertical cable managers, 84”, double sided, 12” W, 8.5” deep front and rear, Standard fingers front, Open fingers rear

1933542-1

TABLE [1] Vertical Cable Management Part Numbers

3. Equipment Racks

a. Equipment racks shall be 19” [2 or 4] -post style. Racks shall be 84” high [with 3” or 6” deep channels].

b. Two post racks shall have double sided EIA universal 3” channel depth rails with 0.625

in, 0.625 in, 0.5 inch mounting spaces, #12-24 pre-tapped mounting holes, and stamped RMU (rack mount unit) markings. Two post racks shall be 6061-T6 aluminum alloy, have a load rating of 1200 lbs [544 kg] (when evenly distributed across rack height), and conform to EIA-310-D.

c. Two post rack shall have 6” deep vertical cable duct channel rails for increased cable

capacity and D-rings for out-of-the-box cable management. Two post racks shall have double sided rails with 0.625, 0.625, 0.5 inch mounting spaces, and #12-24 pre-tapped mounting holes. Two post racks shall feature large side cable pass-thru holes for rack-to-rack cabling, adjustable waterfalls on top cable management trays, and top angles with

Page 10: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

pre-drilled mounting holes for runway attachment. Two post racks shall be made from 6061-T6 aluminum alloy and be assembled for either 19 inch or 23 inch equipment.

d. Four post rack shall have double sided EIA universal 3” channel depth rails with nearly

360° of access and be completely open to allow excess heat from equipment to quickly dissipate. Four post rack rails shall have 0.625, 0.625, 0.5 inch mounting spaces, #12-24 pre-tapped mounting holes, and RMU (rack mount unit) markings. Rack depth shall be adjustable in 1 inch increments from 30 to 36 inches (overall depth). Four post racks shall be made from 6061-T6 aluminum alloy, have a flat black powder coating, and have a load rating of 2000 lbs [907 kg] (evenly distributed across rack height). Four post racks shall conform to EIA-310-E.

e. Equipment racks shall be TE Connectivity product part number(s) [see Table 1].

Description Part Number 2-Post 19” Equipment Rack, 84” High, 3” Deep Channels, 45U 1933559-1 4-Post 19” Equipment Rack, 84” High, 3” Deep Channels, 45U 1933570-1

2-Post 19” Equipment Rack, 84” High, 6” Deep Channels with D-ring vertical management, 45U 1933560-1

TABLE [1]

EQUIPMENT RACK PART NUMBERS

B. Finishes

1. Cable management and equipment racks shall be black in color.

Page 11: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

SECTION 3

Communications Termination Blocks and Patch Panels

PART 1 GENERAL

1.00 SUMMARY

A. Communications Termination Blocks and Patch Panels

1. Termination block fields shall be mounted on 4’ x 8’ x .75” virgin fire retardant plywood,

unless otherwise noted in drawings, and shall be on the opposite side of the room from the room entrance. Backbone termination fields shall be mounted to the left of the horizontal voice fields. Conduits with 4” minimum diameter shall be used in all closets. Conduits for data backbone shall be located adjacent to the racks and conduits for voice shall be located adjacent to the voice termination fields. Provide inner duct for all backbone fiber runs. Provide required ladder and wall-mount management rings to properly support and dress cables from conduits to racks and frames.

2. Patch panels and fiber enclosures shall be shall be contained in 19” x 7’ rack(s). All

equipment racks shall be augmented with horizontal and vertical cable management hardware, both front and rear, to properly dress horizontal cables and patch cords.

B. Data Center Patch Panels and Fiber Enclosures 1. Patch panels and fiber enclosures shall be mounted in floor standing equipment racks or

cabinets. Rows of racks/cabinets shall be arranged with the fronts facing each other to provide alternating hot and cold aisles. Cold aisles shall be in the front of the racks/cabinets, and hot aisles shall be in the rear of the racks/cabinets. Communication cabling shall be installed in the hot aisle. Blank panels should be installed in unused rack/cabinet spaces to assist the function of the hot and cold aisles.

Page 12: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

PART 2 PRODUCTS

2.00 OWNER FURNISHED

A. Product Options

1. Category 6 Patch Panels for Voice and Data Circuits

a. Horizontal termination for voice and data circuits shall consist of category 6 [angled] patch panels, which shall be [1U, 2U, or 4U] high and provide [24, 48, or 96] modular jack ports wired to [T568A or T568B]. Patch panels shall be configured with individually replaceable jacks. Modular jacks shall be compatible with TE Connectivity SL series modular jack termination tool part number 1725150-1.

b. The front of each 6-port module shall be capable of accepting 9mm to 12mm labels. Each

port shall be capable of accepting an icon to indicate its function. Patch panels shall terminate the building cabling on 110-style insulation displacement connectors. Patch panels shall meet the ANSI/TIA-568-C.2 requirements for category 6 performance.

c. Patch panels shall be TE Connectivity product part number(s) [1375014-2, 1375015-2, 1375016-2, 1499600-2, or 1499601-2 (see Table 1)].

TABLE [1] PATCH PANEL PART NUMBERS

Description Port Count

Rack Mount Units Part

Numbers

Category 6 SL Series Patch Panel 24 1U Jacks not loaded 1375014-2

Category 6 SL Series Patch Panel 48 2U Jacks not loaded 1375015-2

Category 6 SL Series Patch Panel 96 4U Jacks not loaded 1375016-2

Angled, Category 6 SL Series Patch Panel 24 1U Jacks not

loaded 1499600-2

Angled, Category 6 SL Series Patch Panel 48 2U Jacks not

loaded 1499601-2

Angled Patch Patch

Page 13: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

d. Category 6 patch panels shall meet the technical details and performance characteristics listed in Tables [2 and 3].

TABLE [2]

CAT 6 PATCH PANEL TECHNICAL DETAILS

TABLE [3]

CAT 6 PATCH PANEL PERFORMANCE CHARACTERISTICS

Worst-Case Performance Characteristics (meet or exceed ANSI/TIA-568-C.2 and ISO/IEC Category 6/Class E requirements)

Frequency MHz

Insertion Loss dB

Return Loss dB

NEXT dB

FEXT dB

Category 6 Standard Max Category 6

Standard Min Category 6 Standard Min Category 6

Standard Min

1 0.10 0.02 30 52.4 75.0 84.8 75.0 83.7 4 0.10 0.02 30 53.7 75.0 80.3 71.1 74.8 8 0.10 0.02 30 55.3 75.0 77.4 65.0 69.4 10 0.10 0.03 30 56.1 74.0 76.4 63.1 67.5 16 0.10 0.03 30 57.6 69.9 72.0 59.0 62.9 20 0.10 0.04 30 59.3 68.0 71.9 57.1 61.7 25 0.10 0.04 30 59.4 66.0 69.1 55.1 59.8

31.25 0.11 0.05 30 56.8 64.1 67.7 53.2 58.2 62.5 0.16 0.06 28 42.3 58.1 61.5 47.2 52.6 100 0.20 0.06 24 33.2 54.0 57.7 43.1 48.7 200 0.28 0.06 18 21.2 48.0 52.5 37.1 42.2 250 0.32 0.10 16 17.4 46.0 47.9 35.1 40.1

Technical Information Materials

Connector Housing Interface (6-Pack Module) – Polyester molding compound, black Panel – Steel, black powder coat

Modular Jacks – For modular jack materials, see cut sheet for 1375055-X Screws – 12-24 x 0.5in [12.7mm], black

10-32 x 0.5in [12.7mm], carbon steel, cross recessed Approvals

UL Listed – File Number: E81956

Page 14: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

2. Category 6 Termination Blocks

a. Termination block performance shall meet or exceed ANSI/TIA-568-C.2 Category 6 requirements.

b. Termination blocks shall feature disconnect contacts which allow for patch-by-exception

functionality.

c. Test port shall allow for testing capability without removal of any wires. d. Termination block shall support a minimum of 200 re-terminations while maintaining a

contact resistance of less than one (1) milliohm. e. IDC contacts shall be silver-plated and support the conductor at a 45-degree angle for

greater mechanical strength. f. IDC shall be capable of terminating 22-26 AWG solid or stranded conductors. g. Termination block shall be UL certified and verified.

h. Category 6 termination blocks shall be TE Connectivity product part number(s) [see Table

4].

Rack Mount Termination

Page 15: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Description Part Number 300-Pair Category 6 12-way Kit, Consists of (1) wall mount frame, (12) 25-pair HighBand Category 6 modules with rear cable management, and (12) label holders 6450 1 101-10

300-Pair Category 6 Module Kit, Consists of (12) 25-pair HighBand Category 6 modules, (12) label holders and (12) rear cable managers 6468 5 600-10

Label Holder Kit Consists of (12) HighBand label holders, (12) paper inserts and (12) protective windows 6462 2 408-01

12-way Wall Mount Frame (1) 6450 2 155-01

Rack Mount, 4-way Rack Kit, Consists of (4) 25-pair HighBand Category 6 modules, (4) label holders and (1) 19"recessed frame, 2U 6450 1 176-01

Rack Mount, 4-way Recessed Frame (1) 6450 2 176-00 Rack Mount, 8-way Rack Kit, Consists of (8) 25-pair HighBand Category 6 modules, (8) label holders and (1) 19" recessed frame, 3U 6450 1 177-01

Rack Mount, 8-way Recessed Frame (1), 3U 6450 2 177-00 Rack Mount, 12-way Rack Kit, Consists of (12) 25-pair HighBand Category 6 modules, (12) label holder kits and (1) 19" recessed frame, 4U 6450 1 178-01

Rack Mount, 12-way Recessed Frame (1), 4U 6450 2 178-00 Rack Mount, Rear Cable Management Bar 6450 1 210-00

TABLE [4]

CAT 6 TERMINATION BLOCK PART NUMBERS

i. Termination blocks shall contain management cable rings, cable ring covers, a top cable

trough, and a bottom cable trough. The termination block management components shall be TE Connectivity product part number(s) [see Table 5].

Description Part Number 12-way Cable Management Kit Includes (2) cable management rings and (1) cover. 6450 1 103-10

Cable Management Rings (2) 6450 2 156-20 Cable Management Ring Cover (1) 6450 2 158-20 Cable Trough Top (1) 6450 2 157-10 Cable Trough Bottom (1) 6450 2 157-20

TABLE [5]

TERMINATION BLOCK MANAGEMENT PART NUMBERS

Page 16: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

3. LC Fiber Optic Patch Panels/Enclosures

a. Fiber optic cables shall be terminated with LC connectors in each telecommunications room (TR). Terminations shall be housed in [1U, 2U, or 4U] rack-mount enclosures providing protection for the terminated fibers.

b. LC connectors for intra-building backbone shall accept 900µm buffered OM3 50/125um

fiber. LC connectors for inter-building backbone shall accept 250µm coated [OM3 50/125um or single-mode] fiber.

c. Simplex LC connectors shall be no-epoxy/no-polish and meet the most recent revision of

TIA/EIA-568-C.3 standard, and its published addenda.

d. No-epoxy/no-polish LC connectors shall be compatible with TE Connectivity termination tool kit part numbers [1278118-4, or 1754845-1].

e. LC connectors in the TR shall be TE Connectivity product part number [see Table 1].

Simplex LC Connector

No-Epoxy/No-Polish

OM3 50/125um 6754483-4 Single-mode 6754482-1

TABLE [1]

LC CONNECTOR PART NUMBER

Fiber

Fiber Adapter

Page 17: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

f. Each LC connector shall be held by a LC duplex coupler snap-in adapter plate. Adapter plates shall be installed into rack-mount fiber optic enclosure. LC duplex snap-in adapter plate shall be TE Connectivity product part number [see Table 2].

Adapter Description

Fiber Count Fiber Type Adapter

Color Part Number

RMG LC Adapter Plates

12 OM3 50 um Aqua RMG-

12ADPQ2

24 OM3 50 um Aqua RMG-

24ADPQ4

12 Single-mode Blue RMG-

12ADPQ5

24 Single-mode Blue RMG-

24ADPQ8 TABLE [2]

LC ADAPTER PLATES

g. Fiber optic enclosures shall be capable of containing up to [72, 144, or 288] LC simplex connectors.

h. Enclosures shall be designed to protect against bend radius violations. i. Enclosures shall ensure that cable routing paths for all fibers are clear and cable

congestion is minimized. j. Enclosures shall include a hinged front door for protection. The door shall be easily

removable for safe, easy access to installed connectors. k. Fiber optic enclosures shall be TE Connectivity product part number(s) [see Table 3].

Page 18: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Description Fiber Count

Port Count

Rack Units Part Numbers

Rack mount patch enclosure, holds 3 RMG adapter plates 72 36 1U RMG-1000-

000B Rack mount patch enclosure, holds 6 RMG adapter

plates 144 72 2U RMG-2000-000B

Rack mount patch enclosure, holds 12 RMG adapter plates 288 144 4U RMG-4000-

000B

TABLE [3] FIBER ENCLOSURE PART NUMBERS

PART 3 EXECUTION

3.00 INSTALLATION

A. Install all systems in accordance with manufacturer’s printed instructions.

B. Frames shall be oriented so that backbone frames are located on the left and horizontal frames are located on the right of the termination field when facing the frame assembly.

C. The horizontal data terminations shall be contained in 19” x 7’ rack(s). All equipment racks shall

be augmented with horizontal and vertical cable management hardware, both front and rear, to properly dress horizontal cables and patch cords.

D. Each patch panel shall be separated vertically on the rack by a [1U (for 1U patch panels) or 2U (for

2U and 4U patch panels)] horizontal cable management panel.

E. Patch panels and fiber enclosures shall be mounted in floor standing equipment racks or cabinets. Rows of racks/cabinets shall be arranged with the fronts facing each other to provide alternating hot and cold aisles. Blank panels should be installed in unused rack/cabinet spaces to assist the function of the hot and cold aisles. Installation should follow the recommendations listed in ANSI/TIA-942, Telecommunications Infrastructure Standard for Data Centers specification.

Page 19: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

SECTION 4

Communications Optical Fiber Backbone Cabling

PART 1 GENERAL

1.00 SUMMARY

1. Communications Optical Fiber Backbone Cabling

a. Intra-building backbone data cable shall be all-dielectric and shall consist of 900µm tight-buffered 850nm laser-optimized OM3 50/125µm multimode fibers surrounded by aramid strength members and a PVC outer jacket.

b. Inter-building backbone data cable shall be [OM3 50/125 or single-mode] all-dielectric

Outside Plant cable (OSP). OSP cable shall contain 250µm TIA color-coated fibers encased in a colored buffer tube filled with a water-barrier filling compound.

PART 2 PRODUCTS 2.00 MANUFACTURED COMPONENTS 1. Product Options

a. Backbone data cable shall be all-dielectric and shall consist of 900µm tight-buffered 850nm laser-optimized OM3 50/125µm multimode fibers surrounded by aramid strength members and a PVC outer jacket.

b. Cable shall be tested to comply with the most recent revision of TIA/EIA-568-C.3 and

ISO/IEC 11801 standards, and their published addenda. The minimum bandwidth and maximum cable attenuation of the cable shall meet the requirements of table 1. The fibers shall support 10 Gigabit Ethernet to a minimum distance as listed in Table 1. Cables with fiber counts more than 12 shall have two or more subunits and may have a central member. The cable shall have a UL rating of [OFNR (Riser) or OFNP (Plenum)].

Page 20: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

OM3 50/125µm ( 850/1300nm)

Maximum Attenuation 3.2/1.2 dB/km

OFL Bandwidth 1500/500 MHz⋅km

850 nm LASER Bandwidth 2000 MHz-km

1000BASE-SX Distance 800m

1000BASE-LX Distance 550m

10GBASE-S Distance 300m 10GBASE-LX4 Distance 300m

TABLE [1]

FIBER BACKBONE CABLE PERFORMANCE CHARACTERISTICS

c. Backbone fiber cabling shall be TE Connectivity product part number [see Table [2]. The cable jacket shall be Aqua.

OM3 50/125um (Aqua Jacket)

Fiber Count Construction UL/NEC

Rating Part Numbers

6 1x6 Riser (OFNR) 3-1553307-9 Plenum (OFNP) 3-1553308-9

8 1x8 Riser (OFNR) 3-1553309-9 Plenum (OFNP) 3-1553310-9

12 1x12 Riser (OFNR) 3-1553311-9 Plenum (OFNP) 3-1553312-9

24 1x24 Riser (OFNR) 3-1553313-9 Plenum (OFNP) 3-1553314-9

24 2x12 Riser (OFNR) 3-1553315-9 Plenum (OFNP) 3-1553316-9

36 6x6 Riser (OFNR) 3-1553319-9 Plenum (OFNP) 3-1553320-9

48 4x12 Riser (OFNR) 3-1553321-9

Page 21: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Plenum (OFNP) 3-1553322-9

72 6x12 Riser (OFNR) 3-1553323-9 Plenum (OFNP) 3-1553324-9

TABLE [2]

FIBER BACKBONE CABLE PART NUMBERS

2. Intra-building Outside Plant Backbone Cabling for Data Circuits

a. Backbone data cable shall be [OM3 50/125µm or single-mode] all-dielectric outside plant cable (OSP). The OSP cable shall consist of [4, 6, 8, 12, 24, 36, 48, 72, 96, or 144] strain-free fibers. OSP cable shall contain [4, 6, 8, or 12] 250µm TIA color-coated fibers encased in a colored buffer tube filled with a water-barrier filling compound. Dielectric cable constructions shall have water-blocking outer strength members and a medium-density polyethylene (MDPE) black outer jacket.

b. Cable shall be tested to comply with the most recent revision of TIA/EIA-568-C.3,

ISO/IEC 11801, ICEA-640, Telcordia, and GR-20-CORE standards, and their published addenda. The minimum bandwidth and maximum cable attenuation of the cable shall meet the requirements of table 1. The fibers shall support Gigabit Ethernet to a minimum distance as listed in Table 1. The dielectric outside plant cable shall comply with the mechanical specifications and temperature ratings as listed in Tables [2 and 3].

OM3 50/125µm (850/1300nm)

Single-mode (1310/1550nm)

Maximum Attenuation (dB/km) 3.2/1.2 0.4/0.3

OFL Bandwidth (MHz-km) 1500/500 - / -

850 nm LASER Bandwidth (MHz-km) 2000/ - - / -

1000BASE-SX Distance 800m NST

1000BASE-LX Distance 550m 5000m

10GBASE-S Distance 300m NST 10GBASE-LX4 Distance 300m 10000m

TABLE [1]

FIBER BACKBONE CABLE PERFORMANCE CHARACTERISTICS

Page 22: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Cable Type

Fiber count

Nominal O.D.

mm(in.)

Nominal Weight kg/km(lbs/1000ft

)

Rated Tensile Load Minimum Bend Radius

Installation N (lbf)

Long Term N (lbf)

Installation mm(in)

Long Term

mm(in)

Outside Plant,

Dielectric

4

8.3(0.33) 50(34) 2670 (600)

890(200) 176(6.9) 88(3.5) 6

8 12

24 2(12) 11.0(0.43) 100(67) 2670(600) 890(200) 242(9.5) 121(4.8)

36 11.0(0.43) 93(62) 2670(600) 890(200) 242(9.5) 121(4.8)

48 11.0(0.43) 97(65) 2670(600) 890(200) 242(9.5) 121(4.8)

72 11.9(0.47) 130(87) 2700(600) 890(200) 252(9.9) 126(5.0)

96 13.6(0.53) 158(106) 2670(600) 890(200) 287(11.3) 144(5.6)

144 16.6(0.69) 252(169) 2670(600) 890(200) 364(14.3) 182(7.2)

TABLE [2]

FIBER BACKBONE CABLE MECHANICAL SPECIFICATIONS

Operation Installation Storage -40ºC to +70ºC (-40ºF to +158ºF) -30ºC to +60ºC (-22ºF to +140ºF) -40ºC to +70ºC (-40ºF to +158ºF)

TABLE [3]

FIBER BACKBONE CABLE TEMPERATURE RATINGS

c. Inter-building backbone outside plant fiber cabling shall be TE Connectivity product part number [see Tables [4 and 5].

Description Part Number 4-Fiber 6-Fiber 8-Fiber 12-Fiber

Single-mode 6-1553386-3 6-1553387-3 6-1553388-3 6-1553389-3

OM3 50/125µm 6-1553396-4 6-1553397-4 6-1553398-4 6-1553399-4

TABLE [4] OSP DIELECTRIC FIBER BACKBONE CABLE (SINGLE TUBE)

Page 23: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Description Part Number 24-Fiber 36-Fiber 48-Fiber 72-Fiber 96-Fiber 144-Fiber

Single-mode 6-1553390-3

6-1553391-3

6-1553392-3

6-1553393-3

6-1553394-3

6-1553395-3

OM3 50/125µm

6-1553400-4

6-1553401-4

6-1553402-4

6-1553403-4

6-1553404-4

6-1553405-4

TABLE [5]

OSP DIELECTRIC FIBER BACKBONE CABLE (12 FIBERS PER TUBE)

PART 3 EXECUTION 3.00 INSTALLATION

A. Install all systems in accordance with manufacturer’s printed instructions.

B. All backbone cables shall be installed in the following manner.

1. Backbone cables shall be installed separately from horizontal distribution cables

2. Where cables are housed in conduits, the backbone and horizontal cables shall be installed in separate conduits or in separate inner duct(s) within conduits

3. Where cables are installed in an air return plenum, the cable shall be installed in conduit, or

plenum cable shall be installed in a plenum inner duct to provide protection to the cable

4. Where backbone cables and distribution cables are installed in a cable tray or wire-way, backbone cables shall be installed first and bundled separately from the horizontal distribution cables

5. Inside plant cables above four fibers shall support a minimum bend radius of 10 times the

cable diameter under no tensile load, and 20 times the cable diameter under tensile loading to the cable’s rated limit.

Page 24: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

SECTION 5

Communications Copper Horizontal Cabling

PART 1 GENERAL

1.00 SUMMARY

A. Communications Copper Horizontal Cabling

1. Horizontal cabling for [voice and/or data] circuits shall be enhanced category 6, [24 (CMR) or 23 (CMP)] AWG, 4-pair U/UTP, UL/NEC [CMP or CMR] rated, and be independently verified for compliance.

2. Maximum cable diameter for CMP rated 620 cable shall be .215 inches.

3. Maximum cable diameter for CMR rated 620 cable shall be .210 inches.

4. Maximum cable diameter for CMP rated 630 cable shall be .220 inches.

5. Maximum cable diameter for CMR rated 630 cable shall be .235 inches. 6. Cable performance shall be independently verified and characterized to 600 MHz.

7. (TE620P & TE620R) Enhanced category 6 rated cable shall have a margin of 11 dB for pair-pair NEXT at 250 MHz.

8. (TE630P & TE630R) Enhanced category 6 rated cable shall have a margin of 12 dB for pair-

pair NEXT at 250 MHz.

PART 2 PRODUCTS

2.00 MANUFACTURED COMPONENTS

A. Product Options

1. Enhanced category 6 U/UTP Horizontal Cabling

Page 25: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

a. Horizontal cabling for [voice and/or data] circuits shall be [24 (CMR) or 23 (CMP)], 4-

pair U/UTP, NEC/NFPA [CMP or CMR] rated and be independently verified for compliance. Cable performance shall be independently verified by ETL and meet the TIA/EIA-568-C.2 Category 6 requirements.

b. Cable jacketing shall be [white, gray, blue or yellow] and lead-free. Cable shall be

packaged on a 1000ft [reel-in-box, pull-box or reel]. Cable shall be independently verified for flammability by UL and shall comply with NEC article 800 and NFPA 70; [CMP (NFPA 262) or CMR (ANSI/UL 1666)].

c. For horizontal cable, refer to TE Connectivity product part numbers [See Table 1].

Cat 6 TE620 Series 4-

Page 26: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Description NEC/NFPA Rating Packaging Part Numbers

Blue White Gray Yellow

Enhanced Category 6

U/UTP Cable, 620

Series

CMR

Reel-in-box, 1000 ft

TE620R-BLRB

TE620R-WTRB

TE620R-GYRB

TE620R-YLRB

Pull-box, 1000 ft

TE620R-BLII

TE620R-WTII TE620R-GYII TE620R-YLII

Reel, 1000 ft

TE620R-BL02

TE620R-WT02

TE620R-GY02

TE620R-YL02

CMP

Reel-in-box, 1000 ft

TE620P-BLRB

TE620P-WTRB

TE620P-GYRB

TE620P-YLRB

Pull-box, 1000 ft

TE620P-BLII TE620P-WTII TE620P-GYII TE620P-YLII

Reel, 1000 ft

TE620P-BL02

TE620P-WT02

TE620P-GY02

TE620P-YL02

Description NEC/NFPA Rating Packaging Part Numbers

Blue White Gray Yellow

Enhanced Category 6

U/UTP Cable, 630

Series

CMR

Reel-in-box, 1000 ft

TE630R-BLRB

TE630R-WTRB

TE630R-GYRB

TE630R-YLRB

Reel, 1000 ft

TE630R-BL02

TE630R-WT02

TE630R-GY02

TE630R-YL02

CMP

Reel-in-box, 1000 ft

TE630P-BLRB

TE630P-WTRB

TE630P-GYRB

TE630P-YLRB

Reel, 1000 ft

TE630P-BL02

TE630P-WT02

TE630P-GY02

TE630P-YL02

TABLE [1]

HORIZONTAL CABLE PART NUMBERS

d. Horizontal Cabling shall meet the technical details and performance characteristics listed

in Tables below.

Page 27: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

TABLE [2] ENHANCED CAT 6 CABLE PERFORMANCE CHARACTERISTICS

Performance Data, 620 Series CMR Category 6 UTP Cable, TE620R

Freq MHz

Fitted Impedance

Ohms

Insertion Loss dB/100m

Return Loss dB/100m

Pair-Pair NEXT dB/100m

PSNEXT dB/100m

Spec Max Spec Min Spec Min Spec Min Spec 1 100+/-5 1.7 2.0 28.5 20.0 83.8 74.3 81.9 72.3 4 100+/-3 3.4 3.8 32.1 22.9 74.9 65.3 74.3 63.3 8 100+/-3 4.9 5.3 35.0 24.5 74.4 60.8 71.0 58.8 10 100+/-3 5.5 6.0 34.6 25.0 70.3 59.3 68.0 57.3 16 100+/-3 7.0 7.6 31.7 25.0 67.2 56.2 66.7 54.2 20 100+/-3 7.9 8.5 32.1 25.0 66.8 54.8 64.7 52.8 25 100+/-3 8.9 9.5 36.5 24.3 65.6 53.3 63.6 51.3

31.25 100+/-3 9.9 10.7 36.7 23.6 61.8 51.9 60.9 49.9 62.5 100+/-3 14.3 15.4 34.0 21.5 61.0 47.4 59.3 45.4 100 100+/-3 18.4 19.8 30.8 20.1 60.2 44.3 57.4 42.3 155 100+/-3 23.3 25.2 27.3 18.8 54.8 41.4 51.4 39.4 200 100+/-3 26.8 29.0 31.0 18.0 54.9 39.8 52.4 37.8 250 100+/-3 30.4 32.8 28.6 17.3 49.5 38.3 48.5 36.3 300 100+/-3 33.7 – 27.2 – 49.0 – 48.2 – 350 100+/-3 36.7 – 24.3 – 46.3 – 44.8 – 400 100+/-3 39.6 – 25.0 – 47.5 – 45.2 – 550 100+/-3 47.7 – 18.6 – 40.2 – 39.4 – 600 100+/-3 47.5 – 15.2 – 38.3 – 35.4 –

Freq MHz

Pair-Pair ACR dB/100m PSACR dB/100m Pair-Pair ACRF

dB/100m PSACRF dB/100m

TCL dB/100m

ELTCTL dB/100m

Min Spec Min Spec Min Spec Min Spec Min Min 1 82.2 72.3 80.3 70.3 73.6 67.8 72.6 64.8 40.0 35.0 4 71.7 61.5 71.2 59.5 62.7 55.8 61.8 52.8 40.0 23.0 8 69.8 55.4 66.4 53.4 57.2 49.7 56.2 46.7 40.0 16.9 10 65.1 53.3 62.8 51.3 55.2 47.8 54.2 44.8 40.0 15.0 16 60.5 48.7 60.0 46.7 51.1 43.7 49.8 40.7 38.0 10.9 20 59.4 46.3 57.4 44.3 49.3 41.8 48.2 38.8 37.0 9.0 25 57.3 43.8 55.3 41.8 47.4 39.8 46.5 36.8 36.0 7.0

31.25 52.5 41.2 51.3 39.2 45.5 37.9 44.4 34.9 35.1 5.1 62.5 47.3 32.0 45.7 30.0 40.1 31.9 39.4 28.9 32.0 – 100 42.7 24.5 39.8 22.5 36.8 27.8 35.9 24.8 30.0 – 155 32.4 16.3 28.9 14.3 33.6 24.0 33.2 21.0 28.1 – 200 29.6 10.8 26.9 8.8 31.7 21.8 30.6 18.8 27.0 – 250 20.3 5.5 19.3 3.5 29.1 19.8 28.9 16.8 26.0 – 300 16.6 – 15.8 – 26.2 – 25.5 – – – 350 10.9 – 9.4 – 21.3 – 21.8 – – – 400 10.1 – 7.9 – 22.1 – 22.5 – – – 550 – – – – 25.7 – 24.7 – – – 600 – – – – 11.5 – 9.6 – – –

NOTE: The above listed discrete frequency electrical performance values are provided for engineering

information only. Actual compliance testing is based on swept frequency measurements.

Technical Specifications, 620 CMR Category 6 UTP Cable, TE620R Mutual Capacitance: 5.6 nF/100 m maximum Conductor DC Resistance: 28.6 Ω/1000 ft (9.38 Ω/100 m) maximum Voltage: 300 VDC Delay Skew: 25 ns/100 m Propagation Delay: 485 ns/100 m @ 250 MHz nominal Velocity of Propagation: 69% Operating Temperature: -20°C – 60°C (-4°F – 140°F) Storage Temperature: -20°C – 80°C (-4°F – 176°F) installation Temperature: 5°C - 50°C (41°F - 122°F) Bend Radius: 4 × cable diameter Packaging: 1000ft Reel-in-a-box: 1000ft Reel: 1000ft Pull-box: Materials: Conductors: Insulation: Jacket:

31 lbs 28 lbs 28 lbs 24 AWG, Solid Copper (0.0216" nominal) Ø.038 nominal, polyethylene Ø.210 nominal, FR PVC

Compliances: UL Subject 444 (UL)-C(UL) Type CMR ICEA S-90-661 ETL Verified TIA-568-C.2 Category 6 Horizontal Cable

Requirements ISO/IEC 11801 Category 6 Horizontal Cable Requirements 2002/95/EC RoHS

Page 28: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

TABLE [3] ENHANCED CAT 6 CABLE TECHNICAL SPECIFICATIONS

Page 29: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Performance Data, 620 Series CMP Category 6 UTP Cable, TE620P

Freq MHZ

Fitted Impedance

Ohms

Insertion Loss dB/100m

Return Loss dB/100m

Pair-Pair NEXT dB/100m

PSNEXT dB/100m

Spec Max Spec Min Spec Min Spec Min Spec 1 100+/-5 1.7 2.0 28.5 20.0 83.8 74.3 81.9 72.3 4 100+/-3 3.4 3.8 32.1 22.9 74.9 65.3 74.3 63.3 8 100+/-3 4.9 5.3 35.0 24.5 74.4 60.8 71.0 58.8 10 100+/-3 5.5 6.0 34.6 25.0 70.3 59.3 68.0 57.3 16 100+/-3 7.0 7.6 31.7 25.0 67.2 56.2 66.7 54.2 20 100+/-3 7.9 8.5 32.1 25.0 66.8 54.8 64.7 52.8 25 100+/-3 8.9 9.5 36.5 24.3 65.6 53.3 63.6 51.3

31.25 100+/-3 9.9 10.7 36.7 23.6 61.8 51.9 60.9 49.9 62.5 100+/-3 14.3 15.4 34.0 21.5 61.0 47.4 59.3 45.4 100 100+/-3 18.4 19.8 30.8 20.1 60.2 44.3 57.4 42.3 155 100+/-3 23.3 25.2 27.3 18.8 54.8 41.4 51.4 39.4 200 100+/-3 26.8 29.0 31.0 18.0 54.9 39.8 52.4 37.8 250 100+/-3 30.4 32.8 28.6 17.3 49.5 38.3 48.5 36.3 300 100+/-3 33.7 – 27.2 – 49.0 – 48.2- – 350 100+/-3 36.7 – 24.3 – 46.3 – 44.8 – 400 100+/-3 39.6 – 25.0 – 47.5 – 45.2- – 550 100+/-3 47.7 – 18.6 – 40.2 – 39.4 – 600 100+/-3 47.5 – 15.2 – 38.3 – 35.4 –

Freq MHZ

Pair-Pair ACR dB/100m PSACR dB/100m Pair-Pair ACRF

dB/100m PSACRF dB/100m

TCL dB/100m

ELTCTL dB/100m

Min Spec Min Spec Min Spec Min Spec Min Min 1 82.2 72.3 80.3 70.3 73.6 67.8 72.6 64.8 40.0 35.0 4 71.7 61.5 71.2 59.5 62.7 55.8 61.8 52.8 40.0 23.0 8 69.8 55.4 66.4 53.4 57.2 49.7 56.2 46.7 40.0 16.9 10 65.1 53.3 62.8 51.3 55.2 47.8 54.2 44.8 40.0 15.0 16 60.5 48.7 60.0 46.7 51.1 43.7 49.8 40.7 38.0 10.9 20 59.4 46.3 57.4 44.3 49.3 41.8 48.2 38.8 37.0 9.0 25 57.3 43.8 55.3 41.8 47.4 39.8 46.5 36.8 36.0 7.0

31.25 52.5 41.2 51.3 39.2 45.5 37.9 44.4 34.9 35.1 5.1 62.5 47.3 32.0 45.7 30.0 40.1 31.9 39.4 28.9 32.0 – 100 42.7 24.5 39.8 22.5 36.8 27.8 35.9 24.8 30.0 – 155 32.4 16.3 28.9 14.3 33.6 24.0 33.2 21.0 28.1 – 200 29.6 10.8 26.9 8.8 31.7 21.8 30.6 18.8 27.0 – 250 20.3 5.5 19.3 3.5 29.1 19.8 28.9 16.8 26.0 – 300 16.6 – 15.8 – 26.2 – 25.5 – – – 350 10.9 – 9.4 – 21.3 – 21.8 – – – 400 10.1 – 7.9 – 22.1 – 22.5 – – – 550 – – – – 25.7 – 24.7 – – – 600 – – – – 11.5 – 9.6 – – –

NOTE: The above listed discrete frequency electrical performance values are provided for engineering

information only. Actual compliance testing is based on swept frequency measurements.

Page 30: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

TABLE [4]

ENHANCED CAT 6 CABLE PERFORMANCE CHARACTERISTICS TABLE [5]

Technical Specifications, 620 CMP Category 6 UTP Cable, TE620P Mutual Capacitance: 5.6 nF/100 m maximum Conductor DC resistance: 28.6 Ω/1000 ft (9.38 Ω/100 m) maximum Voltage: 300 VDC Delay Skew: 25 ns/100 m Propagation Delay: 454 ns/100 m @ 250 MHz nominal Velocity of Propagation: 75% Operating Temperature: -20°C – 60°C (-4°F – 140°F) Storage Temperature: -20°C – 80°C (-4°F – 176°F) installation Temperature: 5°C - 50°C (41°F - 122°F) Bend radius: 4 × cable diameter Packaging: 1000ft Reel-in-a-box: 1000ft Reel: 1000ft Pull-box:

31 lbs 28 lbs 28 lbs

Materials: Conductors: Insulation: Jacket:

23 AWG, Solid Copper (0.0224" nominal) 0.039 nominal, FEP 0.206 nominal, FR PVC

Compliances: UL Subject 444 (UL)-C(UL) Type CMP ICEA S-90-661 ETL Verified TIA-568-C.2 Category 6 Horizontal Cable

Requirements ISO/IEC 11801 Category 6 Horizontal Cable Requirements 2002/95/EC RoHS

Page 31: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

ENHANCED CAT 6 CABLE TECHNICAL SPECIFICATIONS

Page 32: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

TABLE [6] Performance Data, 630 Series CMR Category 6 UTP Cable, TE630R

Freq MHZ

Fitted Impedance

Ohms

Insertion Loss dB/100m

Return Loss dB/100m

Pair-Pair NEXT dB/100m

PSNEXT dB/100m

Spec Max Spec Min Spec Min Spec Min Spec 1 100+/-5 1.8 2.0 26.2 20.0 85.1 74.3 88.6 72.3 4 100+/-3 3.6 3.8 30.8 22.9 76.9 65.3 77.3 63.3 8 100+/-3 5.1 5.3 33.3 24.5 75.9 60.8 80.5 58.8 10 100+/-3 5.8 6.0 34.0 25.0 75.4 59.3 76.6 57.3 16 100+/-3 7.4 7.6 37.1 25.0 71.3 56.2 74.4 54.2 20 100+/-3 8.2 8.5 37.0 25.0 73.4 54.8 66.9 52.8 25 100+/-3 9.3 9.5 37.4 24.3 68.7 53.3 68.2 51.3

31.25 100+/-3 10.4 10.7 37.8 23.6 69.6 51.9 71.1 49.9 62.5 100+/-3 14.9 15.4 33.9 21.5 66.0 47.4 62.6 45.4 100 100+/-3 19.1 19.8 30.3 20.1 60.0 44.3 60.2 42.3 155 100+/-3 24.1 25.2 27.2 18.8 57.7 41.4 56.2 39.4 200 100+/-3 27.6 29.0 27.6 18.0 56.9 39.8 57.4 37.8 250 100+/-3 31.0 32.8 25.1 17.3 52.8 38.3 50.5 36.3 300 100+/-3 34.3 – 24.3 – 52.6 – 52.1 – 350 100+/-3 37.2 – 22.3 – 53.0 – 51.0 – 400 100+/-3 39.9 – 21.5 – 49.9 – 48.7 – 400 100+/-3 42.7 – 19.9 – 46.4 – 47.0 – 450 100+/-3 45.3 – 18.7 – 39.0 – 42.6 – 550 100+/-3 47.4 – 15.5 – 40.5 – 35.3 – 600 100+/-3 47.5 – 13.4 – 38.3 – 30.6 –

Freq MHZ

Pair-Pair ACR dB/100m PSACR dB/100m Pair-Pair ACRF

dB/100m PSACRF dB/100m

TCL dB/100m

ELTCTL dB/100m

Min Spec Min Spec Min Spec Min Spec Min Min 1 83.5 72.3 82.9 70.3 72.8 67.8 72.7 64.8 40.0 35.0 4 73.4 61.5 73.0 59.5 61.4 55.8 61.4 52.8 40.0 23.0 8 71.1 55.4 70.0 53.4 55.8 49.7 55.7 46.7 40.0 16.9 10 70.0 53.3 68.1 51.3 53.8 47.8 53.6 44.8 40.0 15.0 16 64.2 48.7 60.0 46.7 53.7 43.7 49.7 40.7 38.0 10.9 20 65.5 46.3 62.2 44.3 49.8 41.8 47.7 38.8 37.0 9.0 25 59.5 43.8 62.3 41.8 47.8 39.8 45.9 36.8 36.0 7.0

31.25 59.7 41.2 57.8 39.2 45.8 37.9 44.1 34.9 35.1 5.1 62.5 52.2 32.0 59.0 30.0 44.0 31.9 37.8 28.9 32.0 – 100 41.0 24.5 49.7 22.5 38.0 27.8 34.0 24.8 30.0 – 155 34.7 16.3 39.1 14.3 34.2 24.0 30.6 21.0 28.1 – 200 30.4 10.8 33.5 8.8 28.8 21.8 28.8 18.8 27.0 – 250 23.0 5.5 29.2 3.5 27.6 19.8 27.3 16.8 26.0 – 300 19.6 – 18.4 – 26.5 – 26.4 – – – 350 17.3 – 15.9 – 25.7 – 25.8 – – – 400 13.4 – 12.2 – 25.1 – 25.3 – – – 400 6.4 – 6.0 – 25.0 24.4 – – – 400 -3.9 – -4.0 – 25.4 24.8 – – – 550 -4.2 – -4.7 – 23.3 – 22.4 – – – 600 -5.6 – -5.1 – 20.8 – 19.6 – – –

NOTE: The above listed discrete frequency electrical performance values are provided for engineering information only. Actual compliance testing is based on swept frequency measurements.

Page 33: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

ENHANCED CAT 6 CABLE PERFORMANCE CHARACTERISTICS TABLE [7]

Technical Specifications, 630 CMR Category 6 UTP Cable, TE630R Mutual Capacitance: 5.6 nF/100 m maximum Conductor DC Resistance: 28.6 Ω/1000 ft (9.38 Ω/100 m) maximum Voltage: 300 VDC Delay Skew: 25 ns/100 m Propagation Delay: 485 ns/100 m @ 250 MHz nominal Velocity of Propagation: 69% Operating Temperature: -20°C – 60°C (-4°F – 140°F) Storage Temperature: -20°C – 80°C (-4°F – 176°F) installation Temperature: 5°C - 50°C (41°F - 122°F) Bend Radius: 4 × cable diameter Packaging: 1000ft Reel-in-a-box: 1000ft Reel:

31 lbs/kft 28 lbs/kft

Materials: Conductors: Insulation: Jacket:

24 AWG, Solid Copper (0.0216" nominal) Ø.038 nominal, polyethylene Ø.235 nominal, FR PVC

Compliances: UL Subject 444 (UL)-C(UL) Type CMR ICEA S-90-661 ETL Verified TIA-568-C.2 Category 6 Horizontal Cable

Requirements ISO/IEC 11801 Category 6 Horizontal Cable Requirements 2002/95/EC RoHS

Page 34: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

ENHANCED CAT 6 CABLE TECHNICAL SPECIFICATIONS

Page 35: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

TABLE [8] Performance Data, 630 Series CMP Category 6 UTP Cable, TE630P

Freq MHZ

Fitted impedance

Ohms

Insertion Loss dB/100m

Return Loss dB/100m

Pair-Pair NEXT dB/100m PSNEXT dB/100m

Spec Max Spec Min Spec Min Spec Min Spec 1 100+/-5 1.8 2.0 38.3 20.0 86.8 74.3 87.4 72.3 4 100+/-3 3.6 3.8 31.6 22.9 79.9 65.3 79.5 63.3 8 100+/-3 5.2 5.3 33.2 24.5 71.8 60.8 71.7 58.8 10 100+/-3 5.8 6.0 31.1 25.0 75.2 59.3 72.6 57.3 16 100+/-3 7.4 7.6 33.2 25.0 67.6 56.2 67.5 54.2 20 100+/-3 8.3 8.5 30.7 25.0 64.6 54.8 61.8 52.8 25 100+/-3 9.4 9.5 33.9 24.3 65.3 53.3 69.2 51.3

31.25 100+/-3 10.5 10.7 33.2 23.6 62.2 51.9 65.1 49.9 62.5 100+/-3 15.2 15.4 30.6 21.5 57.3 47.4 59.4 45.4 100 100+/-3 19.6 19.8 28.6 20.1 55.6 44.3 55.6 42.3 155 100+/-3 24.9 25.2 24.1 18.8 53.1 41.4 53.8 39.4 200 100+/-3 28.8 29.0 23.3 18.0 52.3 39.8 50.0 37.8 250 100+/-3 32.6 32.8 19.9 17.3 50.3 38.3 50.3 36.3 300 100+/-3 36.2 – 21.3 – 50.0 – 48.6 – 350 100+/-3 39.5 – 21.0 – 47.2 – 49.8 – 400 100+/-3 42.7 – 23.2 – 48.8 – 47.2 – 450 100+/-3 46.1 – 22.3 – 40.2 – 44.5 – 550 100+/-3 49.1 – 23.1 – 42.7 – 44.6 – 550 100+/-3 51.9 – 18.2 – 42.6 – 44.9 – 600 100+/-3 50.2 – 15.6 – 41.8 – 44.3 –

Freq MHZ

Pair-Pair ACR dB/100m

PSACR dB/100m

Pair-Pair ACRF dB/100m

PSACRF dB/100m

TCL dB/100m

ELTCTL dB/100m

Min Spec Min Spec Min Spec Min Spec Min Min 1 85.1 72.3 82.3 70.3 77.8 67.8 72.6 64.8 40.0 35.0 4 76.3 61.5 73.1 59.5 65.2 55.8 64.9 52.8 40.0 23.0 8 66.7 55.4 66.2 53.4 59.0 49.7 58.4 46.7 40.0 16.9 10 69.5 53.3 66.7 51.3 57.4 47.8 54.2 44.8 40.0 15.0 16 60.3 48.7 60.0 46.7 53.8 43.7 53.0 40.7 38.0 10.9 20 56.5 46.3 56.0 44.3 52.1 41.8 51.0 38.8 37.0 9.0 25 56.3 43.8 55.2 41.8 49.7 39.8 48.6 36.8 36.0 7.0

31.25 51.9 41.2 50.4 39.2 48.6 37.9 47.1 34.9 35.1 5.1 62.5 42.4 32.0 39.7 30.0 43.5 31.9 42.4 28.9 32.0 – 100 36.4 24.5 35.1 22.5 38.1 27.8 37.9 24.8 30.0 – 155 28.6 16.3 28.0 14.3 31.8 24.0 31.6 21.0 28.1 – 200 24.1 10.8 22.1 8.8 32.4 21.8 30.2 18.8 27.0 – 250 18.3 5.5 17.8 3.5 30.5 19.8 28.2 16.8 26.0 – 300 14.5 – 14.0 – 31.5 – 27.9 – – – 350 8.3 – 7.6 – 29.8 – 27.7 – – – 400 6.8 – 5.6 – 28.0 – 25.5 – – – 450 -2.5 – -2.9 – 27.8 – 24.0 – – – 500 -6.3 – -7.1 – 26.8 – 23.4 – – – 550 -9.3 – -9.7 – 22.7 – 22.1 – – – 600 -12.2 – -13.1 – 18.6 – 21.4 – – –

NOTE: The above listed discrete frequency electrical performance values are provided for engineering information only. Actual compliance testing is based on swept frequency measurements.

Page 36: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

ENHANCED CAT 6 CABLE PERFORMANCE CHARACTERISTICS

TABLE [9]

ENHANCED CAT 6 CABLE TECHNICAL SPECIFICATIONS

Technical Specifications, 630 CMP Category 6 UTP Cable, TE630P Mutual Capacitance: 5.6 nF/100 m maximum Conductor DC resistance: 28.6 Ω/1000 ft (9.38 Ω/100 m) maximum Voltage: 300 VDC Delay Skew: 25 ns/100 m Propagation Delay: 470 ns/100 m @ 250 MHz nominal Velocity of Propagation: 73% Operating Temperature: -20°C – 60°C (-4°F – 140°F) Storage Temperature: -20°C – 80°C (-4°F – 176°F) installation Temperature: 5°C - 50°C (41°F - 122°F) Bend radius: 4 × cable diameter Packaging: 1000ft Reel-in-a-box: 1000ft Reel:

32 lbs/kft 30 lbs/kft

Materials: Conductors: Insulation: Jacket:

23 AWG, Solid Copper (0.0224" nominal) 0.039" nominal, FEP 0.220" nominal, FR PVC

Compliances: UL Subject 444 (UL)-C(UL) Type CMP ICEA S-90-661 ETL Verified TIA-568-C.2 Category 6 Horizontal Cable

Requirements ISO/IEC 11801 Category 6 Horizontal Cable Requirements 2002/95/EC RoHS

Page 37: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

PART 3 EXECUTION 3.00 INSTALLATION

A. Install all systems in accordance with manufacturer’s printed instructions. B. All copper horizontal cables shall be installed in the following manner: 1. Cable raceways shall not be filled greater than the NEC maximum fill for the particular

raceway type

2. Cables shall be installed in continuous lengths from origin to destination (no splices) unless specifically addressed in this document

3. The cable’s minimum bend radius of 4 times the cable diameter and maximum pulling tension

of 25 lbs shall not be exceeded

4. If a J-hook or trapeze system is used to support cable bundles all horizontal cables shall be supported at a maximum of four-foot intervals – at no point shall cable(s) rest on acoustic ceiling grids or panels

5. Horizontal distribution cables shall be bundled in groups of not greater than 40 cables (cable

bundle quantities in excess of 40 cables may cause deformation of the bottom cables within the bundle)

6. Cable shall be installed above fire-sprinkler and systems and shall not be attached to the

system or any ancillary equipment or hardware

7. The cabling system and support hardware shall be installed so that it does not obscure any valves, fire alarm conduit, boxes, or other control devices

8. Cables shall not be attached to ceiling grid or lighting support wires

9. Where light support for drop cable legs is required, install clips to support the cabling

10. Any cable damaged or exceeding recommended installation parameters during installation

shall be replaced prior to final acceptance at no cost to the Owner

11. Cables shall be identified by a self-adhesive label

Page 38: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

12. The cable label shall be applied to the cable behind the faceplate on a section of cable that can

be accessed by removing the cover plate

13. Cables shall be dressed and terminated in accordance with the recommendations in ANSI/TIA-568-C standards, manufacturer’s recommendations, and/or best industry practices.

14. Pair untwist at the termination shall not exceed 0.25 inch for connecting hardware

15. Cables shall be neatly bundled and dressed to their respective panels or blocks

16. Each panel or block shall be fed by an individual bundle separated and dressed back to the

point of cable entrance into the rack or frame

17. The cable jacket shall be maintained as close as possible to the termination point

18. Each cable shall be clearly labeled on the cable jacket behind the patch panel at a location that can be viewed without removing the bundle support ties

19. Cable labels shall not be obscured from view

20. Data Center and SAN Communication cabling should run under the access floor in the hot aisle.

Page 39: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

SECTION 6

Communications Faceplates and Connectors

PART 1 GENERAL

1.00 SUMMARY

A. Communications Faceplates and Connectors

1. Wall and modular furniture faceplates shall contain 2 category 6 jacks for voice and

data communications. Faceplate jacks shall be terminated with category 6 cables and inserted into the communications faceplate.

PART 2 PRODUCTS

2.00 MANUFACTURED COMPONENTS

B. Product Options 1. Category 6 Jacks

a. Communications faceplate ports shall contain Category 6 jacks. Jacks shall be terminated to the horizontal cabling and inserted into the communications faceplate.

b. Modular jacks shall terminate using 110-style pc board connectors, color-coded

for both T568A and T568B wiring. Each modular jack shall be wired to T568B. The 110-style insulation displacement connectors shall be capable of terminating 22-24 AWG solid or 24 AWG stranded conductors. The insulation displacement contacts shall be paired with additional space between pairs to improve crosstalk performance. Modular jacks shall utilize a secondary PC board separate from the signal path for crosstalk compensation. Modular jacks shall meet the ANSI/TIA-568-C.2 requirements for category 6 performance.

. c. Modular jacks shall be compatible with the TE Connectivity SL series modular jack termination tool part number 1725150-1. Modular jacks shall be UL Listed under file number E81956.

d. Data jacks shall be TE Connectivity product part number [[1375055-X (X denotes color, see Table-1)] and be [almond, black, white, gray, orange, blue, red, yellow, green, violet, or electrical ivory] in color.

Page 40: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

e. Voice jacks shall be TE Connectivity product part number [[1375055-X (X denotes color, see Table-1)] and be [almond, black, white, gray, orange, blue, red, yellow, green, violet, or electrical ivory] in color.

Description Wiring Pattern Color Part Number

Category 6 SL Series Modular Jacks

T568A/T568B

Almond 1375055-1 Black 1375055-2 White 1375055-3 Gray 1375055-4

Orange 1375055-5 Blue 1375055-6 Red 1375055-7

Yellow 1375055-8 Green 1375055-9 Violet 1-1375055-0

Electrical Ivory 1-1375055-1

Alpine White 1-1375055-3

TABLE [1] CATEGORY 6 MODULAR JACK PART NUMBERS

e. Modular jacks shall meet the technical details and performance characteristics listed in Tables 2 and 3.

Page 41: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Technical Details Materials Modular Jack Housing – Polyphenylene oxide, 94V-0 rated 110 Connecting Blocks

– Polycarbonate, 94V-0 rated

Contacts – Beryllium copper, plated with 1.27µm [50µin] thick gold in localized area and 3.81µm [150µin] minimum thick matte tin in solder area over 1.27 µm [50 µin] minimum thick nickel underplate

Insulation Displacement Contacts –

Phosphorous bronze, plated with 3.81µm [150µin] minimum thick matte tin-lead over 1.27µm [50µin] minimum thick nickel underplate

Integral Dust Cover – Polycarbonate Shield – Copper zinc alloy 260, pre-plated with bright nickel

Strain Relief – Polycarbonate Electrical Characteristics

Modular Jack – 750 mating cycles

Voltage – 150VAC max.

110 Contacts – 200 terminations

Operating Temperature – -40° – 70°C (-40° – 158°F)

Pull Force – 20lbs (89N) Approvals

UL Listed, file number E81956, CSA

TABLE [2]

CAT 6 MODULAR JACK TECHNICAL DETAILS

Page 42: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Worst-Case Performance Characteristics (meet or exceed ANSI//TIA-568-C.2 and ISO/IEC Category 6/Class E requirements)

Frequency MHz

Insertion Loss (dB) Return Loss (dB) NEXT (dB) FEXT (dB) Category 6 Standard Max Category 6

Standard Min Category 6 Standard Min Category 6

Standard Min

1 0.10 0.02 30 52.4 75.0 84.8 75.0 83.7 4 0.10 0.02 30 53.7 75.0 80.3 71.1 74.8 8 0.10 0.02 30 55.3 75.0 77.4 65.0 69.4 10 0.10 0.03 30 56.1 74.0 76.4 63.1 67.5 16 0.10 0.03 30 57.6 69.9 72.0 59.0 62.9 20 0.10 0.04 30 59.3 68.0 71.9 57.1 61.7 25 0.10 0.04 30 59.4 66.0 69.1 55.1 59.8

31.25 0.11 0.05 30 56.8 64.1 67.7 53.2 58.2 62.5 0.16 0.06 28 42.3 58.1 61.5 47.2 52.6 100 0.20 0.06 24 33.2 54.0 57.7 43.1 48.7 200 0.28 0.06 18 21.2 48.0 52.5 37.1 42.2 250 0.32 0.10 16 17.4 46.0 47.9 35.1 40.1

TABLE [3]

CAT 6 PATCH MODULAR JACK PERFORMANCE CHARACTERISTICS

2. Wall Faceplates

a. Work area wall outlets shall be [almond, black, white, gray, electrical ivory,

alpine white] [angled, standard, or HIDEAWAY] [single or dual] gang 2-port faceplates.

b. Faceplates shall be TE Connectivity product part number [see Table 1].

2-Port Standard

Page 43: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Description Box Size Color Part Numbers

Angled 2-Port Faceplate

Single Gang

Almond 1375155-1 Black 1375155-2 White 1375155-3 Gray 1375155-4

Electrical Ivory 1-1375155-1

Alpine White 1-1375155-3

Angled 4-Port Faceplate Single Gang

Almond 406185-1 Black 406185-2 White 406185-3 Gray 406185-4

Electrical Ivory 1-406185-1

Alpine White 1-406185-3

1-Port Faceplate Single Gang

Almond 2111008-1 Black 2111008-2 White 2111008-3 Gray 2111008-4

Electrical Ivory

1-2111008-1

Alpine White 1-2111008-3

1-Port Wall Phone Faceplate Single Gang

Almond 1479152-1 Black 1479152-2 White 1479152-3 Gray 1479152-4

Electrical Ivory

1-1479152-1

2-Port Faceplate Single Gang

Almond 2111009-1 Black 2111009-2 White 2111009-3 Gray 2111009-4

Electrical Ivory

1-2111009-1

Alpine White 1-2111009-3

3-Port Faceplate Single Gang

Almond 2111010-1 Black 2111010-2 White 2111010-3 Gray 2111010-4

Electrical Ivory

1-2111010-1

Alpine White 1-2111010-3

4-Port Faceplate Single Gang

Almond 2111011-1 Black 2111011-2 White 2111011-3 Gray 2111011-4

Page 44: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Electrical Ivory

1-2111011-1

Alpine White 1-2111011-3

6-Port Faceplate Single Gang

Almond 2111012-1 Black 2111012-2 White 2111012-3 Gray 2111012-4

Electrical Ivory

1-2111012-1

Alpine White 1-2111012-3

6-Port Faceplate Double Gang

Almond 2111013-1 Black 2111013-2 White 2111013-3 Gray 2111013-4

Electrical Ivory

1-2111013-1

Alpine White 1-2111013-3

8-Port Faceplate Double Gang

Almond 2111014-1 Black 2111014-2 White 2111014-3 Gray 2111014-4

Electrical Ivory

1-2111014-1

Alpine White 1-2111014-3

12-Port Faceplate Single Gang

Almond 2111015-1 Black 2111015-2 White 2111015-3 Gray 2111015-4

Electrical Ivory

1-2111015-1

Alpine White 1-2111015-3

Hideaway, Multimedia, 4-port Double Gang

Almond 1479946-1 Black 1479946-2 White 1479946-3 Gray 1479946-4

Electrical Ivory 1-1479946-1

TABLE [1] FACEPLATE PART NUMBERS

Page 45: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

3. Modular Furniture Outlets

a. Modular furniture faceplates shall be compatible with the modular furniture brand. [FLEX-MODE faceplates shall be made of polycarbonate molding compound, [almond, black, or gray] in color (if FLEX-MODE faceplates are used)]. [SL Series Furniture Faceplates shall be made of polycarbonate molding compound, [almond, black, or gray] in color (if SL Series furniture faceplates are used)].

b. The faceplate(s) shall be mounted in the appropriate knockout(s) in the furniture

channel. Modular furniture faceplates shall be TE Connectivity product part number [see Table 2].

Description Port Count

Part Numbers

Almond Black White Gray Electrical Ivory

FLEX-MODE Modular Furniture Faceplate, Flush

Blank 558471-2 558471-1 - 558471-4 - 2 558106-2 558106-1 - 558106-4 - 3 558107-2 558107-1 558107-4

SL Series 4 1933134-2 1933134-1 - 1933134-4 -

FLEX-MODE Modular Furniture Faceplate, Flush, for Herman Miller furniture

4 558357-2 558357-1 - 558357-4 -

FLEX-MODE Modular Furniture Faceplate, Standard, for Herman Miller furniture

4 558191-2 558191-1 - 558191-4 -

2 569127-2 569127-1 - 569127-4 -

TABLE [2]

MODULAR FURNITURE FACEPLATE PART NUMBERS

PART 3 EXECUTION 3.00 INSTALLATION

A. Install all systems in accordance with manufacturer’s printed instructions.

FLEX-MODE 2-Port Faceplate

Page 46: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

SECTION 7

Communications Patch Cords, Station Cords, and Cross-Connect Wire

PART 1 GENERAL

1.01 SUMMARY

A. Communications Patch Cords, Station Cords, and Cross-Connect Wire

1. Data and voice cable assemblies for the horizontal cross-connect and the workstation

shall be Category 6 assemblies. Cable assemblies shall be factory-assembled by the manufacturer of the cabling system.

[a]. Each telecommunications room (TR) shall require [8-, 10-, and/or 12-foot] cable

assemblies to connect between the horizontal data patch panels and network equipment. The total quantity of cable assemblies required in each TR shall be equally divided between the three assembly lengths. Each workstation shall require [one or two] [10-foot] cable assemblies for Data.

[b]. [Voice and data] cable assemblies used in each TR for horizontal cross-connect

shall be [HighBand Plug to HighBand plug (wiring block to wiring block), HighBand plug to RJ45 (wiring block to panel), or a standard RJ45 cable assembly for panel to panel cross-connect.] [Voice and data] cable assemblies at each workstation shall be standard RJ45 assemblies. Each workstation shall require [one] [10-foot] cable assembly for voice. [Each workstation shall require [one or two] [10-foot] cable assemblies for Data.]

2. Data backbone cross-connect assemblies in the MC and TR shall be fiber optic cable

assemblies factory-terminated using duplex [OM3 50/125µm or single-mode] cable. Data backbone cross-connect optical fiber cable assemblies shall be duplex LC to [SC, ST, MTRJ, or LC duplex] (depending upon the electronic interface).

Page 47: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

PART 2 PRODUCTS

2.00 MANUFACTURED COMPONENTS

A. TE Connectivity Product Options

1. Category 6 Patch Cords

a. Voice cross-connect and workstation cable assemblies shall be constructed with [RJ45 modular plugs and/or HighBand plugs]. The cable assemblies shall utilize colored cable and "snagless" cable boots. Cable assemblies shall meet the category 6 performance requirements of ANSI/TIA-568-C.2 and be factory-assembled.

b. Voice cross-connect cable assemblies shall be black in color. Cross-connect data

cable assemblies shall be TE Connectivity product part number(s) [Table 1].

c. Voice workstation cable assemblies shall be black in color. Voice workstation cable assemblies shall be TE Connectivity product part number(s) [Table 1].

d. Data cross-connect and workstation cable assemblies shall be constructed using

[RJ45 modular plugs and/or HighBand plugs]. The cable assemblies shall utilize colored cable and "snagless" cable boots. Cable assemblies shall comply with ANSI/TIA-568-C.2 category 6 performance requirements and shall be factory-assembled.

e. Cross-connect data cable assemblies shall be black in color. Cross-connect data

cable assemblies shall be TE Connectivity product part number(s) [Table 1].

f. Workstation data cable assemblies shall be black in color. Workstation data cable assemblies shall be TE Connectivity product part number(s) [Tables 1&2].

Slim Line

HighBand

Page 48: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Description Left Connector

Right Connector Pair Count Color Length (ft) Part Number

Category 6, Slim Line Cable Assemblies RJ45 RJ45 4-Pair

Black ---- TCPC-6RUVB-BKYYF

Gray ---- TCPC-6RUVB-GYYYF

Blue ---- TCPC-6RUVB-BLYYF

Green ---- TCPC-6RUVB-GNYYF

Red ---- TCPC-6RUVB-RDYYF

White ---- TCPC-6RUVB-WTYYF

Yellow ---- TCPC-6RUVB-YLYYF

Orange ---- TCPC-6RUVB-ORYYF

Violet ---- TCPC-6RUVB-VTYYF

YY DENOTES LENGTH IN FEET: EXAMPLE 02 = 2’, 03 = 3’

TABLE [1]

CABLE ASSEMBLY PART NUMBERS

Description Left Connector

Right Connector Pair Count Color Length (ft) Part Number

Category 6, HighBand Cable Assemblies

Rear Rear 4-pair Blue ---- 6451 2 701C-XX

Rear RJ45 4-pair Blue ---- 6451 2 700C-XX

Front Front 1-pair Blue ---- 6451 2 702-XX

Front Front 4-pair Blue ---- 6451 2 703C-XX

Front RJ45 4-pair Blue ---- 6451 2 704C-XX

XX DENOTES LENGTH IN FEET: 10 = 4, 20 = 7, 30 = 10, 40 = 15

TABLE [2] CABLE ASSEMBLY PART NUMBERS

Page 49: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

2. Cable Assemblies for Backbone Data Circuits

a. Backbone data cable assemblies shall be optical fiber assemblies factory-

terminated using duplex [OM3 50/125um or Single-mode] cable.

b. Optical fiber cable assemblies shall be duplex LC to [Duplex LC, MTRJ, ST, or SC] (depending upon the electronic interface).

c. Optical fiber cable assemblies shall be [riser or plenum] rated.

d. Optical fiber cable assemblies shall be TE Connectivity product part number(s)

[Table 3].

(Replace R with P for plenum rated fiber cable assemblies)

Connector End 1

Fiber Type Connector End 2

Standard MT-RJ Duplex SC Duplex LC Dual ST

Duplex LC OM3 50/125um

PAT-LCMC-R30CxxxM

PAT-LCSC-R30CxxxM

PAT-LCLC-R30CxxxM

PAT-LCTC-R30CxxxM

Duplex LC Single-mode PAT-LCMC-RS0CxxxM

PAT-LCSC-RS0CxxxM

PAT-LCLC-RS0CxxxM

PAT-LCTC-RS0CxxxM

XXX DENOTES LENGTH IN METERS

TABLE [3] FIBER OPTIC CABLE ASSEMBLY PART NUMBERS

PART 3 EXECUTION 3.03 INSTALLATION

A. Install all systems in accordance with manufacturer’s printed instructions.

Page 50: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

SECTION 8

Additional Information

8.0 FIRE STOP

All penetrations through fire rated building structures (walls and floors) shall be sealed with an appropriate fire stop system and labeled in accordance with NFPA, local, and/or state codes. This requirement applies to through penetrations (complete penetration) and membrane penetrations (through one side of a hollow fire rated structure). Any penetrating items i.e., riser slots and sleeves, cables, conduit, cable tray, and raceways, etc. shall be properly fire stopped. Contractors shall follow NFPA, state, and/or local code guidelines including UL Classified to ASTM E814 (UL 1479) and shall be approved by a qualified Professional Engineer (PE), licensed (actual or reciprocal) in the state where the work is to be performed. A drawing showing the proposed fire stopped system, stamped/embossed by the cognizant PE shall be provided to the Owner’s Technical Representative prior to installing the fire stop system(s). If needed, check with FM Global ’s publications (FM Global – TE Insurance – Check with FM Team).

8.1 FIRE STOP SYSTEM INSTALLATION

All fire stop systems shall be installed in accordance with the manufacturer’s recommendations and shall be completely installed and available for inspection by the local inspection authorities prior to or after cabling system acceptance; depends on items being installed.

9.0 GROUNDING AND BONDING

The facility shall be equipped with a Telecommunications Bonding Backbone (TBB). This backbone shall be used to ground all telecommunications cable shields, equipment, racks, cabinets, raceways, and other associated hardware that has the potential for acting as a current carrying conductor. The TBB shall be installed independent of the buildings electrical and building ground and shall be designed in accordance with the recommendations contained in the Telecommunications Bonding and Grounding Standard J-STD-607A. The main entrance facility/equipment room in each building shall be equipped with a telecommunications main grounding bus bar (TMGB). Each telecommunications closet shall be provided with a telecommunications ground bus bar (TGB). The TMGB shall be connected to the building electrical entrance grounding facility. The intent of this system is to provide a grounding system that is equal in potential to the building electrical ground system. Therefore, ground loop current potential is minimized between telecommunications equipment and the electrical system to which it is attached.

Page 51: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

9.1 PRODUCT SPECIFICATIONS

All racks, metallic backboards, cable sheaths, metallic strength members, splice cases, cable trays, etc. entering or residing in the TR or ER shall be grounded to the respective TGB or TMGB using a minimum #6 AWG stranded copper bonding conductor and compression connectors. Where metallic panels attached to the rack do not have sufficient metal to metal contact to provide an adequate path to ground, they shall be bonded to the rack using a minimum #14 AWG copper conductor. The copper conductor size shall be upgraded based on the largest power conductor feeding any rack mount equipment. The conductor shall be continuous; attaching all isolated components in a daisy chain fashion from top to bottom and bonded to the rack using the appropriate compression connector. All wires used for telecommunications grounding purposes shall be identified with a green insulation. Non-insulated wires shall be identified at each termination point with a wrap of green tape. All cables and bus bars shall be identified and labeled in accordance with the System Documentation Section of this specification.

9.2 GROUND SYSTEM INSTALLATION

The TBB shall be designed and/or approved by a qualified PE, licensed (actual or reciprocal) in the state that the work is to be performed. (Check with FM Team) The TBB shall adhere to the recommendations of the J-STD-607A standards, and shall be installed in accordance with best industry practices. Installation and termination of the main bonding conductor to the building service entrance ground, at a minimum, shall be performed by a licensed electrical contractor.

10.0 DOCUMENTATION

The following section describes the installation, administration, testing, and as-built documentation required to be produced and/or maintained by the contractor during the course of the installation.

10.1 CABLING SYSTEM LABELING

Customer will negotiate an appropriate labeling scheme with the contractor. The labeling system shall designate the cables origin and destination and a unique identifier for the cable within the system. Racks and patch panels shall be labeled to identify the location within the cabling system infrastructure. All labeling information shall be recorded on the as-built drawings and all test documents shall reflect the appropriate labeling scheme. All label printing will be machine generated using indelible ink ribbons or cartridges. Self-laminating labels will be used on cable jackets, appropriately sized to the outside diameter of the cable, and placed within view at the termination point on each end. Outlet labels will be the manufacturer’s labels provided with the outlet assembly.

Page 52: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

Labeling In order to insure the Uniform Wiring can be managed, a uniform numbering plan must be adhered to in all TE Connectivity buildings. It is our intention to keep all numbering plans as simple as possible. All cables shall be labeled as their respective cable number plus the letter "D" for data, "V" for voice, and "F" for fiber.

A. Patch Panels Twisted Pair - Data: 24 and 48 port 4-PR-110 SL style patch panels will be used for all new buildings and for renovation projects installed on 84" racks for all Data station cabling (reference scope of work). Patch panels will be labeled starting with 01. Ports on those panels will remain 1-48. Station labeling shall be as follows: Example 1A01D01 1 = Floor A = Telecommunications Room (IDF) 01 = Patch Panel D = Data 01-48= Patch Panel Port Example 1AA01D01 1 = Floor AA = Main Distribution Frame (MDF) 01 = Patch Panel D = Data 01-48= Patch Panel Port C. 110 Cross Connect Voice Frame:

AMP NETCONNECT 110Connect XC Connect System will be used for all voice cabling installations. The 110 frame will be labeled starting with 01 and numbering consecutively 1-48. Example 1A01V01

1 = Floor A = Telecommunications Room (IDF) 01 = First 48 station cables V = Voice

01-48= Represents 48 individual station cables

Voice station cable number shall match data station cable as much as possible. Example 1A01V48 and 1A01D48 to the same outlet location.

Page 53: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

10.2 AS-BUILT DRAWINGS

If requested the installation contractor can be provided with layout drawings at the start of the project. Contractor will provide any changes to layout as requested. The Contractor shall provide the central drawing set, printed plus electronic, to the owner at the conclusion of the project. The electronic file format shall be AutoCAD compatible drawing (or as directed). The marked up drawing set will accurately depict the as-built status of the system including termination locations, cable routing, and all administration labeling for the cabling system. In addition, a narrative will be provided that describes any areas of difficulty encountered during the installation that could potentially cause problems to the telecommunications system.

10.3 TEST DOCUMENTATION

Test documentation from the contractor shall be provided upon request. Each major heading shall be further sectioned by test type. The test document shall detail the test method used and the specific settings of the equipment during the test.

11.0 WARRANTY AND SERVICES

If needed, TE Connectivity can provide warranty information covering the installed cabling system against defects in workmanship, components, and performance. If Contractor is NDI Certified = 25 year Labor Warranty.

11.1 INSTALLATION WARRANTY

The contractor shall warrant the cabling system against defects in workmanship for a 1 year period. The warranty shall cover all labor and materials necessary to correct a failed portion of the system and to demonstrate performance within the original installation specifications after repairs are accomplished. This warranty shall be provided at no additional cost to the owner.

11.2 CABLING SYSTEM WARRANTY

The contractor shall facilitate a 25-year performance warranty between the manufacturer and the Owner. An extended component warranty shall be provided which warrants functionality of all components used in the system for 25 years from the date of acceptance. The performance warranty shall warrant the installed horizontal copper, and both the horizontal and the backbone optical fiber portions of the cabling system. Copper links shall be warranted against the link performance minimum expected results defined in the TIA/EIA 568B Standard. Fiber optic links shall be warranted against the link and segment performance minimum expected results defined in the TIA/EIA 568B Standard.

Page 54: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

11.3 PROJECT MANAGEMENT / GENERAL

The contractor shall establish a single point of contact with Tyco Electronics who will be responsible for reporting progress and updating Tyco’s Technical Representative with issues that the Owner must address to facilitate the cabling system installation. The contractor’s POC shall provide daily written reports to Tyco’s Technical Representative detailing progress (unless otherwise directed). Requests for access to limited access or restricted areas shall be made (the day prior to the required access). Information critical to the completion of the task or project shall be communicated to the Tyco’s Technical Representative as the requirement becomes known. Casual information shall be passed during the scheduled progress report. The contractor shall maintain Tyco’s facility in a neat and orderly manner during the installation of the communications cabling system. Tyco’s facilities shall be maintained in broom clean condition at the completion of each work day. At the completion of work in each area, the contractor will perform a final cleaning of debris prior to moving the installation crew to the next work area.

12.0 CABLING SYSTEM ACCEPTANCE

Tyco Electronics’ Technical Representative will make periodic inspection of the project in progress. One inspection will be performed at the conclusion of cable pulling, prior to closing of the false ceiling, to inspect the method of cable routing and support, and the fire stopping of penetrations. A second inspection will be performed at completion of cable termination to validate that cables were dressed and terminated in accordance with TIA/EIA specifications for jacket removal and pair untwist, compliance with manufacturer’s minimum bend radius, and that cable ends are dressed neatly and orderly.

12.1 FINAL INSPECTION

Upon completion of the project, Tyco’s Technical Representative will perform a final inspection of the installed cabling system with the Contractor’s Project Foreman. The final inspection will be performed to validate that all horizontal and backbone cables were installed as defined in the drawing package, and that the installation meets the aesthetic expectations of Tyco Electronics.

12.2 TEST VERIFICATION

Upon receipt of the test documentation, Tyco Electronics reserves the right to perform spot testing of a representative sample of the cabling system to validate test results provided in the test document. Tyco testing will use the same method employed by the contractor, and minor variations will be allowed to account for differences in test equipment. If significant discrepancies are found the Contractor will be notified for resolution.

12.2 SYSTEM PERFORMANCE

During the three week period between final inspection and delivery of the test and as-built documentation, Tyco can activate the cabling system. Tyco Electronics will validate operation of the cabling system during this period.

Page 55: Telecommunications Structured Cabling System … standards. ... ANSI/TIA/EIA-606-B, Administration Standard for the Telecommunications Infrastructure of ... TIA-1179, Healthcare Facility

12.4 FINAL ACCEPTANCE

Completion of: the installation; in-progress and final inspections; receipt of the test and as-built documentation; and successful performance of the system for a two week period will constitute acceptance of the system.