IEEE 802.3 HSSG Telecommunications Infrastructure Telecommunications Infrastructure Standard for Data Centers Standard for Data Centers ANSI/TIA ANSI/TIA - - 942 942 Chris DiMinico [email protected] MC Communications

Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

Embed Size (px)

DESCRIPTION

Describes ANSI/TIA-942 TelecommunicationsInfrastructure Standard for Data Centers

Citation preview

Page 1: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Telecommunications Infrastructure Telecommunications Infrastructure Standard for Data CentersStandard for Data Centers

ANSI/TIAANSI/TIA--942942

Chris [email protected] Communications

Page 2: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Data Center StandardsANSI/TIAANSI/TIA--942 Telecommunications 942 Telecommunications Infrastructure Standard for Data Centers Infrastructure Standard for Data Centers

CoCo--chairs: Chris DiMinico & Jonathan Jew chairs: Chris DiMinico & Jonathan Jew Published 2005 Published 2005 –– available through TIA at available through TIA at www.tiaonline.orgwww.tiaonline.org

ANSI/NECA/BICSIANSI/NECA/BICSI--002 Data Center Design 002 Data Center Design and Implementation Best Practicesand Implementation Best Practices

coco--chairs: Jonathan Jew & John Kacperskichairs: Jonathan Jew & John Kacperskibest practices best practices –– complements TIAcomplements TIA--942 942 ––2007 target2007 target

Page 3: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Who Developed TIA-942?Developed by the TIA TRDeveloped by the TIA TR--42.1.1 Network 42.1.1 Network Distribution Nodes subcommittee as Project Distribution Nodes subcommittee as Project No. 3No. 3--00920092Participants included:Participants included:

Architecture & Engineering FirmsArchitecture & Engineering FirmsConsultantsConsultantsEnd UsersEnd UsersManufacturersManufacturers

Page 4: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Purpose of TIA-942Encourage early participation of telecom Encourage early participation of telecom designers in data center design processdesigners in data center design processFill a void by providing standards for planning Fill a void by providing standards for planning of data centers, computer rooms, server of data centers, computer rooms, server rooms, and similar spaces.rooms, and similar spaces.The standard encompasses much more than The standard encompasses much more than just telecommunications infrastructure.just telecommunications infrastructure.Close to half of the technical content deals Close to half of the technical content deals with facility specifications.with facility specifications.

Page 5: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Purpose of TIA-942Define a standard telecommunications Define a standard telecommunications infrastructure for data centersinfrastructure for data centers

Structured cabling system for data centers using Structured cabling system for data centers using standardized architecture and mediastandardized architecture and mediaAccommodates a wide range of applications (LAN, Accommodates a wide range of applications (LAN, WAN, SAN, channels, consoles)WAN, SAN, channels, consoles)Accommodates current and future protocols Accommodates current and future protocols (e.g., 10+ (e.g., 10+ GbEGbE ))Replaces unstructured pointReplaces unstructured point--toto--point cabling that point cabling that uses different cabling for different applicationsuses different cabling for different applications

Page 6: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Purpose of TIA-942Specifications for data center Specifications for data center telecommunications pathways and spacestelecommunications pathways and spacesRecommendations on media and distance for Recommendations on media and distance for applications over structured cabling applications over structured cabling Establish a standard for data center tiers to Establish a standard for data center tiers to replace several proprietary standards. The replace several proprietary standards. The TIA data center tier standard is:TIA data center tier standard is:•• A tool to evaluate existing data centersA tool to evaluate existing data centers•• A tool to communicate design A tool to communicate design

requirementsrequirements

Page 7: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Unstructured CablingH

eate

r -A/

C

Heater - A/CHeater - A/C Heater - A/C

247-7538

HALONABORTHALON

RELEASE

247-7543

HALONPANEL

LOCKER

TAPE RACK

NETWORKCABINET

H5

NETWORKCABINET

H4

NETWORKCABINET

H3

NETWORKCABINET

H2

NETWORKCABINET

H6

NETWORKCABINET

H7

NETWORKCABINET

H1

NETWORKCABINET

G4

NETWORKCABINET

G3

NETWORKCABINET

G2

NETWORKCABINET

G1

NETWORKCABINET

G5

TAB

LE

TAPE RACK

NET

WOR

KCA

BIN

ET

I8

NETW

ORK

CABI

NET

I7

NET

WOR

KC

ABIN

ETI6

NET

WOR

KCA

BIN

ET

I5

NETW

ORK

CAB

INET

I4

NETW

ORK

CAB

INET

I3

NETW

ORK

CAB

INET

I2

NET

WOR

KC

ABIN

ETI1

TAPE RACK

NETWORKCABINET

H8

NETWORKCABINET

G6

NETWORKCABINET

G7

NETWORKCABINET

F4

NETWORKCABINET

F3

NETWORKCABINET

F2

NETWORKCABINET

F5

LANCABINET

F1

NETWORKCABINET

F6

NETWORKCABINET

E5

NETWORKCABINET

E4

NETWORKCABINET

E3

NETWORKCABINET

E2

NETWORKCABINET

E1

NETWORKCABINET

E6

SAACABINET

D2

NETWORKCABINET

E 7IBMCAB

SAACABINET

D1

NETWORKCABINET

B5

NETWORKCABINET

B4

NETWORKCABINET

B3

NETWORKCABINET

B2

NETWORKCABINET

B1

NETWORKCABINET

B6

NETWORKCABINET

C5

NETWORKCABINET

C4

NETWORKCABINET

C3

NETWORKCABINET

C2

NETWORKCABINET

C1

NETWORKCABINET

C6

NETWORKCABINET

B7

CD ROMSCANNER

AT &T

DEFINITY

UNIT

HPPRINTER

NETWORKCABINET

A6

NETWORKCABINET

A5

NETWORKCABINET

A 4

NETWORKCABINET

A3

NETWORKCABINET

A2

TABLE247-7589

TABLE

CISCO

RO

UTE

RC

ONS

OLE

F/X

IBMDASD

IBMDASD

IBMAS-400

IBMAS-400

IBMS-390R34

IBM3746-900

IBM3745-17A

IBM3745-L13

IBM

3745-41D

IBM3745-A11

POM

ON

AA

/C U

NIT

#8

STO

RAG

EC

ABI

NE

T

DES

K

DESKSTORAGECABINET

PAC

BELL

CAB

INE

TA1

3174CABINET

TABLE STORAGECABINET

STORAGECABINET

LIEBERTPDU-C

3174CABINET

3174CABINET

3174CABINET

3174CABINET

3174CABINET

POMONAA/C UNIT

#6

POMONAA/C UNIT

#7

FI LE

CABINETFILE

CABI NET

FILE

CABINET

FILE

CABINET

G H I J K L M N O P Q R S T U V W X Y Z AA AB AC AD AE AF AG AH AI AJ AK AL AM AN AO AP AQ AR ASC D E FBA

2

1

3

4

5

6

7

8

9

10

11

12

13

14

15

16

NETWORK

INSTALL A CABLE WHEN YOU NEED IT (SINGLE-USE, UNORGANIZED CABLING)

Page 8: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Structured CablingH

eate

r -A

/C

Heater - A/CHeater - A/C Heater - A/C

247-7538

HALONABORTHALON

RELEASE

247-7543

HALONPANEL

LOCKER

TAPE RACK

NETWORKCABINET

H5

NETWORKCABINET

H4

NETWORKCABINET

H3

NETWORKCABINET

H2

NETWORKCABINET

H6

NETWORKCABINET

H7

NETWORKCABINET

H1

NETWORKCABINET

G4

NETWORKCABINET

G3

NETWORKCABINET

G2

NETWORKCABINET

G1

NETWORKCABINET

G5

TA

BLE

TAPE RACK

NETW

OR

KC

ABIN

ETI8

NET

WOR

KCA

BIN

ET

I7

NETW

OR

KCA

BIN

ETI6

NETW

ORK

CAB

INET

I5

NETW

ORK

CAB

INET

I4

NETW

ORK

CABI

NET

I3

NETW

ORK

CABI

NET

I2

NETW

OR

KC

ABIN

ETI1

TAPE RACK

NETWORKCABINET

H8

NETWORKCABINET

G6

NETWORKCABINET

G7

NETWORKCABINET

F4

NETWORKCABINET

F3

NETWORKCABINET

F2

NETWORKCABINET

F5

LANCABINET

F 1

NETWORKCABINET

F6

NETWORKCABINET

E5

NETWORKCABINET

E4

NETWORKCABINET

E3

NETWORKCABINET

E2

NETWORKCABINET

E1

NETWORKCABINET

E6

SAACABINET

D2

NETWORKCABINET

E7IBMCAB

SAACABINET

D1

NETWORKCABINET

B5

NETWORKCABINET

B4

NETWORKCABINET

B3

NETWORKCABINET

B2

NETWORKCABINET

B1

NETWORKCABINET

B6

NETWORKCABINET

C5

NETWORKCABINET

C4

NETWORKCABINET

C3

NETWORKCABINET

C2

NETWORKCABINET

C1

NETWORKCABINET

C6

NETWORKCABINET

B 7

CD ROMSCANNER

AT&TDEFINITY

UNIT

HPPRINTER

NETWORKCABINET

A6

NETWORKCABINET

A5

NETWORKCABINET

A4

NETWORKCABINET

A3

NETWORKCABINET

A2

TABLE247-7589

TABLE

CISC

O

RO

UTER

CO

NSO

LE

F/X

IBMDASD

IBMDASD

IBMAS-400

IBMAS-400

IBMS-390R34

IBM3746-900

IBM3745-17A

IBM3745-L13

IBM

3745-41D

IBM3745-A11

PO

MO

NA

A/C

UN

IT

#8

STO

RAG

EC

ABIN

ET

DESK

DESKSTORAGECABINET

PAC

BEL

LC

ABI

NE

TA

1

3174CABINET

TABLE STORAGECABINET

STORAGECABINET

LIEBERTPDU-C

3174CABINET

3174CABINET

3174CABINET

3174CABINET

3174CABINET

POMONAA/C UNIT

#6

POMONAA/C UNIT

#7

FILECABINET

FILECABINET

FIL ECABINET

FIL ECABINET

G H I J K L M N O P Q R S T U V W X Y Z AA AB AC AD AE AF AG AH AI AJ AK AL AM AN AO AP AQ AR ASC D E FBA

2

1

3

4

5

6

7

8

9

10

11

12

13

14

15

16

FIBER MDF& CORE

COPPER MDF

IDFIDF

IDF

IDF

IDF

STRUCTURED CABLING SYSTEM (ORGANIZED, REUSABLE, FLEXIBLE CABLING)

IDF

IDF IDF

IDFIDF

Mainframe

IBM 3745s

Page 9: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Cabling DesignCabling DesignFacility DesignFacility DesignNetwork DesignNetwork Design

Informative annex’s: Provide best practicesInformative annex’s: Provide best practicesAnnex A Annex A -- Cabling Design ConsiderationsCabling Design ConsiderationsAnnex BAnnex B-- Telecommunications infrastructure Telecommunications infrastructure administrationadministrationAnnex CAnnex C--Access provider informationAccess provider informationAnnex DAnnex D-- Coordination of equipment plans with Coordination of equipment plans with other engineersother engineersAnnex EAnnex E-- Data center space considerationsData center space considerationsAnnex FAnnex F-- Site selectionSite selection

Design Elements

Page 10: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Design ElementsCabling Design:Cabling Design:

Copper and fiber cabling performanceCopper and fiber cabling performanceConnectors, cables, distribution hardwareConnectors, cables, distribution hardwareCabling distancesCabling distancesSpace managementSpace management

Facility Design:Facility Design:

Data center sizingData center sizingPower distribution methodologiesPower distribution methodologiesPathways and spacesPathways and spacesHVAC, security, operations, and administration.HVAC, security, operations, and administration.Flexibility, scalability, reliability and space Flexibility, scalability, reliability and space managementmanagement

Page 11: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Design Elements

Network Design:Network Design:

Support of legacy systemsSupport of legacy systemsEnable rapid deployment of new and emerging Enable rapid deployment of new and emerging technologies such as 10 technologies such as 10 GbEGbE and 10+ and 10+ GbEGbEcopper and fiber applications. copper and fiber applications.

Page 12: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Relationship of SpacesBUILDING SITE

DATA CENTERDATA CENTERELECTRICAL &MECHANICAL ROOMS

SUPPORTSTAFFOFFICES

OPERATIONSCENTER

STORAGE ROOMS& LOADING DOCKS

BUILDING SHELLGENERAL OFFICESPACE

OFFICE BUILDINGSUPPORT SPACE

ENTRANCEROOM(S)

TELECOM ROOMS &EQUIPMENT ROOMSfor spaces outside datacenter

COMPUTER ROOM

TELECOM ROOM(S)for data centersupport spaces

Page 13: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

MC

IC IC IC IC

Entrance Facility

MC

Carriers Carriers

HC

Offices, OperationsCenter, Support Rooms

Data Center

HC HC HC

Carriers

Carriers

Active Equipinterconnect

Active EquipStorage Area Devices

interconnect

Active Equip

interconnect

Active Equipinterconnect

Active Equipinterconnect

Active Equipinterconnect

Secondary Entrance Room

Entrance Room

Back boneCabling

Active Equipinterconnect

ZoneDistributionHorizontal

Cabling

Data Center Topology

Page 14: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

TIA-942 SpacesEntrance Room (ER) Entrance Room (ER) -- location of interface location of interface with campus and carrier entrance facilitieswith campus and carrier entrance facilitiesMain Distribution Area (MDA)Main Distribution Area (MDA) –– location of location of main crossmain cross--connect (MC)connect (MC)Horizontal Distribution Area (HDA)Horizontal Distribution Area (HDA) –– location location of horizontal crossof horizontal cross--connect (HC)connect (HC)Zone Distribution Area (ZDA)Zone Distribution Area (ZDA) –– location of location of zone outlet (ZO) or consolidation point (CP)zone outlet (ZO) or consolidation point (CP)Equipment Distribution Area (EDA)Equipment Distribution Area (EDA) –– location location of equipment cabinets and racksof equipment cabinets and racks

Page 15: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

MC

IC IC

MC

HC HC

Active Equipinterconnect Active Equip

interconnect

Active Equipinterconnect

ZoneDistribution

Area

HorizontalCabling

MainDistribution

Area

HorizontalDistribution

Area

EquipmentDistribution

Area

BackboneCabling

Data Center Cabling

Horizontal cabling is the cabling from the horizontal cross-connect (in the main distribution area or horizontal distribution area) to the outlet in the equipment distribution area or zone distribution area.

Page 16: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Recognized Cables:Recognized Cables:a) 100-ohm twisted-pair cable (ANSI/TIA/EIA-568-B.2), category 6 recommended (ANSI/TIA/EIA-568-B.2-1)b) multimode optical fiber cable, either 62.5/125 micron or 50/125 micron (ANSI/TIA/EIA-568-B.3), 50/125 micron 850 nm laser optimized multimode fiber is recommended (ANSI/TIA-568-3-1)c) singlemode optical fiber cable (ANSI/TIA/EIA-568-B.3)d) 75-ohm (734 and 735 type) coaxial cable (Telcordia Technologies GR-139-CORE)

Horizontal and Backbone Cabling

Page 17: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Horizontal cabling distances The maximum horizontal distance is 90 m The maximum horizontal distance is 90 m independent of media type.independent of media type.The maximum channel distance including The maximum channel distance including equipment cords is 100 m. equipment cords is 100 m. The maximum cabling distance in a data The maximum cabling distance in a data center not containing a horizontal center not containing a horizontal distribution area is:distribution area is:

300 m for an optical fiber channel including 300 m for an optical fiber channel including equipment cords.equipment cords.100 m for copper cabling including equipment 100 m for copper cabling including equipment cords. cords.

Page 18: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Backbone CablingIncludes cabling from MDA to ER, HDAIncludes cabling from MDA to ER, HDAOptional cabling between Optional cabling between HDAsHDAs allowedallowedMaximum backbone cable lengths depend on Maximum backbone cable lengths depend on applications to be supportedapplications to be supportedCentralized optical fiber cabling supported Centralized optical fiber cabling supported with interconnect, splice, or pullwith interconnect, splice, or pull--through at through at the HDAthe HDAStar topology with no intermediate crossStar topology with no intermediate cross--connectsconnectsVarious topologies permit redundancy and Various topologies permit redundancy and flexibility to support various data center sizesflexibility to support various data center sizes

Page 19: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Computer Room & Entrance Room Requirements

Min clear height of 2.6m/8.5 ftMin clear height of 2.6m/8.5 ftMin door size 1m/3ft wide 2.13/7ft highMin door size 1m/3ft wide 2.13/7ft highMin dist floor loading 7.2 kPA/150lbf/ft2, Min dist floor loading 7.2 kPA/150lbf/ft2, recommended min 12 kPA/250 lbf/ft2recommended min 12 kPA/250 lbf/ft220 degrees C to 25 degrees C20 degrees C to 25 degrees C40% to 55% relative humidity (reduces ESD)40% to 55% relative humidity (reduces ESD)Any sprinkler systems must be preAny sprinkler systems must be pre--action action systemsystemCommon bonding network (CBN) Common bonding network (CBN) ––equipotential ground referenceequipotential ground reference

Page 20: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Main Distribution AreaLocation of Main CrossLocation of Main Cross--Connect (MC), the Connect (MC), the central point of distribution for data center central point of distribution for data center structured cabling systemstructured cabling systemCentrally located to avoid exceeding Centrally located to avoid exceeding maximum distance restrictions (typically for Emaximum distance restrictions (typically for E--1s, E1s, E--3s, T3s, T--1s and T1s and T--3s)3s)Install separate racks for Fiber, UTP, and Install separate racks for Fiber, UTP, and coaxial cable distributioncoaxial cable distribution

Page 21: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Horizontal Distribution AreaLocation of Horizontal CrossLocation of Horizontal Cross--Connect (HC), Connect (HC), the distribution point for cabling to equipment the distribution point for cabling to equipment distribution area distribution area Distribution LAN, SAN, KVM switches and Distribution LAN, SAN, KVM switches and console servers located in HDAconsole servers located in HDAMDA may also include an HC for nearby MDA may also include an HC for nearby equipment distribution areaequipment distribution areaNumber of Number of HDAsHDAs depends on the density of depends on the density of cabling and the size of the data centercabling and the size of the data center

Page 22: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Horizontal Distribution AreaThe capacity of the cable tray system and the The capacity of the cable tray system and the size of the crosssize of the cross--connect creates practical connect creates practical limits on the size of the HClimits on the size of the HCGuideline is maximum of 2,000 4Guideline is maximum of 2,000 4--pair UTP or pair UTP or coax cable terminations per HDAcoax cable terminations per HDAArrange patch bays to minimize patch cable Arrange patch bays to minimize patch cable lengths and to simplify cable managementlengths and to simplify cable management

Separate racks for fiber, UTP, and coaxSeparate racks for fiber, UTP, and coaxLocate switches and patch panels to Locate switches and patch panels to minimize patch cord lengthsminimize patch cord lengths

Page 23: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Zone Distribution Area Rack, cabinet, or under floor enclosure that houses a Rack, cabinet, or under floor enclosure that houses a zone outlet (ZO) or consolidation point (CP) zone outlet (ZO) or consolidation point (CP) ZO ZO -- structured cabling termination for floorstructured cabling termination for floor--standing standing equipment that cannot accept patch panels (e.g. equipment that cannot accept patch panels (e.g. mainframes and large servers).mainframes and large servers).CP CP -- intermediate termination point (e.g. cabling to intermediate termination point (e.g. cabling to areas where floor plan is uncertain or dynamic)areas where floor plan is uncertain or dynamic)No crossNo cross--connects within the ZDAconnects within the ZDANo active equipment shall be located in the ZDANo active equipment shall be located in the ZDAMaximum of 144 connections in a ZDAMaximum of 144 connections in a ZDAMaximum of one ZDA within a horizontal cable runMaximum of one ZDA within a horizontal cable run

Page 24: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Equipment CabinetsFront rails of cabinets must be recessed to provide adequate room for patch cables and wire managersRecommend 1-to-1 ratio of patching to cable managementArrange switches and patch panels to minimize patching between cabinets & racksPerforated tiles at front of cabinetsOne edge of cabinets placed at edge of tile

Page 25: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Raised FloorBetter appearance than overhead cabling.Better appearance than overhead cabling.Allows higher power densities, better control Allows higher power densities, better control of cooling, and more flexibility in location of of cooling, and more flexibility in location of cooling equipmentcooling equipmentMost standMost stand--alone computer systems are alone computer systems are designed for cabling from belowdesigned for cabling from belowCoordinate under floor cabling with Coordinate under floor cabling with mechanical & electrical engineers mechanical & electrical engineers Recommend wire basket cable trays in hot Recommend wire basket cable trays in hot aisles for telecom cablingaisles for telecom cabling

Page 26: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Example of Wire Basket Cable Trays For Cabling Under Raised Floor

24"On Center

RAISED FLOOR TILE

SUPPORT STRUT

36"

24"

4"

9"

FIBER

5"

SUPPORT STRUT

18"COPPER

CABLING4"

13.5"

DIVIDER

FIBER

5"18"COPPER

CABLING

12"

1.375"

1"

1"

Open Area

Page 27: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Overhead Cable TraysLess expensive than raised floor systemsLess expensive than raised floor systemsCable trays can be attached to the top of Cable trays can be attached to the top of racks and cabinets (if they are uniform in racks and cabinets (if they are uniform in height) height) Cable trays suspended from the ceiling Cable trays suspended from the ceiling provides more flexibility for supporting provides more flexibility for supporting cabinets/racks of various heights and for cabinets/racks of various heights and for adding and removing cabinets/racks.adding and removing cabinets/racks.Cable trays can be installed with several Cable trays can be installed with several layerslayersCoordinate location with lighting, ducts, Coordinate location with lighting, ducts, overhead conduits, overhead power overhead conduits, overhead power distributiondistribution

Page 28: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Overhead Cable Tray Example3 Layer cable tray system:3 Layer cable tray system:

Bottom layer Bottom layer –– signal signal Middle layer Middle layer –– power power Top layer Top layer –– fiberfiberSignal Reference Grid in Signal Reference Grid in brackets attached to lower brackets attached to lower layer of trayslayer of traysFiber patch cables may be Fiber patch cables may be in fiber duct attached to in fiber duct attached to threaded rodsthreaded rods

Page 29: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Infrastructure Administration

Informative annex with TIAInformative annex with TIA--606606--A standards A standards compliant labeling scheme for all compliant labeling scheme for all components.components.Labeling scheme extended for use in data Labeling scheme extended for use in data centerscentersCabinets and racks labeled by location using Cabinets and racks labeled by location using tile grid or row/position identifierstile grid or row/position identifiersAll cabinets, racks, patch panels, cables, and All cabinets, racks, patch panels, cables, and patch cords should be labeledpatch cords should be labeled

Page 30: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Labeling ExampleAK AL AM AN AO AP AQ AR AS AT AU AV AW AX AY AZ BA BB BC BDAE AF AG AH AI AJAC ADAB

09

10

11

12

13

AA

01

02

03

04

05

06

07

08

"X" COORDINATE

"Y" COORDINATE

CABINET AJ05

RIGHTFRONT

CORNER CABINET AQ03

Cat 6 x 24

01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

AJ05-A to AQ03-B Ports 01-24

A A

Patch Panel for 24 Cat 6 from 1st Panel in Cab AJ05 to 2nd Panel in Cab AQ03

Page 31: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Site Selection

Informative annex with guidelines for Informative annex with guidelines for selection of a site for a data centerselection of a site for a data center

ArchitecturalArchitecturalElectricalElectricalMechanicalMechanicalTelecommunicationsTelecommunicationsSecuritySecurityOtherOther

Page 32: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Facilities Specifications & TiersInformative annex with general architectural, Informative annex with general architectural, structural, electrical, mechanical, and structural, electrical, mechanical, and telecommunications recommendations requirements telecommunications recommendations requirements Annex includes detailed architectural, security, Annex includes detailed architectural, security, electrical, mechanical, and telecommunications electrical, mechanical, and telecommunications recommendations for each Tierrecommendations for each TierRecommended specifications by tier are a uniform Recommended specifications by tier are a uniform way to rate aspects of a data center design and are a way to rate aspects of a data center design and are a starting point for initiating design requirements with starting point for initiating design requirements with qualified architects and engineersqualified architects and engineers

Page 33: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Data Center TiersTier 1 Tier 1 –– basic data center basic data center

no redundancyno redundancyTier 2 Tier 2 –– redundant componentsredundant components

Single distribution path with redundant Single distribution path with redundant componentscomponents

Tier 3 Tier 3 –– concurrently maintainableconcurrently maintainableMultiple distribution paths with only one Multiple distribution paths with only one activeactive

Tier 4 Tier 4 –– fault tolerantfault tolerantMultiple active distribution pathsMultiple active distribution paths

Page 34: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Redundant Topologies

Primary EntranceRoom

(Tier 1 and higher)

Horiz Dist Area

Equip DistArea

ComputerRoom

Horiz Dist AreaZone Dist Area

Offices, OperationsCenter, Support

Rooms

Telecom Room

OptionalCabling

Main Dist Area(Tier 1 and higher)

Horiz Dist Area

Equip DistArea

Equip DistArea

SecondaryEntrance Room

(Tier 3 and higher)

Secondary DistArea

(Optional for Tier 4)

Carriers

Primary CustomerMaintenance Hole(Tier 1 and higher)

SecondaryCustomer

Maintenance Hole(Tier 2 and higher)

Tier 1

Tier 3

Tier 1

Tier 4

Tier 3

Tier 2

Tier 4

Tier 3

Tier 4

Carriers Carriers Carriers

Data Center

Tier 3

Page 35: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

Data Center TiersHigher tiers correspond to higher availability, but also Higher tiers correspond to higher availability, but also have higher construction costs have higher construction costs Data Center can have different tier ratings for Data Center can have different tier ratings for different portions of its infrastructure (architectural, different portions of its infrastructure (architectural, security, mechanical, electrical, telecommunications)security, mechanical, electrical, telecommunications)The overall rating for the data center is equal to the The overall rating for the data center is equal to the lowest tier rating lowest tier rating Capacity of systems may need to be upgraded to Capacity of systems may need to be upgraded to maintain tier rating as data center load increasesmaintain tier rating as data center load increasesHuman error and operating procedures have a major Human error and operating procedures have a major impact on availabilityimpact on availability

Page 36: Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

IEEE 802.3 HSSG

ConclusionTIATIA--942 is the first standard to specifically addresses data 942 is the first standard to specifically addresses data center infrastructure.center infrastructure.Primarily a telecom infrastructure standard, but about half Primarily a telecom infrastructure standard, but about half of the content deals with facility requirements.of the content deals with facility requirements.Provides a flexible and manageable structured cabling Provides a flexible and manageable structured cabling system using standard media.system using standard media.Builds on existing standards, when applicableBuilds on existing standards, when applicableGuidelines on a wide range of subjects useful to someone Guidelines on a wide range of subjects useful to someone designing or managing a data center.designing or managing a data center.An official An official tieringtiering standard for determining the quality of a standard for determining the quality of a center. A way to objectively compare one center with center. A way to objectively compare one center with another.another.