    SWITCH YARD

    No. of bays 12 (Including 1 for future)

    Generator bays 4

    Bhilwara line bays 2

    Dausa line bays 2

    Kota line bay 1

    Spare bay 1

    Bus caupler bay 1

    Bus transfer section bay 1

    Bus switching scheme Double main and transfer bus

    Double main busACSR Moose conductor spaced 250 mm.

    in square formation

    Rated Current 1250 Amp

    Fault Current 31.5 KA

    Transfer bus

    2 Moose Conductor used for transfer of one

    feeder at a time through transfer bus

    breaker spaced at 250 mm

    Minimum clearance

    Phase to Phase Clearance 2700 mm

    Phase to Earth clearance 2300 mm

    Ground clearance 2580 mm

    Equipment bus height 6200 mm from plinth level

    Section clearance 4500 mm

  • 7/29/2019 switch yard NTPC anta

    2/6

    LIST OF EQUIPMENTS

    Circuit breaker SF6

    Make ABB Germany-10 Nos ABB India- 1 No

    Type ELF SL-5-2 and ELF SL-4-1

    Rating 245/220 kv,2000 A

    Breaking Capacity 40 kv

    Insulation Level 1050 kv (Peak)

    No. of Breaks per pole Two

    Type of Operating Mechanism Closing : Spring, Opening : Hydraulic

    Gas Pressure 7 Kg/cm

    Closing time 70m Sec.

    Opening time 20 m Sec.

    Isolator (without E/S)

    Make S & S Madras

    No. of Provided 10

    Type RC 300 Horizontal Centre Break, Tandem

    Rating 245 kv, 1250 A

    No. of Poles 3

    Rated SC with stand Current 31.5 kA, 1 Sec.

  • 7/29/2019 switch yard NTPC anta

    3/6

    Isolator (With Single E/S)

    Make S & S Madras

    No. of Provided 10

    Type RC 300 Horizontal Centre Break

    Rating 245 kv, 1250 A

    No. of Poles 3

    Rated SC with stand Current 31.5 kA, 1 Sec.

    Isolator (With Double E/S)

    Make S & S Madras

    No. of Provided 2000 A-2 Nos., 1250 A - 10 Nos

    Type RC 300 Horizontal Centre Break

    Rating 245 kv, 2000 A

    No. of Poles 3

    Rated SC with stand Current 31.5 kA, 1 Sec.

    Current Transformer

    Make ABB India

    No. of Provided 30 Nos (1200-600/1A), 3 No (2000-1000/1)

    Type TMBR

    Rating 245 kv, 1245 A

    No. of Cores 5

  • 7/29/2019 switch yard NTPC anta

    4/6

    CVTs

    Make ABB India

    No. of Provided 21

    Type WP 245 N, Single Phase

    Rating 245 kv

    No. of Cores 3

    Ratio 220/3 kv/110/3 V

    Capacitance in pF-Primary 4868

    Capacitance in pF-Intermediate 48400

    Capacitance in pF-Effective 4400 + 10%, -5%

    Lightening

    Make WSI

    No. of Provided 27

    Type CPL-II, Heavy duty Station class

    Rating 198 kv, 11 kA

    Minimum discharge Capacity 5 kj/kv

  • 7/29/2019 switch yard NTPC anta

    5/6

    Bus Post Insulator

    Make WSI Bangalore

    Nos Provided 71

    Type Solid Core 220 kv

    Wave Trap

    Make WSI

    Nos Provided 6

    Rating 0.5 mH, 1250 A, 220 kv

    Contral & Relay Panel

    Make ABB India

    Nos. Provided 2

    Bay Marshaling Kiosk

    Make Saravana, Switchgear

    Nos. Provided 11

    Marshaling Cubical (CT/CVTs)

    Make Saravana, Switchgear

    Nos Provided 11 (CT), 7 (CVT)

  • 7/29/2019 switch yard NTPC anta

    6/6

    Batteries for PLCC System

    Make Exide Ltd.

    Type Lead acid Cell, 2 Volts/Cell

    Rating 48V, 300 AH

    Battery Charger (PLCC)

    Make Chhabi

    Nos. Provided 1 (Normal), 1 (Reserve)

    PLCC Equipments & Panel

    Make ABB India

    Nos Provided 8

    Disturbance Recorder (Provided on Dausa & Bhilwara Feeders

    Make ABB India

    Type Industic 65 C

    Distance to Fault Locator (Provided on Dausa & Bhilwara Feeders)

    Make ASEA

    Type RANZA