SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS Brampton Transit Yard 185 Clark Boulevard Brampton, Ontario Prepared For: City of Brampton 2 Wellington Street West Brampton, Ontario Presented by: ECOH Inc. 6130 Tomken Road Mississauga, Ontario Building Code: S-001-01 ECOH Project No.: 14963 April 13, 2015

SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

SURVEY FOR DESIGNATED SUBSTANCES

AND HAZARDOUS MATERIALS

Brampton Transit Yard 185 Clark Boulevard Brampton, Ontario

Prepared For:

City of Brampton 2 Wellington Street West

Brampton, Ontario

Presented by:

ECOH Inc. 6130 Tomken Road Mississauga, Ontario

Building Code: S-001-01

ECOH Project No.: 14963

April 13, 2015

Page 2: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

TABLE OF CONTENTS

ECOH Inc.

1.0  INTRODUCTION ...............................................................................................................1 

2.0  METHODOLOGY AND SCOPE .......................................................................................1 

3.0  FINDINGS ...........................................................................................................................1 

4.0  RECOMMENDATIONS .....................................................................................................3 

5.0  LIMITATIONS OF ASSESSMENT ...................................................................................3 

6.0  CLOSURE ...........................................................................................................................4 

APPENDICES

Appendix I Survey Drawings

Appendix II Inventory of Identified Hazardous Materials

Appendix III Observation Report

Appendix IV Results of Bulk Sample Analysis

Appendix V Inventory of Underground/Aboveground Storage Tanks (UST/AST)

Page 3: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

CITY OF BRAMPTON DESIGNATED SUBSTANCES SURVEY BRAMPTON TRANSIT YARD 185 CLARK BOULEVARD, BRAMPTON, ONTARIO ECOH PROJECT NO. 14963 APRIL, 2015

ECOH Inc. Page 1

1.0 INTRODUCTION

ECOH was retained by the City of Brampton to conduct a designated substances survey of the Brampton Transit Yard located at 185 Clark Boulevard, Brampton, Ontario (hereby referred to as the “facility” or “project area”). The assessment was performed to establish the location and type of hazardous building materials incorporated in the facility’s structure(s) and its finishes, and to provide recommendations as necessary to fulfil requirements set forth under the Ontario Occupational Health and Safety Act and associated regulations.

Ms. Maja Mitrovic of ECOH performed the fieldwork on March 16, 2015.

This designated substance assessment was performed for the purposes of long-term management of designated substances and hazardous materials contained within building materials, and not for construction or renovation purposes. An additional pre-

renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any future demolition, renovation or maintenance activities that may disturb building materials that potentially contain designated materials or hazardous substances.

2.0 METHODOLOGY AND SCOPE

The methodology and scope of the Designated Substances Survey completed at this site are detailed in the overview document titled “Designated Substances Survey Scope of Work and Methodology Report”, dated October 2014, prepared by ECOH Inc. A copy of this document is available from the City of Brampton, and forms part of this report by reference.

3.0 FINDINGS

Material Findings

Asbestos Asbestos-containing materials (ACM) were identified in the facility as follows:

Vinyl floor tile (VFT 2 – 12”x12” Beige with Purple Specks) in Locations 1010 (Lost & Found) and 1070 (Washroom).

Transite pipe (visually confirmed) in various locations throughout the facility.

Refer to asbestos reassessment for current calendar year for most current information.

Page 4: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

CITY OF BRAMPTON DESIGNATED SUBSTANCES SURVEY BRAMPTON TRANSIT YARD 185 CLARK BOULEVARD, BRAMPTON, ONTARIO ECOH PROJECT NO. 14963 APRIL, 2015

ECOH Inc. Page 2

Material Findings

Assumed ACM were identified in the facility as follows:

Transite pipe in various locations throughout the facility.

Flex connector, window caulking, roofing materials, mechanical gaskets, internal components of boilers/water heaters or other mechanical systems were not sampled and should be assumed to be asbestos-containing if present. All assumed ACM materials observed were found to be in GOOD condition at the time of the survey.

Lead All paints observed are present in good condition and should be treated as lead-based until sampled.

No other major sources of lead or lead-containing products were identified during the survey; however, lead may be present in:

Ceramic tiles, Wiring connectors and electric cable sheathing, and Piping and solder joints/bell-and-spigot joints on piping.

Mould Visible mould growth was not observed within this facility.

Mercury Minor quantities are present as a vapour within fluorescent tubes lights and as a possible constituent of paints and adhesives.

Silica Present in all concrete and masonry products.

Polychlorinated Biphenyls (PCBs)

Assumed to be present as a component of ballasts for fluorescent lights/ high-intensity discharge (HID) lights. Approximately 200 light fixtures are present within the facility.

Assumed to be present as a component of electrical transformers suspected to be present in No Access in Location EC-10 (Electrical Room).

Benzene Chlorobenzene is assumed to be present as a component of electrical transformers that may be located in No Access Location EC-10 (Electrical Room).

Other Designated Substances and Hazardous Materials

Acrylonitrile, Arsenic, Coke Oven Emissions, Ethylene Oxide, Isocyanates, and Vinyl Chloride Monomer were not noted in significant quantities or forms, if at all.

Underground/ Aboveground Storage Tanks (UST/AST)

One UST/AST was identified within the facility, present in following location:

Underground Storage Tank on the Exterior of the facility (Location 0000).

Specific details regarding UST/AST are provided in Appendix V – Inventory of Underground/Aboveground Storage Tanks (UST/AST).

Page 5: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

CITY OF BRAMPTON DESIGNATED SUBSTANCES SURVEY BRAMPTON TRANSIT YARD 185 CLARK BOULEVARD, BRAMPTON, ONTARIO ECOH PROJECT NO. 14963 APRIL, 2015

ECOH Inc. Page 3

Further findings are presented in attached Appendices:

Appendix I – Survey Drawings, depicting the location of presumed and assumed asbestos-containing materials and room location numbers referenced throughout the report.

Appendix II – Inventory of Hazardous Materials, providing a general description of the quantity or nature of the designated substance identified in each location within the facility.

Appendix III – Observation Report, documenting instances of damaged hazardous materials and/or mould growth.

Appendix IV – Results of Bulk Sample Analysis, providing a summary of all bulk sampled collected as well as laboratory chain of custodies and certificates of analyses.

Appendix V – Inventory of Underground/Aboveground Storage Tanks (UST/AST).

4.0 RECOMMENDATIONS

All Designated Substances identified on-site are present in good condition with immediate no remedial action required.

As asbestos is confirmed to be present within the facility, an Asbestos Management Plan (AMP) must be implemented (refer to the overview document for more details).

General recommendations for compliance with applicable regulations have been provided in overview document titled “Designated Substances Survey Scope of Work and Methodology Report”, dated October 2014, prepared by ECOH Inc. A copy of this document is available from the City of Brampton.

Prior to future construction or renovation projects, additional assessments will be required to confirm the presence of Designated Substances that have been assumed to be on-site and/or that may be present in concealed areas (such as above solid ceilings). The impact to Designated Substances during future construction or renovation work should be assessed on a project-by-project basis.

5.0 LIMITATIONS OF ASSESSMENT

Due to the nature of building construction and on-going building activities, some limitations exist as to the possible thoroughness of a building survey. The field observations, measurements and analysis are considered sufficient in detail and scope to form a reasonable basis for the findings and conclusions presented in this report. The findings and conclusions drawn by ECOH Inc. (ECOH) are limited to the specific scope of work for which ECOH was retained and are based solely on information generated as a

Page 6: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

CITY OF BRAMPTON DESIGNATED SUBSTANCES SURVEY BRAMPTON TRANSIT YARD 185 CLARK BOULEVARD, BRAMPTON, ONTARIO ECOH PROJECT NO. 14963 APRIL, 2015

ECOH Inc. Page 4

result of the specific scope of work authorized by the City of Brampton. The results of the assessment are limited to visual inspection of areas made accessible to ECOH personnel and information obtained from facility personnel, when obtained.

ECOH warrants that the findings and conclusions contained herein have been made in accordance with generally accepted evaluation methods in the industry and applicable regulations at the time of the performance of the assessment. However, there is no warranty, expressed or implied, that this assessment has uncovered all environmental concerns on the subject site. In addition, ECOH cannot guarantee the completeness or accuracy of information supplied by a third party.

This report was prepared by ECOH for the City of Brampton. The material in it reflects ECOH’s professional interpretation of information available at the time of report preparation. Any use which a third party makes of this report, or any reliance on or decisions to be made based on it, are the responsibility of such third parties. ECOH accepts no responsibility for damages, if any, suffered by any third party as a result of decisions made or actions based on this report. Should additional information become available that suggests other environmental issues of concern beyond that described in this report, ECOH retains the right to review this information and modify conclusions and recommendations

presented in this report accordingly.

6.0 CLOSURE

Should there be any questions regarding the contents of this report, please contact the

undersigned at 905-795-2800.

ECOH Environmental Consulting Occupational Health

Prepared by: Reviewed by:

Maja Mitrovic, M.Env.Sc. Zafar Iqbal, B.Eng. (Civil) Environmental Scientist Senior Project Manager

Page 7: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

APPENDIX I SURVEY DRAWINGS

Page 8: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

1050

12A

1049

NAR

MC-11

1048

1053

10581059

EC-10

1062

1063

ST-02

1061

1060

10671068

1078

1070

1071

1072

1074

1073

1080

10791081

1069 1076

1075

1077

1066ST-01

1057

MC-12

10561055

1054 1047JC-11

1046

2000

2001

ST-02

07C

10C

15D

15E

07A,B 12B04A,C

08B 05C16E

12C

13A-CBus Area Floor Plan

Locations of Designated Substances &Hazardous Materials

BUILDING NAME:

CLIENT: City of BramptonPROJECT NUMBER:

CAD FILE:

DATE:

SCALE:

DRW BY:

CHK BY:

14963-S-016-01 April 2015 MM

ZINot to ScaleFIG1-2 P14963-S-016-01 ACM-bsmt-ground

Figure 1

Legend

LOCATION:

185 Clark Boulevard,Brampton, Ontario

Brampton Transit Yard

All information relating to room size and location isapproximate and for visual aid only. ECOH does notguarantee the drawing to be complete, absolute, accurateor current. The drawing should not be used by any party inlieu of obtaining architectural drawings.

N

Environmental ConsultingOccupational Health

ECOH

1001 Location Numbers

Non-Friable Asbestos-Containing Material

Friable Asbestos-Containing Material

01AAsbestos Bulk Sample Location(14963-S-016-01-ASB-XX)

NAR No Access to Room

Page 9: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

1010

1011

1012

MC-101013

1028

1029

1030103110321033

1034

1037 1036

1039 1040

1038

1035

1041

1019 1020 1021

1022

102310171018

10421016

10141043 JC-10

1024

1009

1008

1007

1006

1000

1001

1027

1002

16F

11A-C

08C

01C

14C

15A

01A14B

04B

10A,B

03A-C

09A-C

14A

16A

NAR

NAR

16C

15B

16D

15C

06A-C

02A,B

08A

01B

1015

02C

16G

05B

16B

05A

NAR

Office Area Floor PlanLocations of Designated Substances &

Hazardous Materials

BUILDING NAME:

CLIENT: City of BramptonPROJECT NUMBER:

CAD FILE:

DATE:

SCALE:

DRW BY:

CHK BY:

14963-S-016-01 April 2015 MM

ZINot to ScaleFIG1-2 P14963-S-016-01 ACM-bsmt-ground

Figure 2

Legend

LOCATION:

185 Clark Boulevard,Brampton, Ontario

Brampton Transit Yard

All information relating to room size and location isapproximate and for visual aid only. ECOH does notguarantee the drawing to be complete, absolute, accurateor current. The drawing should not be used by any party inlieu of obtaining architectural drawings.

N

Environmental ConsultingOccupational Health

ECOH

1001 Location Numbers

Non-Friable Asbestos-Containing Material

Friable Asbestos-Containing Material

01AAsbestos Bulk Sample Location(14963-S-016-01-ASB-XX)

NAR No Access to Room

Page 10: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

APPENDIX II INVENTORY OF IDENTIFIED HAZARDOUS MATERIALS

Refer to asbestos reassessment for current calendar year for most current information.

Page 11: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

The Corporation of the City of BramptonSurvey Summary Table

Location Number Location Name Building

System Material ObservedPotential

Hazardous Material

Sample ID Analytical Result

Qua

ntity

Con

ditio

n

Acc

ess

Aba

tem

ent

Prio

rity

Notes or Other Observations

0000 Exterior Roof Roofing Material Asbestos Not Sampled ACM Assumed 150,000 SF Good C 3

0000 Exterior Walls Caulking Asbestos Not Sampled ACM Assumed 200 EA Good A 3

1000 Vestibule Ceiling Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-15None Detected - - - -

1001 Reception Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1002 Open Office Floor Vinyl Sheet Flooring 1 Asbestos 14963-S-016-01-ASB-01A None Detected - - - - VSF 1 - Grey with White Specks

1002 Open Office Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1002 Open Office Ceiling Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-15None Detected - - - -

1002 Open Office Ceiling Ceiling Tile 1 Asbestos 14963-S-016-01-ASB-08C None Detected - - - -CT 1 - 2'x2' Small and Medium Pinhole

1002 Open Office Other Baseboard Mastic Asbestos14963-S-016-01-ASB-14B,

14CNone Detected - - - -

1006 Office Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1006 Office Ceiling Ceiling Tile 4 Asbestos14963-S-016-01-ASB-11A to

11CNone Detected - - - -

CT 4 - 2'x2' Sprayed

1007 Office Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1007 Office Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1008 Office Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1008 Office Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1009 Vestibule Ceiling Drywall Joint Compound Asbestos 14963-S-016-01-ASB-15A None Detected - - - -

1010 Lost & Found Floor Vinyl Floor Tile 2 Asbestos 14963-S-016-01-ASB-04B 3% Chrysotile 150 SF Good A 3VFT 2 - 12"x12" Beige with Purple SpecksMastic is non-asbestos

1010 Lost & Found Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1010 Lost & Found Ceiling Ceiling Tile 3 Asbestos14963-S-016-01-ASB-10A,

10BNone Detected - - - -

CT 3 - 2'x2' Pinholes and Wavy Fissures

1011 Male Washroom Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1012 Female Washroom Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

MC-10 Mechanical Pipe Transite Asbestos Not Sampled Visually Confirmed 15 LF Good B 3

Project Number: Building Name: Building Address:

14963-S-016-01Brampton Transit Yard185 Clark Boulevard

Date(s) of Current Survey:Organization Completing Survey:Facilty Coordinator:

March 16, 2015ECOH Inc.Dale Morin

Appendix II - Inventory of Identified Hazardous Materials Page 1 of 7

Page 12: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

The Corporation of the City of BramptonSurvey Summary Table

Location Number Location Name Building

System Material ObservedPotential

Hazardous Material

Sample ID Analytical Result

Qua

ntity

Con

ditio

n

Acc

ess

Aba

tem

ent

Prio

rity

Notes or Other Observations

Project Number: Building Name: Building Address:

14963-S-016-01Brampton Transit Yard185 Clark Boulevard

Date(s) of Current Survey:Organization Completing Survey:Facilty Coordinator:

March 16, 2015ECOH Inc.Dale Morin

1013 IT-Server Floor Vinyl Floor Tile 1 Asbestos14963-S-016-01-ASB-03A to

03CNone Detected - - - -

VFT 1 - 12"x12" White with Black/Grey Specks

1013 IT-Server Walls Drywall Joint Compound Asbestos 14963-S-016-01-ASB-16A None Detected - - - -

1013 IT-Server Ceiling Ceiling Tile 2 Asbestos14963-S-016-01-ASB-09A to

09CNone Detected - - - -

CT 2 - 2'x4' Small Pinholes

1013 IT-Server Pipe Transite Asbestos Not Sampled Visually Confirmed 20 LF Good B 3

1013 IT-Server Other Baseboard Mastic Asbestos 14963-S-016-01-ASB-14A None Detected - - - -1013 IT-Server Other Flex Connector Asbestos Not Sampled ACM Assumed 1 EA Good B 3

1014 Storage Floor Vinyl Floor Tile 3 Asbestos 14963-S-016-01-ASB-05A None Detected - - - -VFT 3 - 12"x12" White with Blue Specks

1014 Storage Walls Drywall Joint Compound Asbestos 14963-S-016-01-ASB-16B None Detected - - - -

1014 Storage Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1015 Closet Floor Vinyl Sheet Flooring 1 Asbestos 14963-S-016-01-ASB-01B None Detected - - - - VSF 1 - Grey with White Specks

1015 Closet Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1015 Closet Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1016 Office - - - - - - - - -No Access during 2015 ECOH DSS

1017 Meeting Room Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1017 Meeting Room Ceiling Ceiling Tile 1 Asbestos 14963-S-016-01-ASB-08A None Detected - - - -CT 1 - 2'x2' Small and Medium Pinhole

1018 Office Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1018 Office Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1019 Radio Room Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1019 Radio Room Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1020 Office Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1020 Office Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1021 Office Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1021 Office Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1022 Board Room Walls Drywall Joint Compound Asbestos 14963-S-016-01-ASB-16F None Detected - - - -

1022 Board Room Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1023 Lunch Room Floor Vinyl Sheet Flooring 1 Asbestos 14963-S-016-01-ASB-01C None Detected - - - - VSF 1 - Grey with White Specks

1023 Lunch Room Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1023 Lunch Room Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

Appendix II - Inventory of Identified Hazardous Materials Page 2 of 7

Page 13: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

The Corporation of the City of BramptonSurvey Summary Table

Location Number Location Name Building

System Material ObservedPotential

Hazardous Material

Sample ID Analytical Result

Qua

ntity

Con

ditio

n

Acc

ess

Aba

tem

ent

Prio

rity

Notes or Other Observations

Project Number: Building Name: Building Address:

14963-S-016-01Brampton Transit Yard185 Clark Boulevard

Date(s) of Current Survey:Organization Completing Survey:Facilty Coordinator:

March 16, 2015ECOH Inc.Dale Morin

1024 Closet Floor Vinyl Sheet Flooring 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-01None Detected - - - -

VSF 1 - Grey with White Specks

1024 Closet Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1024 Closet Ceiling Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-15None Detected - - - -

1027 Corridor Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1027 Corridor Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1028 Storage - - - - - - - - -No Access during 2015 ECOH DSS

1029 Closet - - - - - - - - -No Access during 2015 ECOH DSS

1030 Female Washroom Walls Drywall Joint Compound Asbestos 14963-S-016-01-ASB-16C None Detected - - - -

1030 Female Washroom Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1031 Male Washroom Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1031 Male Washroom Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

JC-10 Janitor's Closet Floor Vinyl Floor Tile 3 Asbestos 14963-S-016-01-ASB-05B None Detected - - - -VFT 3 - 12"x12" White with Blue Specks

JC-10 Janitor's Closet Walls Drywall Joint Compound Asbestos 14963-S-016-01-ASB-16G None Detected - - - -

JC-10 Janitor's Closet Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1032 Quiet Room Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1032 Quiet Room Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1033 Bid Room Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1033 Bid Room Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1034 Service Development Walls Drywall Joint Compound Asbestos 14963-S-016-01-ASB-16D None Detected - - - -

1034 Service Development Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1034 Service Development Ceiling Drywall Joint Compound Asbestos 14963-S-016-01-ASB-15B None Detected - - - -

1035 Staff Lounge Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1035 Staff Lounge Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1035 Staff Lounge Ceiling Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-15None Detected - - - -

1036 Meeting Room Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1036 Meeting Room Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1036 Meeting Room Ceiling Drywall Joint Compound Asbestos 14963-S-016-01-ASB-15C None Detected - - - -

Appendix II - Inventory of Identified Hazardous Materials Page 3 of 7

Page 14: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

The Corporation of the City of BramptonSurvey Summary Table

Location Number Location Name Building

System Material ObservedPotential

Hazardous Material

Sample ID Analytical Result

Qua

ntity

Con

ditio

n

Acc

ess

Aba

tem

ent

Prio

rity

Notes or Other Observations

Project Number: Building Name: Building Address:

14963-S-016-01Brampton Transit Yard185 Clark Boulevard

Date(s) of Current Survey:Organization Completing Survey:Facilty Coordinator:

March 16, 2015ECOH Inc.Dale Morin

1037 Office Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1037 Office Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1038 Planning Room Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1038 Planning Room Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1039 Marketing Office Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1039 Marketing Office Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1040 Vestibule Floor Vinyl Floor Tile 3 AsbestosVisually Consistent with 14963-

S-016-01-ASB-05None Detected - - - -

VFT 3 - 12"x12" White with Blue Specks

1040 Vestibule Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1040 Vestibule Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1041 Dispatch Floor Vinyl Sheet Flooring 2 Asbestos14963-S-016-01-ASB-02A,

02BNone Detected - - - -

VSF 2 - White with Blue Dots

1041 Dispatch Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1041 Dispatch Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1042 Locker Room Floor Vinyl Sheet Flooring 2 Asbestos 14963-S-016-01-ASB-02C None Detected - - - - VSF 2 - White with Blue Dots

1042 Locker Room Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1042 Locker Room Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - -

CT 1 - 2'x2' Small and Medium Pinhole

1043 Storage Floor Vinyl Floor Tile 4 Asbestos14963-S-016-01-ASB-06A to

06CNone Detected - - - -

VFT 4 - 12"x12" Brown with Black Specks

1043 Storage Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1043 Storage Ceiling Ceiling Tile 1 AsbestosVisually Consistent with 14963-

S-016-01-ASB-08None Detected - - - - CT 1 - 2'x2' Small and Medium

Pinhole1046 Wash Bay Exterior Pipe Transite Asbestos Not Sampled Visually Confirmed 100 LF Good C 3

1047 Washroom Ceiling Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-15None Detected - - - -

JC-11 Janitor's Closet Ceiling Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-15None Detected - - - -

1048 Garage Pipe Transite Asbestos Not Sampled Visually Confirmed 600 LF Good C 3

1049 Garage - - - - - - - - -

No suspect ACM identified. Other hazardous materials or designated substances were not noted in any signficiant quantities or forms.

1050 Garage - - - - - - - - -

No suspect ACM identified. Other hazardous materials or designated substances were not noted in any signficiant quantities or forms.

Appendix II - Inventory of Identified Hazardous Materials Page 4 of 7

Page 15: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

The Corporation of the City of BramptonSurvey Summary Table

Location Number Location Name Building

System Material ObservedPotential

Hazardous Material

Sample ID Analytical Result

Qua

ntity

Con

ditio

n

Acc

ess

Aba

tem

ent

Prio

rity

Notes or Other Observations

Project Number: Building Name: Building Address:

14963-S-016-01Brampton Transit Yard185 Clark Boulevard

Date(s) of Current Survey:Organization Completing Survey:Facilty Coordinator:

March 16, 2015ECOH Inc.Dale Morin

EC-10 Electrical - - - - - - - - -No Access during 2015 ECOH DSS

MC-11 Sprinkler Room - - - - - - - - -

No suspect ACM identified. Other hazardous materials or designated substances were not noted in any signficiant quantities or forms.

1053 Mechanic's Service Area Pipe Transite Asbestos Not Sampled Visually Confirmed 50 LF Good C

1054 Storage Ceiling Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-15None Detected - - - -

1055 Oil Storage Ceiling Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-15None Detected - - - -

1055 Oil Storage Pipe Transite Asbestos Not Sampled Visually Confirmed 10 LF Good C

1056 Tool Room Ceiling Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-15None Detected - - - -

1057 Storage Ceiling Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-15None Detected - - - -

MC-12 Compressor Room Ceiling Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-15None Detected - - - -

ST-01 Stair 1 - - - - - - - - -

No suspect ACM identified. Other hazardous materials or designated substances were not noted in any signficiant quantities or forms.

1058 Brake Service - - - - - - - - -

No suspect ACM identified. Other hazardous materials or designated substances were not noted in any signficiant quantities or forms.

1059 Office Floor Vinyl Floor Tile 3 AsbestosVisually Consistent with 14963-

S-016-01-ASB-05None Detected - - - -

VFT 3 - 12"x12" White with Blue Specks

1059 Office Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1059 Office Ceiling Ceiling Tile 3 Asbestos 14963-S-016-01-ASB-10C None Detected - - - -CT 3 - 2'x2' Pinholes and Wavy Fissures

1060 Welding Room - - - - - - - - -

No suspect ACM identified. Other hazardous materials or designated substances were not noted in any signficiant quantities or forms.

1061 Service Area - - - - - - - - -

No suspect ACM identified. Other hazardous materials or designated substances were not noted in any signficiant quantities or forms.

1062 Wash Bay IntBeam/Deck/J

oistSpray Fireproofing Asbestos

Visually Consistent with 14963-S-016-01-ASB-13

None Detected - - - -

1063 Storage RoomBeam/Deck/J

oistSpray Fireproofing Asbestos

14963-S-016-01-ASB-13A to 13C

None Detected - - - -

Appendix II - Inventory of Identified Hazardous Materials Page 5 of 7

Page 16: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

The Corporation of the City of BramptonSurvey Summary Table

Location Number Location Name Building

System Material ObservedPotential

Hazardous Material

Sample ID Analytical Result

Qua

ntity

Con

ditio

n

Acc

ess

Aba

tem

ent

Prio

rity

Notes or Other Observations

Project Number: Building Name: Building Address:

14963-S-016-01Brampton Transit Yard185 Clark Boulevard

Date(s) of Current Survey:Organization Completing Survey:Facilty Coordinator:

March 16, 2015ECOH Inc.Dale Morin

ST-02 Stair 2Beam/Deck/J

oistSpray Fireproofing Asbestos

Visually Consistent with 14963-S-016-01-ASB-13

None Detected - - - -

1066 Maintenance - - - - - - - - -

No suspect ACM identified. Other hazardous materials or designated substances were not noted in any signficiant quantities or forms.

1067 Stock Room Pipe Transite Asbestos Not Sampled Visually Confirmed 25 LF Good C 3

1068 Stock Room - - - - - - - - -

No suspect ACM identified. Other hazardous materials or designated substances were not noted in any signficiant quantities or forms.

1069 Stock Room Office Floor Vinyl Floor Tile 3 AsbestosVisually Consistent with 14963-

S-016-01-ASB-05None Detected - - - -

VFT 3 - 12"x12" White with Blue Specks

1069 Stock Room Office Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1069 Stock Room Office Ceiling Ceiling Tile 5 AsbestosVisually Consistent with 14963-

S-016-01-ASB-12None Detected - - - -

CT 5 - 2'x4' Pinholes and Fissures

1070 Washroom Floor Vinyl Floor Tile 2 Asbestos14963-S-016-01-ASB-04A,

04C3% Chrysotile 20 SF Good A 3

VFT 2 - 12"x12" Beige with Purple SpecksMastic is non-asbestos

1070 Washroom Ceiling Ceiling Tile 1 Asbestos 14963-S-016-01-ASB-08B None Detected - - - -CT 1 - 2'x2' Small and Medium Pinhole

1071 Stock Room/Office Floor Vinyl Floor Tile 5 Asbestos14963-S-016-01-ASB-07A,

07BNone Detected - - - -

VFT 5 - 12"X12" Grey with White Specks

1071 Stock Room/Office Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1071 Stock Room/Office Ceiling Ceiling Tile 5 Asbestos 14963-S-016-01-ASB-12B None Detected - - - - CT 5 - 2'x4' Pinholes and Fissures

1072 Maintenance Library Floor Vinyl Floor Tile 5 Asbestos 14963-S-016-01-ASB-07C None Detected - - - -VFT 5 - 12"X12" Grey with White Specks

1072 Maintenance Library Ceiling Ceiling Tile 5 Asbestos 14963-S-016-01-ASB-12A None Detected - - - - CT 5 - 2'x4' Pinholes and Fissures1073 Corridor Ceiling Drywall Joint Compound Asbestos 14963-S-016-01-ASB-15D None Detected - - - -

1074 Washroom - - - - - - - - -

No suspect ACM identified. Other hazardous materials or designated substances were not noted in any signficiant quantities or forms.

1075 Corridor Ceiling Ceiling Tile 5 AsbestosVisually Consistent with 14963-

S-016-01-ASB-12None Detected - - - -

CT 5 - 2'x4' Pinholes and Fissures

1076 Office Floor Vinyl Floor Tile 3 Asbestos 14963-S-016-01-ASB-05C None Detected - - - -VFT 3 - 12"x12" White with Blue Specks

1076 Office Walls Drywall Joint Compound Asbestos 14963-S-016-01-ASB-16E None Detected - - - -

1076 Office Ceiling Ceiling Tile 5 AsbestosVisually Consistent with 14963-

S-016-01-ASB-12None Detected - - - -

CT 5 - 2'x4' Pinholes and Fissures

1077 Vestibule Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1077 Vestibule Ceiling Ceiling Tile 5 AsbestosVisually Consistent with 14963-

S-016-01-ASB-12None Detected - - - -

CT 5 - 2'x4' Pinholes and Fissures

1078 Lunch Room Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

Appendix II - Inventory of Identified Hazardous Materials Page 6 of 7

Page 17: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

The Corporation of the City of BramptonSurvey Summary Table

Location Number Location Name Building

System Material ObservedPotential

Hazardous Material

Sample ID Analytical Result

Qua

ntity

Con

ditio

n

Acc

ess

Aba

tem

ent

Prio

rity

Notes or Other Observations

Project Number: Building Name: Building Address:

14963-S-016-01Brampton Transit Yard185 Clark Boulevard

Date(s) of Current Survey:Organization Completing Survey:Facilty Coordinator:

March 16, 2015ECOH Inc.Dale Morin

1078 Lunch Room Ceiling Ceiling Tile 5 Asbestos 14963-S-016-01-ASB-12C None Detected - - - - CT 5 - 2'x4' Pinholes and Fissures

1079 First Aid Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1079 First Aid Ceiling Ceiling Tile 5 AsbestosVisually Consistent with 14963-

S-016-01-ASB-12None Detected - - - -

CT 5 - 2'x4' Pinholes and Fissures

1080 Men's Changeroom Walls Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-16None Detected - - - -

1080 Men's Changeroom Ceiling Drywall Joint Compound AsbestosVisually Consistent with 14963-

S-016-01-ASB-15None Detected - - - -

1080 Men's Changeroom Ceiling Ceiling Tile 5 AsbestosVisually Consistent with 14963-

S-016-01-ASB-12None Detected - - - -

CT 5 - 2'x4' Pinholes and Fissures1081 Laundry Ceiling Drywall Joint Compound Asbestos 14963-S-016-01-ASB-15E None Detected - - - -2000 Mezzanine Other Flex Connector Asbestos Not Sampled ACM Assumed 1 EA Good A 3 Yellow

2001 Storage - - - - - - - - -

No suspect ACM identified. Other hazardous materials or designated substances were not noted in any signficiant quantities or forms.

ST-02 Stair 2Beam/Deck/J

oistSpray Fireproofing Asbestos

Visually Consistent with 14963-S-016-01-ASB-13

None Detected - - - -

Surveyor's Field Notes

Appendix II - Inventory of Identified Hazardous Materials Page 7 of 7

Page 18: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

APPENDIX III OBSERVATION REPORT

(NO INFORMATION TO REPORT)

Page 19: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

APPENDIX IV RESULTS OF BULK SAMPLE ANALYSIS

Page 20: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

TABLE 1 Summary of Analysis - Collected Asbestos Bulk Samples

Sample Number Sample Location Sample Description Results

14963-S-016-01-ASB-01A

1002 (Open Office) Vinyl Sheet Flooring 1 - Grey with White Specks

None Detected

14963-S-016-01-ASB-01B

1015 (Closet) Vinyl Sheet Flooring 1 - Grey with White Specks

None Detected

14963-S-016-01-ASB-01C 1023 (Lunch Room)

Vinyl Sheet Flooring 1 - Grey with White Specks

None Detected

14963-S-016-01-ASB-02A

1041 (Dispatch)

Vinyl Sheet Flooring 2 - White with Blue Dots None Detected

Associated Mastic

14963-S-016-01-ASB-02B

1041 (Dispatch) Vinyl Sheet Flooring 2 - White with Blue Dots

None Detected

14963-S-016-01-ASB-02C

1042 (Locker Room) Vinyl Sheet Flooring 2 - White with Blue Dots

None Detected

14963-S-016-01-ASB-03A

1013 (IT-Server)

Vinyl Floor Tile 1 - 12"x12" White with Black/Grey Specks None Detected

Associated Mastic

14963-S-016-01-ASB-03B

1013 (IT-Server) Vinyl Floor Tile 1 - 12"x12" White with Black/Grey Specks

None Detected

14963-S-016-01-ASB-03C

1013 (IT-Server) Vinyl Floor Tile 1 - 12"x12" White with Black/Grey Specks

None Detected

14963-S-016-01-ASB-04A

1070 (Washroom)

Vinyl Floor Tile 2 - 12"x12" Beige with

Purple Specks 3% Chrysotile

Associated Mastic None Detected

14963-S-016-01-ASB-04B

1010 (Lost & Found) Vinyl Floor Tile 2 - 12"x12" Beige with

Purple Specks

Not Analyzed – Stop Positive

Page 21: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

TABLE 1 Summary of Analysis - Collected Asbestos Bulk Samples

Sample Number Sample Location Sample Description Results

14963-S-016-01-ASB-04C

1070 (Washroom) Vinyl Floor Tile 2 - 12"x12" Beige with

Purple Specks

Not Analyzed – Stop Positive

14963-S-016-01-ASB-05A

1014 (Storage) Vinyl Floor Tile 3 - 12"x12" White with

Blue Specks None Detected

14963-S-016-01-ASB-05B

JC-10 (Janitor's Closet) Vinyl Floor Tile 3 - 12"x12" White with

Blue Specks None Detected

14963-S-016-01-ASB-05C

1076 (Office) Vinyl Floor Tile 3 - 12"x12" White with

Blue Specks None Detected

14963-S-016-01-ASB-06A

1043 (Storage) Vinyl Floor Tile 4 - 12"x12" Brown with

Black Specks None Detected

14963-S-016-01-ASB-06B

1043 (Storage) Vinyl Floor Tile 4 - 12"x12" Brown with

Black Specks None Detected

14963-S-016-01-ASB-06C

1043 (Storage)

Vinyl Floor Tile 4 - 12"x12" Brown with

Black Specks None Detected

Associated Mastic

14963-S-016-01-ASB-07A

1071 (Stock Room/Office)

Vinyl Floor Tile 5 - 12"x12" Grey with

White Specks None Detected

14963-S-016-01-ASB-07B

1071 (Stock Room/Office)

Vinyl Floor Tile 5 - 12"x12" Grey with

White Specks None Detected

14963-S-016-01-ASB-07C

1072 (Maintenance Library)

Vinyl Floor Tile 5 - 12"x12" Grey with

White Specks None Detected

14963-S-016-01-ASB-08A

1017 (Meeting Room) Ceiling Tile 1 - 2'x2'

Small/Medium Pinholes None Detected

14963-S-016-01-ASB-08B

1070 (Washroom) Ceiling Tile 1 - 2'x2'

Small/Medium Pinholes None Detected

14963-S-016-01-ASB-08C

1002 (Open Office) Ceiling Tile 1 - 2'x2'

Small/Medium Pinholes None Detected

14963-S-016-01-ASB-09A

1013 (IT-Server) Ceiling Tile 2 - 2'x4'

Small Pinholes None Detected

Page 22: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

TABLE 1 Summary of Analysis - Collected Asbestos Bulk Samples

Sample Number Sample Location Sample Description Results

14963-S-016-01-ASB-09B

1013 (IT-Server) Ceiling Tile 2 - 2'x4'

Small Pinholes None Detected

14963-S-016-01-ASB-09C

1013 (IT-Server) Ceiling Tile 2 - 2'x4'

Small Pinholes None Detected

14963-S-016-01-ASB-10A

1010 (Lost & Found) Ceiling Tile 3 - 2'x2'

Pinholes & Wavy Fissures

None Detected

14963-S-016-01-ASB-10B

1010 (Lost & Found) Ceiling Tile 3 - 2'x2'

Pinholes & Wavy Fissures

None Detected

14963-S-016-01-ASB-10C

1059 (Office) Ceiling Tile 3 - 2'x2'

Pinholes & Wavy Fissures

None Detected

14963-S-016-01-ASB-11A

1006 (Office) Ceiling Tile 4 - 2'x2'

Sprayed None Detected

14963-S-016-01-ASB-11B

1006 (Office) Ceiling Tile 4 - 2'x2'

Sprayed None Detected

14963-S-016-01-ASB-11C

1006 (Office) Ceiling Tile 4 - 2'x2'

Sprayed None Detected

14963-S-016-01-ASB-12A

1072 (Maintenance Library)

Ceiling Tile 5 - 2'x4' Pinholes and Fissures

None Detected

14963-S-016-01-ASB-12B

1071 (Stock Room/Office)

Ceiling Tile 5 - 2'x4' Pinholes and Fissures

None Detected

14963-S-016-01-ASB-12C

1078 (Lunch Room) Ceiling Tile 5 - 2'x4' Pinholes and Fissures

None Detected

14963-S-016-01-ASB-13A

1063 (Storage) Spray Fireproofing None Detected

14963-S-016-01-ASB-13B

1063 (Storage) Spray Fireproofing None Detected

14963-S-016-01-ASB-13C

1063 (Storage) Spray Fireproofing None Detected

14963-S-016-01-ASB-14A

1013 (IT-Server) Baseboard Mastic None Detected

14963-S-016-01-ASB-14B

1002 (Open Office) Baseboard Mastic None Detected

14963-S-016-01-ASB-14C

1002 (Open Office) Baseboard Mastic None Detected

Page 23: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

TABLE 1 Summary of Analysis - Collected Asbestos Bulk Samples

Sample Number Sample Location Sample Description Results

14963-S-016-01-ASB-15A

1009 (Vestibule) Drywall Joint

Compound-Ceiling None Detected

14963-S-016-01-ASB-15B

1034 (Service Development)

Drywall Joint Compound-Ceiling

None Detected

14963-S-016-01-ASB-15C

1036 (Meeting Room) Drywall Joint

Compound-Ceiling None Detected

14963-S-016-01-ASB-15D

1073 (Corridor) Drywall Joint

Compound-Ceiling None Detected

14963-S-016-01-ASB-15E

1081 (Laundry) Drywall Joint

Compound-Ceiling None Detected

14963-S-016-01-ASB-16A

1013 (IT-Server) Drywall Joint

Compound-Wall None Detected

14963-S-016-01-ASB-16B

1014 (Storage) Drywall Joint

Compound-Wall None Detected

14963-S-016-01-ASB-16C

1030 (Female Washroom)

Drywall Joint Compound-Wall

None Detected

14963-S-016-01-ASB-16D

1034 (Service Development)

Drywall Joint Compound-Wall

None Detected

14963-S-016-01-ASB-16E

1076 (Office) Drywall Joint

Compound-Wall None Detected

14963-S-016-01-ASB-16F

1022 (Board Room) Drywall Joint

Compound-Wall None Detected

14963-S-016-01-ASB-16G

JC-10 (Janitor's Closet) Drywall Joint

Compound-Wall None Detected

Pink highlighted rows, if present, indicate asbestos-containing materials

Page 24: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

EMSL Canada Inc.2756 Slough Street, Mississauga, ON L4T 1G3Phone/Fax: 289-997-4602 / (289) 997-4607http://www.EMSL.com [email protected]

551502760CustomerID: 55ECOH45CustomerPO: 14963-S-016-01ProjectID:

EMSL Canada Or

Attn: Maja MitrovicECOH Management, Inc.6130 Tomken RoadMississauga, ON L5T 1X7

Received: 03/19/15 4:03 PM

14963-S-016-01 BRAMPTON TRANSIT YARD

Fax: (905) 795-2870Phone: (905) 795-2800

Project:

3/27/2015Analysis Date:Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

14963-S-016-01-ASB-01A551502760-0001

1002 (Open Space) - Vinyl Sheet Flooring 1- Grey with White Specks

Gray/White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-01B551502760-0002

1015 (Closet) - Vinyl Sheet Flooring 1- Grey with White Specks

Gray/White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-01C551502760-0003

1023 (Lunch Room) - Vinyl Sheet Flooring 1- Grey with White Specks

Gray/White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-02A-Vinyl Sheet Flooring551502760-0004

1041 (Dispatch) - Vinyl Sheet Flooring 2- White with Blue Dots

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-02A-Mastic551502760-0004A

1041 (Dispatch) - Vinyl Sheet Flooring 2- White with Blue Dots

Yellow None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-02B551502760-0005

1041 (Dispatch) - Vinyl Sheet Flooring 2- White with Blue Dots

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

1Test Report PLM-7.28.9 Printed: 3/30/2015 5:00:37 PM

Matthew Davisor other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%Samples analyzed by EMSL Analytical, Inc. San Diego, CA NVLAP Lab Code 200855-0, CA ELAP 2713

Initial report from 03/30/2015 17:00:37

Mariah Barfield (35)Natalia Toscano (21)

Page 25: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

EMSL Canada Inc.2756 Slough Street, Mississauga, ON L4T 1G3Phone/Fax: 289-997-4602 / (289) 997-4607http://www.EMSL.com [email protected]

551502760CustomerID: 55ECOH45CustomerPO: 14963-S-016-01ProjectID:

EMSL Canada Or

Attn: Maja MitrovicECOH Management, Inc.6130 Tomken RoadMississauga, ON L5T 1X7

Received: 03/19/15 4:03 PM

14963-S-016-01 BRAMPTON TRANSIT YARD

Fax: (905) 795-2870Phone: (905) 795-2800

Project:

3/27/2015Analysis Date:Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

14963-S-016-01-ASB-02C551502760-0006

1042 ( Locker Room) - Vinyl Sheet Flooring 2- White with Blue Dots

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-03A-Vinyl Floor Tile551502760-0007

1013 (IT-Server) - Vinyl Floor Tile 1- 12"x12" White with Black/ Grey Specks

White/Black None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-03A-Mastic551502760-0007A

1013 (IT-Server) - Vinyl Floor Tile 1- 12"x12" White with Black/ Grey Specks

Black None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-03B551502760-0008

1013 (IT-Server) - Vinyl Floor Tile 1- 12"x12" White with Black/ Grey Specks

White/Black None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-03C551502760-0009

1013 (IT-Server) - Vinyl Floor Tile 1- 12"x12" White with Black/ Grey Specks

White/Black None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-04A-Vinyl Floor Tile551502760-0010

1070 (Washroom) - Vinyl Floor Tile 2- 12"x12" Beige with Purple Specks

BeigeNon-Fibrous

Homogeneous

Chrysotile3%Non-fibrous (other)97%

2Test Report PLM-7.28.9 Printed: 3/30/2015 5:00:37 PM

Matthew Davisor other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%Samples analyzed by EMSL Analytical, Inc. San Diego, CA NVLAP Lab Code 200855-0, CA ELAP 2713

Initial report from 03/30/2015 17:00:37

Mariah Barfield (35)Natalia Toscano (21)

Page 26: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

EMSL Canada Inc.2756 Slough Street, Mississauga, ON L4T 1G3Phone/Fax: 289-997-4602 / (289) 997-4607http://www.EMSL.com [email protected]

551502760CustomerID: 55ECOH45CustomerPO: 14963-S-016-01ProjectID:

EMSL Canada Or

Attn: Maja MitrovicECOH Management, Inc.6130 Tomken RoadMississauga, ON L5T 1X7

Received: 03/19/15 4:03 PM

14963-S-016-01 BRAMPTON TRANSIT YARD

Fax: (905) 795-2870Phone: (905) 795-2800

Project:

3/27/2015Analysis Date:Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

14963-S-016-01-ASB-04A-Mastic551502760-0010A

1070 (Washroom) - Vinyl Floor Tile 2- 12"x12" Beige with Purple Specks

Yellow None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-04B551502760-0011

1010 (Lost & Found) - Vinyl Floor Tile 2- 12"x12" Beige with Purple Specks

Stop Positive (Not Analyzed)

14963-S-016-01-ASB-04C551502760-0012

1070 (Washroom) - Vinyl Floor Tile 2- 12"x12" Beige with Purple Specks

Stop Positive (Not Analyzed)

14963-S-016-01-ASB-05A551502760-0013

1014 (Storage) - Vinyl Floor Tile 3- 12"x12" White with Blue Specks

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-05B551502760-0014

JC-10 (Janitor's Closet) - Vinyl Floor Tile 3- 12"x12" White with Blue Specks

White None DetectedFibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-05C551502760-0015

1076 (Office) - Vinyl Floor Tile 3- 12"x12" White with Blue Specks

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

3Test Report PLM-7.28.9 Printed: 3/30/2015 5:00:37 PM

Matthew Davisor other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%Samples analyzed by EMSL Analytical, Inc. San Diego, CA NVLAP Lab Code 200855-0, CA ELAP 2713

Initial report from 03/30/2015 17:00:37

Mariah Barfield (35)Natalia Toscano (21)

Page 27: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

EMSL Canada Inc.2756 Slough Street, Mississauga, ON L4T 1G3Phone/Fax: 289-997-4602 / (289) 997-4607http://www.EMSL.com [email protected]

551502760CustomerID: 55ECOH45CustomerPO: 14963-S-016-01ProjectID:

EMSL Canada Or

Attn: Maja MitrovicECOH Management, Inc.6130 Tomken RoadMississauga, ON L5T 1X7

Received: 03/19/15 4:03 PM

14963-S-016-01 BRAMPTON TRANSIT YARD

Fax: (905) 795-2870Phone: (905) 795-2800

Project:

3/27/2015Analysis Date:Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

14963-S-016-01-ASB-06A551502760-0016

1043 (Storage) - Vinyl Floor Tile 4- 12"x12" Brown with Black Specks

Brown None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-06B551502760-0017

1043 (Storage) - Vinyl Floor Tile 4- 12"x12" Brown with Black Specks

Brown None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-06C-Vinyl Floor Tile551502760-0018

1043 (Storage) - Vinyl Floor Tile 4- 12"x12" Brown with Black Specks

Brown/Black None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-06C-Mastic551502760-0018A

1043 (Storage) - Vinyl Floor Tile 4- 12"x12" Brown with Black Specks

Yellow None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-07A551502760-0019

1071 (Stock Room/ Office) - Vinyl Floor Tile 5- 12"x12" Grey with White Specks

Gray None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-07B551502760-0020

1071 (Stock Room/ Office) - Vinyl Floor Tile 5- 12"x12" Grey with White Specks

Gray None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

4Test Report PLM-7.28.9 Printed: 3/30/2015 5:00:37 PM

Matthew Davisor other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%Samples analyzed by EMSL Analytical, Inc. San Diego, CA NVLAP Lab Code 200855-0, CA ELAP 2713

Initial report from 03/30/2015 17:00:37

Mariah Barfield (35)Natalia Toscano (21)

Page 28: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

EMSL Canada Inc.2756 Slough Street, Mississauga, ON L4T 1G3Phone/Fax: 289-997-4602 / (289) 997-4607http://www.EMSL.com [email protected]

551502760CustomerID: 55ECOH45CustomerPO: 14963-S-016-01ProjectID:

EMSL Canada Or

Attn: Maja MitrovicECOH Management, Inc.6130 Tomken RoadMississauga, ON L5T 1X7

Received: 03/19/15 4:03 PM

14963-S-016-01 BRAMPTON TRANSIT YARD

Fax: (905) 795-2870Phone: (905) 795-2800

Project:

3/27/2015Analysis Date:Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

14963-S-016-01-ASB-07C551502760-0021

1070 (Washroom) - Vinyl Floor Tile 5- 12"x12" Grey with White Specks

Gray None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-08A551502760-0022

1017 (Meeting Room) - Ceiling Tile 1- 2'x2' Small/ Medium Pinholes

Tan None DetectedFibrous

Homogeneous

Cellulose40%Min. Wool30%

Perlite10%Non-fibrous (other)20%

14963-S-016-01-ASB-08B551502760-0023

1070 (Washroom) - Ceiling Tile 1- 2'x2' Small/ Medium Pinholes

Tan None DetectedFibrous

Homogeneous

Cellulose40%Min. Wool30%

Perlite10%Non-fibrous (other)20%

14963-S-016-01-ASB-08C551502760-0024

1002 (Open Office) - Ceiling Tile 1- 2'x2' Small/ Medium Pinholes

White None DetectedFibrous

Homogeneous

Cellulose40%Min. Wool30%

Perlite10%Non-fibrous (other)20%

14963-S-016-01-ASB-09A551502760-0025

1013 (IT Server) - Ceiling Tile 2- 2'x4' Small Pinholes

Tan None DetectedFibrous

Homogeneous

Cellulose40%Min. Wool15%

Perlite15%Non-fibrous (other)30%

14963-S-016-01-ASB-09B551502760-0026

1013 (IT Server) - Ceiling Tile 2- 2'x4' Small Pinholes

Tan None DetectedFibrous

Homogeneous

Cellulose40%Min. Wool15%

Perlite20%Non-fibrous (other)25%

14963-S-016-01-ASB-09C551502760-0027

1013 (IT Server) - Ceiling Tile 2- 2'x4' Small Pinholes

White None DetectedFibrous

Homogeneous

Cellulose40%Min. Wool30%

Perlite10%Non-fibrous (other)20%

5Test Report PLM-7.28.9 Printed: 3/30/2015 5:00:37 PM

Matthew Davisor other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%Samples analyzed by EMSL Analytical, Inc. San Diego, CA NVLAP Lab Code 200855-0, CA ELAP 2713

Initial report from 03/30/2015 17:00:37

Mariah Barfield (35)Natalia Toscano (21)

Page 29: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

EMSL Canada Inc.2756 Slough Street, Mississauga, ON L4T 1G3Phone/Fax: 289-997-4602 / (289) 997-4607http://www.EMSL.com [email protected]

551502760CustomerID: 55ECOH45CustomerPO: 14963-S-016-01ProjectID:

EMSL Canada Or

Attn: Maja MitrovicECOH Management, Inc.6130 Tomken RoadMississauga, ON L5T 1X7

Received: 03/19/15 4:03 PM

14963-S-016-01 BRAMPTON TRANSIT YARD

Fax: (905) 795-2870Phone: (905) 795-2800

Project:

3/27/2015Analysis Date:Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

14963-S-016-01-ASB-10A551502760-0028

1010 (Lost & Found) - Ceiling Tile 3- 2'x2' Pinholes & Wavy Fissures

Tan None DetectedFibrous

Homogeneous

Cellulose60%Min. Wool10%

Perlite20%Non-fibrous (other)10%

14963-S-016-01-ASB-10B551502760-0029

1010 (Lost & Found) - Ceiling Tile 3- 2'x2' Pinholes & Wavy Fissures

Tan None DetectedFibrous

Homogeneous

Cellulose60%Min. Wool10%

Perlite20%Non-fibrous (other)10%

14963-S-016-01-ASB-10C551502760-0030

1059 (Office) - Ceiling Tile 3- 2'x2' Pinholes & Wavy Fissures

Tan None DetectedFibrous

Homogeneous

Cellulose40%Min. Wool30%

Perlite10%Non-fibrous (other)20%

14963-S-016-01-ASB-11A551502760-0031

1006 (Office) - Ceiling Tile 4- 2'x2' Sprayed

Tan None DetectedFibrous

Homogeneous

Min. Wool80% Non-fibrous (other)20%

14963-S-016-01-ASB-11B551502760-0032

1006 (Office) - Ceiling Tile 4- 2'x2' Sprayed

Tan None DetectedFibrous

Homogeneous

Min. Wool80% Non-fibrous (other)20%

14963-S-016-01-ASB-11C551502760-0033

1006 (Office) - Ceiling Tile 4- 2'x2' Sprayed

White None DetectedFibrous

Homogeneous

Min. Wool80% Non-fibrous (other)20%

6Test Report PLM-7.28.9 Printed: 3/30/2015 5:00:37 PM

Matthew Davisor other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%Samples analyzed by EMSL Analytical, Inc. San Diego, CA NVLAP Lab Code 200855-0, CA ELAP 2713

Initial report from 03/30/2015 17:00:37

Mariah Barfield (35)Natalia Toscano (21)

Page 30: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

EMSL Canada Inc.2756 Slough Street, Mississauga, ON L4T 1G3Phone/Fax: 289-997-4602 / (289) 997-4607http://www.EMSL.com [email protected]

551502760CustomerID: 55ECOH45CustomerPO: 14963-S-016-01ProjectID:

EMSL Canada Or

Attn: Maja MitrovicECOH Management, Inc.6130 Tomken RoadMississauga, ON L5T 1X7

Received: 03/19/15 4:03 PM

14963-S-016-01 BRAMPTON TRANSIT YARD

Fax: (905) 795-2870Phone: (905) 795-2800

Project:

3/27/2015Analysis Date:Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

14963-S-016-01-ASB-12A551502760-0034

1072 (Maintenance Library) - Ceiling Tile 5- 2'x4' Pinholes & Fissures

Tan None DetectedNon-Fibrous

Homogeneous

Min. Wool15%Cellulose60%

Perlite10%Non-fibrous (other)15%

14963-S-016-01-ASB-12B551502760-0035

1071 (Stock Room/ Office) - Ceiling Tile 5- 2'x4' Pinholes & Fissures

Tan None DetectedFibrous

Homogeneous

Cellulose60%Min. Wool10%

Perlite10%Non-fibrous (other)20%

14963-S-016-01-ASB-12C551502760-0036

1078 (Lunch Room) - Ceiling Tile 5- 2'x4' Pinholes & Fissures

White None DetectedFibrous

Homogeneous

Cellulose60%Min. Wool10%

Perlite10%Non-fibrous (other)20%

14963-S-016-01-ASB-13A551502760-0037

1063 (Storage) - Spray Fireproofing

White None DetectedNon-Fibrous

Homogeneous

Min. Wool60%Cellulose2%

Non-fibrous (other)38%

14963-S-016-01-ASB-13B551502760-0038

1063 (Storage) - Spray Fireproofing

White None DetectedNon-Fibrous

Homogeneous

Min. Wool60% Non-fibrous (other)40%

14963-S-016-01-ASB-13C551502760-0039

1063 (Storage) - Spray Fireproofing

Gray None DetectedFibrous

Homogeneous

Min. Wool60% Non-fibrous (other)40%

7Test Report PLM-7.28.9 Printed: 3/30/2015 5:00:37 PM

Matthew Davisor other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%Samples analyzed by EMSL Analytical, Inc. San Diego, CA NVLAP Lab Code 200855-0, CA ELAP 2713

Initial report from 03/30/2015 17:00:37

Mariah Barfield (35)Natalia Toscano (21)

Page 31: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

EMSL Canada Inc.2756 Slough Street, Mississauga, ON L4T 1G3Phone/Fax: 289-997-4602 / (289) 997-4607http://www.EMSL.com [email protected]

551502760CustomerID: 55ECOH45CustomerPO: 14963-S-016-01ProjectID:

EMSL Canada Or

Attn: Maja MitrovicECOH Management, Inc.6130 Tomken RoadMississauga, ON L5T 1X7

Received: 03/19/15 4:03 PM

14963-S-016-01 BRAMPTON TRANSIT YARD

Fax: (905) 795-2870Phone: (905) 795-2800

Project:

3/27/2015Analysis Date:Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

14963-S-016-01-ASB-14A551502760-0040

1013 (IT Server) - Baseboard Mastic

Yellow None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-14B551502760-0041

1002 (Open Office) - Baseboard Mastic

Yellow None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-14C551502760-0042

1002 (Open Office) - Baseboard Mastic

Brown None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-15A551502760-0043

1009 (Vestibule) - Drywall Joint Compound- Ceiling

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-15B551502760-0044

1034 (Service Development) - Drywall Joint Compound- Ceiling

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-15C551502760-0045

1036 (Meeting Room) - Drywall Joint Compound- Ceiling

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-15D551502760-0046

1073 (Corridor) - Drywall Joint Compound- Ceiling

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

8Test Report PLM-7.28.9 Printed: 3/30/2015 5:00:37 PM

Matthew Davisor other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%Samples analyzed by EMSL Analytical, Inc. San Diego, CA NVLAP Lab Code 200855-0, CA ELAP 2713

Initial report from 03/30/2015 17:00:37

Mariah Barfield (35)Natalia Toscano (21)

Page 32: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

EMSL Canada Inc.2756 Slough Street, Mississauga, ON L4T 1G3Phone/Fax: 289-997-4602 / (289) 997-4607http://www.EMSL.com [email protected]

551502760CustomerID: 55ECOH45CustomerPO: 14963-S-016-01ProjectID:

EMSL Canada Or

Attn: Maja MitrovicECOH Management, Inc.6130 Tomken RoadMississauga, ON L5T 1X7

Received: 03/19/15 4:03 PM

14963-S-016-01 BRAMPTON TRANSIT YARD

Fax: (905) 795-2870Phone: (905) 795-2800

Project:

3/27/2015Analysis Date:Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

14963-S-016-01-ASB-15E551502760-0047

1081 (Laundry) - Drywall Joint Compound- Ceiling

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-16A551502760-0048

1013 (IT Server) - Drywall Joint Compound- Wall

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-16B551502760-0049

1014 (Storage) - Drywall Joint Compound- Wall

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-16C551502760-0050

1030 (Female Washroom) - Drywall Joint Compound- Wall

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-16D551502760-0051

1034 (Service Development) - Drywall Joint Compound- Wall

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-16E551502760-0052

1076 (Office) - Drywall Joint Compound- Wall

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

14963-S-016-01-ASB-16F551502760-0053

1022 (Board Room - Drywall Joint Compound- Wall

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

9Test Report PLM-7.28.9 Printed: 3/30/2015 5:00:37 PM

Matthew Davisor other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%Samples analyzed by EMSL Analytical, Inc. San Diego, CA NVLAP Lab Code 200855-0, CA ELAP 2713

Initial report from 03/30/2015 17:00:37

Mariah Barfield (35)Natalia Toscano (21)

Page 33: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

EMSL Canada Inc.2756 Slough Street, Mississauga, ON L4T 1G3Phone/Fax: 289-997-4602 / (289) 997-4607http://www.EMSL.com [email protected]

551502760CustomerID: 55ECOH45CustomerPO: 14963-S-016-01ProjectID:

EMSL Canada Or

Attn: Maja MitrovicECOH Management, Inc.6130 Tomken RoadMississauga, ON L5T 1X7

Received: 03/19/15 4:03 PM

14963-S-016-01 BRAMPTON TRANSIT YARD

Fax: (905) 795-2870Phone: (905) 795-2800

Project:

3/27/2015Analysis Date:Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

14963-S-016-01-ASB-16G551502760-0054

JC-10 (Janitor's Closet - Drywall Joint Compound- Wall

White None DetectedNon-Fibrous

Homogeneous

Non-fibrous (other)100%

10THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.9 Printed: 3/30/2015 5:00:37 PM

Matthew Davisor other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%Samples analyzed by EMSL Analytical, Inc. San Diego, CA NVLAP Lab Code 200855-0, CA ELAP 2713

Initial report from 03/30/2015 17:00:37

Mariah Barfield (35)Natalia Toscano (21)

Page 34: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

APPENDIX V INVENTORY OF UST/AST STORAGE TANKS

Page 35: SURVEY FOR DESIGNATED SUBSTANCES AND HAZARDOUS MATERIALS · renovation/pre-demolition assessment for designated substances and hazardous materials should be conducted prior to any

TABLE 2 UST/AST Summary of Key Findings

Tank #1

Storage Tank Type (AST/UST) Underground Storage Tank

Equipment Details Double walled fibreglass tank with 360°

containment, located on exterior of building (Location 0000)

Fuel Type Diesel

Make and Capacity Containment Solutions Inc., DWT6, 90,630 L

Type of Equipment Construction Double walled fibreglass

Installation date September 2014

Condition of the system (Tank and pipes)

Intact

Compliance with TSSA regulation TSSA inspected and approved, equipped with monitoring system, emergency vents and

valves, pumps, overfill prevention. Cathodic Protection Test Station and

adequacy of protection level

Location observations (stains, leaks) None