Supply, testing, installation and commissioning of 5 kY A UPS system as per the following specification: 1 Capacity 5 kY A UPS system with APFC system 2 Input supply Suitable for400±15% Y, 3 phase, 50 ±10% Hz 3 Inlets Through MCB 4 Input Power factor & harmonic Input currents shall be sinusoidal. Correction For all types of loads (linear & non linear) above 25% of the rating: (1) Power factor ~ 0.95, using active power factor correction system. ". (2) THDI less than 10 %, using active harmonic conditioners. 5 Rated Output Power 5 kV~ at a power factor 0.8 lag or better 6 Out put supply 3 phase 4 wire, 230 Y phase-neutral for all phases, 3 separate outlets for distribution +E tem1inal Voltage Regulation: Range: ± 1% steady state for a static 100%) balanced lunbalanced load, 5% for a 0 to 100% load step. Mean deviation for 0-100% step load response: less than ±3%. - Recovery time to ± 1%: max 20 ms 7 Output Waveform and Pure Sinusoidal wave. frequency Voltage Distortion (THO): Less than 2% for linear load, Less than 3 % for non-liner load . 50 ± 0.1 % Hz free running and ± 2 % provision for synchronized with mains 8 Outlets (output panel) through MCB and HRC Fuse, with separate earthing terminal 9 Max. phase difference ilp- olp < 10 degrees 10 Crest factor rating 3: 1 or Better 11 Overall efficiency (normal ~ 95% at rated load and not below 90% at 25% load. mode) 12 Bypass Automatic bypass: Static bypass to provide an uninterruptible transfer of the load to the utility in case of failure of any of the system components or malfunctioning and shall retum the load automatically to the UPS when the malfunction or overload is cleared. The switching time from inverter to reserve (bypass) and vice-versa shall be of No-Break The automatic by-pass switch shall be able to activate manually by a switch/push button to test bypass operation with a disabling feature The maintenance by-pass shall be based on a manually

Supply, testing, installation and commissioning of 5 kYA … · Supply, testing, installation and commissioning of 5 kYA UPS system as per the following specification: 1 Capacity

  • Upload
    hathien

  • View
    227

  • Download
    2

Embed Size (px)

Citation preview

Page 1: Supply, testing, installation and commissioning of 5 kYA … · Supply, testing, installation and commissioning of 5 kYA UPS system as per the following specification: 1 Capacity

Supply, testing, installation and commissioning of 5 kYA UPS system as per thefollowing specification:

1 Capacity 5 kYA UPS system with APFC system2 Input supply Suitable for400±15% Y, 3 phase, 50 ±10% Hz

3 Inlets Through MCB4 Input Power factor & harmonic Input currents shall be sinusoidal.

Correction For all types of loads (linear & non linear) above 25% ofthe rating:(1) Power factor ~ 0.95, using active power factorcorrection system. ".

(2) THDI less than 10 %, using active harmonicconditioners.

5 Rated Output Power 5 kV~ at a power factor 0.8 lag or better6 Out put supply 3 phase 4 wire, 230 Y phase-neutral for all phases, 3

separate outlets for distribution +E tem1inalVoltage Regulation: Range: ± 1% steady state for a static100%) balanced lunbalanced load, 5% for a 0 to 100%load step.Mean deviation for 0-100% step load response: less than±3%. -Recovery time to ± 1%: max 20 ms

7 Output Waveform and Pure Sinusoidal wave.frequency Voltage Distortion (THO): Less than 2% for linear load,

Less than 3 % for non-liner load .50 ± 0.1 % Hz free running and ± 2 % provision forsynchronized with mains

8 Outlets (output panel) through MCB and HRC Fuse, with separate earthingterminal

9 Max. phase difference ilp - olp < 10 degrees10 Crest factor rating 3: 1 or Better11 Overall efficiency (normal ~ 95% at rated load and not below 90% at 25% load.

mode)12 Bypass Automatic bypass: Static bypass to provide an

uninterruptible transfer of the load to the utility in case offailure of any of the system components ormalfunctioning and shall retum the load automatically tothe UPS when the malfunction or overload is cleared.The switching time from inverter to reserve (bypass) andvice-versa shall be of No-BreakThe automatic by-pass switch shall be able to activatemanually by a switch/push button to test bypassoperation with a disabling featureThe maintenance by-pass shall be based on a manually

Page 2: Supply, testing, installation and commissioning of 5 kYA … · Supply, testing, installation and commissioning of 5 kYA UPS system as per the following specification: 1 Capacity

Switchover voltage to inverterConversion TechnologyOverload

Minimum Short CircuitcapabilityDC side

operated switch, which allows the electrical isolation ofthe UPS from the load while still supplying the loaddirectly from the mains.Transfer Time (in Sync Mode with suitable syn. controller)to and from any internal bypass shall be no-break (lessthan 5 ms).

< 320V and > 450VSinusoidal PWM with IGBTUPS: J 20 % for 10 min, 150% for 1 min.Battery operation: 150% for 30 sec,200% for 5 CyclesBypass operation: 120% Continuous5*1 for invertor,20*1 for bypass~ 240 V; Higher voltage support with intelligent batteryman::lgement system is always preferredSealed Maintenance free typeapproved/accepted make and BIS certified.Backup Capacity: 10 minutes at full load; Ampere-hourrating of the battery and no. of batteries selected shall besuitable for the specified back up time.Recharge time: in the order of 6 hours or less for 90%capacity;The battery charger output voltage shall be automaticallyadjusted in proportion to the ambient temperature of thebattery as per the battery supplier's recommendation toavoid over-charging; .The end of discharge voltage of the batteries must beload dependent in order to prevent deep discharging ofthe batteries whilst utilizing maXImum availablecapacity;The rectifier/charger output cun"ent and voltage shall belimited to the battery supplier's recommendation;Constant current charging under floating voltage thenconstant voltage, support with intelligent batterymanagement system. After recharging batteries to fullcapacity, the charger will enter the rest mode to increasethe battery lifetime. Hence, continuous float charging ofthe battery shall not be allowed.Mains -OverfUnder Voltage, Phase Failure,DC OverfUnder Voltage, Inverter OverfUnder Voltage,Inverter Overload, Overheat, Overload trip with manualreset; Low battery trip with audible warning 3 minutesadvance; Battery Over charge, Battery Over current,reverse polarity fault conditions, Battery line fuse;Emergency power off; MCB -Built-in Soft Start ;

Page 3: Supply, testing, installation and commissioning of 5 kYA … · Supply, testing, installation and commissioning of 5 kYA UPS system as per the following specification: 1 Capacity

EMI and surge protection; For safety purposes the UPSshall be equipped with a backfeed protection contactor inthe bypass circuit. This backfeed protection shall beinstalled standard inside the UPS cabinet.

20 Indication/ LCD Display front panel display consisting of a graphical LCD displaywith back light: Mains Voltage-frequency-current input;Output Voltage-frequency-current ;Battcry and DC bus Voltage; Run time on mains failure;Total run time; (or Digital meters for above items)Mains On, Inverter ON, Battery On Charge, MainsOver/Under Voltage, Phase Fail, Low Battery, DCOver/Under Voltage, Inverter Over/Under Voltage,Invelier Overload, Overheat, Load On Inverter, BypassOn, Manual Bypass On;

.\; .Name plate with minimum data:-Name ofManufacturer, Model no, batch-serial no, Date ofmanufacturing, Rating shall be provided on outside underclear visible place.

21 Audible alann with Mains failure, On battery, On bypass, Overload, Lowindication/display & reset Battery, replacement of battery

22 Mounting On Castor wheels with standard leveling feet

23 Data Storage Sufficient to store history for minimum one week or 200events; .

24 Cooling Forced Air

25 Ambient UPS & battery -Suitable for continuous optimumoperation (& storage) without any air conditioning underan ambient temperature 0-45°C & 5 to 95%RH

26 Audible noise < 50 dBA at 1 meter from all sides in all modes.

27 Protection degree IP 20 or better (IEC 60529)

28 Standards Construction & Modular construction -IEC 62040-1, IEC 60950, ENsafety 50091-1

29 Standards EMC IEC 62040-2 ,EN 50091-2

30 Surge capacity IEC 1000-4-5

31 Harmonics standard IEC 61000-3-2/4

32 Performance and topology IEC 62040-3, EN 50091-3

33 Electrostatic Discharge withstand a minimum 8 kV without damage and shall notaffect the critical load.

34 Software interface LCD screen, PC interface with software SNMP as anoption with all necessary accesso ri es/ interfaci ngconnectors/adapters, for Monitoring, controlling andshutdown of the UPS system from remote & local,compatible with Windows 2k,NT,Linex platform

35 WarTantee Minimum 3 years for the complete installation: includingall the pmis and system of UPS and Battery

36 Scope of supply Supply, wiring/cabling of UPS & battery, battery stand,

Page 4: Supply, testing, installation and commissioning of 5 kYA … · Supply, testing, installation and commissioning of 5 kYA UPS system as per the following specification: 1 Capacity

Important:Offer shall be considered onlyif it contains:

Special Conditions at the timeof supply

software interfacing, maintenance manuals, testing &commissioning at specified location as per the relevantIndian standard/ nonns

(I) Technical specification (for each item given herein serial number vise from 1-38) with supportingprinted manual or catalogue for technical items,for the model offered and type test report of themodel offered (attaching a copy of thespecification indicating "comply" IS notacceptable). Technical specifications /Deviationsif any shall be highlighted for each item quoted inserial number vise.

(2) Specify clearly the model, type, make, indicatingoutput power and cU'rrent

(3) Full technical data of the battery offered and shallprovide calculation to show the number of cellsrequired and their capabilities which shall matchthe load requirement and 'the chargingcharacteristics of the UPS requirement beingoffered.(battery back up calculation with batterydischarge/UPS efficiency at different loads shallbe submitted)

(4) ,List of institutions In India where the samemodel/makeirating is commissioned

(5) Nearest servIce center shall be indicated.Maximum response time shall be 24 hours for theservice call. The tenderer shall provide evidence andundertake that round the clock on-call service isavailableto attend to systemfailure.

(6) Certificate of approved dealership from theoriginal manufacturer, if required

(7) AMC charges (after 3 year warranty period)without any conditions for 4th and 5th year shallbe separately specified in the offer

The item will be accepted only after the organisation issatisfied that it is strictly in compliance with the abovetechnical specifications. The finn shall produceacceptance test certificate along with the supply ofequipment, for all the parameters for the UPS offered(same serial number and model) from CPRI, Bangaloreor from Dept. of Electrical Engg.,NIT Calicut.Corresponding test charges shall be borne by the finn.Rejection of the UPS for not satisfying the technicalspecifications or delay in supply /installation as per theabove conditions without valid and sufficient reasonssatisfactory to us, after placing purchase order will leadto blacklisting the finn and/or further penalty as decided