TECHNICAL SUBMITTAL
FORSUBSTATION LIGHTING
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 2/29
TABLE OF CONTENTS
1 . B1 2 2 /2 S u b s t a t io n L ig h t in g a n d
S m a l l P o w er La y o u t
2 . L ig h t in g C a lcu la t io n f o r B1 2 2 /2
S u b s t a t io n
3 . M a t er ia l S u b m i t t a l
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 3/29
B122/2 SUBSTATION
LIGHTING AND SMALL
POWER LAYOUT
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 4/29
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 5/29
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 6/29
B122/2 SUBSTATION
LIGHTING CALCULATION
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 7/29
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 8/29
Rev. B
GENERAL INFORMATION
Location: B122/2 Substation
Area to be lighted: 3.3KV Switchgear Room
Design level of illumination: 23 fc (initial)
15 fc (service)
DESCRIPTION OF AREA AND LUMINAIRE
Dimensions
Room Length….……………………………………………… 11.96 m (39 ft)
Room Width……………………………………………….… 6.60 m (22 ft)
Height of Room between luminaire and work plane (hrc). : 1.5 m (4.92 ft)
Distance from luminaire plane to ceiling (hcc)…………….. .5 m (1.64 ft)
Height of work plane above floor (hfc)………………………1 m ( 3.28 ft)
Room Surface Reflectances Luminaire
Ceiling………………………………………………………… 80% Manufacturer……….… Thorn
Walls above luminaire plane…………………………………50% Catalog No. ……………PP236
Walls between luminarie and workplane……………………50% No. & Type lamps……..2 x 36W Flourescent lamp
Walls below work plane……………………………………… 50% Lumens/Lamp……… : 2650
Floor…………………………………………………………… 20% Maint. Factor...….... : 70%
SELECTION OF COEFFICIENT OF UTILIZATION
1. Determine cavity ratios by formula:
5 x hcc x (L + W)
(L x W)
5 x 1.64 x (39 + 22)
(39 x 22)
5 x hrc x (L + W)
(L x W)
5 x 4.92 x (39 + 22)
(39 x 22)
2. Obtain ef fective cei ling cavi ty ref lectances (pcc) from Table A; pcc = 71%
3. Obtain effective floor cavity reflectances (pfc) from Table A; pfc = 19%
4. Find coefficient of util ization from published data (for pfc=20%) C.U. = 0.66
using RCR, pcc and wall reflectance.
Foot Candle x Area of Room (Sq. ft)
Lamps/Fixture x lumens/lamp x c.u. x m.f.
LIGHTING CALCULATION FOR NEW PACKAGED
(ZONAL CAVITY METHOD)
Contract No. CB / PD / 1105
Project: KNPC VACUUM RE-RUN REVAMP
PROJECT
DOC. NO. 9063B-004-A4111-001
Page 2 of 8
= 1.75 or 1.8
= 8 LUMINAIRES
=23 x (22 x 39)
2 x 2650 x .66 x .7
No.of fixture required =
Ceiling Cavity Ratio (CCR): =
= .58 or .60
Room Cavity Ratio (RCR): =
hrc
hfc
hcc
work plane
floor
ceiling
luminaire
B
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 9/29
Rev. B
GENERAL INFORMATION
Location: B122/2 Substation
Area to be lighted: Low Voltage Room
Design level of illumination: 23 fc (initial)
15 fc (service)
DESCRIPTION OF AREA AND LUMINAIRE
Dimensions
Room Length….……………………………………………… 16.538 m (54 ft)
Room Width……………………………………………….… 6.60 m (22 ft)
Height of Room between luminaire and work plane (hrc). : 1.5 m (4.92 ft)
Distance from luminaire plane to ceiling (hcc)…………….. .5 m (1.64 ft)
Height of work plane above floor (hfc)………………………1 m ( 3.28 ft)
Room Surface Reflectances Luminaire
Ceiling………………………………………………………… 80% Manufacturer……….… Thorn
Walls above luminaire plane…………………………………50% Catalog No. ……………PP236
Walls between luminarie and workplane……………………50% No. & Type lamps……..2 x 36W Flourescent lamp
Walls below work plane……………………………………… 50% Lumens/Lamp……… : 2650
Floor…………………………………………………………… 20% Maint. Factor...….... : 70%
SELECTION OF COEFFICIENT OF UTILIZATION
1. Determine cavity ratios by formula:
5 x hcc x (L + W)
(L x W)
5 x 1.64 x (54 + 22)
(54 x 22)
5 x hrc x (L + W)
(L x W)
5 x 4.92 x (54 + 22)
(54 x 22)
2. Obtain ef fective cei ling cavi ty ref lectances (pcc) from Table A; pcc = 73%
3. Obtain effective floor cavity reflectances (pfc) from Table A; pfc = 19%
4. Find coefficient of utilization from published data (for pfc=20%) C.U. = 0.66 using RCR, pcc and wall reflectance.
Foot Candle x Area of Room (Sq. ft)
Lamps/Fixture x lumens/lamp x c.u. x m.f.
= 1.57
LIGHTING CALCULATION FOR NEW PACKAGED
(ZONAL CAVITY METHOD)
Contract No. CB / PD / 1105
Project: KNPC VACUUM RE-RUN REVAMP
PROJECT
DOC. NO. 9063B-004-A4111-001
Page 3 of 8
2 x 2650 x .66 x .7
No.of fixture required =
Ceiling Cavity Ratio (CCR): =
= .52 or .5
Room Cavity Ratio (RCR): =
= 11.15 or 12 LUMINAIRES
=23 x (54 x 18)
hrc
hfc
hcc
work plane
floor
ceiling
luminaire
B
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 10/29
Rev. B
GENERAL INFORMATION
Location: B122/2 Substation
Area to be lighted: Fire Fighting Gas Cylinder Room
Design level of illumination: 23 fc (initial)
15 fc (service)
DESCRIPTION OF AREA AND LUMINAIRE
Dimensions
Room Length….……………………………………………… 2.50 m (8 ft)
Room Width……………………………………………….… 1.50 m (5 ft)
Height of Room between luminaire and work plane (hrc). : 1.5 m (4.92 ft)
Distance from luminaire plane to ceiling (hcc)…………….. .5 m (1.64 ft)
Height of work plane above floor (hfc)………………………1 m ( 3.28 ft)
Room Surface Reflectances Luminaire
Ceiling………………………………………………………… 80% Manufacturer……….… Thorn
Walls above luminaire plane…………………………………50% Catalog No. ……………PP236
Walls between luminarie and workplane……………………50% No. & Type lamps……..2 x 36W Flourescent lamp
Walls below work plane……………………………………… 50% Lumens/Lamp……… : 2650
Floor…………………………………………………………… 20% Maint. Factor...….... : 70%
SELECTION OF COEFFICIENT OF UTILIZATION
1. Determine cavity ratios by formula:
5 x hcc x (L + W)
(L x W)
5 x 1.64 x (8 + 5)
(8 x 5)
5 x hrc x (L + W)
(L x W)
5 x 4.92 x (8 + 5)
(8 x 5)
2. Obtain ef fective cei ling cavi ty ref lectances (pcc) from Table A; pcc = 49%
3. Obtain effective floor cavity reflectances (pfc) from Table A; pfc = 16%
4. Find coefficient of util ization from published data (for pfc=20%) C.U. = 0.58 using RCR, pcc and wall reflectance.
Foot Candle x Area of Room (Sq. ft)
Lamps/Fixture x lumens/lamp x c.u. x m.f.
= .4 or 1 LUMINAIRE
=23 x (8 x 5)
2 x 2650 x .58 x .7
No.of fixture required =
Ceiling Cavity Ratio (CCR): =
= .2.67
Room Cavity Ratio (RCR): =
= 8.0
LIGHTING CALCULATION FOR NEW PACKAGED
(ZONAL CAVITY METHOD)
Contract No. CB / PD / 1105
Project: KNPC VACUUM RE-RUN REVAMP
PROJECT
DOC. NO. 9063B-004-A4111-001
Page 4 of 8
hrc
hfc
hcc
work plane
floor
ceiling
luminaire
B
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 11/29
Rev. B
GENERAL INFORMATION
Location: B122/2 Substation
Area to be lighted: Battery Room
Design level of illumination: 23 fc (initial)
15 fc (service)
DESCRIPTION OF AREA AND LUMINAIRE
Dimensions
Room Length….……………………………………………… 2.40 m (7.87 ft)
Room Width……………………………………………….… 2.05 m (6.7 ft)
Height of Room between luminaire and work plane (hrc). : 1.5 m (4.92 ft)
Distance from luminaire plane to ceiling (hcc)…………….. .5 m (1.64 ft)
Height of work plane above floor (hfc)………………………1 m ( 3.28 ft)
Room Surface Reflectances Luminaire
Ceiling………………………………………………………… 80% Manufacturer……….… Thorn
Walls above luminaire plane…………………………………50% Catalog No. ……………Petrelux 7, P7236 /HF
Walls between luminarie and workplane……………………50% No. & Type lamps……..2 x 36W Flourescent lamp
Walls below work plane……………………………………… 50% Lumens/Lamp……… : 2650
Floor…………………………………………………………… 20% Maint. Factor...….... : 70%
SELECTION OF COEFFICIENT OF UTILIZATION
1. Determine cavity ratios by formula:
5 x hcc x (L + W)
(L x W)
5 x 1.64 x (7.87 + 6.7)
(7.87 x 6.6)
5 x hrc x (L + W)
(L x W)
5 x 4.92 x (7.87 + 6.7)
(7.87 x 6.7)
2. Obtain ef fective cei ling cavi ty ref lectances (pcc) from Table A; pcc = 53%
3. Obtain effective floor cavity reflectances (pfc) from Table A; pfc = 16%
4. Find coefficient of util ization from published data (for pfc=20%) C.U. = 0.58 using RCR, pcc and wall reflectance.
Foot Candle x Area of Room (Sq. ft)
Lamps/Fixture x lumens/lamp x c.u. x m.f.
= 6.8
LIGHTING CALCULATION FOR NEW PACKAGED
(ZONAL CAVITY METHOD)
Contract No. CB / PD / 1105
Project: KNPC VACUUM RE-RUN REVAMP
PROJECT
DOC. NO. 9063B-004-A4111-001
Page 5 of 8
2 x 2650 x .58 x .7
No.of fixture required =
Ceiling Cavity Ratio (CCR): =
2.26
Room Cavity Ratio (RCR): =
= .56 or 1 LUMINAIRE
=23 x (7.87 x 6.7)
hrc
hfc
hcc
work plane
floor
ceiling
luminaire
B
B
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 12/29
Rev. B
GENERAL INFORMATION
Location: B122/2 Substation
Area to be lighted: Walkways and stairs area
Design level of illumination: 3.3 fc (initial)
2 fc (service)
DESCRIPTION OF AREA AND LUMINAIRE
Dimensions
Length (L) ….…………………………………………… : 2.3 m (6.89 ft)
Height (H) ………………………………………………. : 3 m (9.84 ft)
Distance (D) ………………………………………..….. : 3.66 m (12 ft)
Luminaire
Manufacturer……….……. : Thorn
Catalog No. …………….... : DBV1040
No. & Type lamps……... : 1 x 70W Son-E High Pressure Sodium lamp
Lumens/Lamp……… : 5800
Maint. Factor...….... : 70%
Candle Power……….: 870
Foot candle computation:fc = CP x H x LLF
D³
where:
fc - Foot Candles
CP - Candle Power of Luminaire
H - Mounting Height
D - Distance
LLF - Light Loss Factor or Maintenance Factor
fc = 870 x 9.84 x .7
(12)³
= 3.47 fc
* Since the foot candle computed is larger than the design level of illumination (3.47 > 3.3)
then the lamp proposed is adequate.
LIGHTING CALCULATION FOR NEW PACKAGED
SUBSTATION B122/2
(POINT BY POINT METHOD)
Contract No. CB / PD / 1105
Project: KNPC VACUUM RE-RUN REVAMP
PROJECT
DOC. NO. 9063B-004-A4111-001
Page 6 of 8
floor
wall
H
luminaire
L
D
B
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 13/29
Rev. B
GENERAL INFORMATION
Location: B122/2 Substation
Area to be lighted: Transformer Area
Design level of illumination: 3.3 fc (initial)
2 fc (service)
DESCRIPTION OF AREA AND LUMINAIRE
Dimensions
Length (L) ….…………………………………………… : 5.9 m (19.35 ft)
Height (H) ………………………………………………. : 4.5 m (14.76 ft)
Distance (D) ………………………………………..….. : 7.42 m (24.34 ft)
Luminaire
Manufacturer……….……. : Thorn
Catalog No. …………….... : Sonpak 7/15 OT100T.4
No. & Type lamps……... : 1 x 100W HPS-T High Pressure Sodium Lamp
Lumens/Lamp……… : 9,200
Maint. Factor...….... : 70%
Candle Power……….: 5,520
Foot candle computation:fc = CP x H x LLF
D³
where:
fc - Foot Candles
CP - Candle Power of Luminaire
H - Mounting Height
D - Distance
LLF - Light Loss Factor or Maintenance Factor
fc = 5,520 x14.76 x .7
(20.87)³
= 3.96 fc
* Since the foot candle computed is larger than the design level of illumination (3.96 > 3.3)
then the lamp proposed is adequate.
LIGHTING CALCULATION FOR NEW PACKAGED
SUBSTATION B122/2
(POINT BY POINT METHOD)
Contract No. CB / PD / 1105
Project: KNPC VACUUM RE-RUN REVAMP
PROJECT
DOC. NO. 9063B-004-A4111-001
Page 7 of 8
floor
wall
H
luminaire
L
D
B
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 14/29
90 70 50 30 80 70 50 30 70 50 30 70 50 30 65 50 30 10 50 30 10 50 30 10
0 90 90 90 90 80 80 80 80 70 70 70 50 50 50 30 30 30 30 20 20 20 10 10 10
0.1 90 89 88 87 79 79 78 78 69 69 68 59 49 48 30 30 29 29 20 20 20 10 10 10
0.2 89 88 86 85 79 78 77 76 68 67 66 49 48 47 30 29 29 28 20 20 19 10 10 9
0.3 89 87 85 83 78 77 75 74 68 66 64 49 47 46 30 29 28 27 20 19 18 10 10 9
0.4 88 86 83 81 78 76 74 72 67 65 63 48 46 45 30 29 27 26 20 19 18 11 10 9
0.5 88 85 81 78 77 75 73 70 66 64 61 48 46 44 29 28 27 25 20 19 17 11 10 9
0.6 88 84 80 76 77 75 71 68 65 62 59 47 45 43 29 28 26 25 20 18 17 11 10 9
0.7 88 83 78 74 76 74 70 66 65 61 58 47 44 42 29 28 26 24 20 18 16 11 10 8
0.8 87 82 77 73 75 73 69 65 64 60 56 47 43 41 29 27 25 23 19 18 16 11 10 8
0.9 87 81 76 71 75 72 68 63 63 59 55 46 43 40 29 27 25 22 19 17 15 11 9 8
1 86 80 74 69 74 71 66 61 63 58 53 46 42 39 29 27 24 22 19 17 15 11 9 8
1.1 86 79 73 67 74 71 65 60 62 57 52 46 41 38 29 26 24 21 19 17 15 11 9 8
1.2 86 78 72 65 73 70 64 58 61 56 50 45 41 37 29 26 23 20 19 16 14 12 9 7
1.3 85 78 70 64 73 69 63 57 61 55 49 45 40 36 29 26 23 20 19 16 14 12 9 7
1.4 85 77 69 62 72 68 62 55 60 54 48 45 40 35 28 26 22 19 19 16 13 12 9 7
1.5 85 76 68 61 72 68 61 54 59 53 47 44 39 34 28 28 22 18 20 16 13 12 9 7
1.6 85 75 66 59 71 67 60 53 59 52 45 44 39 33 28 25 21 18 19 15 13 12 9 7
1.7 84 74 65 58 71 66 59 52 58 51 44 44 38 32 28 25 21 17 19 15 12 12 9 7
1.8 84 73 64 56 70 65 58 50 57 50 43 43 37 32 28 25 21 17 19 15 12 12 9 6
1.9 84 73 63 55 70 65 57 49 57 49 42 43 37 31 28 25 20 16 19 15 11 12 9 6
2 83 72 62 53 69 64 56 48 56 48 41 43 37 30 28 24 20 16 18 15 11 12 9 6
2.1 83 71 61 52 69 63 55 47 56 47 40 43 36 29 28 24 20 16 19 15 11 13 9 6
2.2 83 70 60 51 68 63 54 45 55 46 39 42 36 29 28 24 19 15 19 14 11 13 9 6
2.3 83 69 59 50 68 62 53 44 54 46 38 42 35 28 28 24 19 15 19 14 11 13 9 6
2.4 82 68 58 48 67 61 52 43 54 45 37 42 35 27 28 24 19 14 19 14 10 13 9 6
2.5 82 68 57 47 67 61 51 42 53 44 36 41 34 27 27 23 18 14 18 14 10 13 9 6
2.6 82 67 56 46 66 60 50 41 53 43 35 41 34 26 27 23 18 13 18 14 9 13 9 5
2.7 82 66 55 45 66 60 49 40 52 43 34 41 33 26 27 23 18 13 18 14 9 13 9 5
2.8 81 66 54 44 66 59 48 39 52 42 33 41 33 28 27 23 18 13 18 14 9 13 9 5
2.9 81 65 53 43 65 58 48 38 51 41 33 40 33 25 27 23 17 12 18 13 9 13 9 5
3 81 64 52 42 65 58 47 38 51 40 32 40 32 24 27 22 17 12 18 13 9 13 8 5
3.1 80 64 51 41 64 57 46 37 50 40 31 40 32 24 27 22 17 12 18 13 9 13 8 5
3.2 80 63 50 40 64 57 45 36 50 39 30 40 31 23 27 22 16 11 18 12 8 13 8 5
3.3 80 62 49 39 64 56 44 35 49 39 30 39 31 23 27 22 16 11 18 12 8 13 8 5
3.4 80 62 48 38 63 56 44 34 49 38 29 39 31 22 27 22 16 11 18 12 8 13 8 53.5 79 61 48 37 63 55 43 33 48 38 29 39 30 22 26 22 16 11 18 12 8 13 8 5
3.6 79 60 47 36 62 54 42 33 48 37 28 39 30 21 26 21 15 10 17 12 8 13 8 5
3.7 79 60 46 35 62 54 42 32 48 37 27 38 30 21 26 21 15 10 17 12 7 13 8 4
3.8 79 59 45 35 62 53 41 31 47 36 27 38 29 21 26 21 15 10 17 12 7 13 8 4
3.9 78 59 45 34 61 53 40 30 47 36 26 38 29 20 26 21 15 10 17 12 7 13 8 4
4 78 58 44 33 61 52 40 30 46 35 26 38 29 20 26 21 15 9 17 12 7 13 8 4
4.1 78 57 43 32 60 52 39 29 46 35 25 37 28 20 26 21 14 9 17 11 7 13 8 4
4.2 78 57 43 32 60 51 39 29 46 34 25 37 28 19 26 20 14 9 17 11 7 13 8 4
4.3 78 56 42 31 60 51 38 28 45 34 25 37 28 19 26 20 14 9 17 11 7 13 8 4
4.4 77 56 41 30 59 51 38 28 45 34 24 37 27 19 26 20 14 8 17 11 6 13 8 4
4.5 77 55 41 30 59 50 37 27 45 33 24 37 27 19 25 20 14 8 17 11 6 14 8 4
4.6 77 55 40 29 59 50 37 26 44 33 24 36 27 18 25 20 14 8 17 11 6 14 8 4
4.7 77 54 40 29 58 49 36 26 44 33 23 36 26 18 25 20 13 8 17 11 6 14 8 4
4.8 76 54 39 28 58 49 36 25 44 32 23 36 26 18 25 19 13 8 17 11 6 14 8 4
4.9 76 53 38 28 58 49 35 25 44 32 23 36 26 18 25 19 13 7 17 11 6 14 8 4
5 76 53 38 27 57 48 35 25 43 32 22 36 26 17 25 19 13 7 17 11 6 14 8 4
TABLE A - EFFECTIVE CAVITY REFLECTANCES
% Ceiling or Floor
Reflectance 90 80 70 50
LIGHTING CALCULATION FOR NEW PACKAGED
SUBSTATION B122/2
Contract No.CB/PD/1105
C e i i n g o r F l o o r C a v i t y R a t i o
30 20 10
% Wall Reflectance
Project: KNPC VACUUM RE-
RUN REVAMP PROJECT
Doc. No.9063B-004-A4111-001
Rev. B Page 8 of 8
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 15/29
MATERIAL SUBMITTAL
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 16/29
L IST OF MATERIALS
Sn DESCRIPTION AREA USED CAT. NO. MAKE
1. Fluorescent battenfitting of slim cross-section, T8 - 2 x36W, switch start,with clip-on coverplate and adjustableend cap system withreflector.
Substation,Indoor GeneralLighting
PP236 +PPRE24
Thorn-UK
2. Fluorescent battenemergency fitting ofslim cross-section, T8 - 2 x 36W, switchstart, with 3 hoursback-up power from
self containedbattery with charger.Clip-on cover plateand adjustable endcap system withreflector.
Substation,IndoorEmergencyLighting
E3PP236+ PPRE24
Thorn-UK
3. Fluorescent battenemergency fitting ofslim cross-section, T8 - 1 x 36W, switchstart, with 3 hoursback-up power fromself containedbattery with charger.Clip-on cover plateand adjustable endcap system.
Substation,Indoor GeneralLighting (AirLock area)
E3PP136 Thorn-UK
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 17/29
4. Fluorescent batten
fitting of slim cross-section, T8 - 2 x36W, switch start,with clip-on coverplate and adjustableend cap system withreflector.
Fire Fighting Gas
Cylinder Room
PP236 +
PPRE24
Thorn-
UK
5. EEX ed, ATEX Cat 2
Gas group IIB & IICcertified,polycarbonate L alloybodied fluorescentfitting withpolycarbonate coverand rapid fix flexibleinstallation channel. T8 – 2 x 36W, HFElectroniccontrolgear.
Battery Room P7236/S4
/HF
Thorn-
UK
6. Cast Aluminumbulkhead lampfitting with mouldedglass cover fordischarge lamps.IP65 protection.HPS-E 70W HighPressure SodiumLamp with Integral
Gear.
SubstationExternal Lighting(Mounted onexterior walls ofSubstation)
DB70 Thorn-UK
7. Enclosed Floodlightwith black aluminumbody and frame,housing flat glass.Integral controlgearand assymetricalreflector for 100WHPS-T lamp.
SubstationExternal Lighting – TransformerArea (Mountedon exterior wallsof Substation)
SONPAK7/15OT100T.4
Thorn-UK
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 18/29
8. Self contained single
sided exit sign with8W fluorescent lampfor non-maintainedemergency lightingfor 3 hour duration.
Substation Exit
Sign on Doors.
EFX3-NM Thorn-
UK
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 19/29
INDOOR
LIGHTING FIXTURES
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 20/29
www.thornlighting.co.uk 90
Popular Range Battens1:10
The only one called ‘Pop Pack’,the original fluorescent batten.
• 5 year guarantee* on‘Super Pack’ versions
• ‘Super Pack’ versions suppliedwith HF ballast and Tri-Phosphorlamp for maximum economicoperation and minimummaintenance
• No conversions - standardrange includes maintainedemergency versions. Battens,louvre and reflector
attachments are suitable foremergency lighting.
• Adjustable twin lampholderprovides uniform light inlow ceiling installations ordownward light in highmounting positions
• Tool-less clip-on cover platefor quick installation
• Dimmable Digital Controliteversions allow dimming downto 1% lamp power
• Single and Twin body in 5lengths from 600mm to2400mm (2ft – 8ft)
• High frequency electronic orswitch start wire wound gear
• A range of diffusers andreflectors covering everyapplication requirement
• Can be surface orsuspension mounted
•Twist-lock lampholders forreliable electrical contact
• Slim spine with durable,corrosion resistant finish
* Conditions apply
Materials/FinishBatten: Rolled steel section inpre-coated high reflectivitywhite paint.Lampholder assembly:Tough white polycarbonate.
Twin ( lampholder narrow posit ion) Twin ( lampholder wide posi tion)
81
82 125
64
Single
82
60
42
18W, 36W, 58W, 70W, 100W Standard T8 (3500K) G13 Super Pack T8 835 (3500K) G13
EN 60598, (Emergency EN 60598 2.22) SLL LG3 65°, 500cd/m2 for VDT insert louvres (1000cd/m2 for single Architectural Up/Downlight louvre - 2 x 36W is 1500cd/m2)
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 21/29
www.thornlighting.co.uk 91
Ordering Guide Supplied complete with lamp(s), (switchstart 3500Kstandard white, high frequency 835), unless otherwise stated. To ordera complete luminaire quote required batten and correspondingattachment catalogue number(s).
Lamp type Overall Weight Cat. No. Emergency version Cat. No.& rating Length (kg) Weight (kg)
(mm)
Super Pack - High Frequency Electronic BallastT8 1 x 36W 1223 1.90 PPZXL136* 2.75 E3 PZXL136*T8 2 x 36W 1223 2.10 PPZXL236* 2.95 E3 PZXL236*T8 1 x 58W 1523 2.05 PPZXL158* 3.05 E3 PZXL158*T8 2 x 58W 1523 2.25 PPZXL258* 3.30 E3 PZXL258*T8 1 x 70W 1787 2.30 PPZXL170* 3.45 E3 PZXL170*T8 2 x 70W 1787 2.50 PPZXL270* 3.65 E3 PZXL270*
SwitchstartT8 1 x 18W 613 1.80 PP118T8 2 x 18W 613 2.16 PP218T8 1 x 36W 1223 2.60 PP136 3.45 E3 PP136T8 2 x 36W 1223 4.10 PP236 4.85 E3 PP236T8 1 x 58W 1523 3.40 PP158 4.40 E3 PP158T8 2 x 58W 1523 5.45 PP258 6.25 E3 PP258T8 1 x 70W 1787 3.70 PP170 4.85 E3 PP170T8 2 x 70W 1787 6.12 PP270 7.25 E3 PP270T8 1 x 100W 2398 5.23 PP1100T8 2 x 100W 2398 7.95 PP2100
Controlite Digital Dimming Versions (Lamps to be ordered separately).T8 1 x 36W 1223 2.10 PP136CLDLL 2.95 E3PP136CLDLLT8 2 x 36W 1223 2.30 PP236CLDLL 3.15 E3PP236CLDLLT8 1 x 58W 1523 2.35 PP158CLDLL 3.35 E3PP158CLDLLT8 2 x 58W 1523 2.55 PP258CLDLL 3.55 E3PP258CLDLL
* With 835 (3500K) lamp.
0°
100
50
150
30°
60°
90°
30°
90°
120° 180°
120°
60°
cd/1000 lm
TA
Cat. No. PP258 (Narrow Position)ULOR: 0.30 DLOR: 0.64 LOR: 0.94 LMC: A
Utilisation factors UF (F)
Mounting: Ceiling
Reflectances Room IndexC W F 1.0 2.0 3.0 4.0 5.0
0.8 0.6 0.2 0.61 0.78 0.85 0.89 0.920.5 0.56 0.73 0.82 0.86 0.890.3 0.48 0.67 0.76 0.81 0.85
0.7 0.6 0.2 0.57 0.73 0.80 0.84 0.860.5 0.53 0.69 0.77 0.81 0.840.3 0.46 0.63 0.72 0.77 0.80
0.5 0.6 0.2 0.51 0.65 0.71 0.74 0.760.5 0.48 0.62 0.69 0.72 0.750.3 0.42 0.57 0.64 0.69 0.72
Cat. No. E3PPZXL258 (Narrow Position)
2m Escape route
Min illum M ounting Max spacing (m)
( lux ) he ig ht (m) ce nt re to en d b et wee n c en tr es
2.5 3.25 9.101.0 trans 3.0 3.25 9.20
3.5 3.15 9.30
2.5 2.70 7.001.0 axial 3.0 2.70 7.40
3.5 2.65 7.60
Open area
Min Mounting Max spacing (m)
illum height centre to end between centres
(lux) (m) Trans Axial Trans Axial
2.5 2.95 2.95 9.80 8.800.5 3.0 3.05 3.05 10.30 9.503.5 3.10 3.10 10.80 10.00
Installation/MountingFour-way terminal block withcapacity for 2 x 2.5mm2 cables.Angled terminal block foreasy wiring.Ambient temperature: Switchstart-5°C to 25°C, High frequencyelectronic -15°C to 25°C.Normal, dry, indoor atmospheres.Fixings via three BESA piercings,one central and two at fixingcentres: 600mm - 500mm,1200/1500/1800mm - 600mm,2400mm - 1200mm (HF electronicversions have no central fixing.)Bare battens can be mountedend-to-end (except emergencyversions - recommended minimumspace between luminaires 50mm).Emergency fixing centres:E3PP158/E3PP170 - 600mm,E3PP136/E3PP236/E3PPZXL13/E3PPZXL236 - 1110mmE3PP258/E3PP270/E3PPZXL15/E3PPZXL258/E3PPZXL170/E3PPZXL270 - 1410mm.
SpecificationTo specify state:Fluorescent batten fitting of slim
cross-section with clip-on coverplate and adjustable endcap system.As Thorn Popular Pack Batten.
Popular Range Batten with Architectural Up/Downlight Attachment
I ND O OR C O M ME R C I A L
F L U OR E S C E N
T B A T T E N S &
S Y S T E M S
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 22/29
www.thornlighting.co.uk 93
Popular Range Reflectors 4:10
Choice of Economy, Asymmetricand Rack reflectors for use withPopular Battens.
Economy Reflectors
• For cost conscious schemes
• Narrow reflector for lowest cost
• Wide reflector for highestlight output
• Wire guard available• Continuous end to end
mounting possible (exceptemergency versions and wireguard) 50mm spacingminimum recommended
Materials/FinishReflectors: Steel with precoathigh reflectivity white finishWire guards: Steel, brightZinc plated
Specification
To specify state:Open-ended, trough reflector inwhite stove enamelled steel withoptional wire guard (PP/PT GE).As Thorn Popular Range MetalReflector (PPR).
Ordering Guide
Description Cat. No. Optional wire guardfor reflector Cat. No.
Economy reflector - nar row - for 1 & 2 x 36W PPRE 4 PP/PT GE 4Economy reflector - nar row - for 1 & 2 x 58W PPRE 5 PP/PT GE 5Economy reflector - nar row - for 1 & 2 x 70W PPRE 6 PP/PT GE 6Economy reflector - narrow - for 1 x 100W PPRE 8 PP/PT GE 8Economy reflector - wide - for 1 & 2 x 36W PPRE 24 PP/PT GE 24Economy reflector - wide - for 1 & 2 x 58W PPRE 25 PP/PT GE 25Economy reflector - wide - for 1 & 2 x 70W PPRE 26 PP/PT GE 26
Economy reflector - wide - for 1 & 2 x 100W PPRE 28 PP/PT GE 28Rack reflector for 1 & 2 x 58W PPRL 5Rack reflector for 1 & 2 x 70W PPRL 6Asymmetrical reflector for 1 & 2 x 36W PPA 4Asymmetrical reflector for 1 & 2 x 58W PPA 5Asymmetrical reflector for 1 & 2 x 70W PPA 6
Narrow economy reflector Wide economy reflector with wire guard
121
92.5 92.5
167.5
51
287
199
121
92.5
Narrow reflector (lampholder narrow position)
Narrow reflector
Wide reflector (lampholder narrow position) Rack lighting
79
133
Asymmetrical metal reflector single
133
110
Asymmetrical metal reflector twin
Rack Lighting Reflector
• For use where verticalillumination is required innarrow aisle racking
• Continuous end to endmounting possible (except
emergency versions)
SpecificationTo specify state:Rack lighting reflector in highreflectivity polished aluminium.As Thorn Popular Range RackLighting Reflector (PPRL).
Asymmetrical MetalReflector
• For use where wall washinglight is required
• Twin batten offers alternativelumen distribution with
adjustable lampholder
SpecificationTo specify state:Single side angled reflector inwhite stove enamelled steel.As Thorn Popular Range AngledMetal Reflector (PPA).
Rack lighting reflector Asymmetrical metal reflector
I ND O OR C O M ME R C I A L
F L U OR E S C E N
T B A T T E N S &
S Y S T E M S
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 23/29
EXPLOSION PROOF
LIGHTING FIXTURES
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 24/29
www.thornlighting.co.uk 301
Petrelux 71:1
18W, 36W, 58W, 70W T8 bi pin 36W, 55W TC-L 2G11 For Standards see below
• Ideal for general indoorand outdoor lighting
• Please ask for adviceregarding use in
atmospheres withorganic contaminants
• Lamp/gear access fromeither end of luminaire
• Lightweight for easeof installation
A Zone 1 (ATEX Catagory 2)Flameproof EEx d linearfluorescent luminaire for surfaceor suspended mounting.
Ordering Guide Lamps to be ordered separately.
Lamp type Weight Cat. No. Weight Emergency & rating (kg) (kg) Cat. No.
T8 600mm 1 x 18W 5.5 P 7118/S2/HFT8 1200mm 1 x 36W 9.0 P 7136/S4/HF 11.5 P 7136/S4/HF/EM
T8 1500mm 1 x 58W 9.5 P 7158/S5/HF 12.0 P 7158/S5/HF/EMT8 1800mm 1 x 70W 10.0 P 7170/S6/HFT8 600mm 2 x 18W 5.5 P 7218/S2/HFT8 1200mm 2 x 36W 9.0 P 7236/S4/HF 12.0 P 7236/S4/HF/EMT8 1500mm 2 x 58W 9.5 P 7258/S5/HF 12.5 P 7258/S5/HF/EMT8 1800mm 2 x 70W 10.0 P 7270/S6/HFTC-L 2 x 36W 5.5 P7236/S2/HF 6.0 P 7236/S2/HF/EMTC-L 2 x 55W 5.5 P7255/S2/HF - -
Accessories
Description Cat. No.Overhead canopy for 18W T8/36W x 55WTC-L luminaires P 718/SCOverhead canopy for 36W T8 luminaires P 736/SCOverhead canopy for 58W T8 luminaires P 758/SCOverhead canopy for 70W T8 luminaires P 770/SCWire guard for 18W T8/36W x 55WTC-L luminaires P 718/WGWire guard for 36W T8 luminaires P 736/WGWire guard for 58W T8 luminaires P 758/WGWire guard for 70W T8 luminaires P 770/WG
Pole clamp mounting kit for 40mm Ø pole P 7/PC40Pendant mounting kit P 7/PM
Materials/FinishBody: Aluminium alloy finishedPetrelux green. 2 pack epoxy withpre-treated and primed surface.Overtube: Polycarbonate.
Installation/Mounting2 x M8 tapped holes - verticaland horizontal at each end.Cable entries: 2 x 20mm eachend - ISO thread - 3 entries
fitted with plugs.Terminals: 3 wire plus earth -max conductor 4mm2 andsuitable for looping.
SpecificationTo specify state:EEx d Flameproof/Emergencyfluorescent luminaire inaluminium alloy and
polycarbonate overtube. IP66.As Thorn Petrelux 7/Petrelux 7Emergency.
• New high output compactfluorescent lamp versions
• Integral high frequencyelectronic ballast
• Emergency (3hr duration)versions available as standard
158
2 x M20 or equiv. each end M8 each end
A
B 140
Standards
Zone: ATEX Cat 2 (can also be used in Cat 3)
Zone 1 (can also be used in Zone 2)
Gas Groups: 11C 18W T8, 36W TC-L and 55W TC-L
11B 36W T8, 58W T8 and 70W T8
T Rating: T4 - T5 - T6 (see certification detail)
Voltage: 220/240V, 50/60Hz
IP Rating: IP66 to IEC 529
Certi ficat ion Code: EEx d 11B and 11C T5 - T6
Certification Standard: EN50014 and 50018
Approval Authority: SIRACertificate Number: 01 ATEX 1033
Certification Detail: 18W T6 @ Ta = 40°C 11C
36W T8 T6 @ Ta = 40°C 11C
58W T6 @ Ta = 40°C 11C
70W T5 @ Ta = 40°C 11C
36W TC-L T6 @ Ta = 40°C 11C
55W TC-L T6 @ Ta = 40°C 11C
I ND U S T R I A L
P R O OF |
H A
Z A R D O U S A R E A
L U MI NA I R E S
Dim A fixing Dim B o/a Dim B o/acentres length Standard length Emergency
18W T8/36W + 55W TC-L 632 752 75236W T8 1242 1362 149058W T8 1542 1662 179070W T8 1806 1926 -
Emergency version
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 25/29
OUTDOOR
LIGHTING FIXTURES
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 26/29
www.thornlighting.co.uk 300
DB Bulkhead1:1
70W HPS-E E27 150W, 200W GLS E27 220/240V, 50Hz IP65 EN 60598
A tough bulkhead fordischarge or tungsten lampsfor use in non-hazardous areas.
• Ideal for localised lighting
• Robust cast aluminium bodyand glass bowl resist impactand corrosion
• Wire guard option foradded protection
Materials/FinishBody: Pressure die castLM6 aluminium finishedhammer grey.Bowl: Moulded borosilicateprismatic glass in hingedaluminium frame retained byfour stainless steel Allen screws.
Reflector/gear tray: Whitepainted steel.
Installation/Mounting
Direct ceiling or wall mounting.M20 cable entry at each end,one with removable plug forthrough wiring. Suitable for40°C maximum ambientdepending on orientation.
SpecificationTo specify state:Cast aluminium bulkhead withmoulded glass cover fordischarge/tungsten lamps.IP65 protection.As Thorn DB Bulkhead.
296 fxg crs
314
192
170105
fxg crs
Cat. No. DB70Lamp: 70W HPS-EULOR: 0.10 DLOR: 0.69 LOR: 0.79 SHR max: 1.92 LMC: E
50
100
150
90°
30°30° 0°
60°60°
90°
cd/1000 lm
AT
Utilisation factors UF (F)
Reflectances Room IndexC W F 1.0 2.0 3.0 4.0 5.0
0.8 0.6 0.2 0.49 0.64 0.71 0.75 0.780.5 0.44 0.60 0.68 0.72 0.750.3 0.37 0.53 0.62 0.67 0.70
0.7 0.6 0.2 0.47 0.61 0.68 0.72 0.750.5 0.43 0.58 0.65 0.69 0.720.3 0.36 0.51 0.59 0.65 0.68
0.5 0.6 0.2 0.44 0.57 0.63 0.66 0.690.5 0.40 0.53 0.60 0.64 0.670.3 0.34 0.48 0.56 0.60 0.63
Ordering Guide HPS-E versions supplied complete with lamp,
GLS less lamp.Lamp type Description Weight Cat. No.& rating (kg)
HPS-E 70W Integral gear 6.0 DB70GLS 150/200W ES lamp not supplied 4.3 DB200
Spares and Attachments
Description Cat. No.Glass bowl DBGWire guard DBW
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 27/29
www.thornlighting.co.uk 373
Ordering Guide Supplied complete with lamp.
Lamp type Windage Weight Cat. No.& rating (m2) (kg)
HPS-T (external ignitor) 70W 0.105 9.0 OT70T.4HPS-T 100W 0.105 9.0 OT100T.4HPS-T 150W 0.105 9.0 OT150T.4HIT-DE 150W 0.105 9.0 OTMH150D.4
Export voltages available, refer to page 553 for details.
Attachments
Description Cat. No.Wire guard OTWGBLouvre* OTLBSpill shield for environmentally sensitive areas* OTSSB
Pole clamp for use with 48-89mm Ø poles OHA4613Sonpak single mounting bracket (76mm Ø shaft) QCB F1Sonpak twin stirrup version mounting bracket (76mm Ø shaft) QCB F2Sonpak triple stirrup version mounting bracket (76mm Ø shaft) QCB F3 DELTASonpak 4-way stirrup version mounting bracket (76mm Ø shaft) QCB F4 CROSS
Note that brackets above are suitable for use with QC-TC and QCZR (76mm Ø shaft) columns.*Supplied with 4 screws and washers. These attachments cannot be mounted together,one on the other. See page 372 for attachments.
O U T D O OR
A R E A
F L O OD
L I GH T I N G
Sonpak 7/151:1
Discharge floodlight forgeneral area lighting.
• Choice of high pressure sodiumor double-ended metal halidelamps in a variety of wattages
• Robust die-cast aluminium
body and front frame• Asymmetrical reflector
• Toughened glass front
• Integral control gear
• Spill shield available forreduced glare (see page 372)
• Easy installation with drop downfront glass and cable entry
• Adjustable streamlined stirrupfor flexibility in mounting
• Sealed to IP65
Materials/FinishBody and front frame: Die-castaluminium, painted black,RAL 9005.Reflector: Dimpled anodisedaluminium.Lens: Tempered 4mm flat glasswith stainless steel bolts andsilicone rubber gasket.Stirrup: 3mm mild steel, polyesterpainted black, RAL 9005.
Installation/MountingOne glanded cable entry for9-13mm o/d cable with 3 poleterminal block for up to 10mm2
cables.21mm Ø knockout at rear forthrough wiring.Stirrup fixed by single boltthrough 21mm Ø hole. Twoadditional 11mm Ø fixing holesat 102mm centres, with a furthertwo 13mm Ø fixing holes at250mm centres.Aiming angle of floodlight aidedby goniometer.
SpecificationTo specify state:Enclosed floodlight with blackaluminium body and frame,housing flat glass. Integral controlgear and asymmetrical reflectorfor 70W/100W/150W HPS-Tor 150W HIT-DE lamp.Sealed to IP65.As Thorn Sonpak 7/15.
127
256
335
115
400 365
192
-90° -60° -30° 0° 30° 60° 90°
900
750
600
450
300
250
0
cd/1000 lm
horizontalvertical
Cat. No. OT150T.4Lamp: 150W HPS-T
70W HPS-T E27 (external ignitor) 100W, 150W HPS-T E40 150W HIT-DE Rx7s
IP65 EN 60598 5 joules 960˚ Hotwire Ta Max: +25˚C
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 28/29
EMERGENCY
LIGHTING FIXTURES
8/12/2019 Submittal for Substation Lighting
http://slidepdf.com/reader/full/submittal-for-substation-lighting 29/29
E ME R GE N C Y
L I GH T I N G
1:1
Voyager 8W Single Sided Exit
C O M ME R C I A L L I GH T I N G
A simple cei ling or wallmounted emergency exitsign luminaire for generalinterior use.
Key Features
Ceiling or wall mounting options
Choice of white or brass finish
Strong, durable construction
Non-maintained, maintained andsustained options to matchapplication needs
Extensive choice of legend panelsto match scheme style
Lamp Type
8W, T5, white fluorescent,cap: G5
Materials/Finish
Body: Folded steel construction withwhite stove enamelled or brass finish
Electrical Characteristics
Supply voltage: 220/240V
Input current: 50mAFrequency: 50Hz
Ordering GuideSupplied complete with lamp. Legends to be ordered separately.
Lamp type Description Duration Weight Cat. No.& rating (hrs) (kg)
Non-Maintained
T5 8W White 3 2.8 EFX3 NM
T5 8W Brass 3 2.8 EFX3 NM/BR
Maintained
T5 8W White 3 2.8 EFX3
T5 8W Brass 3 2.8 EFX3/BR
Sustained
T5 8W White 3 2.8 EFXS3
T5 8W Brass 3 2.8 EFXS3/BR
Attachments
Euro Legends Cat. No. Pictograms Cat. No.
EFXF EFXF 7
EFXE 1 EFXF 8
EFXE 2 EFXF 9
EFXE 3 EFXF 10
EFXE 4 EFXF 11
320mmfixingcentres
515mm
60mm
150mm fixing centres
191mm
Installation/Mounting
Ceiling or wall mounting, 20mmBESA provision in back plate or20mm Ø conduit knockout on eitherend. Screw fixings in back face.4 way terminal block,2 x 2.5mm2 capacity.
Standards
Designed and manufactured tocomply with EN 60598 2.22
Ta: -5°C to +25°C
Photometric Data
For signage only.
Specification
To specify state:Self contained single sided exit signwith 8W fluorescent lamp formaintained/non-maintained/sustainedemergency lighting for 3 hourduration. Steel construction.As Thorn EFX3.