SUBMITTAL DATA SHEET
SINGLE PACKAGE AIR CONDITIONERS ANDGAS HEAT/COOLING UNITS, 3 THROUGH 12-1/2 TONSMODELS: ZQ04 THRU 06, ZX04 THRU 14, ZY04 THRU 12, AND ZL08 THRU 14
JOB NAME: LOCATION:
PURCHASER: ORDER NO:
ENGINEER:
SUBMITTED TO: FOR: REF: APPROVAL: CONSTRUCTION:
SUBMITTED BY: DATE:
UNIT DESIGNATION: SCHEDULE NO. MODEL NO.
COOLING PERFORMANCE
TOTAL CAPACITY- - - - - - - - - - - - - - _____ MBH
SENSIBLE CAPACITY - - - - - - - - - - - _____ MBH
OUTDOOR DESIGN TMP. _________ °F DB/WB
TOTAL SUPPLY AIR - - - - - - - - - - - - _____ CFM
TEMP. OF AIR ENTERINGEVAPORATOR COIL - - - - - - - - - - - - - - _____ °F
POWER INPUT REQ. - - - - - - - - - - - - - _____ KW(LESS BLOWER MOTOR)
HEATING PERFORMANCE
ELECTRIC HEAT - - - - - - - - - - - - - - - - _____ KW
GAS-FIRED INPUT CAP. - - - - - - - - - _____ MBH
SUPPLY AIR BLOWER PERFORMANCE
TOTAL SUPPLY AIR - - - - - - - - - - - - _____ CFM
EXT. STATIC PRESS. - - - - - - - - - - - _____ IWG
BLOWER SPEED- - - - - - - - - - - - - - - - ____ RPM
POWER OUTPUT REQ. - - - - - - - - - - _____ BHP
MOTOR RATING - - - - - - - - - - - - - - - - _____ HP
POWER INPUT REQ. - - - - - - - - - - - - - _____ KW
ELECTRICAL DATA
POWER SUPPLY - - - - - - - - - - - - - - -__________
TOTAL UNIT AMPACITY - - - - - - - - _____ AMPS
MAX. OVERCURRENT DEVICE__ FUSE __ BREAKER - - - - - - - - - _____ AMPS
TOTAL UNIT WEIGHT
INCLUDING FACTORY- INSTALLEDOPTIONS- - - - - - - - - - - - - - - - - - - - - _____ LBS
Johnson Controls Ducted Systems 1171989-YSD-F-0220
1171989-YSD-F-0220
ZQ04-06/ZX04-14/ZY04-12/ZL08-14 Unit Dimensions
ZQ04-05, ZX04-06 and ZY04
2 Johnson Controls Ducted Systems
1171989-YSD-F-0220
ZQ 06, ZXA7, ZX07 and ZY05-06
Johnson Controls Ducted Systems 3
1171989-YSD-F-0220
ZX08, ZYA7, and ZY07
4 Johnson Controls Ducted Systems
1171989-YSD-F-0220
ZX09/12, ZY08/09 and ZL08/09
Johnson Controls Ducted Systems 5
1171989-YSD-F-0220
ZX14, ZY12 and ZL12/14
6 Johnson Controls Ducted Systems
1171989-YSD-F-0220
ZQ04-06, ZX04-14/ZY04-12, ZL08-14 Unit Roof Curb Dimensions
1RC0456, 1RC0458 Roof Curb Dimensions
NOTE: If utilities are required thru the base of the unit or thruthe roof curb the following field installed accessoriescan be purchased thru your dealer or contractor:
1TB0401 - Thru the base electrical and thru the curbgas
1TB0403 - Thru the base electrical and gas
ZQ04-06, ZXA7, and ZY04-06 Unit Clearances
Direction Distance (in.) Direction Distance (in.)
Top1
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
72 Right 18
Front 36 Left 12
Rear 182/363
2. Units without economizer or power exhaust.3. Units equipped with an Economizer or Power Exhaust. Flue
products must not be discharged within 10 Feet of the rear of the unit.
Bottom4
4. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.
1
ZX08-14, ZY07-12, ZL08-14 Unit Clearances
Direction Distance (in.) Direction Distance (in.)
Top1
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
72 Right 18
Front 48 Left 12
Rear 182/363
2. Units without economizer or power exhaust.3. Units equipped with an Economizer or Power Exhaust. Flue
products must not be discharged within 10 Feet of the rear of the unit.
Bottom4
4. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.
1
O.D.40.688
40.684
X
70.871
4.961
I.D.
37.188
5.422
67.375
I.D.
32.188
13.781
3.000
20.406
17.781
14.000
23.591 11.961
70.875 O.D.
RET
UR
N
SUPP
LY
RETU
RNSU
PPLY
1RC0456 X= 14" Height1RC0458 X= 24" Height
Notes:1. Sides, ends and cross support are 18-G90. Deck pans, R/A & S/A supports are 20-G90.2. Full perimeter wood nailer.3. Insulated deck pans.
FRONT
FRONT
RIGHT
RIGHT
Unit Models used with 1RC0456, 1RC0458 Roof Curb
ZQ04 ZX04 ZY04
ZQ05 ZX05 ZY05
ZQ06 ZX06 ZY06
ZX07
ZXA7
Johnson Controls Ducted Systems 7
1171989-YSD-F-0220
1RC0457, 1RC0459 Roof Curb Dimensions
NOTE: If utilities are required thru the base of the unit or thruthe roof curb the following field installed accessoriescan be purchased thru your dealer or contractor:
1TB0402 - Thru the base electrical and thru the curbgas
1TB0404 - Thru the base electrical and gas
26.000
X
81.746
84.000 O.D. O.D.53.500
53.496
11.417
6.043
24.8134.173
34.313
I.D.
50.000
78.250
I.D.
40.188
15.469
3.000
15.813
31.531
81.750 O.D.
RET
UR
N
SUPP
LY
RETU
RNSU
PPLY
FRONT
RIGHT
FRONTRIGHT
1RC0457 X= 14" Height1RC0459 X= 24" Height
Notes:1. Sides, ends, unit locator and cross support are 18-G90. Deck pans, R/A & S/A supports are 20-G90.2. Full perimeter wood nailer.3. Insulated deck pans.
Unit Models used with 1RC0457, 1RC0459 Roof Curb
ZYA7
ZX08 ZY07 ZL08
ZX09 ZY08 ZL09
ZX12 ZY09 ZL12
ZX14 ZY12 ZL14
8 Johnson Controls Ducted Systems
1171989-YSD-F-0220
Roof Curb Cutaway
3/4” X 1-1/4” WIDE GASKETING FOR CURBFRAME AND ALL DUCT SUPPORT SURFACES
2“
UNIT BASE
WOOD NAILER
8“ MIN. ABOVE FINISHED ROOF
CURB FRAME
INSULATION
UNIT BASE RAILS
COUNTERFLASHING
CAN’T STRIP
INSULATION AND ROOFING MATERIAL
ROOF DECK AND SUPPORT STRUCTURE
14”
3.56”
3.75”
Johnson Controls Ducted Systems 9
1171989-YSD-F-0220
Economizer Options
Field Installed Vertical Flow Economizer
Economizer UsageApplication Description Accessory Kit Number
Economizer Vertical Flow Econ, DB, Vertical Flow, Small Footprint 2EE04706724Econ, DB, Vertical Flow, Large Footprint 2EE04706824
Economizer Horizontal Flow
Econ, DB, Horizontal Flow, Small Footprint, Short Cabinet 2EE04707024Econ, DB, Horizontal Flow, Small Footprint, Tall Cabinet 2EE04707124Econ, DB, Horizontal Flow, Large Footprint, Short Cabinet 2EE04707224Econ, DB, Horizontal Flow, Large Footprint, Tall Cabinet 2EE04707324
Power Exhaust Vertical Flow
Power Exhaust Vert Flow Small Footprint 208V-230V 1-ph 2PE04704206Power Exhaust Vert Flow Small Footprint 208V-230V 3-ph 2PE04704225Power Exhaust Vert Flow Small Footprint 460V 3-ph 2PE04704246Power Exhaust Vert Flow Small Footprint 575V 3-ph 2PE04704258Power Exhaust Vert Flow Large Footprint 208V-230V 1-ph 2PE04704306Power Exhaust Vert Flow Large Footprint 208V-230V 3-ph 2PE04704325Power Exhaust Vert Flow Large Footprint 460V 3-ph 2PE04704346Power Exhaust Vert Flow Large Footprint 575V 3-ph 2PE04704358
Power Exhaust Horizontal Flow
Power Exhaust Horiz Flow Small Footprint 208V-230V 1-ph 2PE04704406Power Exhaust Horiz Flow Small Footprint 208V-230V 3-ph 2PE04704425Power Exhaust Horiz Flow Small Footprint 460V 3-ph 2PE04704446Power Exhaust Horiz Flow Small Footprint 575V 3-ph 2PE04704458Power Exhaust Horiz Flow Large Footprint 208V-230V 1-ph 2PE04704506Power Exhaust Horiz Flow Large Footprint 208V-230V 3-ph 2PE04704525Power Exhaust Horiz Flow Large Footprint 460V 3-ph 2PE04704546Power Exhaust Horiz Flow Large Footprint 575V 3-ph 2PE04704558
10 Johnson Controls Ducted Systems
1171989-YSD-F-0220
Field Installed Vertical Flow Economizer W/Power Exhaust
Field Installed Horizontal Flow Economizer
Johnson Controls Ducted Systems 11
1171989-YSD-F-0220
Field Installed Horizontal Flow Economizer W/Power Exhaust
12 Johnson Controls Ducted Systems
FACTORY INSTALLED OPTIONS
ELECTRIC HEATER MODEL - KW_____VOLTS_____STAINLESS STEEL HEAT EXCHANGER - - - - - - - - - - ALUMINIZED STEEL HEAT EXCHANGER - - - - - - - - - STAINLESS STEEL DRAIN PAN- - - - - - - - - - - - - - - - - ECONOMIZER, DOWNFLOW, END RETURN HORIZON-TAL- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - POWER EXHAUST - - - - - - - - - - - - - - - - - - - - - - - - - - MOTORIZED AIR DAMPER - - - - - - - - - - - - - - - - - - - - HIGH STATIC INDOOR BLOWER MOTOR - - - - - - - - - DISCONNECT SWITCH - - - - - - - - - - - - - - - - - - - - - - - CONVENIENCE OUTLET, POWERED - - - - - - - - - - - - CONVENIENCE OUTLET, NON-POWERED - - - - - - - - SMOKE DETECTOR (RETURN) - - - - - - - - - - - - - - - - - SMOKE DETECTOR (SUPPLY) - - - - - - - - - - - - - - - - - PHASE MONITOR1 - - - - - - - - - - - - - - - - - - - - - - - - - - COIL GUARD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - DIRTY FILTER SWITCH- - - - - - - - - - - - - - - - - - - - - - - FILTERS, 2" PLEATED, MERV 7 - - - - - - - - - - - - - - - - FILTERS, 4" PLEATED, MERV 13 - - - - - - - - - - - - - - - PHENOLIC COATED EVAPORATOR COILS - - - - - - - - PHENOLIC COATED CONDENSER COILS- - - - - - - - - E-COAT EVAPORATOR COILS - - - - - - - - - - - - - - - - - E-COAT CONDENSER COILS - - - - - - - - - - - - - - - - - - INTELLISPEED WITH VFD - - - - - - - - - - - - - - - - - - - - INTELLISPEED, VFD AND MANUAL BYPASS - - - - - - INTELLISPEED, VFD READY (FOR CUSTOMER-PRO-VIDED, FIELD-INSTALLED DRIVE) - - - - - - - - - - - - - - VAV W/VFD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - VAV W/VFD AND MANUAL BYPASS - - - - - - - - - - - - - VAV, VFD READY (FOR CUSTOMER-PROVIDED, FIELD-INSTALLED DRIVE) - - - - - - - - - - - - - - - - - - - - - - - - - - BAS OPTION
Smart Equipment™ w/Communication - - - - - - - - - - - BACnet MS/TP (programmable to Modbus or N2 proto-cols) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Verasys - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
FIELD INSTALLED ACCESSORIES
ROOF CURB, 8" - - - - - - - - - - - - - - - - - - - - - - - - - - - - ROOF CURB, 14"- - - - - - - - - - - - - - - - - - - - - - - - - - - - TRANSITION ROOF CURB - - - - - - - - - - - - - - - - - - - - COIL GUARD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - HAIL GUARD- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - PERMANENT FILTERS - - - - - - - - - - - - - - - - - - - - - - - METAL FILTER FRAME KIT - - - - - - - - - - - - - - - - - - - - DIRTY FILTER SWITCH - - - - - - - - - - - - - - - - - - - - - - - AIR PROVING SWITCH - - - - - - - - - - - - - - - - - - - - - - - BURGLAR BARS (DOWNFLOW ONLY) - - - - - - - - - - - LOW AMBIENT KIT - - - - - - - - - - - - - - - - - - - - - - - - - - SMOKE DETECTOR (RETURN) - - - - - - - - - - - - - - - - - SMOKE DETECTOR (SUPPLY) - - - - - - - - - - - - - - - - - CO2 SENSOR - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - PHASE MONITOR1 - - - - - - - - - - - - - - - - - - - - - - - - - - ECONOMIZER, DOWNFLOW, END RETURN HORIZON-TAL- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ECONOMIZER, HORIZONTAL - - - - - - - - - - - - - - - - - - SINGLE ENTHALPY- - - - - - - - - - - - - - - - - - - - - - - - - - DUAL ENTHALPY - - - - - - - - - - - - - - - - - - - - - - - - - - - POWER EXHAUST - - - - - - - - - - - - - - - - - - - - - - - - - - MOTORIZED OUTDOOR AIR DAMPER - - - - - - - - - - - MANUAL OUTDOOR AIR DAMPER - - - - - - - - - - - - - - ELECTRIC HEATER MODEL - KW_____VOLTS_____FLUE EXTENSION KIT- - - - - - - - - - - - - - - - - - - - - - - - GAS PIPING KIT - - - - - - - - - - - - - - - - - - - - - - - - - - - - GAS HEAT PROPANE ADAPTER KIT - - - - - - - - - - - - - GAS HEAT HIGH ALTITUDE KIT, NATURAL GAS - - - - GAS HEAT HIGH ALTITUDE KIT, PROPANE- - - - - - - - -60°F GAS HEAT KIT - - - - - - - - - - - - - - - - - - - - - - - - - WALL MOUNT TEMPERATURE SENSOR- - - - - - - - - - WALL MOUNT TEMPERATURE SENSOR WITHOVERRIDE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - WALL MOUNT TEMPERATURE SENSOR WITHOVERRIDE & SET POINT ADJ. - - - - - - - - - - - - - - - - - - HUMIDITY SENSOR - - - - - - - - - - - - - - - - - - - - - - - - -
1. Phase monitor standard on units with scroll compressors.
Subject to change without notice. Printed in U.S.A. 1171989-YSD-F-0220Copyright © 2019 by Johnson Controls, Inc. All rights reserved. Supersedes: 1171989-YSD-E-0918