Submittal Data Sheet
Luna MSC-30HRDN1-MP0W / MOG-30HDN1-MPOW 30,000 Btu High Wall Mounted Heat Pump System
Project Name Location Date
Location Approval Date
Engineer Unit Designation
Submitted To Drawing Number
Submitted By
Reference Approval Construction (Circle One)
Performance SpecificationIndoor Unit Model MSC-30HRDN1-MP0W Air Circulation (Low, Medium, High) 942/750/680
Outdoor Unit Model MOG-30HDN1-MP0WNoise Level Cooling Indoor(High) (Dba) 50
Cooling Capacity (BTUH) 30,000Noise Level Heating Indoor (High) (Dba) 50
Sensible Capacity (BTUH) 30,000Noise Level Cooling Outdoor (High) (Dba) 54
SEER 16.5Noise Level Heating Outdoor (High) (Dba) 55
EER Cooling 10.0 Connection (Tubing) Flare
EER Heating 10.0 Connection Pipe size Supply/Return 5/8”/3/8”
HSPF (BTUH/H/W) 10.0 Maximum Tube Length (Feet) 82.02
Moisture Removal (Pints) 6.3 Maximum Height Difference (Feet) 32.80
Energy Star No
Operating Range Cooling 5F to 122F PhysicalOperating Range Heating 5F to 86F Net Weight (Indoor/Outdoor) (LBS) 53/157
Height Condensing Unit (Inches) 33.78
Electrical Depth Condensing Unit (Inches) 13.0
Voltage/Phase/Cycle 230/1/60 Length Condensing Unit (Inches) 35.25
Cable Indoor to outdoor14AWG/4 conductor
Shielded Height Indoor Unit (Inches) 13.38
Minimum Circuit Ampacity 16.0 Depth Indoor Unit (Inches) 10.88
Recommended Fuse Size 25.0 Length Indoor Unit (Inches) 56.88
Current Rating Cooling 13.0 Refrigerant R-410a
Current Rating Heating 13.0
W
Model W D HMSV1-24HRDN1-
MQ0W56.8
810.8
813.3
8
Model W D H W1 A B
MOG-24HDN1-MQ0W35.2
5 13.033.7
8
NOTE: Test conditions based on ARI 210/240.Rating conditions: Indoor: 80º db / 67º wb; Outdoor 95º db / 75º wb
H