Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 2
Contents Purpose Statement/Summary of goals ......................................................................................................... 4
Design Loads ................................................................................................................................................. 4
Dead Loads ................................................................................................................................................ 4
Live Loads .................................................................................................................................................. 4
Wind Loads ................................................................................................................................................ 4
Snow Loads ............................................................................................................................................... 4
Seismic Loads ............................................................................................................................................ 5
Structural System Description ...................................................................................................................... 5
Gravity System .............................................................................................................................................. 6
Slab Design ................................................................................................................................................ 6
Pre-Cast Beams and Columns ................................................................................................................... 6
Tilt-Wall Design ......................................................................................................................................... 7
Foundation Design .................................................................................................................................... 8
Geotechnical Analysis ........................................................................................................................... 8
Basement Wall ...................................................................................................................................... 9
Isolated Footing Design ......................................................................................................................... 9
Strip Footing ........................................................................................................................................ 10
Lateral System ............................................................................................................................................. 10
Shear Walls ............................................................................................................................................. 10
Connections ................................................................................................................................................ 11
Appendix A – Resources .............................................................................................................................. 13
Section 1. Precast Beams and Columns .................................................................................................. 13
Section 2. Foundation ............................................................................................................................. 15
Section 3. Written Resources .................................................................................................................. 15
Appendix B – Example Calculations ............................................................................................................ 16
Section 1. Dead Loads ............................................................................................................................. 16
Section 2. Live Loads ............................................................................................................................... 17
Section 3. Wind Loads ............................................................................................................................. 18
Sections 4. Snow Loads ........................................................................................................................... 19
Section 5. Seismic Loads ......................................................................................................................... 20
Section 6. Slab Design ............................................................................................................................. 21
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 3
Section 7. Precast Beams and Columns .................................................................................................. 22
Section 8. Tilt Wall Design ....................................................................................................................... 25
Section 9. Foundation Design ................................................................................................................. 27
Section 10. Shear Wall Design ................................................................................................................ 29
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 4
Purpose Statement/Summary of goals The structural design of Growing Power’s vertical farm was done such that an efficient design would be
informed by the architectural expression prescribed by the architect and also support the functional
building’s needs. The goals of structural design included developing a structural design that would allow
the building to safely perform under normal and extreme loading conditions. Within the design,
different building systems and options were investigated, the decisions for which are described
hereafter in this narrative.
Design Loads
Dead Loads Per the IBC 2009, the dead loads considered include the building elements and equipment. Much of the
dead load which drove the design was due to the self-weight of the structure. This includes the weight
of the greenhouses, the estimated weight calculations of which can be seen in Appendix B Section 1. An
additional 30psf of dead load was applied uniformly across the building slabs to account for mechanical
equipment. This decision was made before the completion of mechanical design to allow room for their
loads, and was confirmed with them afterwards to be sure their systems were within this load. See an
example table of these forces in Appendix B Section 1. Additionally, the evacuated tube solar collectors
which are to be mounted on the building’s east and west exterior facades were considered a dead load
in the tilt wall design.
Live Loads Following the Standards from IBC 2009 for occupancy loads, we found the live loads acting at the
different designated areas per floor. The occupancy loads used in the analysis for each floor can be
found in Appendix B Section 2. For easier constructability, we assumed an even slab over the entire
span of each floor. In order to do this, we optimized the slabs for the largest occupancy load each floor
experienced based on the provisions stated in IBC 2009. The tributary areas for the beams were then
calculated for each floor to find the effective live load force acting along the length of the beam. This
distributed load was then used as the live load force when calculating the factored load used for sizing
the structural members of the building.
Wind Loads Wind loads were calculated to the standards of ASCE 7 as called for in IBC 2009. The wind load was
calculated for a main wind-force resisting system (MWFRS) as described in ASCE 7. The windward and
leeward wind pressures were calculated for both the North-South and East-West directions. The
windward and leeward pressures of these wind directions were combined to find the total wind
pressure per floor. The tributary area of each floor was calculated to find the force acting on each floors’
diaphragm. The spreadsheet of these calculations for the North-South wind direction can be found in
Appendix B Section 3. These loads were assumed to be effectively transferred through the rigid
diaphragms to the shear walls which act as the building’s lateral system.
Snow Loads Snow loads were determined using the method detailed in ASCE 7-10. The snow load acts directly on
the roof of all greenhouses and was included in the calculation of the greenhouse load. A ground snow
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 5
load was determined for Milwaukee, Wisconsin. This value was then converted into a snow load applied
on a flat roof as shown in the calculation found in Appendix B Section 4. This value was then adjusted
for a sloped roof, and applied perpendicularly to the slope of the greenhouse roof.
Seismic Loads Seismic Loads were calculated using parameters set in ASCE 7-10. The seismic loads act against the
foundation systems of the structure, and therefore are calculated against those loads. To appropriately
account for the seismic load, we analyzed the seismic loads for the heaviest load on the interior
columns, the corner exterior columns, the heaviest load on the exterior columns, and the heaviest loads
on the strip footing. The factors were established based on the structure type, soil type, and location of
the site, Milwaukee. After analyzing the loads, they are found to be less than the wind loads, and
therefore the lateral bracing system designed for the wind load is sufficient to account for the seismic
load as well.
Structural System Description The structural system for Growing Power’s
vertical farm was greatly informed by the
architectural expression of the building.
The firmness of the building informed a
concrete construction, rather than steel or
wood. In the architectural schemes, the
architect identifies concrete construction
as well as preliminary placement of precast
concrete columns and beams. Following
this system, the building’s structure was
designed such that the cast-in-place slabs,
precast beams, and precast columns would
be the main gravity load system. The
lateral forces are carried by shear walls
surrounding a vertical core in the main
section of the building. The lateral and
gravity systems frame into the foundation
where cast-in-place concrete walls were
designed to resist soil pressures. The floor
of the basement is a slab on grade. These
rest on a strip footing around the
perimeter of the building and isolated
column footings. The greenhouses are
assumed to be designed by a separate
subcontractor per the architect’s
instructions. They are assumed to be self-
supporting against gravity and lateral
forces with their gravity loads framing into
our gravity system. Figure 1. Structural Systems
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 6
Gravity System
Slab Design The floor system for this building is designed as a one way slab spanning in the east-west direction and
continuously cast across a centerline of precast beams. The slab design for a given floor is continuous
across the entirety of that floor despite any variance in occupancy loading. The maximum occupancy
load is used as the design load for any given floor.
Floors 2, 4, and 5 have a maximum occupancy load of 100 psf. This load is supported by a 9 inch slab
continuously spanning across two 30’-2” spans. The slabs are reinforced with No. 9 bars at a spacing of
12 inches and No. 3 bars also at a spacing of 12 inches running perpendicularly to the primary
reinforcement for temperature and shrinkage reinforcement.
Floors 1 and 3 have a maximum occupancy load of 125 psf. The slab used on floors 2, 4, and 5 will
satisfy the strength requirements of floors 1 and 3; however, it fails to meet the required deflection
limits under the greater load. The increased load can be supported by either increasing the slab depth
to 10 inches, leaving the slab depth constant or by increasing the bar size to No. 10 bars and leaving the
slab depth constant. In order maintain consistency throughout the building and allow for ease of
construction the 9 inch slab with No. 10 bars and 12 inch spacing will be used.
The elevator lobby on the back side on the building has the same slab design as the rest of the floor on
which it is located, despite having a significantly shorter span. Because the area is so small it seems
impractical to design a separate slab. Using the same slab design will increase the efficiency of
construction.
The basement slab is supported directly by the soil underneath, and is cast separately from the
foundation to allow for independent movement as recommended in the geotechnical report. To allow
for proper drainage, the basement slab rests on 6 inches of clean, free draining granular fill with less
than 5% passing the #200 sieve also as prescribed in the geotechnical report. Due to continuous support
from the soil beneath, deflection was assumed not to be the controlling criterion. A 9 inch slab will be
used with No. 9 reinforcement bars at a spacing of 10 inches and No. 3 bars for temperature and
reinforcement bars running in the transverse direction.
The standard procedure outlined in ACI 318-11 was used in designing each slab. Sample design
calculations can be viewed in Appendix B Section 6.
Pre-Cast Beams and Columns The architect prescribed a precast structural framing system for this building as well as the general
layout of all columns and beams. Columns are located along the perimeter of the building as well as
down the center line. Beams span between columns in the north-south direction. Exact column and
beam locations are delineated in the construction documents. A precast structural system is ideal for
this project. Precast systems can easily span large distances and can result in a shorter construction
schedule.
The loads acting on each floor are transferred from the slab to precast concrete beams spanning a
typical distance of 30’-2”. In order to determine the force applied on each precast beam as a distributed
line load, occupancy loads acting on the slab are first multiplied by the tributary width of the
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 7
corresponding beam, where the tributary width is the distance from the midway point between one
neighboring beam to the midway point between the other. This value is then added to the weight of the
slab supported by the beam and an estimated value for the member’s self-weight, thereby yielding the
distributed load acting on the member. All precast beams were selected using the PCI Design Handbook
for precast and prestressed concrete based on the distance spanned and the calculated distributed line
load acting on the member. Specific beam sizes can be viewed in the beam schedule at the end of the
construction documents.
The loads acting on each beam are transferred to precast columns with half of the weight of each beam
and the load it supports being transfer to each supporting column. The dead load supported by each
column was determined by summing the weight of the all slabs, columns, beams, and greenhouse loads
within the column’s tributary area. The live load was determined similarly by summing all occupancy
loads multiplied by the area over which they were spread within the columns tributary area. The
greater of 2 basic load combinations (1.4D and 1.2D+1.6L) was assumed to be the maximum axial load to
be supported by the column. The moment experienced by each column was determined by dividing the
difference between the axial load of the given column and the axial load of the column directly above by
the maximum eccentricity, where the maximum eccentricity is the maximum column dimension divided
by 2. This eccentricity was used because the column uses a seat on which the precast beam sits to
transfer its axial loads into the column. The distance of this seat to the centerline of the column is the
column’s maximum dimension divided by 2. The axial load on the seat of the column is assumed to be
fully transferred into the centerline of the column before reaching the floor below. As such, the moment
experienced by a column on any given floor is assumed not to transfer to the column on the floor below.
We then selected the smallest possible column for which the combination of calculated axial load and
moment plotted within the bounds of the column interaction diagram. Specific column sizes can be
viewed in the column schedule at the end of the construction documents.
For the purposes of this project, we provide only the outer dimensions of each precast member,
allowing the casting contractor to design all necessary steel reinforcement.
Tilt-Wall Design A tilt wall system was chosen for the building’s walls to allow for ease of construction of the
architecturally expressed concrete walls. While tilt walls can carry shear load, we assumed that the
lateral forces of the system were to be resisted by the shear wall around the building’s core. As such, the
tilt walls’ job structurally is to transfer the wind pressure into the diaphragms at each floor as well as
carry the load of the evacuated solar collection system and its own weight.
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 8
To design the tilt walls, the building’s
facades were first looked at for the
necessary geometry of the walls
themselves. Panel points were then
determined in order to ensure that
joints did not interfere with window
placement and were practical for
construction purposes.
The walls’ thickness was initially sized
using the rule of thumb that an
economic tilt wall with a single mat of
reinforcing has a length to thickness
ratio of roughly 50. This yielded a 13”
thickness maximum.
The walls’ load were then calculated. As previously stated, the wall was designed to transfer the wind
loads from the walls to the floor diaphragms. Because a given wall could be either windward or leeward,
the wind load was idealized as being the windward wall at the building’s maximum wind pressure of
26.6 psf. Observing a sample 18” width of wall section, the 13” wall only required a single #3 bar at 18”
in order to resist this wind load.
The tilt walls also carry the load from the mounted evacuated tube solar collection system as well as its
own self-weight. In order to find this load, the weight of the solar panels while functioning was
determined (so as to account for the weight of the fluid the system holds). This weight was then found
as a uniform load across the face of the solar panel. Again a single width of the wall was analyzed.
Idealizing a 12” section, the walls were sized to support their own self weight as well as the moment
created by the eccentricity of the solar panels’ weight from the centerline of the wall. From SAP, an
interaction diagram was formed in order to find the capacity of the wall under combined moment and
axial load as can be seen Appendix B Section 7.
An additional load case was considered in the tilt wall design. In the construction process, the wall must
be lifted from flat on the ground to its vertical position. As such, the wall acts as a one way slab loaded
by its own self weight when being lifted.
Foundation Design
Geotechnical Analysis The soil supporting our building was analyzed to have a soil bearing capacity of 1500 psf (given in
geotechnical report from architect). Looking at the heaviest load we had coming down onto the soil, we
found that the two central columns continuing through all 5 floors of the building (C10 and C11) carried
the most load. The force coming down from these columns were acting as a point load of 1700 kips
onto a soil with a bearing capacity of 1500 psf. Since this results in a square footing with approximately
33’ sides as a necessity for the central columns, we looked into increasing the soil bearing capacity. In
order to have a reasonable size footing (within 6’ x 6’), we need the soil to be able to support a load of
Figure 2. Tilt Wall Assembly
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 9
at least 68 ksf. We designed our foundation systems assuming we could use a form of soil strengthening
to get our soil bearing capacity up to this point.
For the structural wall of the basement, we also had to calculate the total unit weight of the soil to find
the pressure acting upon the wall from the soil. Using an estimated total unit weight based on the blow
count from the Standard Penetration Test (SPT), we found the greatest total unit weight that would be
acting upon our wall. For this, we analyzed the three boring logs found closest to our site: P2, P3, and
B3. Of these, the greatest total unit weight estimated from the SPT was found to be 130 pcf.
Basement Wall The basement wall is responsible for supporting the weight of the tilt walls above it, as well as for
resisting the load created by the total unit weight of the soil acting against its exterior in combination
with the force from the water beginning from where the water table resides (5 ft from the surface).
Each basement wall was idealized as a one way horizontal slab, not accounting for the self-weight of the
wall since it will be distributed axially along the member. The wall is being analyzed as simply
supported, with a triangular distributed force acting upon the member to account for the weight of the
soil. An additional increase in the triangular distributed force beginning 5 feet from the edge will be
added to account for pressure from the water, beginning at the ground water table given in the
geotechnical report.
The basement wall was designed in accordance with ACI 318-11. For ease in constructability, the wall
was designed for worst case scenario, and made uniform throughout all exterior walls in the basement.
Additionally, we would not expect to see much variation within the design as the primary controlling
factor is the moment force caused by the load of the soil acting on the wall, which would only change
slightly as the total unit density of the soil changed around our site. We designed the slab to be acting in
tension, which meant the controlling design factor would be the moment acting upon our slab. In order
to account for this, we designed it such that the steel reinforcement would be capable of supporting the
tensile stress caused by the moment. The controlling design parameter for the slab was the thickness of
the concrete determining how much steel was required to support the moment force. This caused an
increase in our wall thickness as the moment we experienced increased with the depth of the wall,
causing a larger moment toward the base of the wall. Once we had adequate reinforcement to support
the tensile stress of the slab that also fit within the parameters of allowable are of reinforcement, we
accounted for the necessary transverse reinforcement of the slab as a function of the area of concrete
per 1’ width of the slab. An example calculation for the basement design can be found in Appendix B
Section 9.
The final basement wall design yielded 14” thick walls with No. 7 bars at 7” spacing on center, with
transverse reinforcement of No. 4 bars at 15” on center.
Isolated Footing Design The isolated footings support the columns coming down in the building and distribute the weight across
an acceptable area such that the pressure transferred from the footing to the soil is less than the soil
bearing capacity. Since the loads coming down in columns change only slightly based on orientation, we
are idealizing for the greatest loads within the central columns, and the greatest loads within the
exterior columns.
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 10
The largest controlling factor for the central isolated footing was the distribution of the load across an
area large enough such that the soil bearing capacity could support the footing. As stated in the
geotechnical section above, we are assuming we could increase the soil bearing capacity to a value of 68
ksf. By doing so, we are able to distribute the load of the central two columns (C10 and C11) over a 6’
square footing. Once the bearing capacity of the soil was adequate, the next major controlling factor of
the footing became the shear capacity of the concrete to prevent column punching from occurring.
The isolated footing is designed in accordance with ACI 318-11. To account for the large shear capacity
necessary of the concrete, we were able to increase the depth such that the concrete was taking all of
the shear capacity, and no shear reinforcement was necessary within the design. However, we are still
accounting for tensile developments along the underside of the footing, and therefore had to calculate
the necessary reinforcement within the tension region of the concrete footing to prevent failure. The
necessary area of reinforcement was calculated with respect to the depth of the concrete, the width of
the concrete, and the strength of the steel and concrete. An example calculation of this can be found in
Appendix B Section 9. The calculations for the exterior columns followed the same process as that with
the interior, but with a much lower force acting down upon the member.
The final designs we yielded for the central footings were 60” x 60” x 34” isolated footing with No. 7 bars
at a spacing of 9” on center.
The final designs we yielded for the perimeter footing were 48” x 48” x 20” isolated footing with No. 6
bars at 6” spacing on center.
Strip Footing The strip footing supports the base of the basement wall and distributes the total load coming down on
it across the soil, such that the soil bearing capacity is less than the distributed load of the strip footing.
The strip footing follows the layout of the basement wall and connects with the isolated footings around
the perimeter.
The weight of the tilt walls and the loads they support, as well as the basement wall and its self-weight,
is a fraction of the load coming down onto the isolated footings. Therefore, the requirements laid out
above for the isolated footing design can be used again for the strip footing design.
Because the strip footing’s concrete and soil pressure were adequate to resist the moment found by the
foundation and tilt walls above, the reinforcing in the strip footing was designed for ease of construction
in the monolithic pour with the column footing. It is idealized that 3 of the bars within the column
footing would be carried continuously through the strip footing on both sides of the column footing.
Because of this, the final design we yielded for the strip footing is No. 6 bars at 6” spacing through the
strip footing.
Lateral System
Shear Walls The lateral force resisting system for this building is a set of shear walls surrounding a vertical stairwell
core near the buildings system. This system was used in order to simplify the design process of the tilt
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 11
walls and save the material that would have been needed to reinforce the tilt walls to carry significant
shear loads.
In the shear loads of the building were found from the wind load calculations previously described in the
loading section. Once the shear force was found at each floor height, the moment and axial forces
carried by the shear walls were able to be calculated. Each shear wall is idealized as a deep concrete
beam which is cantilevered vertically from the ground. Thus, the moment acting on this cantilever is the
sum of the shear force from each floor diaphragm times the height at which the force is applied. The
axial force acting on the shear walls was idealized to be the walls’ self-weight as well as a portion of load
from the slab on each floor.
Once the forces on the wall were analyzed, the shear wall was designed in accordance to ACI 318-11. In
this design, the total shear capacity of a given wall is the sum of the shear capacity of the concrete and
the shear capacity of the reinforcement. Three total shear walls were designed; a single wall in the
North-South orientation, and two equally sized and loaded walls in the East-West direction. The height
of the walls themselves required relatively thick walls which provided a large portion of the shear
capacity. Once the concrete’s shear capacity was found, the amount of steel reinforcement was
determined which was dictated by minimum wall area to reinforcement area ratios per the ACI code. An
example calculation for the North-South oriented wall can be found in Appendix B Section 10.
The final wall designs yielded 8” thick walls with #6’s at 18” o.c. horizontally and vertically in both the
North-South and East-West oriented walls.
Connections Connection design of the building’s main gravity system connections was assumed to be within the
scope of the precast concrete manufacturer. The columns were designed assuming that they would
have seats which extend from their outer dimensions on which the precast beams sit. Above this, the
slab formwork would be shored and cast. It was also assumed that the connections of the floor
diaphragms to the concrete shear walls would be enough to fully transfer the building’s shear loads.
The precast columns will be bolted into the cast-in-place concrete footing using anchor bolts at all four
corners of the column. The anchor bolts are to be cast with the footing itself and then the precast
column will be placed over the bolts and secured. In order to size the anchor bolts, a proprietary
software called Profis by the company Hilti was used (see figure 3). The anchor bolts were sized for the
largest column in the building’s interior. In modelling the column base, the geometry of the largest
column was placed and analyzed under its applied loads. Under the condition of the compressive load it
carries and the moment it experiences, the compressive force is theoretically enough to counteract the
tension produced from the moment. In order to account for some tension, the compressive force was
removed and the anchor bolts were sized under purely the moment the column experiences. From this,
1-3/8” diameter hex-head anchor bolts with a 12” embedment were selected. While they barely failed
under the maximum moment, it is still safe to prescribe this because there is never a load case in which
there is absolutely no compressive load on this particular column.
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 12
It is also assumed that there are steel dowels capable of developing full load transfer in the connections
of the foundation walls into the strip footing as well as from the floor slabs into the shear walls.
Figure 3. Connection Plate Modeled in Profis
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 13
Appendix A – Resources
Section 1. Precast Beams and Columns
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 14
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 15
Section 2. Foundation
Section 3. Written Resources Bowles, Joseph E. Foundation Analysis and Design. New York: McGraw-Hill, 1996. Print.
Building Code Requirements for Structural Concrete (ACI 318-11) and Commentary. Farmington Hills, MI:
American Concrete Institute, 2011. Print.
Hilti. Hilti's Profis. Computer software. N.p., 2014. Web.
IBC ; International Building Code 2009. Country Club Hills: International Code Council, 2009. Print.
Minimum Design Loads for Buildings and Other Structures. Reston, VA: American Society of Civil
Engineers, 2010. Print.
PCI Design Handbook: Precast and Prestressed Concrete. Chicago: Precast/Prestressed Concrete
Institute, 2014. Print.
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 16
Appendix B – Example Calculations
Section 1. Dead Loads
Cro
ss-
Sect
ion
al
Are
a
(in
^2)
Tota
l
Len
gth
of
Mu
llio
ns
(ft)
Vo
lum
e
(ft^
3)
We
igh
t
(lb
s)
Len
gth
(ft)
Lin
ear
We
igh
t
(lb
/ft)
Are
a
(ft^
2)
We
igh
t
(lb
)
Lin
ear
We
igh
t
(lb
/ft)
Sno
w
Load
(lb
/ft^
2)
Sno
w
Load
(lb
/ft)
Tota
l
Lin
e L
oad
(lb
/ft)
Tota
l
Lin
e L
oad
(k/f
t)
East
12.5
100
8.68
0556
1484
.375
16.6
789
.044
6934
6.5
570.
2813
34.2
1003
13.2
322
0.54
4112
3.25
470.
1232
55
We
st12
.510
08.
6805
5614
84.3
7516
.67
89.0
4469
346.
557
0.28
1334
.210
0313
.23
220.
5441
123.
2547
0.12
3255
No
rth
12.5
198.
2517
.209
229
42.7
7365
45.2
7344
991.
2516
31.4
3225
.098
9613
.23
859.
9570
.372
40.
0703
72
Sou
th12
.538
0.25
33.0
0781
5644
.336
6586
.835
9419
01.2
531
29.1
4148
.140
6313
.23
859.
9513
4.97
660.
1349
77
East
12.5
453.
9062
566
7.96
8814
.83
45.0
4172
203
420.
9199
28.3
8373
.424
730.
0734
25
We
st12
.545
3.90
625
667.
9688
14.8
345
.041
7220
342
0.91
9928
.383
73.4
2473
0.07
3425
0
Sno
w L
oad
at
revi
ne
18.9
0
(Tre
at a
s co
nce
ntr
ate
d lo
ad)
0 0
5th
Flo
or
Cal
ucl
uat
ion
s
East
12
.534
029
.513
8950
46.8
7580
63.0
8594
346.
557
0.28
137.
1285
1613
.23
1.05
8470
.214
450.
0702
14
We
st12
.534
029
.513
8950
46.8
7580
63.0
8594
346.
557
0.28
137.
1285
1613
.23
1.05
8470
.214
450.
0702
14
No
rth
12.5
198.
2517
.209
229
42.7
7365
45.2
7344
991.
2516
31.4
3225
.098
9613
.23
0.85
995
70.3
724
0.07
0372
Sou
th12
.538
0.25
33.0
0781
5644
.336
6586
.835
9419
01.2
531
29.1
4148
.140
6313
.23
0.85
995
134.
9766
0.13
4977
2 1/
2" x
5"
Un
it W
eig
ht
Alu
min
um
(lb
/ft^
3):
171
Un
it W
eig
ht
Gla
ss (
lb/f
t^3)
:15
8
Mu
llio
ns
Gla
ss (
t=1/
8" t
hic
k)Sn
ow
Lo
adTo
tal
Gre
en
ho
use
Lo
ad C
alcu
lati
on
s
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 17
Dead Load Examples
Element Weight Unit
Concrete
General 145 pcf
24x24 column 580 plf
18x18 column 326.25 plf
16x16 column 257.7778 plf
32x24 beam 773.3333 plf
9in slab 108.75 psf
Other
Solar Panel 256 lb ea.
Misc. Mechanical
30 psf
Section 2. Live Loads
Occupancy Loads (psf) Floor 1 Floor 2 Floor 3
Lobby 100 Lobby 100 Lobby 100
Staircase 100 Staircase 100 Staircase 100
Office 50 Garden Area 100 Garden Area 100
Market 100 Office 50 Office 50
Loading 125 Bathroom 50 Bathroom 50
Processing 125 Gathering 100 Corridor 100
Wood Shop 100 Break-out 100 Storage 125
Classrooms 40
Kitchen 100
Floor 4 Floor 5
Lobby 100 Lobby 100 These occupancy
Staircase 100 Staircase 100 loads were selected
Garden Area 100 Garden Area 100 using IBC-2009.
Office 50
Bathroom 50
Meeting Rm 100
Copy Area 100
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 18
Section 3. Wind Loads
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 19
Sections 4. Snow Loads
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 20
Section 5. Seismic Loads
Factors/Constants
Site Class C
Ss 0.1
Fa 1.2
Sds 0.08
ρ 1
ap 1
Rp 1.5
Wp 9
Ip 1.5
z/h 1
Seismic Loads D Qe =Fp Earthquake Load (kips)
Heaviest Interior Column 47.2 0.864 1.620
North Corner Columns 31.6 0.864 1.369
South Corner Columns 6.6 0.864 0.970
Heaviest Exterior Columns 33.0 0.864 1.392
Strip Footing 16.0 0.864 1.120
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 21
Section 6. Slab Design
Sample Slab Design Concrete Properties Steel Properties Loads
f'c (ksi) 4 fy (ksi) 60 wL (psf) 100
E (ksi) 3605.00 E (ksi) 29000 wD (psf) 30
density (psf) 145 wo/w (psf) 108.75
Slab Dimensions Strength Capacity wf (psf) 326.5
Slab Depth (in) 9 Mf (k-ft) 33.014 w service (psf) 238.75
Span Length (ft) 30.17 a 1.471 Deflections
Clear Cover (in) 0.75 φMr (k-ft) 37.191 Limit 1.01
φMr>Mf Good Ig (in^4) 729.00
Reinforcement Spacing Requirments Fr (ksi) 0.47
Depth (in) 7.686 S (in) 11.294 Mcr (k-ft) 6.40
Bar Number 9 Sf (in) 13.125 Ma (k-ft) 24.14
Number of Bars 1 Sf (in) 12 rho 0.01
Bar Diameter (in) 1.128 Smax (in) 12 n 8.04
Bar Area (in^2) 1 S Final (in) 11.294 k 0.32
As Required (in^2) 1.063 Temperature Reinforcement x 2.45
As Min (in^2) 0.194 As Required (in^2) 0.0972 Icr 279.38
As Max (in^2) 1.705 Bar Number 3 Immediate Deflection
7/8 As Max (in^2) 1.492 Bar Diameter 0.375 Ma (k-ft) 14.03
Asmin<Asrqd<Asmax Good Bar Area 0.11 Ie (in^4) 322.14
Delta DL (in) 0.28
Longterm Deflection Ma (k-ft) 24.14
Ie 287.77 Delta TL 0.54 Sustained LL Deflection
Ma (k-ft) 16.05
Ie 307.93 Delta SLL 0.33 Deflection 0.93
Deflection<Limit Good
This excel spread sheet was used to design the slab for floors 2, 4,
and 5 using the process outlined in ACI 318-11. The design for all
other slabs was done using the same process.
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 22
Section 7. Precast Beams and Columns
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 23
Occ
up
ancy
Cat
ego
ryM
agn
itu
deU
nit
Gro
win
g A
rea
100
psf
Occ
up
ancy
LL'
sva
rie
s
Slab
Se
lf W
eig
ht
108.
75p
sf
Max
Co
lum
n d
im.
24in
Max
Co
lum
n D
im.
24in
580
plf
be
am d
ep
th32
in
be
am w
idth
16in
515.
5556
plf
Ge
ne
ric
De
ad30
psf
Gre
en
ho
use
Lo
ad99
0p
lf
25ft
Co
lum
n L
oad
s
He
igh
t ab
ove
56ft
He
igh
t ab
ove
56ft
Axi
al A
bo
ve40
6.48
68ft
Axi
al A
bo
ve46
9.36
41ft
Trib
Are
a19
1.31
7sf
Trib
Are
a38
2.48
3sf
LL23
.914
63k
LL47
.810
38k
DL
49.5
6221
kD
L74
.828
54k
Fact
ore
d L
oad
169
.387
1k
1.4
DFa
cto
red
Lo
ad 1
104.
76k
1.4
D
Fact
ore
d L
oad
297
.738
05k
1.2
D +
1.6
LFa
cto
red
Lo
ad 2
166.
2908
k1.
2 D
+ 1
.6 L
Max
Axi
al L
oad
504.
2248
kM
ax A
xial
Lo
ad63
5.65
5k
Max
Ecc
en
tric
ity
12in
Max
Ecc
en
tric
ity
12in
Min
Mo
me
nt
97.7
3805
k-ft
Min
Mo
me
nt
166.
2908
Size
All
ow
able
16x1
6Si
ze A
llo
wab
le18
x18
1st
Flo
or
Pre
cast
Co
lum
n S
izin
g
Live
Lo
ads
De
ad L
oad
s
colu
mn
se
lf w
eig
ht
be
am s
elf
we
igh
t
Gre
en
ho
use
lin
e lo
ad o
n s
lab
Gre
en
Ho
use
Lo
ad L
en
gth
C1/
16C
2/17
/18
slab
+co
l+b
eam
s+G
H
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 24
He
igh
t ab
ove
56ft
He
igh
t ab
ove
56ft
He
igh
t ab
ove
56ft
He
igh
t ab
ove
42ft
Axi
al A
bo
ve52
1.91
63ft
Axi
al A
bo
ve13
92.4
86ft
Axi
al A
bo
ve91
4.73
78ft
Axi
al A
bo
ve57
6.86
55ft
Trib
Are
a34
2.31
7sf
Trib
Are
a76
4.12
25sf
Trib
Are
a68
3.88
59sf
Trib
Are
a60
3.34
sf
LL34
.231
7k
LL95
.515
31k
LL85
.485
74k
LL60
.334
k
DL
67.8
8413
kD
L12
7.78
1k
DL
115.
2768
kD
L10
2.72
45k
Fact
ore
d L
oad
195
.037
78k
1.4
DFa
cto
red
Lo
ad 1
178.
8934
k1.
4 D
Fact
ore
d L
oad
116
1.38
75k
1.4
DFa
cto
red
Lo
ad 1
143.
8144
k1.
4 D
Fact
ore
d L
oad
213
6.23
17k
1.2
D +
1.6
LFa
cto
red
Lo
ad 2
306.
1617
k1.
2 D
+ 1
.6 L
Fact
ore
d L
oad
227
5.10
94k
1.2
D +
1.6
LFa
cto
red
Lo
ad 2
219.
8038
k1.
2 D
+ 1
.6 L
Max
Axi
al L
oad
658.
1479
kM
ax A
xial
Lo
ad16
98.6
48k
Max
Axi
al L
oad
1189
.847
kM
ax A
xial
Lo
ad79
6.66
93k
Max
Ecc
en
tric
ity
12in
Max
Ecc
en
tric
ity
12in
Max
Ecc
en
tric
ity
12in
Max
Ecc
en
tric
ity
12in
Min
Mo
me
nt
136.
2317
k-ft
Min
Mo
me
nt
306.
1617
k-ft
Min
Mo
me
nt
275.
1094
k-ft
Min
Mo
me
nt
219.
8038
k-ft
Size
All
ow
able
18x1
8Si
ze A
llo
wab
le24
x24
(12)
#11
Size
All
ow
able
24x2
4Si
ze A
llo
wab
le20
x20
He
igh
t ab
ove
42ft
He
igh
t ab
ove
56ft
He
igh
t ab
ove
56ft
He
igh
t ab
ove
56ft
Axi
al A
bo
ve39
8.59
39ft
Axi
al A
bo
ve41
1.20
58ft
Axi
al A
bo
ve48
4.66
34ft
Axi
al A
bo
ve43
0.33
96ft
Trib
Are
a30
3.34
sfTr
ib A
rea
151
sfTr
ib A
rea
382.
483
sfTr
ib A
rea
342.
317
sf
LL30
.334
kLL
18.8
75k
LL38
.248
3k
LL42
.789
63k
DL
80.8
9954
kD
L36
.183
34k
DL
74.8
2854
kD
L67
.884
13k
Fact
ore
d L
oad
111
3.25
94k
1.4
DFa
cto
red
Lo
ad 1
50.6
5667
k1.
4 D
Fact
ore
d L
oad
110
4.76
k1.
4 D
Fact
ore
d L
oad
195
.037
78k
1.4
D
Fact
ore
d L
oad
214
5.61
38k
1.2
D +
1.6
LFa
cto
red
Lo
ad 2
73.6
2001
k1.
2 D
+ 1
.6 L
Fact
ore
d L
oad
215
0.99
15k
1.2
D +
1.6
LFa
cto
red
Lo
ad 2
149.
9244
k1.
2 D
+ 1
.6 L
Max
Axi
al L
oad
544.
2078
kM
ax A
xial
Lo
ad48
4.82
59k
Max
Axi
al L
oad
635.
655
kM
ax A
xial
Lo
ad58
0.26
39k
Max
Ecc
en
tric
ity
12in
Max
Ecc
en
tric
ity
12in
Max
Ecc
en
tric
ity
12in
Max
Ecc
en
tric
ity
12in
Min
Mo
me
nt
145.
6138
k-ft
Min
Mo
me
nt
73.6
2001
k-ft
Min
Mo
me
nt
150.
9915
k-ft
Min
Mo
me
nt
149.
9244
k-ft
Size
All
ow
able
16x1
6Si
ze A
llo
wab
le16
x16
Size
All
ow
able
18x1
8Si
ze A
llo
wab
le18
x18
He
igh
t ab
ove
28ft
He
igh
t ab
ove
28ft
He
igh
t ab
ove
14ft
He
igh
t ab
ove
14ft
Axi
al A
bo
ve24
1.90
75ft
Axi
al A
bo
ve28
1.31
91ft
Axi
al A
bo
ve0
ftA
xial
Ab
ove
0ft
Trib
Are
a30
3.34
sfTr
ib A
rea
606.
68sf
Trib
Are
a15
1sf
Trib
Are
a30
1.67
sf
LL30
.334
kLL
60.6
68k
LL15
.1k
LL30
.167
k
DL
80.8
9954
kD
L55
.943
98k
DL
67.5
4157
kD
L85
.577
6k
Fact
ore
d L
oad
111
3.25
94k
1.4
DFa
cto
red
Lo
ad 1
78.3
2157
k1.
4 D
Fact
ore
d L
oad
194
.558
19k
1.4
DFa
cto
red
Lo
ad 1
119.
8086
k1.
4 D
Fact
ore
d L
oad
214
5.61
38k
1.2
D +
1.6
LFa
cto
red
Lo
ad 2
164.
2016
k1.
2 D
+ 1
.6 L
Fact
ore
d L
oad
210
5.20
99k
1.2
D +
1.6
LFa
cto
red
Lo
ad 2
150.
9603
k1.
2 D
+ 1
.6 L
Max
Axi
al L
oad
387.
5213
kM
ax A
xial
Lo
ad44
5.52
07k
Max
Axi
al L
oad
105.
2099
kM
ax A
xial
Lo
ad15
0.96
03k
Max
Ecc
en
tric
ity
12in
Max
Ecc
en
tric
ity
12in
Max
Ecc
en
tric
ity
12in
Max
Ecc
en
tric
ity
12in
Min
Mo
me
nt
145.
6138
k-ft
Min
Mo
me
nt
164.
2016
k-ft
Min
Mo
me
nt
105.
2099
k-ft
Min
Mo
me
nt
150.
9603
k-ft
Size
All
ow
able
16x1
6Si
ze A
llo
wab
le16
x16
Size
All
ow
able
16x1
6Si
ze A
llo
wab
le16
x16
C12
C13
C4
C10
/11
slab
+co
l+b
eam
s+G
Hsl
ab+c
ol+
be
ams+
GH
+
C5/
20C
8
slab
+co
l+b
eam
s+G
Hsl
ab+c
ol+
be
ams+
GH
+
slab
+co
l+b
eam
s+G
Hsl
ab+c
ol+
be
ams+
GH
C3
C19
slab
+co
l+b
eam
s+G
Hsl
ab+c
ol+
be
ams+
GH
slab
+co
l+b
eam
s+G
Hsl
ab+c
ol+
be
ams+
GH
C6/
21C
14
slab
+co
l+b
eam
s+G
Hsl
ab+c
ol+
be
ams+
GH
+
C7/
22C
15
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 25
Section 8. Tilt Wall Design
wall thickness 13.5 in Ø 0.9
wall width 38 ft 456 in
wall height 56 ft 672 in
f'c 4000 psi 4 ksi
fy 60000 psi 60 ksi
26.63 psf d (depth) 6.75 in
b (effective base) 18 in
^ factored (*1.0) 26.63 psf 978.6525 lb-ft
14 ft 11743.83 lb-in
168 in 11.74383 k-in
0.978653 k-ft
As req'd 0.032295 in^2
As provided 0.11 in^2
Entire wall red'd 0.032295
9.135 k self weight/12" width
0.15213 k solar collector weight/12" width
9.28713 k Total axial/12" width of wall
Interaction Diagram Check from SAP2000
Axial Force
471.6 lb-in/ftMoment acting on
Wall
worst case wind
pressure
unbraced length
Mr (Worst
moment caused
by wind)
Design for Wind Resistance
TILT WALL DESIGN
Check to account for solar panel moment and axial load
(Bars provided vertically per 18")
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 26
Thickness 12 in Bar area 0.66 in^2 Thickness 12 in Bar area 1.502 in^2
Height 42 ft Spacing 8 in Height 56 ft Spacing 8 in
Width 38 ft Depth 9 in Width 38 ft Depth 9 in
fy 60 ksi 145 pcf fy 60 ksi 145 pcf
f'c 4 ksi f'c 4 ksi
Self weight 145 psf 0.99 Self weight 145 psf 2.253
31972.5 lb-ft 56840 lb-ft
31.9725 k-ft a 1.4559 56.84 k-ft a 3.3132
383.67 k-in PhiMr 442.22 k-in 682.08 k-in PhiMr 893.41 k-in
PhiMr>Mf? Yes PhiMr>Mf? Yes
Final Design 2 mats of #4 at 8" vertical, 2 mats of #3 at 18" horizontalFinal 2 mats of #6 at 8" vertical, 2 mats of #3 at 18" horizontal
Thickness 12 in Bar area 2.044 in^2
Height 70 ft Spacing 8 in
Width 38 ft Depth 9 in
fy 60 ksi 145 pcf
f'c 4 ksi
Self weight 145 psf 3.066
88812.5 lb-ft
88.8125 k-ft a 4.5088
1065.75 k-in PhiMr 1116.8 k-in
PhiMr>Mf? Yes
Final Design 2 mats of #7 at 8" vertical, 2 mats of #3 at 18" horizontal
Controlling Tilt Wall Design Condition
Check againstself-weight while being lifted (4 stories high)Check againstself-weight while being lifted (3 stories high)
Conc
Weight
Moment
(12"
section)
As prov/12"
width
Check againstself-weight while being lifted (5 stories high)
Conc
Weight
As
prov/12"
Moment
(12" section)
Conc
Weight
As
prov/12"
Moment
(12" section)
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 27
Section 9. Foundation Design
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 28
STRUCTURAL DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 29
Section 10. Shear Wall Design
1
5
3
2
4
2' -
4"
30' -
2"
30' -
2"
2' -
4"
A
IB
HC D E F G
2' - 0"
25' - 4" 25' - 4" 25' - 4" 20' - 0" 20' - 0" 20' - 0"
2' - 0"
60" x 60" X 34" FOOTING - #7 @ 9" O.C. BOTH WAYSTYP. AT ISOLAED FOOTING ALONG GRID 3
9" THICK ONE WAY CONCRETE SLAB#9 @ 10" O.C., #3 @ 12" O.C. TRANSVERSE REINF.
CONT. 24" x 24" STRIP FOOTING BELOW FOUNDATION WALLWITH (3) #6's @ 6" O.C. CONT.
14” THICK CONC. WALLS - TYP. @ BASEMENT#7 @ 7” O.C. VERT. & #4 @ 15” O.C. HORIZ.
Scale
Project numberDateDrawn byChecked by As indicated
S001FOUNDATION/BASEMENT PLAN
11-2015GROWING POWER
VERTICAL FARM2/11/15AuthorChecker
No. Description Date
1" = 20'-0"1 Basement
1
5
3
2
4
A
IB
HC D E F G
9" THICK ONE WAY CONCRETE SLAB#10 @ 12" O.C., #3 @ 12" O.C. TRANSVERSE REINF.
B2 B2 B1 B1 B1
B3 B3 B4 B2 B2 B2
B2 B2 B3 B1 B1 B1
C4 C3 C3 C4 C4 C4
C4 C1 C2 C4 C4
C4 C3 C4 C4 C4
C1 C1
(3) SHEAR WALLS, 8" THICK,#6's @ 18" O.C. VERT. AND HORIZ.- CONT. THROUGH 5TH FLOOR
C3 C3
Scale
Project numberDateDrawn byChecked by As indicated
S002FIRST FLOOR PLAN
11-2015GROWING POWER
VERTICAL FARM2/11/15AuthorChecker
No. Description Date
1" = 20'-0"2 Level 1
1
5
3
2
4
A
IB
HC D E F G
9" THICK ONE WAY CONCRETE SLAB#9 @ 12" O.C., #3 @ 12" O.C. TRANSVERSE REINF.
B2 B2 B1 B1 B1
B4 B4 B4 B2 B2 B2
B2 B2 B2 B1 B1 B1
C4 C3 C3 C4 C4 C4
C4 C1 C2 C4 C4
C4 C3 C4 C4 C4
C1 C1
C3 C3
Scale
Project numberDateDrawn byChecked by As indicated
S003SECOND FLOOR PLAN
11-2015GROWING POWER
VERTICAL FARM2/11/15AuthorChecker
No. Description Date
1" = 20'-0"2 Level 2
1
5
3
2
4
A
IB
HC D E F G
9" THICK ONE WAY CONCRETE SLAB#10 @ 12" O.C., #3 @ 12" O.C. TRANSVERSE REINF.
B2 B2 B1 B1
B4 B4 B4 B2 B2
B2 B2 B2 B1 B1
C4 C3 C3 C4 C4
C4 C1 C2 C4
C4 C3 C4 C4
C1 C1
C3 C3
Scale
Project numberDateDrawn byChecked by As indicated
S004THIRD FLOOR PLAN
11-2015GROWING POWER
VERTICAL FARM2/11/15AuthorChecker
No. Description Date
1" = 20'-0"2 Level 3
1
5
3
2
4
A
IB
HC D E F G
9" THICK ONE WAY CONCRETE SLAB#9 @ 12" O.C., #3 @ 12" O.C. TRANSVERSE REINF.
B1 B1 B1
B3 B3 B3 B3
B1 B1 B1 B1
C4 C3 C3 C4
C4 C1 C2
C4 C3 C4
C1 C1
C3 C3
Scale
Project numberDateDrawn byChecked by As indicated
S005FOURTH FLOOR PLAN
11-2015GROWING POWER
VERTICAL FARM2/11/15AuthorChecker
No. Description Date
1" = 20'-0"2 Level 4
1
5
3
2
4
A
IB
HC D E F G
9" THICK ONE WAY CONCRETE SLAB#9 @ 12" O.C., #3 @ 12" O.C. TRANSVERSE REINF.
B1 B1
B3 B3 B3
B1 B1 B1
C4 C3 C3 C4
C4 C1
C4 C3
C1 C1
C3 C3
Scale
Project numberDateDrawn byChecked by As indicated
S006FIFTH FLOOR PLAN
11-2015GROWING POWER
VERTICAL FARM2/11/15AuthorChecker
No. Description Date
1" = 20'-0"2 Level 5
1
5
3
2
4
A
IB
HC D E F G
B1 B1
B1 B1
B1
B1
C4 C3 C3 C4
C4 C1
C4 C3
C1 C1
C3 C3
B1
B1
Scale
Project numberDateDrawn byChecked by 1" = 20'-0"
S007ROOF PLAN / SCHEDULES
11-2015GROWING POWER
VERTICAL FARM2/11/15AuthorChecker
No. Description Date
1" = 20'-0"1 Roof
TYP. AT 70' TILT WALL -12" CONC. TILT WALL, 2 MATS OF #7 @ 8" O.C. VERT.2 MATS OF #3 @ 18" O.C. HORIZ.
TYP. AT 56' TILT WALL -12" CONC WALL, 2 MATS OF #6 @ 8" O.C. VERT.2 MATS OF #3 @ 18" O.C. HORIZ.
TYP. AT 42' TILT WALL -12" CONC WALL, 2 MATS OF #4 @ 8" O.C. VERT.2 MATS OF #3 @ 18" O.C. HORIZ.
51' - 0"33' - 8"34' - 2 1/2"22' - 5 1/2"
1/2" EXP. JOINT TYP.AT PANEL POINTS
Scale
Project numberDateDrawn byChecked by 1" = 20'-0"
S008TILT WALL ELEVATION
11-2015GROWING POWER
VERTICAL FARM2/11/15AuthorChecker
No. Description Date
1" = 20'-0"1 Tilt Wall Elevations
AEI TEAM 11-2015
AEI TEAM 11-2015
Contents Statement of Goals ............................................................................................................................................. 1
Building Shell Efficiency ...................................................................................................................................... 1
Narrative of Systems & Solutions ................................................................................................................... 1
Rationale for System Selections & Solutions .................................................................................................. 1
Greenhouse Energy Modeling ............................................................................................................................ 3
Design Requirements.................................................................................................................................. 4
Rationale and Narrative of System Selections and Solutions ......................................................................... 4
Results ........................................................................................................................................................ 4
Conclusion .................................................................................................................................................. 5
Solar System Design – Renewable Energy Potential .......................................................................................... 5
Rationale and Narrative of System Selections and Solutions ......................................................................... 5
Photovoltaic (PV) Analysis .......................................................................................................................... 5
Panel Angle Optimization ........................................................................................................................... 6
Hot Water Solar Collectors ......................................................................................................................... 6
Solar Radiation on Walls ............................................................................................................................. 7
Determination of System Capacities .......................................................................................................... 8
Building Demand Calculations .................................................................................................................... 8
Cost Analysis of Systems ............................................................................................................................. 8
Summary of Results .................................................................................................................................... 9
HVAC System Determination ............................................................................................................................ 10
Mechanical and Energy Systems Design........................................................................................................... 10
HVAC System Determination ........................................................................................................................ 10
Calculations for HVAC Equipment ............................................................................................................ 11
Selection of zonal and central HVAC components based on cooling and heating load components ...... 11
Conclusion ................................................................................................................................................ 12
Energy Analysis of HVAC System .................................................................................................................. 12
Methodology ............................................................................................................................................ 12
Results ...................................................................................................................................................... 13
Conclusion ................................................................................................................................................ 13
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 1
Statement of Goals Our overall goal for the structure is to set a precedent for renewable energy in an Urban Farm and to
optimize the design choices to reduce energy costs. For the greenhouse portion of the structure, we want
to optimize economic and energy efficiency through plant designations and glass glazing. We separated the
analysis of the greenhouse and rest of the complex in order to optimize window glazing, window shading
and insulation of the office space. To set a precedent for renewable energy, we want to include solar panels
and hot water heaters to offset the energy used by the standard mechanical systems in the most energy
efficient manner possible. Our final goal is to choose the most energy efficient heating and cooling system
for the Urban Farm.
Building Shell Efficiency
Narrative of Systems & Solutions The window orientation and shading can be an important component of decreasing direct solar admissions
into the building. Although the design project already calls for windows on the east and west facades, we
can still add shading to the windows to decrease direct sunlight. Overhangs will be adjusted to keep the
heat and glare of direct sun from coming through windows and disrupting the thermal comfort and visual
comfort of the building. Since this building is in the northern part of the United States, the windows will
need to have more vertical fins to avoid the low-angle sun during the winter on the east and west facades.
Another element of windows that can control the amount of daylight let into the building is the glazing
property. The amount of daylight and quality of light let into the building regulates the thermal comfort and
visual comfort of the building. There are two properties of window types that we will consider that include
U-factor and Solar Heat Gain Coefficient (SHGC). The U-factor represents the thermal conductivity of a
window, which is the rate that heat transfers from the hotter side to the colder side. For this building, we
are looking for a low U-value because we don’t want to lose a lot of hot air inside the building to the cold
climate outside of the building. The Solar Heat Gain Coefficient measures how much of the solar heat
hitting the window surface actually enters the building. It depends on the number of panes as well as tinted
or reflective coating. We want to use the lowest U-value and SHGC values so that the heat transfer is
minimal.
Aside from window characteristics, the insulation that goes into the building also contributes to the
efficiency of a building. The insulation in a building disrupts the heat flow in or out of the building envelope.
Since the building we are optimizing is located in Wisconsin, we do not want to lose any heat to the outside
air during the cold winter months. To mitigate this behavior, we will beef up the insulation in the walls and
roofs of the vertical farm. Adjusting all the properties mentioned above is aimed at reducing the amount of
light and heat transfer into the building in order to achieve maximum efficiency.
Rationale for System Selections & Solutions The results we ended up getting are as we expected considering the environment our building is in.
Wisconsin is a very cold climate and the winters require a lot of heating to maintain thermal comfort. The
maximum amount of gas consumption is in the coldest months of January and December. But summers in
Wisconsin are not necessarily hot like Texas summers. It remains pretty cool during the summer months,
that’s why we see a little bit of gas consumption during the summertime. Electric consumption spikes
during the summertime though, which can be explained by the increase in space cooling displayed in the
Table. The area lights stay consistent throughout the year.
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 2
The baseline model was assumed to have R-19 insulation for walls and roof, no solar shading on the
windows, and single pane windows. In comparison to the baseline, we saved about 61,690 kWh and $7,631
annually across all three categories. The amount of money saved annually is not necessarily a big number,
but we feel that there are more areas of the building that can be optimized to cut back on energy bills.
Unfortunately, the scope of our project was just the building envelope and we feel that we accomplished
what we sought out to accomplish.
Compared to the baseline (single pane), the double pane reflective windows yielded a much lower annual
energy consumption and saved approximately $5,000 annually.
As expected, more shading resulted in less energy consumption compared to no shading at all. The success
of fins can be attributed to the low-angle sun during the winter time in Wisconsin.
Extreme winter conditions in Wisconsin mean that buildings require more insulation in the walls and roof
so that the hot air warming up the building does not escape to the outside. Our results are as expected with
the more insulation being the best option.
Figure 1: Window Properties
Figure 2: Window Shading
Figure 3: Insulation
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 3
Project Outcomes
Roof Insulation: R-38
Wall Insulation: R-21
Fins and Overhangs: 3 ft ea.
Windows: Double pane reflective tint
Table 1: Electric and Gas Consumption
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total
Electric Consumption (kWh x000)
Space Cooling 0.96 0.86 1.14 1.09 1.91 6.65 10.66 7.7 4.91 2.06 0.82 1 39.76
Ventiliation Fans 1.49 1.35 1.49 1.56 1.49 1.49 1.56 1.49 1.49 1.56 1.27 1.56 17.8
Pumps & Aux. 1.28 1.15 1.28 1.34 1.28 1.28 1.34 1.28 1.28 1.34 1.09 1.34 15.28
Misc. Equipment 4.17 3.77 4.17 4.32 4.17 4.15 4.34 4.17 4.15 4.34 3.65 4.34 49.74
Area Lights 10.52 9.52 10.52 10.98 10.52 10.51 11.00 10.52 10.51 11.00 9.08 11.00 125.68
Total 18.42 16.65 18.6 19.29 19.4 24.1 28.9 25.2 22.3 20.3 15.91 19.24 248.26
Gas Consumption (kBtu x000
Space Heating 377000 286700 247200 161300 93700 58000 39500 31700 36700 73700 139900 293000 1838400
Total 377000 286700 247200 161300 93700 58000 39500 31700 36700 73700 139900 293000 1838400
Figure 4: Monthly Electric Consumption
Figure 5: Monthly Gas Consumption
Greenhouse Energy Modeling This section focuses only on the greenhouse portion of the building. We were able to determine the
optimal window glazing and perform a cost analysis. Our research also includes different types of plants
that can be grown in the greenhouse and the required minimum and maximum temperature ranges for the
0
5
10
15
20
25
30
35
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
(kWh)
THO
USA
ND
S
E L E C T R I C C O N S U M P T I O N
0
100
200
300
400
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
(kWh)
THO
USA
ND
S
G A S C O N S U M P T I O N
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 4
plants. We chose to model our greenhouse in the eQuest software because of the available energy and cost
analysis outputs.
Design Requirements The types of plants chosen impact the energy used to heat the greenhouse. Because energy efficiency is
one of the main goals of the urban farm, primarily flexible plants were chosen, and plants with similar
needs will be housed in the same greenhouse. Plant tables can be found in the Assumptions section of this
report under Supporting Documents.
Rationale and Narrative of System Selections and Solutions We optimized glass values for the greenhouse. The glass depends on the types of plants grown in each level
of the greenhouse, therefore choosing plants was the first step. Since the plants will be grown and sold to
local restaurants and vendors, we had to make sure to determine an appropriate list of plants that can be
switched out seasonally, have a rapid growth lifecycle, and can grow in a wide range of temperatures.
After deciding which plants would be appropriate to grow in the greenhouse, we modeled the greenhouse
portion of the building in eQuest with the standard wizard mode and started out with baseline default
values in order to compare our savings and cost analysis after optimization. For our project, we compared
high absorption single pane glass to double pane glass. Double pane glass is listed in eQuest as double
clear/tint (double clear ⅛”, ¼” air). This is two pieces of glass insulated with a layer of air in between the
glass panes. The absorptivity of the glass is 0.6. The absorptivity of the high absorption single pane glass is
0.8.
We then compared the monthly energy demands and monthly utility bills of each glass type and were able
to calculate a payback period and annual cost savings with the optimization of the double pane glass. The
baseline model was modeled with single pane glass.
Results Figure 6 compares the monthly energy bill of the single pane, double pane, and high absorption glass.
Figure 6: Energy Cost per Month (gas + electric)
0
50
100
150
200
250
300
350
400
450
500
jan feb mar apr may jun jul aug sep oct nov dec
Co
st (
$)
Month
High Absorption
Single Pane
Double Pane
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 5
We compared the double pane glass and the high absorption glass to the single pane glass when
conducting our analysis. Both of the higher glass qualities lowered the greenhouse energy consumption
throughout the year. The double pane glass saves 116,000 kWh and the high absorption glass saves 18,000
kWh annually. For each glass type, the electric energy used to power the fans varies based on the heating
demand. The task lighting demand remains relatively constant throughout the year. The high absorption
glass saves $120 annually compared the single pane glass used as the baseline. However, due to the margin
of error implied when making assumptions, the saving is negligible. The double pane glass saves $754
annually compared to the single pane glass. We did not conduct a payback period analysis because the high
absorption glass did not significantly reduce the energy bill or the energy used. According to a local
Milwaukee glass manufacturer, double pane glass costs $11 per square foot, and single pane glass costs $8
per square foot. Taking into account that this is a new construction, the payback period for the double pane
glass is 53 years. While the double pane glass would save utility bills by a little over $750 each year, the cost
to install the double pane glass over the single pane glass is still expensive.
Conclusion With a payback period of 53 years, we decided that the double pane glass is not worth the additional cost.
Double pane glass would not improve the health of the plants and, besides the energy savings for this
prototype urban farm, there is not a significant reason to spend extra money on double pane glass. By
comparing economies of scale, the savings on an annual basis is insignificant compared to the initial square
footage cost of the double pane glass. The most important optimization to reduce the required energy by
the greenhouses was optimizing the temperature ranges for the plants. Grouping plants by the lowest
allowable growing temperature increased flexibility in the HVAC requirements, especially in the winter
months. By optimizing the levels of greenhouse by plant types, the temperature set points can be as high or
low as necessary depending on the season. Another energy saving design decision was to forgo cooling the
greenhouse. We optimized the space and systems based on plant comfort, not human, so the only source
of ventilation and cooling is opening windows.
Solar System Design – Renewable Energy Potential
Rationale and Narrative of System Selections and Solutions
Photovoltaic (PV) Analysis As seen in Table 1 Appendix B in Supporting Documents, PV’s were researched from various brands to find
the size, cost, and capacity. From this, the efficiency (W/sf) was calculated and the price per efficiency was
found ($/(W/sf)). These were plotted to show how price interacted with efficiency, as can be found in
Figure 7 below.
Figure 7: Cost in Terms of Efficiency
Astronergy (310) SolarWorld (280)
SolarWorld (315)LG (290)
LG (300), 28.24
Suniva (270)
Astronergy (255)
15
17
19
21
23
25
27
29
14.0 14.5 15.0 15.5 16.0 16.5 17.0 17.5
CO
ST [
$/(
W/S
F)]
EFFICIENCY (W/SF)
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 6
In Figure 7, a trend line is drawn and items are compared thereto. We selected to use the SolarWorld 280W
option, as it was far below this trend line of cost while still being significantly efficient.
Result: Use SolarWorld 280W PV Panels
Panel Angle Optimization Using a single roof plane from an existing model, the optimum solar angle was found using eQuest hourly
report of total solar radiation on the tilted surface [BTU/sf/hr] with the location of the model set to
Milwaukee and with a south facing orientation. While the magnitude of this radiation is not applicable to
our output results, values can be compared for the sake of angle optimization.
Figure 8: Solar Angle Optimization
As seen in Figure 8, the optimum angle was found to be 35.75 degrees. The trend of the radiation
magnitude means the sun is lower in the sky for Milwaukee as expected with its more northern geographic
latitude.
Result: Angle the PV panels at a 36° tilt.
Hot Water Solar Collectors Using our assumed hot water temperature of 50°C and the average ambient air temperatures for January,
April, July, and October (to represent each seasonal condition) from eQuest, we found the change in
temperature which needs to be provided by the hot water solar system for each condition. Figure 1 in
Appendix A under Supporting Documents shows an example of the data provided by the SRCC for a 30-tube
evacuated hot water solar collector called the VHP30.
From this data for various hot water systems, we graphed the change in temperature (Ti-Ta) versus the
output in kWh/panel per day for the given values to find a trendline and then calculated the output at the
changes in temperature our application would use. Once we had the actual output for our changes in
temperature, we calculated the efficiency for each temperature change for each system. This was
calculated by dividing the output of the panel per day by the incoming radiation per area, times the area,
per day. We also calculated the efficiency for the zero temperature change condition for comparison. Table
2 in Appendix B under Supporting Documents shows an example of the capacity resultant and efficiency for
350
370
390
410
430
450
470
490
510
530
550
0 10 20 30 40 50 60 70 80 90
Sola
r R
adia
tio
n (
kBtu
)
Angle of Plane (Degrees)
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 7
the VHP30 system over different temperature conditions. From this, we also calculated the cost as
(price/area)/efficiency. We then plotted the cost versus efficiency for each system for each weather
condition and created a trendline for the systems.
Appendix B (Supporting Documents) Figures 3 and 4 show the efficiency versus cost for the January and July
conditions to account for efficiency variations. From this, various observations can be drawn. The flat plate
system is close in comparison for efficiency with a relatively low cost for the July condition. This makes
sense because the warmer ambient temperature is removing less heat from the surface of the plate in the
summer condition. Yet in winter, the flat plate has a drastically lower efficiency than the other systems
which makes sense because the cooler ambient temperature is removing a larger amount of heat from the
plate’s surface. From this, we have chosen against the use of flat plates for our project. We instead have
decided to use an evacuated tube system because the vacuum tube helps remove influence from the
outside air temperature by decreasing convection with the air. When looking at evacuated tube options,
the VHP30 gives both the highest efficiency and lowest normalized cost for both July and January. Thus, we
decided to utilize the SunMaxx VHP30 evacuated tube solar hot water heating system.
The optimization of the façades' capacities depends heavily on the number of panels which can fit within
the constrained geometry of the building's architectural layout. The HWSC panels were limited to the East
and West façades due to the greenhouses. We looked at the existing layout of windows from the
architectural schematic design and noticed that many window placements were not explicitly specified.
From this, we decided that it was within reason to adjust the existing placement of the windows to
accommodate our systems. After rearranging the windows, we determined that we could fit 29 panels
on the West façade and 40 panels on the East façade. See Figure 2 in Appendix A to see the final placement
of the HWSC panels.
Results: Use the VHP30 Evacuated Tube Solar Collectors. Analyze with 29 Panels on the West and
40 panels on the East.
Solar Radiation on Walls From an existing eQuest model, we ran hourly reports for the amount of solar radiation for the East and
West façades. The hourly report gave the radiation per square foot for each hour of each day in units of
[BTU/sf/hr]. To find the total radiation per square foot for each façade for each day over the entire year, we
took the average of these for each of the 4 seasons as described in the Assumptions section (Appendix C,
Supporting Documents). Doing this, we found the average radiation per day for each season and multiplied
it by (365days/4) and added it together to get the total solar radiation acting on each façade per year. This
is shown as:
𝐴𝑣𝑔. [(𝑆𝑜𝑙𝑎𝑟 𝑅𝑎𝑑𝑖𝑎𝑡𝑖𝑜𝑛
𝑠𝑓−𝑑𝑎𝑦)𝑠𝑎𝑚𝑝𝑙𝑒 𝑑𝑎𝑦 "𝑖"]𝑠𝑎𝑚𝑝𝑙𝑒 𝑠𝑒𝑎𝑠𝑜𝑛 "𝑖" x (
365 𝑑𝑎𝑦𝑠4⁄ ) = …
…𝑇𝑜𝑡𝑎𝑙 𝑅𝑎𝑑𝑖𝑎𝑡𝑖𝑜𝑛𝑠𝑓⁄ 𝑓𝑜𝑟 𝑔𝑖𝑣𝑒𝑛 𝑓𝑎𝑐𝑎𝑑𝑒 𝑒𝑎𝑐ℎ 𝑦𝑒𝑎𝑟
To confirm this method, we found the sum of the total solar radiation on each façade for a year. Comparing
this to our sample day and season method, we varied by 0.2% for the West façade and 0.4% for the east
façade, indicating our method is reliable. Consistently, the East façade showed ~65% of the solar radiation
seen on the West façade, and values per season follow expected results. These were found using:
𝐶𝑎𝑙𝑐𝑢𝑙𝑎𝑡𝑒𝑑𝑅𝑎𝑑𝑖𝑎𝑡𝑖𝑜𝑛
𝑠𝑓 𝑓𝑜𝑟 𝑎 𝑦𝑒𝑎𝑟 𝑢𝑠𝑖𝑛𝑔 𝑠𝑒𝑎𝑠𝑜𝑛𝑎𝑙 𝑎𝑣𝑒𝑟𝑎𝑔𝑒
𝐸𝑄𝑢𝑒𝑠𝑡 𝑅𝑎𝑑𝑖𝑎𝑡𝑖𝑜𝑛
𝑠𝑓 𝑓𝑜𝑟 𝑎 𝑦𝑒𝑎𝑟
⁄ x 100%
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 8
Determination of System Capacities In accordance with the geometry of the front porch and optimized tilt angle, we found that 2 rows of 19
panels each was the maximum system size for the panel array. Production capacity of the PV system was
found by calculating the aperture area of 38 SolarWorld 280W panels and multiplying by the panel
efficiency and seasonal solar radiation total [BTU/sf]. Results show higher electricity production
during sunnier summer months and severely diminished production during short, dark winter days, which is
to be expected because of dependence on incoming solar radiation. The output of the PV system’s
production can be found in Table 3 of Appendix B. Likewise for the HWSC System capacity, we used the
efficiency which had been interpolated from the SRCC tables for each season. We then multiplied these
efficiencies by the seasonal solar radiation [BTU/sf] and effective surface (aperture) area. This gave an
annual production of heat energy. We looked at options for energy produced by using both façades as well
as just the West façade. These results for energy production per façade can be found in Table 4 of Appendix
B.
Building Demand Calculations To calculate an approximate building consumption profile, we consulted the Commercial Building Energy
Consumption Survey 2003 data from the Energy Information Administration
(http://www.eia.gov/consumption/commercial/data/2003/). The building was categorized by type of use
per area, as specified in the architect's floor plans of the proposed design. Tables 6 and 7 in Appendix B
show building’s use by area according to our assumptions to match energy intensity benchmarks.
Intensities for each occupancy type for a building 10,000-100,000sf (ours being 50,000sf total area)
of Electricity consumption [kWh/sf] (EIA CBECS 2003 Table C21) and Domestic Hot Water consumption
[kBTU/sf] (EIA CBECS 2003 Table E6) were used to aggregate a representative annual energy consumption
of our building. This is an approximation, which understandably could be different in implementation
dependent on several factors such as hot water systems used in the aquaponics and greenhouse areas,
HVAC system setpoint temperature, the climate zone 6A, and etc. To manipulate annual consumption
benchmark values, we took demand profiles created by other energy analysis teams working on other
aspects of the Growing Power project: eQuest models of the mixed use interior and of the greenhouse
(separately) gave monthly consumption values, accounting for higher electricity to interior cooling loads in
summer and higher electricity to warming greenhouses in winter (as mentioned above in this report). Using
ratio principles, we created a more dynamic profile of the EIA annual benchmark by extrapolating it into
seasonal totals reflecting changes in consumption seen by modelers in other groups. This was the method
for both PV and HWSC systems.
Result: Building consumption is 490279 kWh for the building’s electricity use and 154758 kBtu for
the hot water use. The systems’ demand vs. capacity is summarized in Tables 3 and 5 in Appendix B
(Supporting Documents).
Cost Analysis of Systems Cost analysis on the final PV system tries to quantify benefits and returns on investments in a system such
as the photovoltaics. It should be noted that costs listed are for panels only, disregarding installation and
maintenance costs in addition to rebates or energy incentives offered by the government. Cost also does
not account for the changing value of currency over time, though this could have notable influence in the
time scale of a few decades. Total annual production [kWh] is multiplied by local electricity cost
($0.09/kWh) to represent annual savings. The initial cost is $350 per panel, with 38 total panels in use.
Convergence of initial cost and annual savings will result in an 8.75 year payback period, which is promising
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 9
with respect to the 25 year expected lifetime of the system. Some may be critical of a payback period this
long, but on a project of this nature—dedicated to green energy and innovative technology as a role model
for the surrounding community—we expect the reduction of carbon footprint to be an additional and
invaluable incentive. Similarly, a cost analysis for the HWSC system was performed. In order to do so, the
annual amount of energy produced by both the west and east façades was multiplied by the regional
cost/therm since it is assumed the energy produced by the HWSC took away from gas that would be used
by the furnace. This translated to an annual savings of $1,488 for the west façade alone and $2,941 for both
the east and west façades combined. The total cost for each option was found by multiplying the cost per
HWSC panel ($949) by the number of panels on each façade. Thus, the west façade only costs $27,521, and
the east façade costs $37,960. Both facades combined will cost $65,481. This creates a payback period of 18
years for the west façade alone and 22 years for both facades. The total capacity vs. demand was the
deciding factor in choosing a configuration, because these options are both within the product’s expected
life of 25-30 years.
Summary of Results In examining these findings, we found that the PV system could cover approximately 3% of the building’s
total energy requirements, as seen below in Figure 9.
Figure 9: PV Capacity vs. Demand
The HWSC options’ capacity vs. the building demand is shown in Figure 10. As shown, neither option covers
the building’s requirements in the winter condition. Also, the option of both façades was grossly over
producing in the spring and summer. Ultimately, we decided to put HWSC on the west façade only because
the capacity was closer to the demand. This will still demonstrate dedication to green energy by the
project, while pragmatically avoiding high initial cost of east façade panels.
Figure 10: HWSC Capacity vs. Building Demand
0
20
40
60
80
100
120
140
Elec
rici
ty (
kWh
x0
00
)
PV Capacity v. Building Demand
Demand EIA
Solar PanelProduction
Winter Spring Summer Fall
0
20
40
60
80
100
120
140
Ener
gy [
kBtu
x00
0]
HWSC Capacity v. Building Demand
Demand
West Only
Both Facades
Winter Spring Summer Fall
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 10
The final design of the building is to provide 38 SolarWorld 280W PV Solar Panels at a 36° tilt on the south
façade. This has a total cost of $13,300 and a payback period of 8.75 years. Additionally, provide 29 VHP 30
Evacuated Tube Hot Water Solar Collectors on the west façade. This has a total cost of $27,520 and a
payback period of 18.5 years. While these payback periods seem long compared to the product’s lifetime,
the impact that it can have on the environment and the impression it would make on the surrounding
community is worth the upfront cost. To calculate reduction in greenhouse gas emissions (shown in
Appendix B, Table 8), we used annual energy production of the solar system in BTU and the EIA’s Carbon
Dioxide Emissions Coefficients, assuming the solar powered hot water is replacing each equivalent BTU
produced by burning natural gas—53.1 kg CO2 per million BTU
(http://www.eia.gov/environment/emissions/co2_vol_mass.cfm)—to calculate metric tons of greenhouse
gas pollution potentially saved by implementing solar energy producing systems. In projects aiming to
support innovative energy solutions and ecological building practices, sustainable building operations can
drive decisions when cost benefits are not obvious.
HVAC System Evaluation
Mechanical and Energy Systems Design
HVAC System Determination We decided to limit our scope to the second floor of the building in order to show a more in depth analysis.
All spaces are predicted to be occupied throughout most of the operating hours. In order to start our
analysis we modeled our building using the program eQuest. In order to get effective results we had to
break the floor down into zones for common areas, shown in Figure 11.
After the zones were created, our next task was to pick the system that we wanted in each zone. These
zones were pretty similar, the only difference being that the restroom had larger ventilation. All zones were
heated and cooled by a DX coil system, except for the restroom where we did not include a heating source.
After our building was completely modeled, we ran a simulation with eQuest and were able to produce the
cooling and heating loads for each zone, shown in Table 2.
Figure 11: Second floor zoning
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 11
Table 2: Heating and cooling loads for second floor
Cooling Q (BTU/hr)
Heating Q (BTU/hr)
Lobby 7428 11595
Restroom 5510 14477
Gathering 156525 47384
The data was as predicted because of the cold climate year round the heating load dominated over the
cooling load. This data was then used to help size our system components.
Calculations for HVAC Equipment We used the heating loads that were presented earlier to help size our diffusers. We first broke down each
zone into separate areas as seen in Appendix D, Table 10 and then found characteristic lengths for each
area. Velocity was found using the equation v=Q/(Air density*(Change in Enthalpy)). The change in enthalpy
was found using a psychometric chart. We assumed a sensible heat ratio of 0.8, a supply temperature of
76°F, and a return air temperature of 80°F. This gave us an enthalpy change of 3 Btu/ lbmair. The air density
was taken to be 0.075 lbm/ft3. The throw was calculated using a ratio of 0.8. Diffuser selection is shown in
Table 9 (Appendix D). As shown in Table 10 (Appendix D), duct diameters ranged from 6 to 18 inches and
the greatest pressure drop occurred in duct section 18-19 at 6836 with a static pressure drop of 2. This data
was then used to help us size the fan needs in order for it to function properly using the pressure drop.
Selection of zonal and central HVAC components based on cooling and heating load components
Chiller: Scroll Chiller Model CGAM The 20 to 130 ton air-cooled scroll chiller model CGAM is factory assembled, charged, and designed for use
in ambient temperatures of 0°F to 125°F. A Trane scroll chiller is equipped with compressors, condenser,
fans, evaporator, and controls. The industrial-grade design for this scroll chiller is ideal for large office
buildings and commercial/industrial facilities. The chillers install easily and quickly on the roof or ground for
comfort or process cooling applications.
VAV box: Dual Duct Dual-duct terminal units will be used in the air distribution system, where the main system has both warm
air and cold air separately ducted to each terminal unit. The flow of both warm air and cool air is
modulated, delivering air to the VAV zone at variable air volumes as well as variable temperatures. Since
full capacity occupied heating is always available, control of additional local heat will not be provided.
Reversible Heat Pump: Aqua Logic® Delta Star® Heat Pumps 1/3 hp, 4,000 BTU/Hr, 10/20 gpm, 3/4"
Inlet/Outlet, 115V.
Heat pumps automatically handle both heating and cooling duties. Pumps include a dual stage digital
temperature controller and will maintain temperatures from 40–85°F (5–29°C). The temperature controller
will keep the temperature within 1 degree of the set point in °F or °C. In heating mode, these heat pumps
work with the liquid refrigerant in reverse. Pumps will be mounted indoors where air temperatures stay
above 55°F.
Control description – sequence of operation During occupied modes, the air handling unit will operate to maintain a constant discharge air temperature
(typically 55°F). The fans will run continuously (at a variable rate), with the outside air damper open to its
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 12
minimum position. Supply fan will operate to maintain a suitable duct static pressure, and exhaust/return
fan will operate to maintain a suitable space static pressure. During unoccupied modes, the air handling
unit will operate to maintain the space temperature between unoccupied heating and cooling set points
(typically 60 and 80 degrees). The below image is a schematic of our system illustrating the flow of Outside
Air.
Economizers The outside air enthalpy or dry bulb sensor will monitor outside air conditions. If outside air conditions are
suitable for cooling, then economizer will be operated. Upon a first stage cooling, economizer operation is
initiated. Outside and return air dampers will begin to modulate in order to maintain a suitable discharge
air temperature (typically between 50 and 56 degrees). In other words, if the economizer controller is set to
allow economizer operation at a higher outside air enthalpy or dry bulb temperature, then the temperature
of the outside air will be higher than what is trying to be maintained at the discharge, and therefore the
outside air damper will run fully open without succeeding to achieve this discharge air temperature set
point.
Conclusion eQuest provided us with proper heating and cooling loads and with that we were able to size the
equipment necessary for our HVAC system. Because of the climate we spent most our calculations
designing for the larger heating load. Our ducts and diffusers results were calculated using the knowledge
obtained this semester in our HVAC design class we believe that for this floor the sizes are appropriate. We
were able to conclude what commercial systems were necessary to make this building work.
Energy Analysis of HVAC System
We decided to optimize the HVAC system because the purpose of this building is to be environmentally
friendly we know that minimizing the amount of energy and gas consumption being used is key to maintain
this concept. We will be using eQuest to model the vertical farm.
Our model will represent what the building will look like without the greenhouses on each floor. We plan
on separating the commercial area from the greenhouse areas with large thermal walls. We did this in
order to ensure that whatever systems we put in the commercial area will not affect the greenhouse area.
The challenge in this project is separating sections of each floor into common zones
Methodology In order to get proper results we decide to run a series of multiple trials on this building shell using the
different options listed in the program eQuest for cooling, heating, and ventilation systems. We used a total
of nine HVAC systems to feed into our zones. For example, the lobbies in all our floors were using the same
HVAC system. In order to get the best results we first needed to set the proper temperature ranges in each
of the HVAC systems.
Table 3: Operational temperatures for each HVAC system
HVAC SYSTEM
COOLER FREEZER STORAGE MARKET PROCESSING KITCHEN REST ROOM
GATHERING LOBBY
TEMP RANGE (F)
35-40 0-(-10) 50-60 70-74 55-65 65-76 65-74 70-74 70-74
Our approach of optimizing the HVAC system was simulating the heating system and cooling system with different
options containing Water-coiled system, Furnace system, and Reversible heat pump system.
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 13
Water Coiled system indicates cooling is provided via chilled water coils (e.g., built-up air handling systems
served by a central chilled water plant) while heating is provided via hot water coils (e.g., built-up air
handling systems served by a central boiler plant). A schematic is shown in Error! Reference source not
found. of Appendix D.
Furnace system indicates heating is provided via a packaged or self-contained furnace. However, since
furnace produces heat by combustion which is not reversible, we combined DX Coil for cooling purpose. A
schematic of the Furnace System with DX Cooling Coil is shown in Error! Reference source not found. of
Appendix D.
DX Coil system indicates cooling is provided via direct expansion coils (e.g., package or self-contained
cooling systems) while heating is provided via direct expansion coils (e.g., air-source or water-source heat
pumps). A schematic of the DX coil system is shown in Error! Reference source not found. of Appendix D.
We compared the cost efficiencies of each by looking at the charts of Annual energy consumption and
Annual Energy cost. Then we chose the system that gave us the lowest value as a default setting in terms of
optimizing further details of the HVAC system.
With the optimized heating/cooling source, the next step was to figure out which HVAC system type is
going to lower the energy consumption. In order to proceed this task, we had to sub divide the task with
varying combination of heating and cooling sources. The zones consisted of only cooling space, only heating
space and cooling/heating space. Determining the system type for only cooling spaces, we had the
following options: Packaged Single Zone DX, Split System Single Zone DX, Packaged Terminal AC, and
Packaged VAV. System research is located in the Supporting Documents.
Results In our initial test we selected to use the DX coil system which resulted in the lowest annual energy
consumption. Both the furnace system and the water coiled systems saw a much higher output of gas
consumption than the DX coil system. Table 4 shows the results from the energy simulations using different
heating and cooling systems.
Table 4: Energy consumption and cost comparison
Coiled Water Furnace DX Coiled
Electricity consumption (kWh) 719 644 688
Gas consumption (Btu) 3900 3052 382
Total Annual Cost ($) 96,587 82,121 58,895
Conclusion After evaluating results, we concluded that the DX coiled source with packaged termianl AC system type to
be the most viable option. With the total space heating load and cooling load, 440 KBTU/hr and 582
KBTU/hr respectively, the annual energy consumption of the DX coiled system was 688.42 Kwh for
electricity and 382.16 Btu for gas, costing $58,895 per year. Due to the location of the building where
climate requires much more heating than cooling, selecting heating source played a significant role in
terms of lowering the energy usage. Comparing the results from previous simulations led us to the
conclusion that optimization of a heating source of the HVAC system in building design can save 30% to
40% on the utility bill each year.
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 14
Appendix A: Resources and Figures
Figure 1. SRCC Data for VHP30
Figure 2. HWSC Panel Placements
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 15
Appendix B: Calculations Table 1. PV Panel Comparison
Brand Unit # Area (sf) Capacity (W) (W/sf) Price ($) Price/(W/sf)
Astronergy 1977310 20.9 310 14.83254 310 20.90
SolarWorld 1922276 17.144 280 16.33224 350 21.43
SolarWorld 1922279 20.45 315 15.40342 385 24.99
LG 1524615 17.65 295 16.71388 408 24.41
LG 1524607 17.65 300 16.99717 480 28.24
Suniva 1524406 17.46 270 15.46392 365 23.60
Astronergy 1970255 17.67 255 14.43124 241 16.70
Table 2. Capacity and Efficiency of the VHP30 system at Different Temperature Conditions
Ta (C)
Ti-Ta
(C) Capacity (kWhr/day) efficiency %
-9.5 59.5 5.6138 0.400411 40.0
7.33 42.67 7.054448 0.503167 50.3
21.7 28.3 8.28452 0.590903 59.1
10.67 39.33 7.340352 0.523559 52.4
0 10.707 0.763689 76.4
Table 3. PV Panel Output vs. Building Demand
Season
SOUTH Porch of PV Panels -
(38 280W Solar World Panels
Oriented 36deg S)
Total
Radiation
on
Surface
(Btu/sf)
PV Output
(BTU)
PV
Output
(kWh)
Electricity
DEMAND -
EIA Total
(kWh)
% of
Demand
Covered
by PVs
Average Incoming Radiation / day 985
Season Total 89908
Average Incoming Radiation / day 1684
Season Total 153681
Average Incoming Radiation / day 1876
Season Total 171210
Average Incoming Radiation / day 1358
Season Total 123944
Annual Incoming Rad. Total (Season Composite)538743
Annual Incoming Radiation Actual Total 529627
% Difference 1.7
Aperature Area (sf)651.472
Panel Efficiency 0.167
115524
122461
136148
116187
490279 3.4
2.5
4.0
4.0
3.4
16887
Winter
Spring
Summer
Fall 3952
16719849
9781592
18626921
13484613
PV Panel Production Output and Demand
Whole Year 57621224
2867
4900
5459
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 16
Figure 3. Efficiency v. Cost - January
Figure 4. Efficiency v. Cost – July
Table 4. HWSC Energy Output
HWSC System
Capacity
Total Incoming Radiation (BTU/sf)
HWSC Efficiency per Season Effective area (sf)
Total Output BTU per Season
W E W E W E
Winter 36300 20719 0.4004 1007 1389 14634960 11521799
Spring 83286 61962 0.5032 1007 1389 42195289 43298808
Summer 105266 78600 0.5909 1007 1389 62630016 64503005
Fall 55681 35707 0.5236 1007 1389 29353105 25963384
Table 5. HWSC Output vs. Building Demand
Output: HWSCs
DEMAND W E Both
Winter 45068 14635 11522 26157
Spring 38364 42195 43299 85494
Summer 32404 62630 64503 127133
Fall 38922 29353 25963 55316
Whole Yr 154758 148813 145287 294100
0
200
400
600
800
1000
1200
1400
1600
1800
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45
Co
st [
($/m
^2)/
Eff.
)
Efficiency [kWhr Output/kWhr Input]
VHP10
VHP20
VHP30
Flat Plat
SunRain-30R
0
200
400
600
800
1000
1200
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Co
st [
($/m
^2)/
Eff.
)
Efficiency [kWhr Output/kWhr Input]
VHP10
VHP20
VHP30
Flat Plat
SunRain-30R
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 17
Table 6. EIA Energy Demand Calculations for Building’s Electricity Usage
Table 7. EIA Energy Demand Calculations for Building’s Hot Water Usage
Table 8. HWSC System Cost and Emissions Savings
(EIA CEBC S
2003 Table C21)
Occupanc
y Basement 1 2 3 4 5
Total
sf/use
Intensity
(kWh/sf)
Electricity
Consumption by
Occupancy Type
Education 0 0 0 1594 0 0 1594 10.2 16258.8
Food
Service 0 0 0 842 0 0 842 24.5 20629
Food
Sales 0 3734 0 0 0 0 3734 11.2 41820.8
Office 2311 166 599 2819 4285 0 10180.46 16.4 166959.5
Public
Assembly 0 810 5081 0 0 0 5891 11.2 65979.2
Warehous
e/Storage 5476 4450 2772 2280 2011 4720 21709 5.5 119399.5
Other 2241 4602 1230 848 787 1062 10770 5.5 59232.5
Total sf 10028 10028 9682 8383 7083 5782 50986 Total 490279 kWh
S&Rs 226440 kWh
Electricity
Consumpt
ion
Calculatio
n Per
Table C21
- EIA
2003
Square Footage in Building
(EIA CEBC S
2003 Table E7)
Occupanc
y Basement 1 2 3 4 5
Total
sf/use
Intensity
(kBtu/sf)
Hot Water Energy
Consumption by
Type
Education 0 0 0 1594 0 0 1594 5.2 8288.8
Food
Service 1164 0 0 842 0 0 2006 40 80240
Food
Sales 0 3734 0 0 0 0 3734 3.2 11948.8
Office 2311 166 599 2819 4285 0 10180.46 1.6 16288.73456
Public
Assembly 0 810 5081 0 0 0 5891 0.9 5301.9
Warehous
e/Storage 4312 4450 2772 2280 2011 4720 20545 0.7 14381.5
Other 2241 4602 1230 848 787 1062 10770 1.7 18308.2
Total sf 10028 10028 9682 8383 7083 5782 50986
Total
Consumpti
on 154758 kBTU
S&Rs 154720 kBTU
Hot Water
Consumpt
ion
Calculatio
n Per
Table E7 -
EIA 2003
Square Footage in Building
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 18
Appendix C: Assumptions
Assumptions/Limitations:
Estimating Seasonal Radiation Totals: Because of variance across days (due to cloudiness, wind
speed, etc.) we took the average solar radiation per area [BTU/sf/hr] per day across 4 seasons (3
months each, Jan-March, Apr-June, July-Aug, Oct-Dec) to produce seasonal totals and a whole year
solar radiation sum. The eQuest simulation results of hourly total solar radiation on an equivalently
oriented surface (BTU/sf) is assumed to accurately model production capacity.
Windows can be moved to accommodate HWSC placement, because exact location is not specified
in floor plans provided by architect. HWSC placement is done in CAD with inflated gross area per
panel blocks, to see maximum allowable number of panels to accommodate façade geometry and
window placement.
No nearby trees or buildings are shading the E or W façades of our building.
The structural system can support added HWSCs and PVs.
A uniform outdoor air temperature as TMY2 Data value in cold weather efficiency of HWSC
calculations. The energy output of the SRCC ratings for the Hot Water Solar Collectors varies
linearly across different changes of temperature allowing for linear interpolation of the actual energy
output for a given ambient air temperature.
PV panel efficiency is assumed unchanging through whole year.
HWSCs need to be placed vertically on 2nd-4th floor façades for pragmatism. (None on 5th floor
because it is all glass greenhouse, and none on the 1st floor because its susceptible to damages.)
Demand calculated from EIA standard values from CBECS 2003 benchmarks for building use/type
as specified. Greenhouse area is treated as Warehouse use type consumption benchmark. We made
composite of these, which is assumed accurate. Seasonal changes from this baseline annual
consumption are assumed based on other teams' dynamic demand profiles. A more accurate idea of
percentage of energy generated renewably could be made by more extensive eQuest modeling or
data analysis of building consumption as built in practice.
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 19
Appendix D: HVAC DESIGN
Room Occupancy
(ft^2/person) ACR
(cfm/ft^2) Humidity Range
(%) T range
winter (F)
Restroom negligible N/A 30-60% 67-76
Locker 6 N/A 30-100% 67-76
Offices 200 0.06 30-60 67-76
Classrooms 25 0.12 30-60 67-76
Corridor - 0.06 30-60 67-76
Elevator - 0.12 30-60 68-75
Kitchen 200 5/hr 68-75 68-75
Greenhouse 300 - <80 -
Conference 20 0.06 30-60 68-75
Auditorium 6.67 0.06 30-60 68-75
Workshop 6.67 0.06 30-60 68-75
Processing 6.67 0.06 30-60 70-75
Shipping/ - 0.12 <50 70-75
receiving - 0.12 <50 70-75
Loading Assume outside Assume outside <50 70-75
Lobby 6.67 5 30-60 68-75
Market 6.67 5 30-60 68-75
Storage - 0.06 30-60 67-76
Cooler R-25 n/a n/a 90-100 35-40
Freezer R-32 n/a 5-1.25 90-100 0-(-10)
Source: ASHRAE Standard 62.1
Design Methodology
The procedure recommended by ASHRAE for selecting diffusers in a room is outlined below: Room air volumetric flow rate at design conditions
The volumetric flow rate was determined by using an energy balance on the room assuming standard air density:
𝑉 =𝑄
𝜌𝛥ℎ
Determine design airflow required (V)
Select Diffuser and return locations
Determine the number of diffusers and returns
required
Lay out supply and return ducts
Size main and branch ducts
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 20
Where V is the air volumetric flow rate supplied to the room, Q is the total design load on the room, ρ is standard air density, and Δh is the total enthalpy difference between supply and return air. The total enthalpy difference, Δh, was determined by the function of the values of temperature range and humidity ratio for each zone using the psychrometric chart as figure below. The maximum of the heating and cooling airflow rates were used to select the diffuser if the room is both heated and cooled by the supply air.
Diffuser type selection
Considering the rooms were typically square, it was appropriate to use circular ceiling diffusers. Each diffuser was centered in a ceiling area that is roughly a square, as the air is supplied in four directions from the diffuser. If only one diffuser was used for a room, the total air flow rate computed occupied the areas of the room. However, if more than one diffuser is used, each was allocated proportionally corresponding to the total supply airflow of the space. The characteristic length for circular ceiling diffuser type is the distance between closest wall or midway to nearest ceiling diffuser. Characteristic length is used when sizing a diffuser by calculating the throw. With the manufacturer’s catalog, using the determined volumetric flow rate and the throw, the appropriate locations and number of diffuser was selected as the charts below:
h2
h1
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 21
Floor Space Design Load
(KBTU/HR)
Δh (BTU/lbm)
V (ft^3/min)
Throw (ft)
Nominal Neck
Size (in)
Basement
Storage 1 4.76 10 103.59 6 6
Storage 2 16.17 10 352.22 12 8
Storage 3 9.23 10 201.09 8 10
Cooler 1 0.97 1 211.11 6 10
Cooler 2 1.25 1 271.24 6 10
Cooler 3 1.38 1 301.53 6 10
Cooler 4 0.69 1 150.76 6 10
Freezer 1 5.67 4 308.80 7 8
Freezer 2 5.67 4 308.80 7 8
Locker Room (M) 4.22 9.5 96.82 8 6
Locker Room (W) 4.22 9.5 96.82 8 6
Lobby 1 16.47 9 398.74 6 10
Lobby 2 8.24 9 199.37 4 10
Lobby 3 8.24 9 199.37 4 10
1st
Market 1 17.22 5 750.50 12 12
Market 2 17.22 5 750.50 12 12
Market 3 17.22 5 750.50 12 12
Processing 1 7.06 6 256.46 10 8
Processing 2 7.06 6 256.46 10 8
Processing 3 7.06 6 256.46 10 8
Workshop 1 4.97 6 180.43 10 6
Workshop 2 4.97 6 180.43 10 6
Loading 9.69 6 351.96 10 8
Receiving 3.93 6 142.56 6 6
Lobby 13.84 9.5 317.28 9 8
Restroom (M) 8.66 10 188.75 4 6
Restroom (W) 8.66 10 188.75 4 6
2nd
Lobby 11.60 9.5 265.91 9 8
Restroom (M) 7.24 10 157.70 4 6
Restroom (W) 7.24 10 157.70 4 6
Break Out Space 1
4.77 5 207.63 9 8
Break Out Space 2
4.77 5 207.63 9 8
Gathering 1 6.31 5 274.90 10 10
Gathering 2 6.31 5 274.90 10 10
Gathering 3 6.31 5 274.90 10 10
Gathering 4 6.31 5 274.90 10 10
Gathering 5 6.31 5 274.90 10 10
Gathering 6 6.31 5 274.90 10 10
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 22
Floor Space Design Load
(KBTU/HR)
Δh (BTU/lbm)
V (ft^3/min)
Throw (ft) Nominal
Neck Size ( in)
3rd
Lobby 11.60 9.5 265.93 9 8
Restroom (M) 6.07 10 132.24 4 6
Restroom (W) 6.07 10 132.24 4 6
Classroom 1 14.35 5 625.36 7 14
Classroom 2 19.43 5 846.41 7 14
Classroom 3 19.43 5 846.45 7 14
Kitchen 1 8.27 6 300.34 5 12
Kitchen 2 8.27 6 300.34 5 12
4th
Lobby 11.60 9.5 266.05 9 8
Restroom (M) 5.92 10 128.99 4 6
Restroom (W) 5.92 10 128.99 4 6
Staff Area 1 5.61 5 244.31 6 8
Staff Area 2 5.61 5 244.31 6 8
Copy Room 2.14 5 93.12 6 6
Reception Area 6.44 5 280.74 6 8
Office Area 1 6.40 5 278.65 5 8
Office Area 2 6.40 5 278.65 5 8
Meeting 6.96 5 303.31 7 10
Director 5.31 5 231.33 6 8
5th Lobby 11.62 9.5 266.57 9 8
Duct Layout
After locating supply and return outlets, next step was to locate air-handling equipment and layout ductwork to connect the discharge of the air handler with all supply diffusers and return air to the return side of the fan. Routing of the ductwork depended on available space and aesthetics. As the image below, two air handling units were located on the basement level and second level. The below one and the above one connected to the bottom three stories and top three stories respectively.
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 23
Sizing Procedures
Assigning fittings to all transitions and sizing all the ducts require numbering each section of ductwork for ready reference. The loss of total pressure within sections was set to be an important criteria for designing a stable system. If the pressure losses of different zones are different, the system layout needs significant changes in order to balance the system. With this Equal-Friction method, it allows a compromise between initial cost and operating cost since the ducts are supposed to be low-velocity. Below char is the pressure loss chart provided by ASHRAE, and knowing the variable of the air volume flow rate allows you to choose the size of the duct. As the arrows in the chart are indicating, the chart will guide to the corresponding values of the pressure loss as well as the air velocity inside the duct. For example, if the size of 30” diameter duct is selected with 10,000 cfm air quantity, the following air velocity and pressure loss in the duct are 2000 fpm and 0.17. For the fittings such as diverging tee or elbows, loss coefficient is an important variable in terms of calculating the total pressure loss. Loss coefficient can be found using the tables published by the ASHRAE.
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 24
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 25
To compute the velocity pressure of each duct section, the equation 𝑃 = (𝑉
4005
2)was used. Also, the losses
through the fittings were calculated by multiplying the velocity pressure by the loss coefficient. The losses through the straight runs were calculated by multiplying the duct length by the pressure drop per unit length.
Flow path Duct section Air flow D L ∆P/L Velocity ∆P
static ∑C
∆P dynamic
∆P total
Gathering
1
1_2 3155 0.2 0.1
2_3 3155 18 10 1700 2 10837.5 10839.5
3_4 2265 0.2 0.1
4_5 2265 16 10 1500 2 8437.5 8439.5
5_6 1698 0.2 0.1
6_7 1698 14 20 1400 4 7350 7354
7_8 1132.5 0.2 0.1
8_9 1132.5 12.5 20 1300 4 6337.5 6341.5
9_10 566 0.2 0.1
10_11 566 9.5 20 1050 4 4134.375 4138.375
2 9_16 566 0.2 0.1
16_17 566 9.5 15 1050 3 4134.375 4137.375
3 7_14 566 0.2 0.1
14_15 566 9.5 20 1050 4 4134.375 4138.375
4 5_12 566 0.2 0.1
12_13 566 9.5 10 1050 2 4134.375 4136.375
Locker Room
5
3_18 890 0.2 0.1
18_19 890 12 10 1350 2 6834.375 6836.375
19_20 340 0.2 0.1
20_21 340 8.5 10 1000 2 3750 3752
21_22 170 0.2 0.1
22_23 170 6 10 800 2 2400 2402
23_24 170 0.2 0.1
24_25 170 6 10 800 2 2400 2402
6 21_26 170 0.2 0.1
26_27 170 6 10 800 2 2400 2402
Lobby 7
19_28 550 0.2 0.1
28_29 550 10 20 1100 4 4537.5 4541.5
29_30 550 0.2 0.1
30_31 550 10 5 1100 1 4537.5 4538.5
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 26
Calculations
Vertical Duct Computations
Basement – Level 2
Duct Section
Airflow, (ft^3/min)
Duct Diameter,
in
Duct Length,
ft
Velocity, ft/min
Velocity Pressure, in. water
Loss Coefficient
Duct P Loss, “.
water/100’
Total P Loss, in.
water
0~1 10417.29 0.25 0.59 0.15
1~2 10417.29 30.00 7.00 2000 0.25 0.17 0.01
2~3 7217.02 0.25 0.14 0.03
3~4 7217.02 26.00 12.17 2000 0.25 0.19 0.02
4~5 2645.98 0.33 0.15 0.05
5~6 2645.98 14.00 10.17 2300 0.33 0.50 0.05
6~7 2645.98 0.33 0.06 0.02
2~8 3200.27 0.25 0.65 0.16
4~9 4571.04 0.25 0.43 0.11
ΔP_7 0.34 in. of water
ΔP_8 0.32 in. of water
ΔP_9 0.32 in. of water
Level 3 – Level 5
0
1
2
26 25 3 4 5
27
28
6
7 8 9 10 11
14 15
29
30
31 16
17
32
33
34 35
36 37
38
39
40
50
49 23
22 24
46 48 47 45
43
21 20
42 41
19 18 1
41
1
12
48
13
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 27
Duct Section
Airflow, (ft^3/min)
Duct Diameter,
in
Duct Length,
ft
Velocity, ft/min
Velocity Pressure, in. water
Loss Coefficient
Duct P Loss, ".
water/100'
Total P Loss, in.
water
0~1 6194.34 0.23 0.06 0.01
1~2 6194.34 24 24 1900 0.23 0.19 0.05
2~3 2745.02 0.09 0.17 0.02
3~4 2745.02 20 12 1200 0.09 0.10 0.01
4~5 266.57 0.02 0.55 0.01
5~6 266.57 10 10.5 600 0.02 0.07 0.01
6~7 266.57 0.02 0.09 0.00
2~8 3449.32 0.09 1.12 0.10
4~9 2478.44 0.12 0.52 0.06
ΔP_7 0.11 in. of water
ΔP_8 0.16 in. of water
ΔP_9 0.15 in. of water
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 28
Horizontal Duct Computations:
Basement
Duct Section
Airflow, (ft^3/min)
Duct Diameter,
in
Duct Length,
ft
Velocity, ft/min
Velocity Pressure, in. water
Loss Coefficient
Duct P Loss, ".
water/100'
Total P Loss, in.
water
0~1 3200.27 17 0.25 0.65 0.16
1~2 3200.27 17 34.92 2000 0.25 0.3 0.10
2~3 2801.53 0.25 0.65 0.16
3~4 2801.53 16 10.42 2200 0.25 0.4 0.04
4~5 2602.16 0.25 0.47 0.12
5~6 2602.16 14 11.25 2200 0.25 0.5 0.06
6~7 2391.05 0.25 0.07 0.02
7~8 2391.05 14 15.00 2100 0.25 0.45 0.07
8~9 2119.80 0.25 0.14 0.03
9~10 2119.80 14 13.50 2000 0.25 0.4 0.05
10~11 1818.28 0.18 0.14 0.02
11~12 1818.28 14 8.00 1700 0.18 0.3 0.02
12~13 1818.28 0.18 0.07 0.01
13~14 1818.28 14 4.67 1700 0.18 0.3 0.01
14~15 1667.52 0.20 0.14 0.03
15~16 1667.52 14 5.50 1800 0.20 0.4 0.02
16~17 770.22 0.04 1.78 0.07
17~18 770.22 12 32.17 800 0.04 0.08 0.03
18~19 474.02 0.05 0.16 0.01
19~20 474.02 10 18.50 900 0.05 0.13 0.02
20~21 276.66 0.03 1.20 0.04
21~22 276.66 9 25.00 700 0.03 0.11 0.03
22~23 100.54 0.02 1.04 0.02
23~24 100.54 6 20.50 500 0.02 0.08 0.02
2~25 398.74 0.04 4.50 0.18
25~26 398.74 10 13.00 800 0.04 0.1 0.01
4~27 199.37 0.02 5.17 0.12
27~28 199.37 8 14.33 600 0.02 0.08 0.01
14~29 150.76 0.01 7.36 0.09
29~30 150.76 8 7.75 450 0.01 0.05 0.00
16~31 897.30 0.09 0.16 0.01
31~32 897.30 12 15.83 1200 0.09 0.18 0.03
32~33 279.71 0.02 0.33 0.01
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 29
Duct Section
Airflow, (ft^3/min)
Duct Diameter,
in
Duct Length,
ft
Velocity, ft/min
Velocity Pressure, in. water
Loss Coefficient
Duct P Loss, ".
water/100'
Total P Loss, in.
water
33~34 279.71 10 9.08 600 0.02 0.065 0.01
34~35 176.11 0.02 0.65 0.01
35~36 176.11 8 9.17 500 0.02 0.06 0.01
34~37 103.59 0.02 1.56 0.03
37~38 103.59 8 10.33 300 0.01 0.055 0.01
38~39 103.59 0.02 0.11 0.00
39~40 103.59 8 6.67 300 0.01 0.055 0.00
18~41 96.82 0.01 13.78 0.08
41~42 96.82 8 10.50 300 0.01 0.02 0.00
20~43 272.93 0.05 0.65 0.03
43~44 272.93 8 4.67 900 0.05 0.17 0.01
44~45 176.11 0.03 1.05 0.03
45~46 176.11 7 20.00 700 0.03 0.15 0.03
44~47 96.82 0.01 3.00 0.03
47~48 96.82 7 5.83 400 0.01 0.045 0.00
22~49 176.11 0.03 1.05 0.03
49~50 176.11 7 20.00 700 0.03 0.15 0.03
ASHRAE Duct Fitting Database, 1994.
Fitting Loss Coefficients
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 30
MECHANICAL AND ENERGY DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 31
Scale
Project numberDateDrawn byChecked by 1" = 20'-0"
M001BASEMENT MECHANICAL PLAN
11-2015GROWING POWER
VERTICAL FARM2/11/15AuthorChecker
No. Description Date
1" = 20'-0"1 Basement
Scale
Project numberDateDrawn byChecked by 1" = 20'-0"
M0021ST FLOOR MECHANICAL PLAN
11-2015GROWING POWER
VERTICAL FARM2/11/15AuthorChecker
No. Description Date
1" = 20'-0"1 1 - Ceiling Mech
Scale
Project numberDateDrawn byChecked by 1" = 20'-0"
M0032ND FLOOR MECHANICAL PLAN
11-2015GROWING POWER
VERTICAL FARM2/11/15AuthorChecker
No. Description Date
1" = 20'-0"1 2 - Ceiling Mech
Scale
Project numberDateDrawn byChecked by 1" = 20'-0"
M0043RD FLOOR MECHANICAL PLAN
11-2015GROWING POWER
VERTICAL FARM2/11/15AuthorChecker
No. Description Date
1" = 20'-0"1 3 - Mech
Scale
Project numberDateDrawn byChecked by 1" = 20'-0"
M0054TH & 5TH MECHANICAL PLAN
11-2015GROWING POWER
VERTICAL FARM2/11/15AuthorChecker
No. Description Date
1" = 20'-0"1 4 - Mech 1" = 20'-0"2 5 - Mech
INTEGRATED DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 1
INTEGRATED DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 2
Contents Introduction .................................................................................................................................................. 3
Duct Sizing and Clash Detection ................................................................................................................... 3
Mounting Hot Water Solar Collectors ........................................................................................................... 3
Selection of Greenhouse Glass Type ............................................................................................................. 3
INTEGRATED DESIGN AEI DESIGN COMPETITION SPRING 2015
AEI TEAM 11-2015 3
Introduction Detailed coordination between the mechanical team and the structural team was required to integrate
the building’s structural systems and mechanical systems. Both systems must be able to function
effectively without being negatively impacted by the function of the other. Decisions made by about the
mechanical design of the building often directly affected the structural design of the building, and
occasionally decisions made by the structural team attached constraints to the mechanical design.
Several instances in which coordination was required between the two disciplines will be described in
the following sections including:
Duct sizing and clash detection
Mounting of hot water solar collectors on tilt wall panels
Mechanical equipment placement
Selection of greenhouse glass type
Duct Sizing and Clash Detection The structural team selected precast beam sizes using occupancy loads determined using IBC-2009.
Beams were sized with depths between 20 and 32 inches deep. The sizes of HVAC ducts were required
to comply with the sizing of all precast beams. Even though the structural and mechanical systems of
the building are exposed, having no suspended ceiling to hide them, a 10 foot invisible ceiling height was
set to allow for ample head room for building occupants.
Both the mechanical and structural systems were modeled in Revit. When clashes were noticed in the
plans, adjustments were made.
Mounting Hot Water Solar Collectors Hot water solar collectors were added to the east and west facades of the building in order to reduce
the net total energy consumption of the building. The addition of hot water solar collectors resulted in a
greater axial force experienced by each tilt wall panel on the east and west facades. Additionally, they
created an eccentricity of about 2 inches from the wall’s surface resulting in a permanently applied
moment on each tilt wall, thereby resulting in the need for a thicker and more heavily reinforced tilt wall
design.
Selection of Greenhouse Glass Type The weight of the various mechanical systems had to be taken into account as a part of the structural
design. We assumed a load of 30 psf when calculating the factored loads as a part of structural design.
The type of glass selected for the greenhouse also played into the structural design. The most efficient
glass type was determined to be single paned glass with a thickness of ¼”. This thickness was then
multiplied by the total surface area of the greenhouse and the density of glass to determine total weight
of glass. This was then added to the total weight of the aluminum framing to determine the load
applied by the greenhouse onto the slabs and beams below.