Spacing and Concrete Cover Requirements for Epoxy- Coated Prestressing Strand in Unconfined Sections Thomas E. Cousins Ph.D., P.E. Assi stant Profes sor Department of Ci vil Engi neer ing Auburn Un iversity Auburn, Alabama Lance H. Francis Graduate Student Auburn Un iversity Auburn, Alabama J. Michael Stallings, Ph.D. 76 Associ ate Profe ssor Depa rt ment of Civil Engi neer ing Auburn University Auburn, Alabama V. Gopu, Ph.D. Professor Department of Ci vil Engineering Louisi ana State University Baton Rouge, Louisi ana A test program was undertaken to determine the spacing and concrete cover requirements of 0.5 in. (12. 7 mm) diamet er seven-wire prestressing strand coated with a grit impregrated epoxy. Spacing and concrete cover requirements were studied by varying the parameters of strand spacing, concrete cover and number of strands . These re- quirements were then compared with the AASHTO Specifications. The transfer length of epoxy-coated prestressing strand was also investigated. It is concluded that strand spacing and concrete cover requirements should be increased somewhat in pre- stressed concrete members without con- finement reinforcement. However, in bridge girders and other prestressed concrete members that typically carry confinement reinforcement in the form of stirrups and end zone reinforcement, increased strand spacing and concrete cover may not be warranted. T oday, prestressed concrete is widely used in the con- struction industry. With the continuous improvement in design me thods and production techniques, pre- cast, prestressed co ncrete is recognized as a durable material with low maintenance costs. In the large majority of appli- cations, hig h quality concrete and proper cover are sufficient to protect the reinforcement from possible corrosion. As with all materials, when prestressed concrete elements are exposed to particularly harsh environments, adeq uate PCI JOURNAL

Spacing and Concrete Cover Requirements for Epoxy Coated

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Spacing and Concrete Cover Requirements for Epoxy Coated

Spacing and Concrete Cover Requirements for Epoxy­Coated Prestressing Strand in Unconfined Sections

Thomas E. Cousins Ph.D., P.E.

Assistant Professor Department of Civil Engineering

Auburn Un iversity Auburn , Alabama

Lance H. Francis Graduate Student Auburn University Auburn , Alabama

J. Michael Stallings, Ph.D.

76

Associate Professor Department of Civil Engineering

Auburn University Auburn , Alabama

V. Gopu, Ph.D. Professor Department of Civil Engineering Louisiana State University Baton Rouge , Louisiana

A test program was undertaken to determine the spacing and concrete cover requirements of 0.5 in. (12. 7 mm) diame ter seven-wire prestressing strand coated with a grit impregrated epoxy. Spacing and concrete cover requirements were studied by varying the parameters of strand spacing, concrete cover and number of strands. These re­quirements were then compared with the AASHTO Specifications. The transfer length of epoxy-coated prestressing strand was also investigated. It is concluded that strand spacing and concrete cover requirements should be increased somewhat in pre­stressed concrete members without con ­finement reinforcement. However, in bridge girders and other prestressed concrete members that typically carry confinement reinforcement in the form of stirrups and end zone reinforcement, increased strand spacing and concrete cover may not be warranted.

T oday, prestressed concrete is widely used in the con­struction industry. With the continuous improvement in design methods and production techniques, pre­

cast, prestressed concrete is recognized as a durable material with low maintenance costs. In the large majority of appli­cations, high quality concrete and proper cover are sufficient to protect the reinforcement from possible corrosion.

As with all materials, when prestressed concrete elements are exposed to particu larly harsh environments, adequate

PCI JOURNAL

Page 2: Spacing and Concrete Cover Requirements for Epoxy Coated

measures must be taken to protect the prestressing steel and mild steel rein­forcement. The consequences of cor­rosion to the reinforcement in concrete structures subjected to harsh environ­mental exposures, such as in very salty coastal regions, may be severe enough to warrant special corrosion resistant materials. Under these conditions, epoxy-coated strand can be beneficial in providing corrosion protection and in ensuring long-term durability of the structure.

Florida Wire and Cable, Inc. (FWC), a major prestressing steel manufac­turer, has developed an epoxy-coated strand which has proven to be effec­tive in preventing the corrosion of pre­stressing steel.' Recently, PC I' s Ad Hoc Committee on Epoxy-Coated Strand published guidelines for using epoxy-coated strand.2 The epoxy coat­ing is impregnated with grit to im­prove its bonding capabilities in pre­stressed concrete members.

Studies conducted in the past decade have indicated splitting of concrete at stress transfer in single strand speci­mensY Splitting of concrete was not observed in uncoated single strand specimens with similar dimensions. The splitting was attributed to the shorter transfer length of epoxy-coated strand causing higher bond stresses, which could be even more severe in members with multiple strands at closer spacings.

The main objective of this research program was to investigate the spac­ing and cover requirements of epoxy­coated prestressing strand. This was done using test specimens with vary­ing strand spacings and concrete covers. Another objective was to de­termine the transfer length of epoxy­coated strand.

TEST PROGRAM Forty specimens were fabricated

and tested at the Structural Engineer­ing Research Laboratory of Auburn University. The specimens were de­signed to study the influence of three parameters : strand spaci ng, strand configuration and concrete cover. The effect of these parameters on transfer length was also investigated.

Parameters were varied to determine

September-October 1993

[±]=t IB±B itt=t=l I f-a-j f--b--1 1-b--l

SINGLE STRAND MULTIPLE STRAND MULTIPLE STRAND

ONE ROW TWO ROWS

Fig. 1. Specimen cross sections showing arrangement of single and multiple strands.

Table 1. Specimen dimensions and strand details.

Overall Center-to-center Minimum Number of dimensions strand spacing cover Number of

strands

I

3

6

* n/a: not applicable. Note: I in.= 25.4 mm.

(in.)

3.5 X 3.5

4 .0 X 4.0

3.75 X 3.75

4.0 X 8.0

4.0 X 8.5

4.5 X 9.0

4.0 X 9.0

4.5 X 9.5

4.5 X 10.0

4 .5 X 10.5

5.0 X 10.5

5.0 X 11.0

7.0 X 9.5

7.25 X 10.0

7.5 X 10.0

7.75 X 10.5

8.0 X 11.0

the minimum concrete cover and strand spacing requirements to prevent specimens from splitting at stress transfer. Nine companion specimens were fabricated with uncoated strand to serve as a control. This experimen­tal program generated a large amount of data on the transfer length of epoxy-coated strand, a summary of which is given in this paper. Full de­tails of the test program are given in the final project report. 5

Specimen Description

As shown in Fig. 1, beam specimens were fabricated using th~ee types of strand configuration: • Single strand • Three strands placed in one layer • Six strands placed in two layers

Specimen dimensions are listed in Table 1. All specimens were rectangu-

(in.)

nla*

nla*

nla*

2.0

2.25

2.5

2.25

2.5

2.75

3.0

2.75

3.0

2.5

2.75

2.5

2.75

3.0

(in.) specimens

1.5 4

1.75 3

1.625 3

1.75 3

1.75 3

1.75 3

1.75 3

2.0 3

2.0 2

2.0 I

2.25 I

2.25 2

2.0 2

2.0 I

2.25 1

2.25 2

2.25 3

lar in cross section with one, three or six concentric strands. No confine­ment reinforcement was used.

Beam lengths for the first set of specimens were 9 and 11 ft (2.73 and 3.34 m) for the uncoated and coated strand specimens, respectively . The beam lengths were increased for the second set of specimens to ensure full transfer length within the length of specimens. The lengths of specimens with coated and uncoated strand were increased to 10 and 12 ft (3.05 and 3.65 m), respectively.

Materials

The concrete mix was designed to yield a compressive strength of 4500 psi (31.1 MPa) in six to seven days and a minimum strength of 5500 psi (38.0 MPa) in 28 days to simulate conditions of a prestressing plant. The

77

Page 3: Spacing and Concrete Cover Requirements for Epoxy Coated

Table 2. Compressive strengths of concrete.

Concrete age f~ (psi) Batch at transfer

No. (days) Transfer 28 days

I 7 4220 5270

2 6 4450 5450

3 10 4240 4640

4 6 5160 5750

5 6 4690 6160*

6 7 4720 5810

7 6 4730 6190

* At 35 days. Note: I psi = 0.006895 MPa.

ready-mixed concrete was provided by a local supplier with super-plasticizer added to obtain a minimum slump of 6 in. (154 mm) at casting.

The original mix design proportions per cubic yard were:

Cement .. .. .. .. .. . 705 Jbs (3136 N) Water ...... 30.5 gallons (0.115 m3

)

Sand .......... .. . 1160 lbs (5160 N) Coarse aggregate ..... .. . . . . .... . . . .. . . . . . . . . . . . . . . . . . . . . 1926 lbs (8567 N) Water-reducing admixture ... . . . . ... . .. .. .. .. .. .. .. . 21.2 ounces (627 cm3

)

Super-plasticizer .... . .. . .. .. . ..... . . . .. .. .. .. .. .. .. .. 56 ounces (1656 cm3

)

This mix was used for the first three batches. Since the concrete strength for these specimens was Jess than desired, the mix design was changed slightly for Batches 4 through 7. Compressive

Table 3. Transfer length results for single strand specimens.

Minimum Transfer length (in.)

Specimen No. Size clear cover /p; (Batch No.) (in.) (in.) (ksi) TR 7 days 28 days

I ( I ) 3.5 X 3.5 1.50 na nc/nc nc/nc nc/nc

2 (I ) 3.5 X 3.5 1.50 na nc*/nc nc*/nc nc*/nc

3 (2) 4x4 1.75 184 18/22* 19/24* 32/28*

4 (2) 4x4 1.75 182 24/24 27/28 27/29

5 (3) 3.75 X 3.75 1.625 na na!na* nc/nc* nc/nc*

6 (3) 3.75 X 3.75 1.625 182 26/26 26/28 38/38

"nc" designates no transfer length determined due to cracking for full length of specimen. "na" means that no data were available. * End adjacent to fl ame cut. Note: I in. = 25.4 mm; I ksi = 6.895 MPa.

strengths obtained from the seven batches of concrete at transfer and at 28 days are listed in Table 2. Tables 3, 4 and 5 match the specimens cast with their appropriate batch number.

All the coated and uncoated pre­stressing steel was manufactured by FWC. The prestressing strand was low-relaxation, 0.5 in. (12.7 mm) di­ameter, seven-wire strand with an ultimate tensile strength of 270 ksi (1862 MPa) . The coating thickness averaged 0.036 in. (0.91 mm).

The uncoated strand was used as a control to ensure satisfactory testing. A few specimens were made with un­coated strand at spacings ranging from the AASHTO minimum to the largest used in the specimens with coated strand. The epoxy coating was imbed-

ded with an aluminum oxide grit to improve bonding with concrete.

Some coated strand sections had no­ticeably less grit than others, with some sections having no grit. These sections, when used, were placed in the middle of the beams to minimize interference with the transfer of the prestressing force.

Specimen Fabrication

Two 46 ft (14.0 m) long stressing beds were constructed in the Structural Engineering Research Laboratory of Auburn University so that two lines of specimens could be cast simultane­ously. Two post-tensioned reinforced concrete end blocks were used to form the stressing bed.

Table 4. Transfer length results for three strand specimens.

Specimen No. Size (Batch No.) (in.)

I (2) 4x8 2 (2) 4x8 3 (3) 4 X 8.5 4 (3) 4 X 8.5 5 (4) 4.5 X 9 6 (4) 4.5 X 9 7 (4) 4x9 8 (4) 4x9 9 (5) 5 X 10.5 10 (5) 4.5 X 20 II (5) 4.5 X J0

12 (5) 4.5 X 9.5 13 (5) 4.5 X 9.5 14 (6) 5 X 11 15 (6) 5 X II 16 (6) 4.5 X 10.5

"c" designates cracked spec1mens. * End adjacent to fl ame cut. Note: I in. = 25.4 mm; I ksi = 6.895 MPa.

78

Minimum Spacing clear cover

(in.) (in.)

2 1.75 2 1.75

2.25 1.75 2.25 1.75

2.5 1.75 2.5 1.75 2.25 1.75 2.25 1.75 2.75 2.25 2.75 2.00 2.75 2.00

2.5 2.00

2.5 2.00

3 2.25

3 2.25 3 2.00

Transfer length (in.) Crack

/p; length (ksi) TR 7 days 28 days (in.)

173 65c/38c 65c/38c 65c/38c 56/31

173 40c/43c* 41c/44c* 43c/45c* 30/40

175 33c/62c 37c/65c 40c/66Ct 19/49

176 34c/53c* 34c/53c* 34c/53c* 27/38

191 28c/37c 30c/42c 31c/55c 12/29

189 30c/34c* 32c/44c* 40c/47c* 21/31 197 29c/40c 32c/44c 33c/45c 12/51

189 27c/32c* 30c/35c* 31c/38c* 25/31

198 34c/26 35c/24 37c/24 23/0

197 39c/24 41c/24 41c/24 21/0 198 30c/28c* 33c/36c* 33c/37c* 25/0

194 45c/28c 46c/43c 47c/48c 29/27

196 37c/18* 38c/18* 38c/25* 24/0

196 24/27 24/30 24/30 0/0 196 28c/21c 31c/26c 46c/37c 19/14

196 34c/55c* 36c/56c* 36c/56c 35/43

PCI JOURNAL

Page 4: Spacing and Concrete Cover Requirements for Epoxy Coated

The strand was pulled through an 8 in. (203 mm) diameter hole in the blocks and held in place at the ends by chucks and steel plates. Form work was fabricated such that the strands could be stressed before placing the form­work and the beam dimensions could be changed with minimal adjustments.

Stressing was accomplished with a hydraulic jack and hand pump. The force in each strand was monitored using load cells at the dead end chucks. A pressure gauge attached to the jack was used to estimate the strand stress and to check that the dead end load cell was operating properly.

The strand stress immediately before construction averaged 74.4, 76.3 and 77.0 percent of 270 ksi (1862 MPa) for the single-, three- and six-strand beams, respectively. Based on calcu­lated elastic shortening losses, this yielded an average strand stress imme­diately after transfer of 67.6, 69.9 and 70.7 percent of 270 ksi (1862 MPa) for the single-, three- and six-strand speci­mens, respectively.

The average concrete compressive stresses at transfer were 2210, 2380 and 2460 psi (15.2, 16.4 and 17.0 MPa), for single-, three- and six-strand speci­mens, respectively. However, the stan­dard deviation of these stresses was fairly high due to the significant change in the cross-sectional dimensions.

It was decided to transfer a force per strand as used typically in a prestress­ing plant despite the resulting varia­tion of PIA stresses. This was believed to be more critical for transfer length and crack propagation.

The prestressing force was trans­ferred instantaneously (with no pre­heating) by acetylene torch to simu­late procedures used in prestressing plants. The strands were flame cut in sequence so as not to exceed the al­lowable stresses in the beam at trans­fer. The specimen ends adjacent to flame cuts are noted in Tables 3, 4 and 5.

The average transfer length for ends adjacent to flame cuts was 38 in. (965 mm) while the average transfer length of all other ends was 31 in. (787 mm). It appears that the transfer lengths of ends adjacent to the flame cuts were substantially larger than the transfer lengths of all other ends.

September-October 1993

Table 5. Transfer length results for six strand specimens.

Minimum Transfer length (in.) Specimen No. Size Spacing clear cover !pi

(Batch No.) (in.) (in.)

I (6) 8 X I] 3 2 (6) 8 X I[ 3 3 (7) 7.25 X 10 2.75 4 (7) 7.75 X 10.5 2.75 5 (7) 7.75x 10.5 2.75 6 (7) 7 X 9.5 2.5 7 (7) 7.5 X 10 2.5

* End adjacent to flame cut. t No data available due to computer malfunction. Note: I in. = 25.4 mm; I ksi = 6.895 MPa.

Fig. 2. Formwork in place with threaded inserts prior to casting specimens.

Instrumentation and Test Procedure

The transfer length is the length over which the force in the prestress­ing strand is transferred to the con­crete. Within this length, the stress in the prestress ing strand varies from zero to the effective stress, f se·

The transfer length for each end of a member is the distance from the beam end to the point where the concrete strain becomes uniform and reaches its maximum. The transfer length of each specimen was measured so that the transfer of prestressing force could be determined.

Immediately after transfer, and at seven and 28 days after transfer, the strain in the concrete and, hence, the transfer length was determined. Mea­surements were taken prior to release with an extensometer so that the dis­tance between gauge points before transfer could be determined.

The distance between gauge points

(in.) (ksi) TR 7 days 28 days

2.25 192 22/22 28/23 30/24 2.25 191 24/34* 24/34* 26/36* 2.00 187 34*/32 34*/32 40*/32 2.25 _t _,_t _,_t _,_t 2.25 190 18/1 2 21/13 22/16 2.00 190 32121 32/21 32/2 1 2.25 193 18/23 21/34 24/37

was also measured immediately after transfer and at seven and 28 days . By subtracting the initial distance from the final distance, the change in length between gauge points was determined. The concrete surface strain due to pre­stress was calculated by dividing the change in length by the gauge length.

The gauge points were set at 2 in. (50.8 mm) intervals along each side of each specimen. An extensometer mea­sured the distance between gauge points over a predetermined gauge length. Threaded inserts embedded in the concrete were used for the gauge points. Fig. 2 shows the threaded in­serts screwed to the forms before the concrete was cast.

For the first batch, a gauge length of 6 in. (152 mm) was specified; how­ever, the accuracy of these results was suspect.

For all succeeding batches, a 10 in. (254 mm) gauge length was used to decrease the relative error. The exten­someter provided a digital record of readings to 0.0001 in. (0.00254 mm) over a 10 in. (254 mm) gauge length. This corresponds to a concrete surface strain of 0.00001 in. per inch.

In addition to strain readings, end slip readings were recorded using a depth micrometer and end slip brack­ets as shown in Fig. 3. End slip read­ings were taken to measure the dis­tance each strand slipped into the concrete following transfer. The end slip brackets were attached to each strand prior to transfer.

The distance from the end of the bracket to the specimen was measured by placing the shaft of the depth mi­crometer through the two small holes in the end slip bracket until the body of

79

Page 5: Spacing and Concrete Cover Requirements for Epoxy Coated

Fig. 3. Depth micrometer and end slip brackets.

the micrometer was flush with the bracket. The shaft was then moved up against the specimen. End slip mea­surements and concrete strain readings were made before and after stress trans­fer. End slip measurements were taken from a digital readout measuring to the nearest 0.00005 in. (0.00127 mm).

0 .0018

0.00 17

0.0016

0 .0015

0.00 14

"' z 0 .00 13

' 0 .0012 z .;::, 0.001 1 z

0 .001 ;{ 0::

0.0009 1-(/)

w 0.0008 1-w 0.0007 0:: 0 z 0 .0006 0 0 0 .0005

0.0004

0.0003

0.0002

0.0001

0 0

TEST RESULTS AND ANALYSIS

Analysis of Transfer Length Results

Surface strain readings from all the beams were recorded in a spreadsheet program. The readings were used to

20 40 60

DISTANCE FROM END E (IN)

determine the concrete strain immedi­ately following transfer, and at seven and 28 days after transfer. These data were used to plot the concrete strain along the length of each beam.

The transfer length was determined by first drawing the best fit horizontal line through the points forming the strain plateau. Note that the transfer length of each beam was defined as the distance from the end of the beam to the point where the concrete strain reaches the strain plateau. Therefore, the transfer length is the distance re­quired for 100 percent of the effective steel stress Use) to be transferred to the concrete.

A representative plot of strain vs. specimen length for three-strand Spec­imen 6 (see Table 4) is illustrated in Fig. 4. A strain plateau of 6.8 x lQ-4 at transfer and an average transfer length of 32.0 in. (813 mm) can be seen in this figure. The right end of this speci­men was adjacent to a flame cut.

80 100 120

D TRANSFER + 7 DAYS <> 28 DAYS

Fig. 4. Typical concrete surface strain plot.

80 PCI JOURNAL

Page 6: Spacing and Concrete Cover Requirements for Epoxy Coated

Table 6. Average and standard deviation of strand transfer length results.

Specimen Number in Average transfer length (in.)/Std. Dev.*

type sample Transfer 7 days 28 days

Coated (cracked) 27 37/10 40/9 42/8

Coated (not cracked) 23 24/5 26/5 28/5

* Standard Deviation. Note: I in. = 25.4 mm; I ksi = 6.895 MPa.

Table 7. Measured and calculated transfer lengths.

Transfer length (in.) Ratio Specimen

type

Coated (cracked)

Coated (not cracked)

* 50 strand diameters. Note: I in. = 25.4 mm.

Measured

37

24

The transfer length results [at trans­fer (TR), and seven and 28 days after transfer] for single-, three-, and six­strand specimens with epoxy-coated strand are presented in Tables 3, 4 and 5, respectively. The transfer lengths shown are the average for each side of a member with the transfer lengths for each end of a member separated by a slash (/).

The transfer length results from Ta­bles 3, 4 and 5 are summarized in Table 6. The average transfer lengths from different specimen types are listed in this table. The number of samples in Table 6 and subsequent ta­bles refers to the number of beam ends tested. For clarity, all transfer length comparisons within thi s paper are made with transfer lengths recorded immediately after transfer unless oth­erwise noted.

A comparison of measured and cal­culated transfer lengths is presented in Table 7. The calculated transfer lengths in Table 7 were computed

Measured AASHTOEq. SOd* AASHTO

31 25 1.2

32 25 0.8

from the transfer length portion of AASHTO Eq. (9-32):6

Transfer Length = fse db 3

where

fse = effective prestress (immedi­ately following transfer for the purpose of this paper)

db = diameter of the prestressing strand

Results for Coated Strand - The average values of transfer lengths for the specimens with coated strand are listed in Table 6. These data were di­vided into two categories (uncracked and cracked specimens) to facilitate transfer length determination in un­cracked specimens. The average trans­fer lengths for uncracked and cracked specimens with coated strand were 24 and 37.2 in. (610 and 945 mm), respectively.

For cracked and uncracked coated strand specimens, the average transfer

lengths were smaller than those mea­sured for uncoated strand specimens. The ratio of measured transfer length to AASHTO calculated transfer lengths, as listed in Table 7, is 1.19 for the coated cracked specimens and 0.76 for the coated uncracked specimens. The AASHTO equation overestimates transfer length for the uncracked coated strand specimens.

As expected, the transfer lengths for the cracked specimens were longer than for the uncracked specimens. When cracking occurred at prestress transfer, the transfer lengths increased because the bond between the concrete and strand was weakened within the cracked area. Cracked specimens de­veloped cracks between strands (spac­ing cracks) and cracks from the strand to the outside edge of the cross section (cover cracks).

The longest crack lengths measured at each end of the specimens are listed in Tables 3 and 4. These crack lengths are the longest occurring on any of the four beam faces . Only one end of one specimen (Specimen 11 in Table 4) had just spacing cracks. These being internal cracks, no crack lengths are given. No cracking was found in any specimen containing six strands.

It can be seen from the crack lengths listed in Tables 3 and 4 that following a rough correlation, transfer length in­creases with crack length. The trans­fer length of cracked specimens using epoxy-coated strand appears to ap­proach the average transfer length of uncracked specimens [24 .0 in. (610 mm)] with increased cover and spacing.

Average transfer lengths of coated strand for various concrete covers are listed in Table 8. For cracked speci­mens, as cover increases the transfer

Table 8. Effect of concrete cover on transfer length for coated strand.

Table 9. Effect of strand spacing on transfer length for coated strand.

Cover (in.)

1.625

1.750

2.000

2.25

* No data available. Note: I in. = 25.4 mm.

Average transfer length (in.) I No. of samples

Cracked Not cracked Both

n/a*/0 26/2 26/2

39/16 22/4 36/20

37/8 27/6 33/14

28/3 23/1 1 24/14

September-October 1993

Spacing (in.)

2.000 2.25 2.50 2.75 3.00

* No data available. Note: I in. = 25.4 mm.

Average transfer length (in.) I No. of samples

Cracked Not cracked Both

47/4 n!a* 47/4 39/8 n/a* 39/8 3417 22/5 29/12 33/4 24/6 28/10 35/4 26/6 29/10

81

Page 7: Spacing and Concrete Cover Requirements for Epoxy Coated

Concrete Cover (in.)

Number of cracked specimen ends~ Number of uncracked specimen enb ~ ~

I I 1C

I c

PIA stresses (c:c) along the transfer length.

The value Ese is the strain at the strain plateau and is derived from the following equation:

2.25 2U

I 2.0

3C

3~ 4C BC 4C

I 1.75

2 2.25 2.5

5U "'su

I I 3C 2C

3U

2.75 3 Strand Spacing (in.)

(2)

where

EPP = steel strain prior to concrete placement

Fig. 5. Matrix of number of cracked and uncracked specimens vs. concrete cover and strand spacing.

dEc = average change in concrete strain from before concrete placement to immediately fol­lowing transfer of prestress

length decreases, whereas for un­cracked specimens, a relationship between cover and transfer length is not discernable. The average transfer lengths for various strand spacings are listed in Table 9. Transfer length ap­pears to decrease and level out with an increase in strand spacing in speci­mens that cracked. For specimens listed in Table 8, strand spacing is not constant; for those listed in Table 9, concrete cover is not constant.

As shown in Fig. 5, the smallest con­crete cover in multi-strand specimens which resulted in no cracking in some specimens was 2.0 in. (50.8 mrn). ·At a cover of 2.0 in. (50.8 mm), eight of the 12 specimen ends cracked, while at a cover of 2.25 in. (57.2 mrn), only three of 16 specimen ends cracked. As cover was increased, cracking significantly decreased . Both of these covers are larger than the minimum cover re­quired by AASHTO 9.25.1.1.6

The smallest center-to-center strand spacing of 2.5 in . (63.5 mm) that caused no cracking is larger than the minimum 2.0 in. (50.8 mm) specified by AASHTO 9.25.2.1. 6 At strand spacings of 2.5, 2.75 and 3 in. (63.5, 69.9 and 76.2 mrn), approximately 58, 33 and 40 percent of the specimen ends cracked, respectively . Also, for groups of specimens with the same cover and increased strand spacings, there were no discernable improve­ments in crack prevention.

Calculated vs. Measured End Slips

End slip is the distance an individ­ual strand slips into the concrete after

82

transfer of prestress. End slip of each strand was determined by taking mea­surements before and after transfer. The difference of these measurements constituted the end slip.

End slip measurements were taken immediately following transfer, and at seven and 28 days after transfer. Some end slip brackets were not installed or were damaged during specimen fabri­cation; thus, no data were obtained at those locations. A complete listing of the end slip data is available in the project final report.5

The end slip of each strand can be calculated based on the concrete and stee l strain data within the transfer length of each specimen.3 The calcu­lated end slip can then be compared to the measured end slip to verify the cal­culations. Fig. 6 shows an idealized plot of steel strain immediately after transfer (€5 ) and concrete strain due to

Note that dEc is the estimated strain loss and is assumed to be the value of the concrete strain plateau at this time. The shape of the steel strain plot within the transfer length and in the strain plateau region is assumed to be a straight line. The relationship is pro­portionally the same as the concrete strain plot due to equilibrium of forces through any beam section . It is as­sumed that a perfect bond exists be­tween the concrete and steel within the strain plateau.

This assumption results in a steel strain plot approximately 10 times greater than the concrete strain plot but of the same shape. The elastic shortening (EI. Sh.) over the transfer length (T.L.) of a specimen is the area under Ec(x):

f T.L. El. Sh. = Jo Ec(x)d.x (3)

The area between the E5 (x) curve and the initial steel strain plateau, EPP'

Epp--r-------------------------;---­

Ese

c:

' c:

.: 0 ... ii)

Transfer

Distance From Member End {in.) Length

Fig. 6. Idealized plot of steel and concrete strain.

PCI JOURNAL

Page 8: Spacing and Concrete Cover Requirements for Epoxy Coated

within the transfer length of the beam is the sum of the elastic shortening and the end slip (E.S.) :

E.S. + El. Sh.= ePP(T.L.) -

r ·\ s(x)dx (4)

By rearranging Eq. (4), the end slip (E.S.) can be determined:

E. S. = e PP (T. L.)-

foT .L.[es(x)+ec(x)]dx (5)

The average slip was calculated for each specimen end from the measured transfer length. Average ratios of mea­sured to calculated end slips are given in Table 9.

From the data provided in Table 10, it is clear that the measured transfer lengths are in good agreement with the calculated values since the average ratio of the measured end slips to cal­culated end slips is 0.98. This gives a standard deviation of 0.29, which can be expected as the variables of con­crete strength, strand surface condition and effective stress can affect these calculations.

Cracking of Specimens

When cracking occurred at prestress transfer, the transfer lengths increased because the bond between the concrete and strand was weakened within the cracked area. Cracked beams devel­oped either spacing cracks or both spacing and cover cracks. Spacing cracks were defined as cracks occur­ring between strands while cover cracks were those which propagated from the strands to the outside edge of the specimen as shown in Fig. 7.

Cracking began at the specimen end and cover cracks sometimes ex­tended along the beam as much as 4.5 ft (1.4 m). The occurrence of cover cracks in specimens using epoxy-coated strands has been previously observed by Cousins,3 and Dorsten, Hunt and Preston.'

Cracking occurred in 31 coated strand specimen ends, with 27 of these being three-strand ends. Of the cracked specimens using three strands, all but a single specimen (one end of Specimen 11 had spacing cracks) ex­perienced cover and spacing cracks.

September-October 1993

Table 10. Average ratio of measured to calculated end slips.

Average Measured (M) to Calculated (C) end slips measured

Strand end slip type (in.) RatioofM/C No. of samples Standard deviation

Coated 0.11 1.0 47 0.29

Note: I in . = 25.4 mm.

Spacing Cover

cj~?g F==;t Crack Length

Fig. 7. Definition of cover and spacing cracks.

No specimen with six strands experi­enced cracking. As expected, cracking increased the transfer length of speci­mens with coated strand (see Table 6).

It appears that the addition of a layer from the three- to six-strand arrange­ment reduces the possibility of crack­ing and thus improves the prestress transfer characteristics. A comparison of specimens with three and six strands is provided in Table 11. Six­strand epoxy-coated specimens with spacings and covers identical to those with three strands did not crack while their three-strand counterparts did . This improvement may be due to con­finement provided by the addition of another layer of coating.

Two single, uncoated strand speci­mens had concrete spall off the end adjacent to flame cutting at transfer. It is believed that the spalling ends re­sulted from flame cutting too close to the beam ends and not from lack of concrete cover. No specimen with un-

coated strands experienced spacing and cover cracking. Therefore, as ex­pected, the cover and spacing required by AASHTO was sufficient for speci­mens with uncoated strand.

Of the specimens which developed cracks, most experienced cover cracks in line with the strand layer on the faces containing gauge points (Fig. 7). From these observations , there was some concern that the gauge points may have induced crack propagation by weakening this area of the beam. However, this concern was unwar­ranted because thorough consolidation was obtained and the gauge points were of very small volume. Also , specimens with uncoated strands did not experience this type of cracking.

It appeared that cover cracks in some specimens with three-coated strands were an extension of horizon­tal spacing cracks. Few specimens that cracked experienced spacing cracks in combination with cover cracks extend-

Table 11. Comparison of three strand and six strand specimens.

Strand Concrete Number of three- Number of six-

spacing cover strand specimens ends strand specimens ends

(in.) (in.) Cracked Uncracked Cracked Uncracked

2.5 2.0 3 I 0 2 2.75 2.0 3 I 0 2 2.75 2.25 I I 0 4 3.0 2.25 2 2 0 4

Note: I m. = 25.4 mm.

83

Page 9: Spacing and Concrete Cover Requirements for Epoxy Coated

ing only to the top and bottom of the cross section. Thus, insufficient spac­ing may develop spacing cracks , which in turn propagate outward to form a cover crack.

This type of crack can be seen in Fig. 7. Cracking typically occurred so quickly that it was difficult to deter­mine where a crack originated, what caused it and what influence other cracks might have had.

CONCLUSIONS AND RECOMMENDATIONS

The following conclusions are bas­ed on the results of this experimental program:

1. Grit impregnated epoxy-coated strand causes spacing and cover cracks at prestress transfer in the transfer zone in multi-strand speci­mens at spacings and covers less than those recommended by the AASHTO Specifications.

2. The cracked specimens using coated strands resulted in transfer lengths about 50 percent greater than those measured in specimens that did not crack.

3. A second layer of epoxy-coated strand improves prestress transfer characteristics and diminishes the like­lihood of concrete cracking.

84

4. The AASHTO equation for trans­fer length overestimates the measured transfer length for coated strand speci­mens that did not crack.

5. The AASHTO requirements for concrete cover and strand spacing are unconservative for the epoxy-coated strand specimens to transfer the pre­stressing force without cracking. Spac­ing and cover requirements should be increased somewhat in pretensioned, prestressed concrete members with no confinement. However, for bridge girders and other pretensioned, pre­stressed concrete members that typi­cally have a significant amount of confinement reinforcement in the form of stirrups and end zone reinforce­ment , increased strand spacing and concrete cover may not be necessary.

ACKNOWLEDGMENT The research reported in this paper

was conducted at Auburn University with the support of the Louisiana Transportation Research Center, the Federal Highway Administration and the Auburn University Highway Re­search Center.

The contents of this paper reflect the views of the authors, who are respon­sible for the facts and accuracy of the data presented. The contents do not

necessarily reflect the official views or policies of the supporting agencies. This paper dQes not constitute a stan­dard, specification or regulation.

REFERENCES I. "Guide Specification for Corrosion

Resistant Prestressing Strand," Florida Wire and Cable Company, Jackson­ville, FL, November 16, 1983.

2. PCI Ad Hoc Committee on Epoxy­Coated Strand, "Guidelines for the Use of Epoxy-Coated Strand," PCI JOUR­NAL, V. 38, No. 4, July-August 1993, pp. 26-32.

3. Cousins, T. E. , "Bond of Epoxy Coated Prestressing Strand," Ph.D. Disserta­tion, North Carolina State University, Raleigh, NC, December 1986.

4. Dorsten, V., Hunt, F., and Preston, H. , "Epoxy Coated Seven-Wire Strand for Prestressed Concrete," PCI JOUR­NAL, V. 29, No. 4, July-August 1984, pp. 120-129.

5. Francis, L. , and Cousins, T., "Spacing and Cover Requirements for Epoxy Coated Prestressing Strand in Uncon­fined Sections," Final Report, Depart­ment of Civil Engineering, Auburn Uni­versity, Auburn, AL, August 24, 1992.

6. AASHTO, Standard Specifications for Highway Bridges, 14th Edition, Amer­ican Association of State Highway and Transportation Officials, Washington, D.C., 1989.