HC900-R700.1 Release R700.1 Software Change Notice 1
HC900-R700.1 R700.1
Software Change Notice
Revision Date: July 30, 2020 Document ID: Software Change Notice
HC900-R700.1 Release R700.1 Software Change Notice 2
Notices and Trademarks
© Honeywell International Inc. 2019. All Rights Reserved.
While this information is presented in good faith and believed to be accurate, Honeywell disclaims the
implied warranties of merchantability and fitness for a particular purpose and makes no express
warranties except as may be stated in its written agreement with and for its customer.
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The
information and specifications in this document are subject to change without notice.
Other brand or product names are trademarks of their respective owners.
Honeywell International
Process Solutions
1860 West Rose Garden Lane
Phoenix, AZ, 85027, USA
+1 800-822-7673
www.honeywell.com/ps
http://www.honeywell.com/ps
HC900-R700.1 Release R700.1 Software Change Notice 3
Symbol Definitions
The following table lists those symbols used in this document to denote certain conditions.
Symbol Definition
ATTENTION: Identifies information that requires special consideration.
TIP: Identifies advice or hints for the user, often in terms of performing a task.
REFERENCE -EXTERNAL: Identifies an additional source of information outside of the bookset.
REFERENCE - INTERNAL: Identifies an additional source of information within the bookset.
CAUTION
Indicates a situation which, if not avoided, may result in equipment or work (data) on the system being damaged or lost, or may result in the inability to properly operate the process.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual.
WARNING: Indicates a potentially hazardous situation, which, if not avoided, could result in serious injury or death.
WARNING symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to
required information in the manual.
WARNING, Risk of electrical shock: Potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms, 42.4 Vpeak, or 60 VDC may be accessible.
ESD HAZARD: Danger of an electro-static discharge to which equipment may be sensitive. Observe precautions for handling electrostatic sensitive devices.
Protective Earth (PE) terminal: Provided for connection of the protective earth (green or green/yellow) supply system conductor.
HC900-R700.1 Release R700.1 Software Change Notice 4
Symbol Definition
Functional earth terminal: Used for non-safety purposes such as noise immunity improvement. NOTE: This connection shall be bonded to Protective Earth at the source of supply in accordance with national local electrical code requirements.
Earth Ground: Functional earth connection. NOTE: This connection shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code
requirements.
Chassis Ground: Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements.
HC900-R700.1 Release R700.1 Software Change Notice 5
Revision History
Revision Version Number Description Date
1 R700.0 Updated for SIL2 UIO module level redundancy
Dec 13, 2019
2 R700.1 Updated for HCD update for fixing PAR
Jul 1, 2020
3 R700.1 Updated for Controller FW patch release
Jul 30, 2020
HC900-R700.1 Release R700.1 Software Change Notice 6
Contents
1 Introduction ........................................................................................................................ 7
1.1 About this Document ..................................................................................................................... 7 1.2 Limitations ...................................................................................................................................... 7 1.3 Technical Assistance ..................................................................................................................... 7
2 Contents of Release ........................................................................................................... 8
3 Getting Started ................................................................................................................... 9
4 Release Overview............................................................................................................. 10
4.1 New Features .............................................................................................................................. 10 4.2 Changes to Existing Functionality ............................................................................................... 10 4.3 Retired Feature ............................................................................................................................ 10
5 Prior-Releases Overview ................................................................................................. 10
5.1 HC900- R700 ............................................................................................................................... 10
6 Software/Hardware/Firmware Compatibility ................................................................... 11
7 Documentation Updates/Additional Information ........................................................... 11
8 Problems Resolved .......................................................................................................... 12
8.1 Problems Resolved in R700.1 ..................................................................................................... 12 8.2 Problems Resolved in R700 ........................................................................................................ 12
9 Installation and Migration ................................................................................................ 14
9.1 Prerequisites ................................................................................................................................ 14 9.2 Migration Considerations ............................................................................................................. 14 9.3 Installation Instructions ................................................................................................................ 15 9.4 Migration Instructions ................................................................................................................... 15 9.5 Retry in case of failure ................................................................................................................. 16 9.6 Post installation Instructions ........................................................................................................ 16
10 Un-Install Instructions ..................................................................................................... 16
11 Known Issues ................................................................................................................... 16
12 Security-Related Issues ................................................................................................... 16
13 Special Considerations.................................................................................................... 17
14 Third-Party Software Components ................................................................................. 17
14.1 External Certified Software Components .................................................................................... 17
15 Appendix .......................................................................................................................... 17
HC900-R700.1 Release R700.1 Software Change Notice 7
1 Introduction
1.1 About this Document
This Software Change Notice (SCN) contains information for all the users of HC900 and must be read prior to usage of HC900 Controller and HCD software. This document describes the new features and enhancements introduced with the HC900 releases. Additionally it contains issues, special considerations and last minute documentation updates.
1.2 Limitations
NA
1.3 Technical Assistance
For support, contact your local Honeywell Process Solutions Customer Contact Center (CCC). To find your local CCC visit the website, https://www.honeywellprocess.com/en-US/contact-us/customer-support-contacts/Pages/default.aspx
https://www.honeywellprocess.com/en-US/contact-us/customer-support-contacts/Pages/default.aspxhttps://www.honeywellprocess.com/en-US/contact-us/customer-support-contacts/Pages/default.aspx
HC900-R700.1 Release R700.1 Software Change Notice 8
2 Contents of Release
Table 1 HC900-R700
Product Model Number
S50 Non-SIL Scanner1 Firmware 50008139-011
S75 Non-SIL Scanner2 Firmware 50008139-012
C30 Non-SIL Controller Firmware 50008139-013
C50 Non-SIL Controller Firmware 50008139-014
C70 Non-SIL Controller Firmware 50008139-015
C75 Non-SIL Controller Firmware 50008139-016
S50 SIL Scanner1 Firmware 50008139-021
S75 SIL Scanner2 Firmware 50008139-022
C30 SIL Controller Firmware 50008139-023
C50 SIL Controller Firmware 50008139-024
C70 SIL Controller Firmware 50008139-025
C75 SIL Controller Firmware 50008139-026
Hybrid Controller Designer Software 51452053
Process Control Utilities Software 51452054
Station Designer Software 50038294-001
Process Control Documentation 51452052-003
HC historian
HC900-R700.1 Release R700.1 Software Change Notice 9
3 Getting Started
3.1.1 Prerequisites
Designer version 7.000 onwards must be installed on PC with Win7 or Win10 operating
system.
3.1.2 Firmware installation or migration checklist
Task order Task Reference
1 Prerequisites See sections Getting Started, Extract
files to be downloaded and Program
Mode part of Read Me document.
2 Applicable modules See section Application modules
3 Installing the Firmware version See section Download procedure part
of Read Me document
3.1.3 Verify the present version on the Controller module
To verify the present version on the module, perform the following steps:
1. Connect HCD to Controller Module.
2. Select Network Device List from the View Menu.
3. Select Honeywell HC900 Controller from the List and then Click OK.
4. Click Monitor Mode from the Toolbar or select it from the Monitor Menu.
5. In the Enter Monitor Mode dialog click OK after selecting the default IP address of
the controller 192.168.1.254 (default IP).
6. Click Controller Diagnostics from the Toolbar or select it from the Monitor
Menu.
For Redundant (C75):
From the Monitor menu: Monitor -> Redundancy -> Lead CPU
Monitor -> Redundancy -> Reserve CPU
7. Code Revision value from Controller Diagnostics window will give the firmware
version of the module.
3.1.4 Copying and extracting the Firmware version
Refer Extract files to be downloaded and Download procedure in Read me document.
Note: Contact TAC for updating the Firmware of CPU(s) and I/O Scanner(s) from 6.001 to 6.005 versions.
HC900-R700.1 Release R700.1 Software Change Notice 10
4 Release Overview The release is intended to address the following issues in the HCD software. Only HCD software and
Controller FW are updated with this release, no other FW has been modified
PAR # RHC900-1361 - In HCD 6.701, while opening older SPP Recipe it changes Segment Time 00:01
to 00:00 and does not operate as expected.
RHC900-6173: Ripple 20 patch code changes for fixing issues in TCP/IP stack of Controller FW
4.1 New Features
No new features added
4.2 Changes to Existing Functionality
HCD software got updated to address the issue mentioned above.
4.3 Retired Feature
None
5 Prior-Releases Overview
5.1 HC900- R700
5.1.1 New Features
The release contains the followings features which are implemented in the HCD and firmware are listed below:
HCD
• Redundant UIO Functions Blocks o Analog Input o Analog Output o Digital Input o Digital Output
• Repair IO
HC900-R700.1 Release R700.1 Software Change Notice 11
Firmware
• UIO
• Redundant Controller and Scanner
Control station
• Redundant UIO Function Block
5.1.2 Changes to Existing Functionality
The release contains the followings features which are implemented in the HCD and firmware are listed below:
HCD NA
Firmware NA
Control station:
NA
5.1.3 Retired Features
NA
6 Software/Hardware/Firmware Compatibility The current HC Designer software release also supports earlier firmware version rev ≥ 1.x.
7 Documentation Updates/Additional Information Document Number
Current Rev & date Document Name
Document Type
51-52-25-109 Rev.26_Nov 19 Function Block Reference Guide Manual
51-52-25-110 Rev.25_ Nov 19 Hybrid Control Designer User Guide Manual
51-52-25-111 Rev.16_ Nov 19 Hybrid Controller Communications User Guide Manual
51-52-25-133 Rev.11_ Nov 19 HC900 Controller Redundancy Overview & System Operation Manual
HC900-R700.1 Release R700.1 Software Change Notice 12
51-52-25-148 Rev.15_ Nov 19 900 Control Station -For use with HC900 Hybrid Controller - User Guide Manual
51-52-25-154 Rev.11_ Nov 19 Installation Manual
Version 7.0 Nov 19 HC Designer and HC Utilities HELP file Help file
51-52-03-31 Nov 19 HC900 Controller Specification
8 Problems Resolved
8.1 Problems Resolved in R700.1
Following issues have been addressed in this release
PAR No Description
RHC900-1361 In HCD 6.701, while opening older SPP Recipe it changes Segment Time 00:01 to 00:00 and does not operate as expected
RHC900-6173: Ripple 20 patch code changes for fixing issues in TCP/IP stack in Controller FW.
8.2 Problems Resolved in R700
This download fixes the following problems:
HC900-R700.1 Release R700.1 Software Change Notice 13
1-7HUCYFL worksheet addition and text addition does not work in attached configuration
1-A1MS1PJ Modbus TCP from Safety Manager: miss-reading extra coil reply as correct data
1-71342LX Update SQL Server capabilities and add to Station Designer Manual
RHC900-907 Led blinks green in reserve controller, when The Real-time Clock (RTC) is not programmed in Redundant controller.
RHC900-393 Cycle time mismatch with HCD(HCD_6.300Z)
RHC900-813 P&C HCD: "Unforce Selected Item" option does not get enabled for a selected tag from Forced Blocks Window from Controller version 6.005
RHC900-385 If *alarm subject * is not configured Email Notification in HCD, Emails are receiving *Email address 1 * as default subject for all three email address.
RHC900-576 R650_UIO Field Current value is wrong in IMM Block.
RHC900-789 Bad channel count in IMM block toggles if bad channel already present in the module
RHC900-1307 Channel status reports “Bad Channel” in the rack diagnostics even after enabling disable pin of analog input function block.
RHC900-1282 When NaN value is passed through CPU to I/O scanner, results in loss of communication.
RHC900-1118 (1-77W0IVG)
Multiple I/O Signal Tags cause difference from display to printout.
RHC900-1351 UIO AO fail safe use value shows 0 instead of 2.4.
RHC900-943 In ASYS function block TimeOff pin does not work after warm Start (Power cycle
with battery)
RHC900-1249 Rack Diagnostics reporting IO module error and Missing/NO comm for unused slots
RHC900-963 Totalizer (TOT function block) does not update after input rate change then hot
start
RHC900-1147 Drastic Cycle Time increase when migrated from rev: ≤ 4.x to ≥ 6.x when including
complex blocks (ex: Free Form Boolean (BOOL) Logic)
RHC900-1146 Periodic Timer (PTMR) not working for 1 Second Pulse with program < 500 mS
RHC900-941 Trendbackfill buffer size increase
RHC900-942 FB category collapses in HCD library
RHC900-727 R650_C70S UIO Blocks/Rack Diagnostics Status is wrong after UIO Module Firmware
Update
HC900-R700.1 Release R700.1 Software Change Notice 14
9 Installation and Migration
9.1 Prerequisites
Before you begin the download, there are a few things you need to be aware of:
1. PRIOR TO STARTING THE UPGRADE, THE PROCESS MUST BE TAKEN OFF-LINE.
The code download procedure requires that the controller be put into the Program mode. In this mode, all outputs are forced to their off state.
2. Code Download can take from approximately 5 minutes using Ethernet.
Therefore, it is highly recommended that you do not start the code download procedure at a time when the likelihood of power failure is increased, such as during thunderstorms.
3. The code download function is only available through the Utilities tab of the Hybrid Control Designer program or the Hybrid Control Utilities program. The upgrade is available only via the controller Ethernet port.
4. The controller will not allow the controller firmware download to begin if there is a low battery diagnostic for both Front and Rear.
5. Code download will destroy the configuration database in the controller. Therefore, before code download is started, you must upload it into the Hybrid Control Designer and save it. Save As a 900 model 6.60x file.
6. The upgrade files are distributed as a complete package and must reside in a unique subdirectory separate from any other previously distributed firmware upgrade files. Failure to comply could result in abnormal behavior when performing the upgrade.
7. Program Mode:
Before starting the Controller Firmware Download, make sure the controller is in the "Program Lock" mode.
To enter "Program Lock" mode, turn the Mode Switch counter-clockwise to the position labeled "Pgm".
NOTE: During Firmware download, HCD UI status update may hang but download will still continue to happen in background. Please do not kill HC application during this stage.
9.2 Migration Considerations
NA
HC900-R700.1 Release R700.1 Software Change Notice 15
9.3 Installation Instructions
NA
9.4 Migration Instructions
Step 1: Backup the controller configuration as described in step 4 of GETTING
STARTED above.
Step 2: Make sure the controller is in "Program Lock" or "Program" mode.
Step 3: Select the Utilities Worksheet tab on the HC Designer or Utilities.
Step 4: From the "Controller Utility Functions" select "Download to Controller". On the sub-menu, select "Controller Firmware", then "Controller Module".
Step 5: Use the "Look in:" drop down list in the "Open" dialog box to select the drive and folder you placed the files in.
Step 6: Select and open the CPU file for you particular HC900 controller model displayed in the file list box.
Step 7: Select the "Port" as Network and "Address" on the "Download File" dialog box.
Step 8: Click on the "Start" button in the "Download File" dialog box. The download will start, and progress is displayed. The download itself will take several minutes, depending on the Port type and connection speed.
Step 9: A "Code download complete. The controller will now reset" status will be displayed in the "Download File" dialog box. If a failure is detected, an error message will appear in the Status section of the "Download File" dialog box. See "Error Messages" for a list of possible messages and resolutions. Also, see “Failure Modes”.
Step 10: Restore the configuration (.CDE file) from the backup copy you previously made.
Step 11: Return the mode switch to "Run" or "Run Lock" if "Program Lock" was used to do the upgrade.
Note: In case of downgrade from 6.6x to older versions, user need to use new loader.s19 file (copy the new loader.s19 file from 6.6x to required Firmware folder).
HC900-R700.1 Release R700.1 Software Change Notice 16
9.5 Retry in case of failure
If there is a download failure indication on the "Download File" dialog box:
• DO the controller power cycle and DO NOT remove the battery
• Check the physical connections.
• Check for power failures.
• Check if you are loading firmware file corresponding to physical module type.
9.6 Post installation Instructions
NA
10 Un-Install Instructions NA
11 Known Issues
Based on information and data available to us to date, this section describes some currently identified issues related to this release.
1-778ZL99 V4.4, C70R controller does not synchronize the email server IP address
1-A6GN957 Sequencer (SEQ) when in Hold still proceeds to next step with Active Event Signal
RHC900-399 Loosing RTC when S1(Non SIL) Scanner is a) downgraded from 6.3 to 6.004 also b) Upgraded from 6.004 to 6.3
RHC900-1407 Both RUIO DO channels show Relinquish fail when scanner cables are disconnected
RHC900-1343 Forced status showing beside output value but output is showing fail safe value
RHC900-1358 Readback Current on the RUIO AO block is showing 30mA momentarily when one of the Rack Powered Off
RHC900-1369 In alarm group -> Alarm details -> Line 2 text missing while migrating from HCDv6.6 to v7.0 Build W
Note: 1-A6NXOJL corrected in 900CS: Station Designer rev: 1.2.6700 (R4 Build 467).
12 Security-Related Issues
User will be required to maintain/remember all passwords. Honeywell will no longer be able to over-ride user passwords.
HC900-R700.1 Release R700.1 Software Change Notice 17
13 Special Considerations NA
14 Third-Party Software Components
14.1 External Certified Software Components
These third party software applications are supported on nodes running this software release.
WARNING
Note that the user assumes all responsibility for issues resulting from the installation and operation of any components that have not been tested as compatible by Honeywell. In addition, it is the customer’s responsibility to ensure that the combinations of third party components have sufficient resources (e.g. memory, CPU performance, disk space, display space, etc.).
15 Appendix NA