Upload
others
View
65
Download
1
Embed Size (px)
Citation preview
Sidel Combi-CombiTherm & CO2 Counter
Installation Guide
Introduction
Thank you for purchasing the Sidel Combi-Combi Therm & CO2 Counter. The
Combi-Combi Therm & CO2 Counter control panel should be installed only by
a qualified electrician, and follow local electrical codes according to the NEC
requirements. This document describes the steps for installing the Sidel Combi-
Combi Therm & CO2 Counter control panel.
For information on programming or to learn how to set up the Sidel Combi-Combi
Therm & CO2 Counter, please refer to the the Sidel Combi-Combi Therm &
CO2 Counter Operation Manual.
Inspecting the unit
Carefully inspect the unit for damage that may have occured during transport.
Verify that the list of materials on the packing slip matches the items in the
container. The Sidel Combi-Combi Therm & CO2 Counter control panel and
accessories were inspected and tested before shipment. Examine the equipment
carefully. If any shipping damage is evident in the unlikely event of material
shortage, notify Sidel Systems immediately.
Warranty
Sidel Systems warrants each Sidel Therm & CO2 Counter controller to be free from
electrical and mechanical defects in materials and workmanship for a period of
one year from the date of shipment.
Sidel Systems Combi-Combi Installation Manual • Page 1
Installation of the Panel
The Sidel Combi-Combi Therm & CO2 Counter panel installation work shall be
performed in strict observance of the procedures and rules described in this
manual.
Pay careful attention to the placement of the Therm & CO2 Counter and associated
sensor cable routing. This can significantly influence the performance and integrity
of the control panel, especially the reading of the temperatures. The maximum
distance of any sensor to the control panel should not exceed 50 ft.
The Therm & CO2 Counter panel should be mounted flush on a flat surface and
should be supported by 5/16” anchor bolts or similar bolts.
The Therm & CO2 Counter is rated for NEMA 4 installations. This means that
when the Combi-Combi Therm & CO2 Counter is properly closed, the panel will be
protected from wind-blown dust and rain.
Power connection
The panel is designed to withstand electrical noise in harsh industrial
environments. It will also conform to requirements that limit electrical emissions.
However, this does not guarantee that the product will be totally immune
from possible malfunction in those cases where severe electrical noise occurs.
Therefore, we strongly recommend that you follow the guidelines outlined in this
guide for proper wire routing and grounding to insure the proper operation of the
control panel.
The control panel must be connected to a good, high-integrity earth ground
both for safety considerations and shielding purposes. Sidel Systems cannot
overemphasize the importance of good grounding. If you fail to use good
grounding procedures during installation, sporadic malfunction of the Therm
& CO2 Counter may occur. Connect the Combi-Combi Therm & CO2 Counter’s
Page 2 • Sidel Systems Combi-Combi Installation Manual
chassis ground terminal to a reliable earth ground with a low-resistance path.
The supply power and ground wire size shall be between a #14 and #12 AWG
(THHN or equivalent). To prevent undesirable interference these wires should be
placed in a separate conduit away from the signal cables. The 120 volt power line
shall be connected to at least a 10 Amp circuit breaker. The colors are: line (black
wire), neutral (white wire) and ground (green wire).
Figure 1: power connection
Connect the line wire to terminal “L”, the neutral to terminal “N”, and the ground
wire to the green and yellow terminal as show at figure 1.
Sidel Systems Combi-Combi Installation Manual • Page 3
Thermocouple sensors installation
There are eight thermocouples to be installed. The six thermocouples with 2”
sensor tips need to be installed on the inlets and outlets of the water connections
and the two thermocouples with the 12” sensor tips need to be installed in the
inlet and outlet of the exhaust air. The threads of the water temperature sensors
should be wrapped with Teflon tape to ensure that they will be free from any
leaking. Once the sensors are properly installed, connect the thermocouple wires
accordingly, and make sure that each wire is connected to the right terminal as
shown in figure 2. The terminal for the red thermocouple wire is painted red and
the terminal for the white thermocouple wire is not painted. In order to ensure
proper connection, make a loop at the end of the wire so that the wire will make a
complete ring around the connecting screw.
Figure 2: Connection of thermocouple: 1) Make a loop on each wire.
2) Red wire to red painted terminal. White to the unpainted terminal.
3) Secure wires to terminals.
Every sensor and thermocouple wire installed should be marked with its
correspondent designation (i.e. lower section inlet water, lower section outlet
water, etc...) to insure that each sensor is properly connected to its respective
terminal at the Therm & CO2 Counter. The thermocouple wires must be routed
inside a separate conduit from the Sidel SRU Flue Gas Condenser unit to the Therm
Page 4 • Sidel Systems Combi-Combi Installation Manual
& CO2 Counter to minimize electrical noise. At the Sidel Combi-Combi Therm &
CO2 Counter panel connect each sensor wire as shown on figure 3.
Figure 4: Output connections
Output signal connections
All outputs are connected to a 120 VAC circuit. The common connection for these
terminals is number 100. The connection for the solenoid valve to close the
Figure 3: Thermocouple wire connections
Sidel Systems Combi-Combi Installation Manual • Page 5
Figure 5: Input connections
chimney valve is terminal number 51. The terminal connection for the solenoid
valve to open the chimney valve is terminal number 52.
The Sidel Combi-Combi Therm & CO2 Counter can be equipped with additional
outputs at a customer request. These outputs can be used to activate an external
device or alarm signal.
Input signal connections
All sensor input signals in the Therm & CO2 Counter panel are low voltage
(24VDC) to the PLC internal circuit. The common connection for these input
circuits is terminal 24.
Safety Precautions
Please observe the following precautions when installing the Sidel Combi-Combi
Therm & CO2 Counter. Failure to comply with these restrictions could result in loss
of life, serious personal injury, or equipment damage. Do not install or operate the unit in areas subject to explosion due to flammable gases or vapors.