    Short Circuit Selective Coordination for Low Voltage CircuitBreakersRetain for future use.

    INTRODUCTION The purpose of this data bulletin is to present short circuit selectivecoordination data for various combinations of Square D low voltage circuitbreakers.The scope of this data bulletin encompasses only breaker-to-breakershort circuit selective coordination. Coordination between circuit breakers inthe overload region of their time-current curves, coordination with fuses andthe protection of motors, transformers and other devices, as well ascoordinated ground fault protection, is not dicussed. Conventional selectivecoordination studies using time-current curves are still required to addressthese issues. See the REFERENCE section, on page 5 , for other databulletins on this subject.

    This data bulletin is a companion to Enhancing Short Circuit SelectiveCoordination with Low Voltage Circuit Breakers , document number0100DB0403.

    Appendix Guide

    SELECTIVE COORDINATIONDATA

    System designers are accustomed to determining the level of short circuitselective coordination between combinations of low voltage circuit breakersusing trip curves. But using trip curves alone sometimes leads to thedetermination of a selective coordination level that is lower than can actuallybe achieved.

    How Trip Curves Are Developed Circuit breaker trip curves are typically developed by conducting interruptiontests at various levels of overload and short circuit current. The timenecessary for the circuit breaker to completely interrupt the current flow isthen measured. In the instantaneous region of the trip curve, it is oftenassumed that the fault clearing time is constant, hence the curve is usually astraight line in that region.

    Current Limiting Circuit Breakers Many modern circuit breakers are designed with blow-open contacts and /or other features to quickly clear high fault currents, resulting in clearingtimes that decrease as the current increases, unlike what the conservativelydrawn trip curves may indicate. Even circuit breakers not UL listed orCSA certified as current limiting may exhibit current limiting characteristics.

    Dynamic Characteristics of CircuitBreakers

    All circuit breakers, when they begin to open, serve to limit the prospectiveflow of current, even if they are not listed or certified as current limiting. Thisis an important factor to consider when two circuit breakers are connected in

    Appendix A: Levels of Short Circuit Selective Coordinationfor UL 489 Standard Circuit Breakers

    Page 6

    Appendix B: Levels of Short Circuit Selective Coordinationfor UL 489 LA/LH Mission Critical CircuitBreakers

    Page 38

    Appendix C: Levels of Short Circuit Selective Coordinationfor ANSI Low-voltage Power Circuit Breakers

    Page 41

    Appendix D: A glossary of terms used in this data bulletin. Page 49

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    2/52

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    3/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 3

    electronic trip circuit breakers that have an OFF position on theinstantaneous switch are also equipped with a short time pick-up and delayfunction, and may also be equipped with an instantaneous selectiveoverride function if necessary for the proper functioning of the circuitbreaker.The adjustment of trip settings does not affect any series rating that may be

    employed as UL

    and CSA

    require series ratings tests to be conductedwith the instantaneous trip adjustment set to its highest position.

    HOW TO USE THE TABLES In order to use the data presented here, some basic information is needed.

    System One-line Diagram A one-line diagram of the system to be studied is absolutely necessary inorder to determine the level of system coordination.

    System Voltage While the system voltage, in and of itself, has no impact on selectivecoordination, it does impact circuit breaker selection, which in turn impactscoordination; thus the system voltage needs to be known.

    Circuit Ampacity The instantaneous trip characteristics of a circuit breaker may be a function

    of the frame or current sensor rating rather than the current rating of thecircuit breaker. However, the current rating required to meet the ampacity ofthe circuit drives the circuit breaker selection, thus it needs to be known.(See NEC Articles 210, 215, 220, 225 and 230.)

    Available Short Circuit Current The available short circuit current at each point in the system should bedetermined in order to select circuit breakers with the proper interruptingrating and in turn to determine the level of selective coordination.

    Determining Levels of SelectiveCoordination

    Based on this information, determine the level of selective coordinationbetween pairs of circuit breakers in the system by finding them in the tablespresented in APPENDIX A on page 6 , APPENDIX B on page 38 andAPPENDIX C on page 41 . The intersection of the upstream anddownstream circuit breakers in the tables lists the level of selectivecoordination between that pair of circuit breakers.

    Example Let's consider a 480Y / 277 Vac system with 35 kA available short circuitcurrent. Assume that the system consists of an NF 250 A main lugs lightingpanelboard with single pole EG 35 kAIR rated circuit breakers fed from aJGA36250 circuit breaker with a 35 kA interrupting rating located in anI-Line power panelboard. Determine the level of selective coordinationbetween the upstream JGA circuit breaker and downstream EG circuitbreakers by following these steps.

    1. Find the 480 Vac table listing EG downstream circuit breakers inAPPENDIX A , Table 6: on page 20 .

    2. Find the column for the EG downstream circuit breaker to be studied.3. Go down the column until the row listing the 250 A JG upstream circuit

    breaker is found.4. Read the selective coordination level at the intersection of the column

    and row, namely 2.4 kA. This means that the JG upstream circuitbreaker is selectively coordinated with downstream EG circuit breakersup to 2,400 amps.

    OPTIMIZING THE SELECTIVECOORDINATION LEVEL

    The selective coordination of a circuit breaker based low voltage system canbe optimized using the techniques presented in the Enhancing ShortCircuit Selective Coordination with Low Voltage Circuit Breakers data

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    4/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved4

    bulletin and the data presented in APPENDIX A on page 6 , andAPPENDIX C on page 41 . The following is a brief summary of thetechniques more fully presented in the Enhancing Short Circuit SelectiveCoordination with Low Voltage Circuit Breakers data bulletin.

    Conduct A Short Circuit Study Conducting a short circuit study may reveal that lower interrupting rated

    downstream circuit breakers can be selected, possibly resulting in higherwithstand ratings.

    Increase Frame Size By increasing the frame size of the upstream circuit breaker, it may bepossible to increase the selective coordination at that level in the system.

    Change Circuit Breaker Type By changing the upstream circuit breaker from a molded case to aninsulated case circuit breaker, it may be possible to increase the selectivecoordination at that level in the system.

    Using the Tables If the level of selective coordination between the two circuit breakers initiallyselected is not sufficient for the application, the tables may be used to findan alternate upstream circuit breaker selection that will yield a higher levelof selective coordination. This may involve a larger frame size or different

    type of circuit breaker, as mentioned above. This may be done by goingdown the tables to find possible upstream breakers that may deliver ahigher level of selective coordination.

    Example Using the same example previously stated under Determining Levels ofSelective Coordination , determine if a higher level of selectivecoordination can be achieved by following these steps:

    1. Move down the column for the EG downstream circuit breaker to bestudied, looking for upstream breakers that will yield a higher level ofselective coordination.

    2. When the desired level of selective coordination is found, read acrossthe row to find the upstream breaker that will yield this level. In this case,a PG circuit breaker will yield a level of selective coordination of 35,000

    amps. This means that the upstream PG circuit breaker is fully selectivewith downstream EG circuit breakers.

    CONCLUSION The actual level of selective coordination between pairs of Square D lowvoltage circuit breakers needs to be considered when designing aselectively coordinated low voltage electrical system. This may be done byfinding the pair of circuit breakers in the tables presented in this data bulletinand reading the actual level of selective coordination.If the level of selective coordination is not sufficient for the application, analternate upstream circuit breaker yielding a higher level of selectivecoordination may be found by reading down the table. The alternate may bean electronic trip circuit breaker whose instantaneous trip function can beturned OFF, a larger frame size circuit breaker or a different type of circuit

    breaker.A short circuit study to determine the level of short circuit current available atvarious points in the system may allow the selection of circuit breakers witha lower interrupting rating and a higher instantaneous trip level.The data bulletin Enhancing Short Circuit Selective Coordination withLow Voltage Circuit Breakers , document number 0100DB0403, should beconsulted for a further explanation of optimizing techniques for enhancingthe level of short circuit selective coordination.

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    5/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 5

    Finally, do not neglect to properly adjust circuit breakers in the field as allSquare D low voltage circuit breakers are shipped from the factory with allbut the ampere-rating switch in the lowest position.

    REFERENCE Enhancing Short Circuit Selective Coordination with Low VoltageCircuit Breakers Document Number: 0100DB0403Overcurrent Protection Document Number: 0600DB0301Reducing Fault Stress with Zone-selective Interlocking Document Number: 0600DB0001

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    6/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved6

    APPENDIX A

    Levels of Short Circuit SelectiveCoordination for UL 489 StandardCircuit Breakers

    The data in the following tables for UL 489 Listed molded and insulatedcase circuit breakers also applies to CSA C22.2 #5-02 and ANCE NMXJ-266 Certified circuit breakers. All data is at 60 Hz. The data does not applyto circuit breakers that are Certified to IEC 60947-2 only or at frequenciesother than 60 Hz.Fully rated and series rated pairs of circuit breakers where there is areasonable expectation of selective coordination are shown. Pairings of thesame frame size or where the upstream circuit breaker might be a currentlimiting circuit breaker are not shown as such pairings would not beexpected to selectively coordinate.Gray shaded cells in the tables indicate series rated combinations. It shouldbe noted that series ratings vary by equipment type, thus publishedinformation regarding the specific type of Square D equipment beingstudied should be consulted for the actual series ratings available in thatequipment.Based on laboratory testing, Square D certifies the following levels ofselective coordination based upon the construction of the specific circuitbreakers referenced as of the date of publication of this document.

    Appendix A

    Type VoltsDownstream

    Circuit Breaker(type or frame size)

    Table No. Page No.

    UL

    240

    QO/B 1 6

    100150 A 2 8

    250 A 3 12

    400 A 4 15

    6001200 A 5 18

    480

    100250 A 6 20

    400 A 7 24

    6001200 A 8 27

    600

    100250 A 9 29

    400 A 10 33

    6001200 A 11 36

    Table 1: UL 240 Vac QO/B Selective Coordination

    Key: Fully Rated Series Rated

    UpstreamCircuit Breaker 2

    Downstream Circuit Breaker - Type / kAIRMaximum Level of Selective Coordination Shown in kA

    Max.Contin-

    uousCurrentRating

    Type QO/B 3 QO/B-VH 3 QH/B 3 QO/B-GFI/EPDQO/B-VHGFI/

    EPD

    QO/B-AFI

    QO/B-VHAFI

    1 Pole120 V

    15-70 A

    2 Pole120/240 V15-125 A

    2 Pole240 V

    15-100 A

    3 Pole240 V

    15-100 A

    1 Pole120 V

    15-30 A

    2 Pole120/240 V15-150 A

    3 Pole240 V

    15-150 A

    1 Pole120 V

    15-30 A

    2 Pole120/240 V

    15-30 A

    3 Pole240 V

    15-150 A

    1 Pole120 V

    15-30 A

    2 Pole120/240 V

    15-60 A

    1 Pole120 V

    15-30 A

    1 Pole120 V

    15-20 A

    1 Pole120 V

    15-20 A

    kAIR 1 10 10 10 10 22 22 22 65 65 65 10 10 22 10 22

    100/ 150 A

    25 HD 4 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

    65

    FH 0.9 0.9 0.9

    HG 4 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

    NT-H800/250 A 65 65 65

    NW-N800/250 A 65 65 65

    100 HJ 4 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

    125 HL 4 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

    250 A

    10 QB 2.0 2.0 2.0 2.0 2.0 2.0 2.0

    25JD 4 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 22 2.3 2.3

    QD 5, 4 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

    65

    JG 4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

    CG 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

    NT-H800/250 A 65 65 65

    PG 65 65 65

    PK 65 65 65

    QG 5, 4 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

    NW-N800/250 A 65 65 65

    100

    JJ 4 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

    PJ 6 25 25 25

    QJ 7, 5, 4, 8 2.1 2.1 2.1 2.1 2.1 2.1 2.1

    125 JL 4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    7/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 7

    400 A

    42LA9 3.2

    LA-MC 18 10 *10

    *10

    *10

    *10

    *10

    *10

    65

    DG 65 3.2 3.2

    LH 65 3.2 3.2

    LH-MC 65 10 *10

    *10

    *10

    *10

    *10

    *10 65 5.6 5.6

    MG11 3.6 65 3.6 3.6

    NT-H1200 A 65 65 65

    NW-N

    2000 A65 65 65

    PG 65 65 65

    PK 65 65 65

    600 A 65

    DG 65 4.8 4.8

    MG11 5.4 65 5.4 5.4

    NT-H1200 A 65 65 65

    NW-N2000 A 65 65 65

    PG 65 65 65

    PK 65 65 65

    RG 65 65 65

    RK 65 65 651 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.3 QO plug-on breakers rated 15100 A only.4 Series rating with 35-150 A QO/B-VH 3-pole circuit breakers only.5 Series ratings limited to 70225 A only.6 Series rating at 42 kA with 1530 A QO/B-VH 2- and 3-pole circuit breakers only.7 Rated 208 Y / 120 Vac8 Series rating with 35150 A QO/B-VH 2-pole circuit breakers only.9 Series rating with 15125 A QO circuit breakers only.10 See Appendix B for additional information about LA-MC and LH-MC levels of selective coordination with QO circuit breakers at 208 Y / 120 Vac.

    Table 1: UL 240 Vac QO/B Selective Coordination (continued)

    Key: Fully Rated Series Rated

    UpstreamCircuit Breaker 2

    Downstream Circuit Breaker - Type / kAIRMaximum Level of Selective Coordination Shown in kA

    Max.Contin-

    uousCurrentRating

    Type QO/B3

    QO/B-VH3

    QH/B3

    QO/B-GFI/EPD

    QO/B-

    VHGFI/ EPD

    QO/B-AFI

    QO/B-VHAFI

    1 Pole120 V

    15-70 A

    2 Pole120/240 V15-125 A

    2 Pole240 V

    15-100 A

    3 Pole240 V

    15-100 A

    1 Pole120 V

    15-30 A

    2 Pole120/240 V15-150 A

    3 Pole240 V

    15-150 A

    1 Pole120 V

    15-30 A

    2 Pole120/240 V

    15-30 A

    3 Pole240 V

    15-150 A

    1 Pole120 V

    15-30 A

    2 Pole120/240 V

    15-60 A

    1 Pole120 V

    15-30 A

    1 Pole120 V

    15-20 A

    1 Pole120 V

    15-20 A

    kAIR 1 10 10 10 10 22 22 22 65 65 65 10 10 22 10 22

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    8/52

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    9/52

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    10/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved10

    800 A

    125 RL 125 125 125 125 125

    200

    NT-L 1200 A 9

    NT-LF 1200 A 9

    NW-L 1600 A 200

    NW-LF 1600 A 200

    1000 A

    50 NT-N 1200 A 50 50

    65

    NT-H 1200 A 65 65

    NW-N 2000 A 65 65

    PG 65 65 65

    PK 65 65

    RG 65 65 65

    RK 65 65

    100

    NT-L1 1200 A 100 100

    NW-H 2000 A 100 100

    PJ 9 9 9 100 100

    RJ 100 100 100 100

    125PL 9 9 9 125

    RL 125 125 125 125 125

    200

    NT-L 1200 A 9

    NT-LF 1200 A 9

    NW-L 1600 A 200

    NW-LF 1600 A 200

    1200 A

    50 NT-N 1200 A 50 50

    65

    NT-H 1200 A 65 65NW-N 2000 A 65 65

    PG 65 65 65

    RG 65 65 65

    RK 65 65

    100

    NT-L1 1200 A 100 100

    NW-H 2000 A 100 100

    PJ 9 9 9 100 100

    PK 100 100

    RJ 100 100 100 100

    125PL 9 9 9 125

    RL 125 125 125 125 125

    200

    NT-L 1200 A 9

    NT-LF 1200 A 9NW-L 1600 A 200

    NW-LF 1600 A 200

    1600 A

    65

    NW-N 2000 A 65 65

    RG 65 65 65

    RK 65 65

    100NW-H 2000 A 100 100

    RJ 100 100 100 100

    125 RL 125 125 125 125 125

    200 NW-L 1600 A 125 200

    Table 2: UL 240 Vac 100150 A Selective Coordination (continued)

    Key: Fully Rated Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    Maximum

    ContinuousCurrentRating

    Type EDB ECB EGB EJB FA HD FH HG FJ HJ HL FI

    kAIR 1 25 65 65 100 25 25 65 65 100 100 125 200

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    11/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 11

    1600 A 200 NW-LF 1600 A 125 200

    2000 A

    65

    NW-N 2000 A 65 65

    RG 65 65 65

    RK 65 65

    100NW-H 2000 A 100 100

    RJ 100 100 100 100

    125 RL 125 125 125 125 125

    200NW-L 2000 A 200

    NW-LF 2000 A 200

    25003000 A

    65RG 65 65 65

    RK 65 65

    100NW-H 3000 A 100 100

    RJ 100 100 100 100

    125 RL 125 125 125 125 125

    200 NW-L 3000 A 200

    40005000 A

    100 NW-H 6000 A 100 100

    200 NW-L 6000 A 2001 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.3 Rated 208 Y / 120 Vac.4 See Appendix B for additional information about LA-MC and LH-MC levels of selective coordination with E frame circuit breakers.

    Table 2: UL 240 Vac 100150 A Selective Coordination (continued)

    Key: Fully Rated Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    Maximum

    ContinuousCurrentRating

    Type EDB ECB EGB EJB FA HD FH HG FJ HJ HL FI

    kAIR 1 25 65 65 100 25 25 65 65 100 100 125 200

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    12/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved12

    Table 3: UL 240 Vac 250 A Selective Coordination

    Key: Fully Rated Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type QB QD JD QG JG PG QJ JJ LE LX PJ JL PL KI

    kAIR 1 10 25 25 65 65 65 100 100 100 100 100 125 125 200

    400 A

    42LA 3.6 3.6 3.6 3.6

    LA-MC 5.6 5.6

    50 NT-N 1200 A 50 50 36 50 50 36

    65

    DG 3.2 3.2

    LH 3.2 3.2 3.2 3.2

    LH-MC 5.6 5.6

    MG 3.6 3.6 3.6 3.6 3.6 3.6

    NT-H 1200 A 65 65 36 65 65

    NW-N 1200 A 65 65 36 65 65

    PG 65 65 65 65 65 65

    PK 65 65 65 65

    100

    DJ 3.2 3.2

    MJ 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

    NT-L1 1200 A 9 100 9 9 9

    NW-H 1200 A 100 100 100 100 36

    PJ 100 100 9 100 9 100 9 9

    125 PL 125 125 125 125

    200

    NT-L 1200 A 9

    NT-LF 1200 A 9

    NW-L 1200 A 200

    NW-LF 1200 A 200

    600 A

    50 NT-N 1200 A 50 50 36 50 36

    65

    DG 4.8 4.8MG 65 5.4 5.4 5.4 5.4 5.4

    NT-H 1200 A 65 65 36 65 65

    NW-N 1200 A 65 65 36 65 65

    PG 22 22 65 65 65 65

    PK 65 65 65 65

    RG 65 65 65 65 51 65 65

    RK 65 65 51 65 65

    100

    DJ 4.8 4.8

    MJ 100 5 5.4 5.4 5.4 5.4 5.4

    NT-L1 1200 A 9 100 9 9

    NW-H 1200 A 100 100 100 100

    PJ 100 100 100 9 100 9 9

    RJ 100 100 100 43 100 100 100 100

    125PL 125 125 125

    RL 125 125 125 125

    200

    NT-L 1200 A 9

    NT-LF 1200 A 9

    NW-L 1200 A 200

    NW-LF 1200 A 200

    800 A50 NT-N 1200 A 50 50 36 50 50

    65 MG 65 65 7.2 65 7.2 7.2

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    13/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 13

    800 A

    65

    NT-H 1200 A 65 65 36 65 65

    NW-N 2000 A 65 65 36 65 65

    PG 65 65 65 65 65 65

    PK 65 65 65 65

    RG 65 65 65 65 51 65 65

    RK 65 65 51 65 65

    100

    MJ 100 100 100 7.2 7.2 7.2 7.2

    NT-L1 1200 A 9 100 9 9 9

    NW-H 2000 A 100 100 100 100 36

    PJ 100 100 100 9 100 9 9

    RJ 100 100 100 100 100 100 100 100

    125PL 125 125 125 125

    RL 125 125 125 125 43

    200

    NT-L 1200 A 9

    NT-LF 1200 A 9

    NW-L 1600 A 200

    NW-LF 1600 A 200

    1000 A

    50 NT-N 1200 A 50 50 36 50 50

    65

    NT-H 1200 A 65 65 36 65 65

    NW-N 2000 A 65 65 36 65 65

    PG 65 65 65 65 65 65

    PK 65 65 65 65

    RG 65 65 65 65 51 65 65

    RK 65 65 51 65 65

    100

    NT-L1 1200 A 9 100 9 9 9

    NW-H 2000 A 100 100 100 100 36

    PJ 100 100 100 9 100 9

    RJ 100 100 100 100 100 100 100 100

    125PL 125 125 125 125

    RL 125 125 125 125 43

    200

    NT-L 1200 A 9

    NT-LF 1200 A 9

    NW-L 1600 A 200

    NW-LF 1600 A 200

    1200 A

    50 NT-N 1200 A 50 50 36 50 50

    65

    NT-H 1200 A 65 65 36 65 65

    NW-N 2000 A 65 65 36 65 65PG 65 65 65 65 65 65

    PK 65 65 65 65

    RG 65 65 65 65 51 65 65

    RK 65 65 36 65 65

    100

    NT-L1 1200 A 100 100 100 100

    NW-H 1200 A 9 100 9 9

    PJ 100 100 100 100 100 100 100

    RJ 100 100 100 100 100 100 100 100

    125 PL 125 125 125 125

    Table 3: UL 240 Vac 250 A Selective Coordination (continued)

    Key: Fully Rated Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    Maximum

    ContinuousCurrentRating

    Type QB QD JD QG JG PG QJ JJ LE LX PJ JL PL KI

    kAIR 1 10 25 25 65 65 65 100 100 100 100 100 125 125 200

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    14/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved14

    1200 A

    125 RL 125 125 125 125 43

    200

    NT-L 1200 A 9

    NT-LF 1200 A 9

    NW-L 1600 A 200

    NW-LF 1600 A 200

    1600 A

    65

    NT-N 1600 A 65 65 36 65 65

    RG 65 65 65 51 65 65

    RK 65 65 51 65 65

    100NW-H 2000 A 100 100 100 100 36

    RJ 100 100 100 100 100 100 100

    125 RL 125 125 125 125 43

    200NW-L 1600 A 200

    NW-LF 1600 A 200

    2000 A

    65

    NT-N 1200 A 65 65 36 65 65

    RG 51 65 65 51 65 65

    RK 65 65 51 65 65

    100NW-H 2000 A 100 100 100 100 36

    RJ 100 100 100 100 100 100 100

    125 RL 125 125 125 125 43

    200NW-L 1600 A 200

    NW-LF1600 A 200

    2500 A

    65RG 51 65 65 51 65 65

    RK 65 65 51 65 65

    100 NW-H 3000 A 100 100 100 100 100RJ 100 100 100 100 100 100 100

    125 RL 125 125 125 125 43

    200 NW L 3000 A 200

    30006000 A100 NW-H 3000 A 100 100 100 100 100

    200 NW-L 6000 A 2001 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

    Table 3: UL 240 Vac 250 A Selective Coordination (continued)

    Key: Fully Rated Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    Maximum

    ContinuousCurrentRating

    Type QB QD JD QG JG PG QJ JJ LE LX PJ JL PL KI

    kAIR 1 10 25 25 65 65 65 100 100 100 100 100 125 125 200

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    15/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 15

    Table 4: UL 240 Vac 400 A Selective Coordination

    Key: Fully RatedSeriesRated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kAMaximum

    ContinuousCurrentRating

    Type Q4 LA LA-MC LHLH-MC DG DJ PG LC LE LX PJ PL LI LXI

    kAIR 1 42 42 42 65 65 65 100 65 100 100 100 100 125 200 200

    600 A

    50 NT-N 1200 A 50 50 50 36 50 50

    65

    DG 5.4 5.4

    MG 5.4 5.4 5.4 5.4 5.4

    NT-H 1200 A 65 65 65 36 65 65

    NW-N 2000 A 65 65 65 36 65 65

    PG 22 22 65 65 65

    PK 22 22 65 65 65

    RG 65 65 65 51 65 65

    RK 65 65 65 51 65 65

    100

    DJ

    MJ 5.4 5.4 5.4 5.4 5.4

    NT-L1 1200 A 9 9 9 9 9

    NW-H 2000 A 100 100 100 100 36

    PJ 9 9 9 9

    RJ 100 100 100 100 100

    125PL 9 9

    RL 43 125 125

    200

    NT-L 1200 A 9 9

    NT-LF 1200 A 9 9

    NW-L 1600 A 200 200

    NW-LF 1600 A 22 22

    800 A

    50 NT-N 1200 A 50 50 50 36

    65

    MG 7.2 7.2 7.2 7.2 7.2

    NT-H 1200 A 65 65 65 36 65 65

    NW-N 2000 A 65 65 65 36 65 65

    PG 22 22 65 65 65

    PK 22 22 65 65 65

    RG 65 65 65 51 65 65

    RK 65 65 65 51

    100

    MJ 7.2 7.2

    NT-L1 1200 A 9 9 9 9 9

    NW-H 2000 A 100 100 100 100 36

    PJ 9 9

    RJ 100 100 100

    125 PL 9 9RL 43 125 125

    200

    NT-L 1200 A 9 9

    NT-LF 1200 A 9 9

    NW-L 1600 A 200 200

    NW-LF 1600 A 22 22

    1000 A

    50 NT-N 1200 A 50 50 50 36 50 50

    65

    NT-H 1200 A 65 65 65 36 65 65

    NW-N 2000 A 65 65 65 36 65 65

    PG 22 22 65 65 65

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    16/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved16

    1000 A

    65

    PK 22 22 65 65 65

    RG 65 65 65 51 65 65

    RK 65 65 65 51 65 65

    100

    NT-L1 1200 A 9 9 9 9

    NW-H 2000 A 100 100 100 36

    PJ 9 9 9

    RJ 100 100

    125PL 9 9

    RL 43 125 125

    200

    NT-L 1200 A 9 9

    NT-LF 1200 A 9 9

    NW-L 1600 A 200 200

    NW-LF 1600 A 22 22

    1200 A

    50 NT-N 1200 A 50 50 50 36 50 50

    65

    NT-H 1200 A 65 65 65 36 65 65

    NW-N 2000 A 65 65 65 36 65 65

    PG 22 22 65 65 65

    PK 65 65 65 65 65

    RG 65 65 65 51 65 65

    RK 65 65 65 36 65 65

    100

    NT-H 1200 A 100 100 100 100 36

    NW-H 2000 A 9 9 9 9 9

    PJ 100 100 100 100

    RJ 100 100 100 100 100

    125PL 9 9

    RL 43 125 125

    200

    NT-L 1200 A 9 9

    NT-LF 1200 A 9 9

    NW-L 1600 A 200 200

    NW-LF 1600 A 22 22

    1600 A

    65

    NW-N 2000 A 65 65 65 36 65 65

    RG 65 65 65 51 65 65

    RK 65 65 65 51 65 65

    100NW-H 2000 A 100 100 100 100 36

    RJ 100 100 100 100 100

    125 RL 43 125 125

    200NW-L 1600 A 200 200

    NW-LF 1600 A 22 22

    Table 4: UL 240 Vac 400 A Selective Coordination (continued)

    Key: Fully Rated SeriesRated

    Upstream Circuit Breaker 2 Downstream Circuit Breaker - Type / kAIRMaximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type Q4 LA LA-MC LHLH-MC DG DJ PG LC LE LX PJ PL LI LXI

    kAIR 1 42 42 42 65 65 65 100 65 100 100 100 100 125 200 200

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    17/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 17

    2000 A

    65

    NW-N 2000 A 65 65 65 36 65 65

    RG 65 65 65 51 65 65

    RK 65 65 65 51 65 65

    100NW-H 2000 A 100 100 100 100 36

    RJ 100 100 100 100 100

    125 RL 43 125 125

    200NW-L 2000 A 200 200

    NW-LF 2000 A 22 22

    2500 A 65 RG 65 65 65 51 65 65

    3000 A

    200 RK 65 65 65 51 65 65

    100NW-H 3000 A 100 100 100 100 100

    RJ 100 100 100 100 100

    125 RL 43 125 125

    200 NW-L 3000 A 200 200

    4000 A 100 NW-H 6000 A 100 100 100 100 100 200 200

    6000 A 200 NW-L 6000 A 200 2001 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

    Table 4: UL 240 Vac 400 A Selective Coordination (continued)

    Key: Fully Rated SeriesRated

    Upstream Circuit Breaker 2 Downstream Circuit Breaker - Type / kAIRMaximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type Q4 LA LA-MC LHLH-MC DG DJ PG LC LE LX PJ PL LI LXI

    kAIR 1 42 42 42 65 65 65 100 65 100 100 100 100 125 200 200

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    18/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved18

    Table 5: UL 240 Vac 6001200 A Selective Coordination

    Key:FullyRated

    Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kAMaximum

    ContinuousCurrentRating

    Type DG DJ LC LE LX LI LXI MG MJ PG PK PJ PL NT NT NT NT

    kAIR 1 65 100 100 100 100 200 200 65 100 65 65 100 125 50 65 100 200

    800 A

    50 NT-N 1200 A 50 50 50 50 36 36 36

    65

    MG 7.2 7.2 7.2 7.2

    NT-H 1200 A 65 65 65 65 36 36 36

    NW-N 2000 A 65 65 65 65 36 36 36 36

    PG 65 65 65 65 22

    PK 65 65 65 65 22

    RG 65 65 65 65 65 51 51

    RK 65 65 65 65 65 51 51

    100

    MJ 7.2 7.2 7.2 7.2

    NT-L1 1200 A 9 9 9 9 9 9

    NW-H 2000 A 100 100 100 100 36 36 36

    PJ 9 9 9 9 9 9

    RJ 100 100 100 100 51 100

    125PL 9 9

    RL 125 125 43

    200

    NT-L 1200 A 9 9

    NT-LF 1200 A 9 9

    NW-L 1600 A 200 200 32

    NW-LF 1600 A 22 22 22

    1000 A

    50 NT-N 1200 A 50 50 50 50 36 36 36

    65

    NT-H 1200 A 65 65 65 65 36 36 36

    NW-N 2000 A 65 65 65 65 36 36 36 36 36PG 65 65 65 65 22

    PK 65 65 65 65 22

    RG 65 65 65 65 65 51 51

    RK 65 65 65 65 65 51 51

    100

    NT-L1 1200 A 9 9 9 9 9 9

    NW-H 2000 A 100 100 100 100 36 36 36

    PJ 9 9 9 9 9

    RJ 100 100 100 100 43 100

    125PL 9 9

    RL 125 125 43

    200

    NT-L 1200 A 9 9

    NT-LF 1200 A 9 9

    NW-L 1600 A 200 200 32NW-LF 1600 A 22 22 22

    1200 A

    50 NT-N 1200 A 50 50 50 50 36 36 36

    65

    NT-L 1200 A 9 9 9 9 9 9 9

    NW-N 2000 A 65 65 65 65 36 36 36 36

    PG 65 65 65 65 22

    PK 65 65 65 65 22

    RG 65 65 65 65 65 51 51

    RK 65 65 65 65 65 51 51

    100 NT-L1 1200 A 100 100 100 100 36 36

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    19/52

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    20/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved20

    Table 6: UL 480 Vac 100250 A Selective Coordination

    Key: Fully RatedSeriesRated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kAMaximum

    ContinuousCurrentRating

    Type ECB 3 EDB 3 EGB 3 EJB 3 FA FH FJ FI HD HG HJ HL JD JG PG JJ LE LX PJ JL PL KI

    kAIR 1 14 18 35 65 18 25 65 200 18 35 65 100 18 35 35 65 65 65 65 100 100 200

    100/150 A

    18FA 0.9

    HD 1.3

    35 HG 1.3 1.3

    50 NT-N/H800/250 A 50 50 50

    65

    HJ 1.3 1.3 1.3 1.3

    NT-L1 800/250 A 65 65 9

    NW-N 800/250 A 65 65 65

    100

    HL 1.3 1.3 1.3 1.3

    NT-L 800/250 A 100 9NT-LF 800/250 A 100 9

    NW-H 800/250 A 100 100

    150NW-L 800/250 A 150

    NW-LF 800/250 A 150

    250 A

    18 JD 2.3 2.3 2.3 2.3

    35JG 2.4 2.4 2.4 2.4

    PG 35 22 35 35

    50NT-N/H 800/250A 50 50 50

    PK 50 50 50

    65

    JJ 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

    NT-L1 800/250 A 65 65 9

    NW-N 800/250 A 65 65 65PJ 65 65 9

    100

    JL 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

    NT-L 800/250 A 8

    NT-LF 800/250 A 9

    NW-H 800/250 A 100

    PL 9 9 9

    150NW-L 800/250 A 150

    NW-LF 800/250 A 150

    400 A

    30LA 3.2 3.2 3.2 3.2 3.2

    LA-MC *4 30.0 30.0

    35

    DG 3.2 3.2 3.2

    LH 3.2 3.2 3.2 3.2

    LH-MC *4 35.0 35.0

    MG 3.6 3.6 3.6 3.6 3.6 3.6 3.6

    PG 35 35 35 35 35 35 35

    50NT-N/H 1200 A 50 50 50 36 50 50 50

    PK 50 50 50 50 50

    65 DJ 3.2 3.2 3.2 3.2

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    21/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 21

    400 A

    65

    MJ 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

    NT-L1 1200 A 65 65 9 9 9 9 9

    NW-N 2000 A 65 65 65 65 65 65 36

    PJ 65 65 9 9 9 9

    100

    NT-L 1200 A 9 9 9

    NT-LF 1200 A 9 9 9

    NW-H 2000 A 36 100 36

    PL 9 9 9 9

    150NW-L 1600 A 150 150

    NW-LF 1600 A 150 150

    600 A

    35

    DG 4.8 4.8 4.8

    MG 5.4 5.4 5.4 5.4 5.4 5.4 5.4

    PG 35 35 35 35 35 35 35

    RG 35 35 35 35 35 35 35

    50NT-N/H 1200 A 50 50 50 50 50 50 36

    PK 50 50 50 50 50 50

    65

    DJ 4.8 4.8 4.8 4.8

    MJ 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

    NT-L1 1200 A 65 65 9 9 9 9 9

    NW-N 2000 A 65 65 65 65 65 65 36

    PJ 65 65 9 9 9 9

    RJ 65 65 65 65 65 65 65

    RK 65 65 65 65 65 65 65

    100

    NT-L 1200 A 9 9 9

    NT-LF 1200 A 9 9 9

    NW-H 2000 A 100 100 36

    PL 9 9 9 9

    RL 100 100 43

    150NW-L 1600 A 150 150

    NW-LF 1600 A 150 150

    800 A

    35

    MG 7.2 7.2 7.2 7.2 7.2 7.2

    PG 35 35 35 35 35 35

    RG 35 35 35 35 35

    50NT-H 1200 A 50 50 50 50 36

    PK 50 50 50

    65

    MJ 7.2 7.2 7.2 7.2 7.2 7.2NT-L1 1200 A 9 9 9 9 9

    NW-N 2000 A 65 65 65 65 36

    PJ 9 9 9 9

    RJ 65 65 65 65 65

    RK 65 65 65 65 65

    Table 6: UL 480 Vac 100250 A Selective Coordination (continued)

    Key: Fully Rated SeriesRated

    Upstream Circuit Breaker 2 Downstream Circuit Breaker - Type / kAIRMaximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type ECB 3 EDB 3 EGB 3 EJB 3 FA FH FJ FI HD HG HJ HL JD JG PG JJ LE LX PJ JL PL KI

    kAIR 1 14 18 35 65 18 25 65 200 18 35 65 100 18 35 35 65 65 65 65 100 100 200

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    22/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved22

    800 A

    100

    NT-L 1200 A 9 9 9

    NT-LF 1200 A 9 9 9

    NW-H 2000 A 100 100 36

    PL 9 9 9 9

    RL 100 100 43

    150NW-L 1600 A 150 150

    NW-LF 1600 A 150 150

    1000 A

    35PG 35 35 35 35 35 35

    RG 35 35 35 35 35

    50NT-N/H 1200 A 50 50 50 50 36

    PK 50 50 50 50

    65

    NT-L1 1200 A 9 9 9 9 9

    NW-N 2000 A 65 65 65 65 36

    PJ 9 9 9 9

    RJ 65 65 65 65 65

    RK 65 65 65 65 65

    100

    NT-L 1200 A 9 9 9

    NT-LF 1200 A 9 9 9

    NW-H 2000 A 100 100 36

    PL 9 9 9 9

    RL 100 100 43

    150NW-L 1600 A 150 150

    NW-LF 1600 A 150 150

    1200 A

    35PG 35 35 35 35 35 35

    RG 35 35 35

    50NT-N/H 1200 A 50 50 50 50 36

    PK 50 50 50 50

    65

    NT-L1 1200 A 9 9 9 9 9

    NW-N 2000 A 65 65 65 65 36

    PJ 9 9 9 9

    RJ 65 65 65 65 65

    RK 65 65 65 65 65

    100

    NT-L 1200 A 9 9 9

    NT-LF 1200 A 9 9 9

    NW-H 2000 A 100 100 36

    NW-H 3000 A 100 100 100PL 9 9 9 9

    RL 100 100 43

    150

    NW-L 1600 A 150 150

    NW-L 3000 A 150 150

    NW-LF 2000 A 150 150

    Table 6: UL 480 Vac 100250 A Selective Coordination (continued)

    Key: Fully Rated SeriesRated

    Upstream Circuit Breaker 2 Downstream Circuit Breaker - Type / kAIRMaximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type ECB 3 EDB 3 EGB 3 EJB 3 FA FH FJ FI HD HG HJ HL JD JG PG JJ LE LX PJ JL PL KI

    kAIR 1 14 18 35 65 18 25 65 200 18 35 65 100 18 35 35 65 65 65 65 100 100 200

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    23/52

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    24/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved24

    Table 7: UL 480 Vac 400 A Selective Coordination

    Key: Fully Rated Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type LA LA-MC LH LH-MC DG DJ PG LC LE LX PJ PL LI LXI

    kAIR 1 30 30 35 35 35 65 35 65 65 65 65 100 200 200

    600 A

    35

    DG 4.8 4.8

    MG 5.4 5.4 5.4 5.4 5.4

    PG 22 22 35 35 35

    RG 35 35 35 35 35 35

    50NT-N/H 1200 A 50 50 50 50 36

    PK 50 50 50 50

    65

    DJ

    MJ 5.4 5.4 5.4 5.4

    NT-L1 1200 A 9 9 9 9 9

    NW-N 2000 A 65 65 65 65 36

    PJ 9 9 9 9

    RJ 65 65 65 65 43

    RK 65 65 65 65 51

    100

    NT-L 1200 A 9 9 9

    NT-LF 1200 A 9 9 9

    NW-H 2000 A 36 100 100

    PL 9 9

    RL 43 100 100

    150NW-L 1600 A 150 150

    NW-LF 2000 A 22 22

    800 A

    35

    MG 7.2 7.2 7.2 7.2 7.2

    PG 22 22 35 35 35

    RG 35 35 35 35 35 35

    50NT-N 1200 A 50 50 50 50 36

    PK 50 50 50 50

    65

    MJ 7.2 7.2 7.2 7.2

    NT-L1 1200 A 9 9 9 9 9

    NW-N 2000 A 65 65 65 65 36

    PJ 9 9 9 9

    RJ 65 65 65 65 43

    RK 65 65 65 65 51

    100

    NT-L 1200 A 9 9 9

    NT-LF 1200 A 9 9 9

    NW-H 2000 A 36 100 100

    PL 9 9

    RL 43 100 100

    150NW-L 1600 A 150 150

    NW-LF 2000 A 22 22

    1000 A 35PG 22 22 35 22 22

    RG 35 35 35 35 51 51

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    25/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 25

    1000 A

    50NT-N/H 1200 A 50 50 50 50 36

    PK 50 50 50 50

    65

    NT-L1 1200 A 9 9 9 9 9

    NW-N 2000 A 65 65 65 65 36

    PJ 9 9 9 9

    RJ 65 65 65 65 43

    RK 65 65 65 65 51

    100

    NT-L 1200 A 9 9 9

    NT-LF 1200 A 9 9 9

    NW-H 2000 A 36 100 100

    PL 9 9

    RL 43 100 100

    150NW-L 1600 A 150 150

    NW-LF 2000 A 22 22

    1200 A

    35PG 22 22 35 35

    RG 35 35 35 35 35

    50NT-N/H 1200 A 50 50 50 36

    PK 50 50 50

    65

    NT-L1 1200 A 9 9 9 9

    NW-N 2000 A 65 65 65 36

    PJ 9 9 9

    RJ 65 65 65 43

    RK 65 65 65 51

    100

    NT-L 1200 A 9 9 9NT-LF 1200 A 9 9 9

    NW-H 2000 A 36 100 100

    NW-H 3000 A 100 100 100

    PL 9 9

    RL 43 100 100

    150

    NW-L 1600 A 100 100

    NW-L 3000 A 150 150

    NW-LF 2000 A 22 22

    1600 A

    35 RG 35 35 35 35 35 35

    65

    NW-N 2000 A 65 65 65 65 36

    RJ 65 65 65 65 43

    RK 65 65 65 65 51

    100NW-H 2000 A 36 100 100NW-H 3000 A 100 100 100

    RL 43 100 100

    150

    NW-L 1600 A 100 100

    NW-L 3000 A 150 150

    NW-LF 2000 A 22 22

    Table 7: UL 480 Vac 400 A Selective Coordination (continued)

    Key: Fully Rated Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    Maximum

    ContinuousCurrentRating

    Type LA LA-MC LH LH-MC DG DJ PG LC LE LX PJ PL LI LXI

    kAIR 1 30 30 35 35 35 65 35 65 65 65 65 100 200 200

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    26/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved26

    2000 A

    35 RG 35 35 35 35 35 35

    65

    NW-N 2000 A 65 65 65 65 36

    RJ 65 65 65 65 43

    RK 65 65 65 65 51

    100

    NW-H 2000 A 36 100 100

    NW-H 3000 A 100 100 100

    NW-H 6000 A 100 100 100

    RL 43 100 100

    150

    NW-L 2000 A 100 100

    NW-L 3000 A 100 100

    NW-L 6000 A 150 150

    NW-LF 2000 A 22 22

    2500

    3000 A

    35 RG 35 35 35 35 35

    65RJ 65 65 65 65 43

    RK 65 65 65 65 51

    100

    NW-H 3000 A 100 100 100

    NW-H 6000 A 100 100 100

    RL 43 100 100

    150NW-L 3000 A 150 150

    NW-L 6000 A 150 150

    4000

    6000 A

    100 NW-H 6000 A 100 100 100

    150 NW-L 6000 A 150 1501 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

    Table 7: UL 480 Vac 400 A Selective Coordination (continued)

    Key: Fully Rated Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    Maximum

    ContinuousCurrentRating

    Type LA LA-MC LH LH-MC DG DJ PG LC LE LX PJ PL LI LXI

    kAIR 1 30 30 35 35 35 65 35 65 65 65 65 100 200 200

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    27/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 27

    Table 8: UL 480 Vac 6001200 A Selective Coordination

    Key: Series Rated Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type DG DJ LC LE LX LI LXI MG MJ PG PJ PL RG RJ RLNT

    N/H

    NT

    L1

    NT

    L

    NT

    LF

    kAIR 1 35 65 65 65 65 200 200 35 65 35 65 100 35 65 100 50 65 100 100

    800 A

    35

    MG 7.2 7.2 7.2 7.2

    PG 35 35 35 35

    RG 35 35 35 35

    50NT-N/H 1200 A 50 50 50 50

    PK 50 50 50 50

    65

    MJ 7.2 7.2 7.2 7.2

    NT-L1 1200 A 9 9 9 9

    NW-N 2000 A 65 65 65 65 36

    PJ 9 9 9 9

    RJ 65 65 65 65

    RK 65 65 65 65

    100

    NT-L 1200 A 9 9

    NT-LF 1200 A 9 9

    NW-H 2000 A 100 100 36 36

    PL 9 9

    RL 100 100

    150NW-L 1600 A 150 150

    NW-LF 1600 A 150 150

    1000 A

    35PG 35 35 35 35 22

    RG 35 35 35 35 35 35

    50NT-N/H 1200 A 50 50 50 50 36 36

    PK 50 50 50 50 22 22

    65

    NT-L1 1200 A 9 9 9 9 9 9NW-N 2000 A 65 65 65 65 36 36 36

    PJ 9 9 9 9 9

    RJ 65 65 65 65 43 43

    RK 65 65 65 65 65 51

    100

    NT-L 1200 A 9 9 9

    NT-LF 1200 A 9 9 9

    NW-H 2000 A 100 100 36 36 36

    PL 9 9

    RL 100 100 43

    150NW-L 1600 A 150 150

    NW-LF 1600 A 150 150

    1200 A

    35PG 35 22 22 22 22

    RG 35 51 51 51 51 51

    50NT-N/H 1200 A 50 50 50 50 36 36

    PK 50 50 50 50 22

    65

    NT-L1 1200 A 9 9 9 9 9 9

    NW-N 2000 A 65 65 65 65 36 36 36

    PJ 9 9 9 9 9

    RJ 65 65 65 65 43 43

    RK 65 65 65 65 65 51

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    28/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved28

    1200 A

    100

    NT-L 1200 A 9 9 9

    NT-LF 1200 A 9 9 9

    NW-H 2000 A 100 100 36 36 36

    NW-H 3000 A 100 100 100 100 100

    PL 9 9

    RL 100 100 43

    150

    NW-L 1600 A 150 150

    NW-L 3000A 150 150

    NW-LF 1600 A 150 150

    1600 A

    35 RG 35 35 35 35 35 35

    65

    NW-N 2000 A 65 65 65 65 36 36 36 36

    RJ 65 65 65 65 43 43

    RK 65 65 65 65 65 51

    100

    NW-H 2000 A 100 100 36 36 36 36

    NW-H 3000 A 100 100 100 59 100 100

    RL 100 100 43

    150

    NW-L 2000 A 150 150

    NW-L 3000 A 150 150

    NW-LF 1600 A 150 150

    2000 A

    35 RG 35 35 35 35 35 35

    65

    NW-N 2000 A 65 65 65 65 36 36 36 36

    RJ 65 65 65 65 43 43

    RK 65 65 65 65 65 51

    100

    NW-H 2000 A 100 100 36 36 36 36NW-H 3000 A 100 100 100 59 100 100

    NW-H 6000 A 100 100 100 77 100 100

    RL 100 100 43

    150 NW-L 2000 A 150 150

    2000 A 150

    NW-L 3000 A 150 150

    NW-L 6000 A 150 150

    NW-LF 2000 A 150 150

    25003000 A

    35 RG 35 35 35 35 35 35

    65RJ 65 65 65 65 43 43

    RK 65 65 65 65 65 51

    100

    NW-H 3000 A 100 100 100 59 100 100

    NW-H 6000 A 100 100 100 77 100 100

    RL 100 100 43

    150NW-L 3000 A 150 150

    NW-L 6000 A 150 150

    40006000 A100 NW-H 6000 A 100 100 100 77

    150 NW-L 6000 A 150 1501 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

    Table 8: UL 480 Vac 6001200 A Selective Coordination (continued)

    Key: Series Rated Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    Maximum

    ContinuousCurrentRating

    Type DG DJ LC LE LX LI LXI MG MJ PG PJ PL RG RJ RL

    NT

    N/H

    NT

    L1

    NT

    L

    NT

    LF

    kAIR 1 35 65 65 65 65 200 200 35 65 35 65 100 35 65 100 50 65 100 100

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    29/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 29

    Table 9: UL 600 Vac 100250 A Selective Coordination

    Key: Fully RatedSeriesRated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kAMaximum

    ContinuousCurrentRating

    Type EDB 3 EGB 3 EJB 3 FA FH FJ 3 HD HG HJ HL FI JD JG PG JJ PJ LE LX JL PL KI

    kAIR 1 14kA 18kA 25kA 14 18 25 14 18 25 50 100 14 18 18 25 25 35 35 50 50 100

    100/150 A

    14FA 0.9

    HD 1.3

    18FH 1.4

    HG 1.3 1.3

    25 HJ 1.3 1.3 1.3

    35 NT-N 800/250 A 35

    50

    HL 1.3 1.3 1.3

    NT-H 800/250 A 50

    NW-N 800/250 A 50

    85 NW-H 800/250 A 85

    100NW-L 800/250 A 100

    NW-LF 800/250 A 100

    250 A

    14 JD 2.3 2.3

    18JG 2.4 2.4 2.4 2.4 2.4 2.4

    PG 18 18 18 18

    25JJ 3 3 3 3 3 3 3 3

    PJ 25 9 25 25

    35 NT-N 800/250 A 35

    50

    JL 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

    NT-H 800/250 A 50

    NW-N 800/250 A 50

    PK 22 5085 NW-H 800/250 A 85

    100NW-L 800/250 A 100

    NW-LF 800/250 A 100

    400 A

    18

    DG 3.2 3.2 3.2 3.2

    MG 3.6 3.6 3.6 3.6

    PG 18 18 18 18 18 18 18

    25

    DJ 3.2 3.2 3.2 3.2

    LH 3.2 3.2 3.2 3.2 3.2

    MJ 3.6 3.6 3.6 3.6 3.6 3.6

    PJ 25 9 25 25 25 9 9

    35 NT-N 1200 A 35 35 35 35

    50NT-H 1200 A 50 50 36

    PK 50 50 5085 NW-H 2000 A 85 85

    100NW-L 1600 A 100 100

    NW-LF 1600 A 100 100

    600 A 18

    DG 4.8 4.8 4.8 4.8

    MG 5.4 5.4 5.4 5.4 5.4 5.4

    PG 18 18 18 18 18 18 18

    RG 18 18 18 18 18 18 18

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    30/52

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    31/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 31

    1200 A

    25PJ 9 25 25 25 9 9

    RJ 25 25 25 25 25 25

    35 NT-N 1200 A 35 35 35 35

    50

    NT-H 1200 A 50 50 36

    NW-N 2000 A 50 50 36

    PK 50 50

    RL 50 50 43

    65 RK 65 65

    85NW-H 2000 A 85 85

    NW-H 3000A 85 85

    100

    NW-L 2000 A 100 100

    NW-L 3000 A 100 100

    NW-LF 1600 A 100 100

    1600 A

    18 RG 18 18 18 18 18 18

    25 RJ 25 25 25 25 25

    50NW-N 2000 A 50 50 36

    RL 50 50

    65 RK 51 65

    85NW-H 2000 A 65 85

    NW-H 3000 A 85 85

    100

    NW-L 2000 A 85 100

    NW-L 3000 A 100 100

    NW-LF 1600 A 100 100

    2000 A

    18 RG 18 18 18 18 18 18

    25 RJ 25 25 25 25 25 25

    50NW-N 2000 A 50 50 36

    RL 50 50 43

    65 RK 51 65

    85 NW-H 2000 A 65 85

    2000 A

    85 NW-H 3000 A 85 85

    100

    NW-L 2000 A 85 100

    NW-L 3000 A 100 100

    NW-LF 2000 A 100 100

    2500 A

    18 RG 18 18 18 18 18

    25 RJ 25 25 25 25 25 25

    50 RL 50 43 4365 RK 51 51

    85 NW-H 3000 A 65 65

    100 NW-L 3000 A 100 100

    3000 A85 NW-H 3000 A 85 85

    100 NW-L 3000 A 100 100

    Table 9: UL 600 Vac 100250 A Selective Coordination (continued)

    Key: Fully Rated SeriesRated

    Upstream Circuit Breaker 2 Downstream Circuit Breaker - Type / kAIRMaximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type EDB 3 EGB 3 EJB 3 FA FH FJ 3 HD HG HJ HL FI JD JG PG JJ PJ LE LX JL PL KI

    kAIR 1 14kA 18kA 25kA 14 18 25 14 18 25 50 100 14 18 18 25 25 35 35 50 50 100

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    32/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved32

    40006000 A85 NW-H 6000 A 85 85

    100 NW-L 6000 A 100 1001 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.3 Rated 600 Y / 347 Vac

    Table 9: UL 600 Vac 100250 A Selective Coordination (continued)

    Key: Fully Rated SeriesRated

    Upstream Circuit Breaker 2 Downstream Circuit Breaker - Type / kAIRMaximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type EDB 3 EGB 3 EJB 3 FA FH FJ 3 HD HG HJ HL FI JD JG PG JJ PJ LE LX JL PL KI

    kAIR 1 14kA 18kA 25kA 14 18 25 14 18 25 50 100 14 18 18 25 25 35 35 50 50 100

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    33/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 33

    Table 10: UL 600 Vac 400 A Selective Coordination

    Key: Fully Rated Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type PG DG LA LH DJ PJ LC LE LX PL LI LXI

    kAIR 1 18 18 22 25 25 25 35 35 35 50 100 100

    600 A

    18

    DG 4.8

    MG 5.4 5.4 18 18

    PG 18 18 18 18

    RG 18 18 18 18 18

    25

    DJ 4.8

    MJ 5.4 5.4 5.4 5.4

    PJ 9 9 9 9

    RJ 25 25 25 25 25

    35 NT-N 1200 A 35 35 35 35

    50

    NT-H 1200 A 36 50 50

    NW-N 2000 A 36 35 50

    PK 22 22 22

    RL 43 50 50

    65 RK 65 65 65 65 65 65

    85 NW-H 2000 A 85 85

    100NW-L 1600 A 100 100

    NW-LF 1600 A 22 22

    800 A

    18

    MG 7.2 7.2 7.2 7.2

    PG 18 18 18 18

    RG 18 18 18 18 18

    25

    MJ 7.2 7.2 7.2 7.2 7.2

    PJ 9 9 9 9 9

    RJ 25 25 25 25 25 2535 NT-N 1200 A 35 35 35 36

    50

    NT-H 1200 A 36 50 50

    NW-N 2000 A 36 50 50

    PK 22 22

    RL 43 50 50

    65 RK 65 65 65 65 65

    85 NW-H 2000 A 85 85

    100NW-L 1600 A 100 100

    NW-LF 1600 A 22 22

    1000 A

    18PG 18 18 18 18

    RG 18 18 18 18 18

    25PJ 9 9 9 9

    RJ 25 25 25 25 25

    35 NT-N 1200 A 35 35 35 36

    50

    NT-H 1200 A 50 36 50 50

    NW-N 2000 A 36 50 50

    PK 22 22

    RL 43 50 50

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    34/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved34

    1000 A

    65 RK 65 65 65 65 65

    85NW-H 2000 A 85 85

    NW-H 3000 A 85 85

    100

    NW-L 1600 A 100 100

    NW-L 3000 A 100 100

    NW-LF 1600 A 22 22

    1200 A

    18PG 18 18 18 18

    RG 18 18 18 18 18

    25PJ 9 9 9 9

    RJ 25 25 25 25 25

    35 NT-N 1200 A 35 35 35 36

    50

    NT-H 1200 A 36 50 50

    NW-N 2000 A 36 50 50

    PK 22 22

    RL 43 50 50

    65 RK 65 65 65 65 65

    85NW-H 2000 A 85 85

    NW-H 3000 A 85 85

    100

    NW-L 1600 A 100 100

    NW-L 3000 A 100 100

    NW-LF 1600 A 22 22

    1600 A

    18 RG 18 18 18 18 18

    25 RJ 25 25 25 25 25

    50 NW-N 2000 A 36 50 50RL 43 50 50

    65 RK 65 65 65 65 65

    85NW-H 2000 A 85 85

    NW-H 3000 A 85 85

    100

    NW-L 1600 A 100 100

    NW-L 3000 A 100 100

    NW-LF 1600 A 22 22

    2000 A

    18 RG 18 18 18 18 18

    25 RJ 25 25 25 25 25

    50NW-N 2000 A 36 50 50

    RL 43 50 50

    65 RK 65 65 65 65 65

    85 NW-H 2000 A 85 85NW-H 3000 A 85 85

    100

    NW-L 2000 A 100 100

    NW-L 3000 A 100 100

    NW-LF 2000 A 22 22

    Table 10: UL 600 Vac 400 A Selective Coordination (continued)

    Key: Fully Rated Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    Maximum

    ContinuousCurrentRating

    Type PG DG LA LH DJ PJ LC LE LX PL LI LXI

    kAIR 1 18 18 22 25 25 25 35 35 35 50 100 100

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    35/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 35

    2500 A

    18 RG 18 18 18 18 18

    25 RJ 25 25 25 25 25

    50 RL 43 50 50

    65 RK 65 65 65 65 65

    85 NW-H 3000 A 85 85

    100 NW-L 3000 A 100 100

    3000 A85 NW-H 3000 A 85 85

    100 NW-L 3000 A 100 100

    40006000 A

    85 NW-H 6000 A 85 85

    100 NW-L 6000 A 100 1001 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

    Table 10: UL 600 Vac 400 A Selective Coordination (continued)

    Key: Fully Rated Series Rated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    Maximum

    ContinuousCurrentRating

    Type PG DG LA LH DJ PJ LC LE LX PL LI LXI

    kAIR 1 18 18 22 25 25 25 35 35 35 50 100 100

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    36/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved36

    Table 11: UL 600 Vac 6001200 A Selective Coordination

    Key:FullyRated

    SeriesRated

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kAMaximum

    ContinuousCurrentRating

    Type

    DG DJ LC LE LX LI LXI MG MJ PG PJ PK RG RJ RL RKNT NT

    N H

    kAIR 1 18 25 35 35 35 100 100 18 25 18 25 50 18 25 50 65 35 50

    800 A

    18

    MG 7.2 7.2 7.2 7.2

    PG 18 18 18 18 18

    RG 18 18 18 18 18 18

    25

    MJ 7.2 7.2 7.2 7.2

    PJ 9 9 9 9 9

    RJ 25 25 25

    35 NT-N 1200 A 35 35 35

    50

    NT-H 1200 A 50 50

    NW-N 2000 A 50 50 36

    PK 22 22

    RL 50 50

    65 RK 65 65 65 65 65

    85 NW-H 2000 A 85 85

    100NW-L 1600 A 100 100

    NW-LF 1600 A 22 22

    1000 A

    18PG 18 18 18 18 18

    RG 18 18 18 18 18 18

    25PJ 9 9 9 9 9

    RJ 25 25 25 25 25 25

    35 NT-N 1200 A 35 35 35 36

    50

    NT-H 1200 A 50 50 36

    NW-N 2000 A 50 50 36 36 36PK 22 22

    RL 50 50 43

    65 RK 65 65 65 65 65 65

    85NW-H 2000 A 85 85

    NW-H 3000 A 85 85

    100

    NW-L 1600 A 100 100

    NW-L 3000 A 100 100

    NW-LF 1600 A 22 22

    1200 A

    18PG 18 18 18 18 18

    RG 18 18 18 18 18 18

    25PJ 9 9 9 9 9 9

    RJ 25 25 25 25 25 25

    35 NT-N 1200 A 35 35 35 36

    50

    NT-H 1200 A 50 50 36

    NW-N 2000 A 50 50 36 36 36

    PK 22 22

    RL 50 50 43

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    37/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 37

    1200 A

    65 RK 65 65 65 65 65 65

    85NW-H 2000 A 85 85 36

    NW-H 3000 A 85 85 85

    100

    NW-L 1600 A 100 100 32

    NW-L 3000 A 100 100 100

    NW-LF 1600 A 22 22 22

    1600 A

    18 RG 18 18 18 18 18 18

    25 RJ 9 9 9 9 9 9

    50NW-N 2000 A 50 50 36 36

    RL 50 50 43

    65 RK 65 65 65 65 65

    85NW-H 2000 A 85 85

    NW-H 3000 A 85 85

    100

    NW-L 1600 A 100 100

    NW-L 3000 A 100 100

    NW-LF 1600 A 22 22

    2000 A

    18 RG 18 18 18

    25 RJ 9 9 9

    50NW-N 2000 A 50 50 36 36 36

    RL 50 50 43

    65 RK 65 65 65 65 65

    85NW-H 2000 A 85 85

    NW-H 3000 A 85 85

    100

    NW-L 2000 A 100 100

    NW-L 3000 A 100 100

    NW-LF 2000 A 22 22

    2500 A

    18 RG 18 18 18 18 18 18

    25 RJ 9 9 9 9 9 9

    50 RL 50 50 43

    65 RK 65 65 65 65 65

    85 NW-H 3000 A 85 85

    100 NW-L 3000 A 100 100

    3000 A85 NW-H 3000 A 85 85

    100 NW-L 3000 A 100 100

    4000

    6000 A

    85 NW-H 6000 A 85 85

    100 NW-L 6000 A 100 1001 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

    Table 11: UL 600 Vac 6001200 A Selective Coordination (continued)

    Key: FullyRated

    SeriesRated

    Upstream Circuit Breaker 2 Downstream Circuit Breaker - Type / kAIRMaximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type

    DG DJ LC LE LX LI LXI MG MJ PG PJ PK RG RJ RL RK NT NTN H

    kAIR 1 18 25 35 35 35 100 100 18 25 18 25 50 18 25 50 65 35 50

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    38/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved38

    APPENDIX B

    Levels of Short Circuit SelectiveCoordination for UL 489 LA/LH MissionCritical Circuit Breakers

    The following data for UL 489 Listed LA and LH Mission Critical circuitbreakers also applies to CSA C22.2 #5-02 Certified circuit breakers. Alldata is at 60 Hz. The data does not apply to circuit breakers that areCertified to ANCE NMX J-266, or IEC 60947-2 only, or at frequenciesother than 60 Hz.Based on laboratory testing, Square D certifies the following levels ofselective coordination based upon the construction of the specific circuitbreakers referenced as of the date of publication of this document.

    Table 12: UL 208 Y / 120 Vac QO/B 1550 A Downstream Circuit Breakers

    Key: Fully Rated Series Rated

    UpstreamCircuit Breaker

    Downstream Circuit Breaker - Type / Ampacity / Voltage Rating / Number of Poles / kAIRMaximum Level of Selective Coordination Shown in kA

    Max.Contin-

    uousCurrentRating

    Type QO/B

    15 A 20 A 30 A 40 A 50 A

    1 Pole

    120 V

    2 Pole

    120/240 V

    3 Pole

    240 V

    1 Pole

    120 V

    2 Pole

    120/240 V

    3 Pole

    240 V

    1 Pole

    120 V

    2 Pole

    120/240 V

    3 Pole

    240 V

    1 Pole

    120 V

    2 Pole

    120/240 V

    3 Pole

    240 V

    1 Pole

    120 V

    2 Pole

    120/240 V

    3 Pole

    240 VkAIR 1 10 kAIR

    200 A

    42 LA-MC

    18 2 18 2 16 2 18 2 18 2 10 2 72 10 2 6.5 2 7 7 6 6 6 5.5

    225 A 18 2 18 2 18 2 18 2 18 2 16 2 11 2 18 2 82 10 10 7.5 10 10 7

    250 A 18 2 18 2 18 2 18 2 18 2 18 2 18 2 18 2 14 2 10 10 10 10 10 9

    400 A 18 2 18 2 18 2 18 2 18 2 18 2 18 2 18 2 18 2 10 10 10 10 10 10

    200 A

    65 LH-MC

    18 2 18 2 16 2 18 2 18 2 10 2 72 10 2 6.5 2 7 7 6 6 6 5.5

    225 A 18 2 18 2 18 2 18 2 18 2 16 2 11 2 18 2 82 10 10 7.5 10 10 7

    250 A 18 2 18 2 18 2 18 2 18 2 18 2 18 2 18 2 14 2 10 10 10 10 10 9

    400 A 18 2 18 2 18 2 18 2 18 2 18 2 18 2 18 2 18 2 10 10 10 10 10 101 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 The Panelboard in which the QO circuit breaker is located is fully rated 10 kA and series rated 18 kA.

    Table 13: UL 208 Y / 120 Vac QO/B 60100 A Downstream Circuit Breakers

    Key: FullyRated

    Series Rated

    UpstreamCircuit Breaker

    Downstream Circuit Breaker - Type / Ampacity / Voltage Rating / Number o f Poles / kAIRMaximum Level of Selective Coordination Shown in kA

    Max.Continuous

    Current Rating

    Type QO/B

    60 A 70 A 80 A 90100 A

    1 Pole120 V

    2 Pole120/240 V

    3 Pole240 V

    1 Pole120 V

    2 Pole120/240 V

    3 Pole240 V

    2 Pole120/240 V

    3 Pole240 V

    2 Pole120/240 V

    3 Pole240 V

    kAIR 1 10 kAIR

    200 A

    42 LA-MC

    52 62 52 52 62 52 5 5 5 5

    225 A 8 2 10 2 6.5 2 72 10 2 62 8 6 6 6

    250 A 10 2 10 2 82 10 2 10 2 7.5 2 10 7.5 10 7.5400 A 10 2 10 2 10 2 10 2 10 2 10 2 10 10 10 10

    200 A

    65 LH-MC

    52 62 52 52 62 52 5 5 5 5

    225 A 8 2 10 2 6.5 2 72 10 2 62 8 6 6 6

    250 A 10 2 10 2 82 10 2 10 2 7.5 2 10 7.5 10 7.5

    400 A 10 2 10 2 10 2 10 2 10 2 10 2 10 10 10 101 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 The Panelboard in which the QO circuit breaker is located is fully rated 10 kA and series rated 18 kA.

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    39/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 39

    Table 14: UL 208 Y / 120 Vac QO/B-VH 1550 A Downstream Circuit Breakers

    Key: Fully Rated Series Rated

    UpstreamCircuit Breaker

    Downstream Circuit Breaker - Type / Ampacity / Voltage Rating / Number of Poles / kAIRMaximum Level of Selective Coordination Shown in kA

    Max.Contin-

    uousCurrentRating

    Type QO/B-VH

    15 A 20 A 30 A 40 A 50 A

    1 Pole120 V

    2 Pole120/240 V

    3 Pole240 V

    1 Pole120 V

    2 Pole120/240 V

    3 Pole240 V

    1 Pole120 V

    2 Pole120/240 V

    3 Pole240 V

    1 Pole120 V

    2 Pole120/240 V

    3 Pole240 V

    1 Pole120 V

    2 Pole120/240 V

    3 Pole240 V

    kAIR 1 22 kAIR

    200 A

    42 LA-MC

    22 22 16 22 22 10 7 10 6.5 7 7 6 6 6 5.5

    225 A 22 22 18 22 22 16 11 22 8 11 18 7.5 10 18 7

    250 A 22 22 18 22 22 18 22 22 14 22 18 10 12 18 9

    400 A 22 22 18 22 22 18 22 22 18 22 22 18 22 22 18

    200 A

    65 LH-MC

    22 22 16 22 22 10 7 10 6.5 7 7 6 6 6 5.5

    225 A 22 22 18 22 22 16 11 22 8 11 18 7.5 10 18 7

    250 A 22 22 18 22 22 18 22 22 14 22 18 10 12 18 9

    400 A 22 22 18 22 22 18 22 22 18 22 22 18 22 22 181

    This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuitbreaker.

    Table 15: UL 208 Y / 120 Vac QO/B-VH 60100 A Downstream Circuit Breakers

    Key:FullyRated

    Series Rated

    UpstreamCircuit Breaker

    Downstream Circuit Breaker - Type / Ampacity / Voltage Rating / Number of Poles / kAIRMaximum Level of Selective Coordination Shown in kA

    Max.Continuous

    Current Rating

    Type QO/B-VH

    60 A 70 A 80 A 90100 A

    1 Pole120 V

    2 Pole120/240 V

    3 Pole240 V

    1 Pole120 V

    2 Pole120/240 V

    3 Pole240 V

    2 Pole120/240 V

    3 Pole240 V

    2 Pole120/240 V

    3 Pole240 V

    kAIR 1 22 kAIR

    200 A

    42 LA-MC

    5 6 5 5 6 5 5 5 5 5

    225 A 8 13 6.5 7 10 6 8 6 6 6

    250 A 10 13 8 10 11 7.5 11 7.5 10 7.5

    400 A 22 22 18 22 22 18 22 18 22 18

    200 A

    65 LH-MC

    5 6 5 5 6 5 5 5 5 5

    225 A 8 13 6.5 7 10 6 8 6 6 6

    250 A 10 13 8 10 11 7.5 11 7.5 10 7.5

    400 A 22 22 18 22 22 18 22 18 22 181 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    40/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved40

    Table 16: UL 480 Y / 277 Vac ED Downstream Circuit Breakers

    Key: Fully Rated Series Rated

    UpstreamCircuit Breaker

    Downstream Circuit Breaker - Type / Ampacity / kAIRMaximum Level of Selective Coordination Shown in kA

    Max.

    Contin-uousCurrentRating

    Type ED

    15 A 20 A 30 A 40 A 50100A

    kAIR 1 18 kAIR

    200 A

    30 LA-MC

    18 10 6 6 6

    225 A 18 14 8 7 7

    250 A 18 18 18 10 8

    400 A 18 18 18 18 18

    200 A

    35 LH-MC

    18 10 6 6 6

    225 A 18 14 8 7 7

    250 A 18 18 18 10 8

    400 A 18 18 18 18 181 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.

    Table 17: UL 480 Y / 277 Vac EG Downstream Circuit Breakers

    Key: Fully Rated Series Rated

    UpstreamCircuit Breaker

    Downstream Circuit Breaker - Type / Ampacity / kAIRMaximum Level of Selective Coordination Shown in kA

    Max.Contin-

    uousCurrentRating

    Type EG

    15 A 20 A 30 A 40 A 50100A

    kAIR 1 35 kAIR

    200 A

    30 LA-MC

    18 10 6 6 6

    225 A 18 14 8 7 7

    250 A 18 18 18 10 8

    400 A 18 18 18 18 18

    200 A

    35 LH-MC

    18 10 6 6 6225 A 18 14 8 7 7

    250 A 18 18 18 10 8

    400 A 18 18 18 18 181 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    41/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 41

    APPENDIX C

    Levels of Short Circuit SelectiveCoordination for ANSI Low VoltagePower Circuit Breakers

    The data in the following tables for ANSI C37.13 and C37.50, UL 1066Listed, low voltage power circuit breakers also applies to CSA C22.2 #31-M89 Certified low voltage power circuit breakers. All data is at60 Hz. The data does not apply to circuit breakers that are UL 489 Listed,or Certified to IEC 60947-2 only, or at frequencies other than 60 Hz.Fully rated pairs of circuit breakers where there is a reasonable expectationof selective coordination are shown. Pairings of the same frame circuitbreakers are not shown, as such pairings would not be expected toselectively coordinate.Based on laboratory testing, Square D certifies the following levels ofselective coordination based upon the construction of the specific circuitbreakers referenced as of the date of publication of this document.

    Appendix C

    Type VoltsDownstream

    Circuit Breaker(frame size)

    Table No. Page No.

    ANSI

    240

    800 A

    18 41

    480 19 42

    600 20 43

    240

    1600 A

    21 44

    480 22 45

    600 23 46

    240

    2000 A

    24 47

    480 25 47

    600 26 48

    Table 18: ANSI 240 Vac 800 A Selective Coordination

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type NT-N1 NW-N1 NW-H1 NW-H2 NW-H3 NW-L1 NW-L1F

    kAIR 1 42 42 65 85 100 200 200

    800 A 42 NW-N1 1600 A 42

    1600 A

    42 NW-N1 1600 A 42

    65 NW-H1 3200 A 65

    85 NW-H2 3200 A 85

    100

    NW-H3 1600 A

    NW-H3 3200 A 100

    200NW-L1 1600 A

    NW-L1 3200 A 200 200

    2000 A

    65NW-H1 2000 A 65

    NW-H1 3200 A 65

    85

    NW-H2 2000 A 85

    NW-H2 3200 A 85

    NW-H2 5000 A 85

    100

    NW-H3 2000 A 77

    NW-H3 3200 A 77

    NW-H3 5000 A 77

    200

    NW-L1 2000 A 32 32

    NW-L1F 2000 A 22 22

    NW-L1 3200 A 200 200

    NW-L1 5000 A 200 200

    3200 A

    65 NW-H1 3200 A 65

    85NW-H2 3200 A 85

    NW-H2 5000 A 85

    100NW-H3 3200 A 77

    NW-H3 5000 A 77

    200NW-L1 3200 A 200 200

    NW-L1 5000 A 200 200

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    42/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved42

    4000 A

    85 NW-H2 5000 A 85

    100 NW-H3 5000 A 77

    200 NW-L1 5000 A 200 200

    5000 A

    85 NW-H2 5000 A 85

    100 NW-H3 5000 A 77

    200 NW-L1 5000 A 200 2001 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

    Table 18: ANSI 240 Vac 800 A Selective Coordination (continued)

    Upstream Circuit Breaker 2 Downstream Circuit Breaker - Type / kAIRMaximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    Current

    Rating

    Type NT-N1 NW-N1 NW-H1 NW-H2 NW-H3 NW-L1 NW-L1F

    kAIR 1 42 42 65 85 100 200 200

    Table 19: ANSI 480 Vac 800 A Selective Coordination

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kAMaximum

    ContinuousCurrentRating

    Type NT-N1 NW-N1 NW-H1 NW-H2 NW-H3 NW-L1 NW-L1F

    kAIR 1 42 42 65 85 100 200 200

    800 A 42 NW-N1 1600 A 42

    1600 A 42

    NW-N1 1600 A 42

    NW-H1 3200 A 65

    NW-H2 3200 A 85

    NW-H3 3200 A 85

    NW-L1 3200 A 200 200

    2000 A

    65NW-H1 2000 A 65

    NW-H1 3200 A 65

    85

    NW-H2 2000 A 85

    NW-H2 3200 A 85

    NW-H2 5000 A 85

    100

    NW-H3 2000 A 77

    NW-H3 3200 A 77

    NW-H3 5000 A 77

    200

    NW-L1 2000 A 32 32

    NW-L1F 2000 A 22 22

    NW-L1 3200 A 200 200

    NW-L1 5000 A 200 200

    3200 A

    65 NW-H1 3200 A 65

    85NW-H2 3200 A 85

    NW-H2 5000 A 85

    100NW-H3 3200 A 77

    NW-H3 5000 A 77

    200NW-L1 3200 A 200 200

    NW-L1 5000 A 200 200

    4000 A

    85 NW-H2 5000 A 85

    100 NW-H3 5000 A 77

    200 NW-L1 5000 A 200 200

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    43/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 43

    5000 A

    85 NW-H2 5000 A 85

    100 NW-H3 5000 A 77

    200 NW-L1 5000 A 200 2001 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

    Table 19: ANSI 480 Vac 800 A Selective Coordination (continued)

    Upstream Circuit Breaker 2 Downstream Circuit Breaker - Type / kAIRMaximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    Current

    Rating

    Type NT-N1 NW-N1 NW-H1 NW-H2 NW-H3 NW-L1 NW-L1F

    kAIR 1 42 42 65 85 100 200 200

    Table 20: ANSI 600 Vac 800 A Selective Coordination

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type NW-N1 NW-H1 NW-H2 NW-H3 NW-L1 NW-L1F

    kAIR 1 42 65 85 85 130 130

    1600 A

    65 NW-H1 3200 A 65

    85 NW-H2 3200 A 85

    85NW-H3 3200 A 85

    NW-L1 3200 A 130 130

    2000 A

    65NW-H1 2000 A 65

    NW-H1 3200 A 65

    85

    NW-H2 2000 A 85

    NW-H2 3200 A 85

    NW-H2 5000 A 85

    85

    NW-H3 2000 A 85

    NW-H3 3200 A 85

    NW-H3 5000 A 85

    130

    NW-L1 2000 A 35 35

    NW-L1F 2000 A 24 24

    NW-L1 3200 A 130 130

    NW-L1 5000 A 130 130

    3200 A

    65 NW-H1 3200 A 65

    85NW-H2 3200 A 85

    NW-H2 5000 A 85

    85NW-H3 3200 A 85

    NW-H3 5000 A 85

    130NW-L1 3200 A 130 130

    NW-L1 5000 A 130 130

    4000 A

    85 NW-H2 5000 A 85

    85 NW-H3 5000 A 85

    130 NW-L1 5000 A 130 130

    5000 A

    85 NW-H2 5000 A 85

    85 NW-H3 5000 A 85

    130 NW-L1 5000 A 130 1301 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    44/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved44

    Table 21: ANSI 240 Vac 1600 A Selective Coordination

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type NW-N1 NW-H1 NW-H2 NW-H3 NW-L1 NW-L1F

    kAIR 1 42 65 85 100 200 200

    2000 A

    65NW-H1 2000 A 65

    NW-H1 3200 A 65

    85

    NW-H2 2000 A 85

    NW-H2 3200 A 85

    NW-H2 5000 A 85

    100

    NW-H3 2000 A 77

    NW-H3 3200 A 77

    NW-H3 5000 A 77

    200

    NW-L1 2000 A 32 32

    NW-L1F 2000 A 22 22

    NW-L1 3200 A 200 200

    NW-L1 5000 A 200 200

    3200 A

    65 NW-H1 3200 A 65

    85NW-H2 3200 A 85

    NW-H2 5000 A 85

    100NW-H3 3200 A 77

    NW-H3 5000 A 77

    200NW-L1 3200 A 200 200

    NW-L1 5000 A 200 200

    4000 A

    85 NW-H2 5000 A 85

    100 NW-H3 5000 A 77

    200 NW-L1 5000 A 200 200

    5000 A

    85 NW-H2 5000 A 85

    100 NW-H3 5000 A 77

    200 NW-L1 5000 A 200 2001 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    45/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 45

    Table 22: ANSI 480 Vac 1600 A Selective Coordination

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type NW-N1 NW-H1 NW-H2 NW-H3 NW-L1 NW-L1F

    kAIR 1 42 65 85 100 200 200

    2000 A

    65NW-H1 2000 A 65

    NW-H1 3200 A 65

    85

    NW-H2 2000 A 85

    NW-H2 3200 A 85

    NW-H2 5000 A 85

    100

    NW-H3 2000 A 77

    NW-H3 3200 A 77

    NW-H3 5000 A 77

    200

    NW-L1 2000 A 32 32

    NW-L1F 2000 A 22 22

    NW-L1 3200 A 200 200

    NW-L1 5000 A 200 200

    3200 A

    65 NW-H1 3200 A 65

    85NW-H2 3200 A 85

    NW-H2 5000 A 85

    100NW-H3 3200 A 77

    NW-H3 5000 A 77

    200NW-L1 3200 A 200 200

    NW-L1 5000 A 200 200

    4000 A

    85 NW-H2 5000 A 85

    100 NW-H3 5000 A 77

    200 NW-L1 5000 A 200 200

    5000 A

    85 NW-H2 5000 A 85

    100 NW-H3 5000 A 77

    200 NW-L1 5000 A 200 2001 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    46/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved46

    Table 23: ANSI 600 Vac 1600 A Selective Coordination

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type NW-N1 NW-H1 NW-H2 NW-H3 NW-L1 NW-L1F

    kAIR 1 42 65 85 85 130 130

    2000 A

    65NW-H1 2000 A 65

    NW-H1 3200 A 65

    85

    NW-H2 2000 A 85

    NW-H2 3200 A 85

    NW-H2 5000 A 85

    85

    NW-H3 2000 A 85

    NW-H3 3200 A 85

    NW-H3 5000 A 85

    130

    NW-L1 2000 A 32 32

    NW-L1F 2000 A 22 22

    NW-L1 3200 A 130 130

    NW-L1 5000 A 130 130

    3200 A

    65 NW-H1 3200 A 65

    85NW-H2 3200 A 85

    NW-H2 5000 A 85

    85NW-H3 3200 A 85

    NW-H3 5000 A 85

    130NW-L1 3200 A 130 130

    NW-L1 5000 A 130 130

    4000 A

    85 NW-H2 5000 A 85

    85 NW-H3 5000 A 85

    130 NW-L1 5000 A 130 130

    5000 A

    85 NW-H2 5000 A 85

    85 NW-H3 5000 A 85

    130 NW-L1 5000 A 130 1301 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    47/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 47

    Table 24: ANSI 240 Vac 2000 A Selective Coordination

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type NW-H1 NW-H2 NW-H3 NW-L1 NW-L1F

    kAIR 1 65 85 100 200 200

    3200 A

    65 NW-H1 3200 A 65

    85NW-H2 3200 A 85

    NW-H2 5000 A 85

    100NW-H3 3200 A 77

    NW-H3 5000 A 77

    200NW-L1 3200 A 200 200

    NW-L1 5000 A 200 200

    4000 A

    85 NW-H2 5000 A 85

    100 NW-H3 5000 A 77

    200 NW-L1 5000 A 200 200

    5000 A

    85 NW-H2 5000 A 85

    100 NW-H3 5000 A 77

    200 NW-L1 5000 A 200 2001 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

    Table 25: ANSI 480 Vac 2000 A Selective Coordination

    Upstream Circuit Breaker 2 Downstream Circuit Breaker - Type / kAIRMaximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type NW-H1 NW-H2 NW-H3 NW-L1 NW-L1F

    kAIR 1 65 85 100 200 200

    3200 A

    65 NW-H1 3200 A 65

    85NW-H2 3200 A 85

    NW-H2 5000 A 85

    100NW-H3 3200 A 77

    NW-H3 5000 A 77

    200NW-L1 3200 A 200 200

    NW-L1 5000 A 200 200

    4000 A

    85 NW-H2 5000 A 85

    100 NW-H3 5000 A 77

    200 NW-L1 5000 A 200 200

    5000 A

    85 NW-H2 5000 A 85

    100 NW-H3 5000 A 77

    200 NW-L1 5000 A 200 2001 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    48/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved48

    Table 26: ANSI 600 Vac 2000 A Selective Coordination

    Upstream Circuit Breaker 2Downstream Circuit Breaker - Type / kAIR

    Maximum Level of Selective Coordination Shown in kA

    MaximumContinuous

    CurrentRating

    Type NW-H1 NW-H2 NW-H3 NW-L1 NW-L1F

    kAIR 1 65 85 85 130 130

    3200 A

    65 NW-H1 3200 A 65

    85NW-H2 3200 A 85

    NW-H2 5000 A 85

    85NW-H3 3200 A 85

    NW-H3 5000 A 85

    130NW-L1 3200 A 130 130

    NW-L1 5000 A 130 130

    4000 A

    85 NW-H2 5000 A 85

    85 NW-H3 5000 A 85

    130 NW-L1 5000 A 130 130

    5000 A

    85 NW-H2 5000 A 85

    85 NW-H3 5000 A 85

    130 NW-L1 5000 A 130 1301 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit

    breaker.2 Number after NW-x indicates frame size.

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    49/52

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    50/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006

    20052006 Schneider Electric All Rights Reserved50

    insulating material, generally 20 to 3000 A in size and used in systems up to600 Vac and 500 Vdc.NMX(Norma Mexicana X) Mexican safety standards. Note to Tech Pubs:This is different than the definition in your glossary, which is incorrect.selective coordination Localization of an overcurrent condition to restrictan outage to the circuit or equipment affected, accomplished by the choice

    of overcurrent protective devices and their ratings or settings. (NEC 100 -Definitions)trip curve A graphical representation of the response of a circuit breakerto current over a period of time.UL See Underwriters Laboratories Inc.Underwriters Laboratories Inc. (UL ) An independent, not-for-profitstandards development, product safety testing and certificationorganization.

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    51/52

    0100DB0501R3/06 Short Circuit Selective Coordination for Low Voltage Circuit Breakers04/2006 Data Bulletin

    20052006 Schneider Electric All Rights Reserved 51

  • 8/11/2019 Short Circuit Selective Coordination for Low Voltage (1)

    52/52

    Short Circuit Selective Coordination for Low Voltage Circuit Breakers 0100DB0501R3/06Data Bulletin 04/2006