35
Shared Services Partnership F iliti S i Facilities Services Fire Compartmentation i H lth in Healthcare Prince Philip Hospital - Thursday 7 th November 2013 Ysbyty Glan Clwyd - Tuesday 19 th November 2013 Royal Glamorgan Hospital Thursday 21 st November 2013 Royal Glamorgan Hospital - Thursday 21 st November 2013

Shared Services Partnership F iliti S iFacilities Services fire precautions and forms of... · impact resistance BS 9999/BS 5234-2. Refer to relevant trade literaturetrade literature

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Shared Services PartnershipF iliti S iFacilities Services

Fire Compartmentationi H lthin Healthcare

Prince Philip Hospital - Thursday 7th November 2013Ysbyty Glan Clwyd - Tuesday 19th November 2013

Royal Glamorgan Hospital Thursday 21st November 2013Royal Glamorgan Hospital - Thursday 21st November 2013

Shared Services PartnershipF iliti S iFacilities Services

Passive Fire Protection andPassive Fire Protection and Forms of Construction

Floors

Floors

All floors are compartment floors min 60 minutes FR

FR measured from undersideFR measured from underside

Constructed from materials of limited combustibility

Concrete (cast in-situ/planks etc)

Consider older building construction (e.g. Lath & plaster g ( g pconstruction).

Timber Floors FR measured from underside

Lath & plaster construction – unlikely to provide even 15 minutes FR without additional protection

No timber floors – existing buildings

Identified through the risk assessment process Identified through the risk assessment process.

Fire Rated Ceilingsg

Fi d ( HTM60) d t t d t bl (l i Firecode (or HTM60) do not accept demountable (lay-in grid) ceilings to contribute to fire resistance

Hazard rooms – where ducts pass through a hazard room a fire resisting ceiling can be provided underneath the ducts to avoid the need for dampersducts to avoid the need for dampers

Period of fire resistance to be a minimum of 30 mins(complete structure including light fittings) when tested(complete structure including light fittings) when tested from below.

Fire Rated Ceilingsg Penetrations and protection – large number of ceiling

t ti i l dipenetrations including: Light fittings, ventilation, speakers, access hatches ....

Lighting Hoodsg g

Ventilation Holes

Over Heatingg

Fire Wall Construction

Bl k k Block work

Dry-lining / Plaster Board (Metal/timber stud)

Board materials

Alternative materials (quilt, firefly, etc)etc)

British Gypsum White Book.....

Lafarge – now known as Siniat.

Fire Walls

Block work up to 4 hours fire resistance and load Block work – up to 4 hours fire resistance and load bearing

Pl t B d Plaster Board Metal/timber stud frames

Very large product range with literally hundreds of combinations of boards for various solutions

V i d f fi i t t 4 h Varying degrees of fire resistance up to 4 hours

Shaft Wall Protected shafts and stairs.

‘Shaft Wall’ Can be constructed

from one side

Up to 4 hours fire presistance

Fire fighting shafts andFire fighting shafts and impact resistance BS 9999/BS 5234-2

Refer to relevant trade literature fortrade literature for

specific board characteristics an

limitationslimitations

Fire Walls

Details available for:AD B cl10.2

Every joint or imperfection Details available for: Junctions

Every joint or imperfection of fit should be adequately

protected by sealing or fi t i Expansion joints

Angles and circular construction

fire-stopping

Deflection heads – suitable head detail or wall designed to resist the additional load from the floor above as the floor sags under fire conditions. Part B para. 8.27 requirementunder fire conditions. Part B para. 8.27 requirement

Varying detail depending on product supplier.

Junctions & Joints

Modular ConstructionModular Construction

M f t d ff it Manufactured off site

Internal or external

Dimensioned off plan

Quality of construction Quality of construction

Speed of construction

Fire stopping detail

Up to 2 hours FR Up to 2 hours FR.

Timber Frame Timber frame – Not allowed in Healthcare in-patient p

facilities (but we do have one)

HTM 05-02 requires elements of structure to beHTM 05 02 requires elements of structure to be constructed from materials of limited combustibility.

Cavity barriersy

Can be solid, fabric or mineral Must provide adequate barrier to the passage of smoke and

flamesflames

Method of fixing important Refer to manufacturers specificationse e to a u actu e s spec cat o s

Service penetrations Use proprietary sealing products in line with the manufacturers y g

specifications

Many different products and solutions Refer to manufacturers specification for materials and fixing

detail.

Quilt Fire BarriersQRefer to relevantRefer to relevant trade literature for specific thickness and performanceand performance.

Quilt Fire B iBarriers

Fixing detail Access – doors Control of maintenance

staff and contractors

Quilt Fire B iBarriers

Fabric Fire B iBarriers

Fire Doors Integrity of fire doors critical to maintainIntegrity of fire doors critical to maintain

compartmentation

High degree of use – continual opening and closing High degree of use – continual opening and closing

Susceptible to damage

Wedging of fire doors - barrier to normal use

Use of automatic door closing devicesUse of automatic door closing devices

All fire doors should have cold smoke protection (except doors in cavity barriers)doors in cavity barriers)

Previous workshops (slides available via website).

Fire Rated Glazing Numerous types of FR Glass &

gyp

Glazing systems(Eg Pilkington Pyrostop® - (EI glazing), Pyrodur® -(EW glazing), Pyroclear® - (E glazing), Pyroshield™)

Firecode imposes size & location restrictions

Beading details are critical forBeading details are critical for effective performance

Labelling Labelling

Reglazing.

Firecode Glazing RestrictionsGlazing in a compartment wall

gGlazing in a compartment wall

6.12 Any glazing provided in a compartment wall should have the same period of fire resistance (integrity and insulation) as the p ( g y )compartment wall.

Glazing should have a permanent, legible mark giving the manufacturer, product name, fire resistance rating and any requirement for impact safety performance according to BS 6206 or BS EN 12600.

Firecode Glazing RestrictionsGlazing in sub-compartment walls5 29 Uninsulated fire resisting glazed screens may only be provided in

g5.29 Uninsulated fire-resisting glazed screens may only be provided in

sub-compartment walls provided they satisfy the following requirements:a. the glazing should provide a minimum period of 30 minutes’ fire

resistance (integrity only);b. the area of integrity-only glazing should be limited to a maximum of b t e a ea o teg ty o y g a g s ou d be ted to a a u o

1000 mm2 in any room.5.30 There is no limit on the use of glazed screens that provide a

minimum period of fire resistance of 30 minutes (integrity andminimum period of fire resistance of 30 minutes (integrity and insulation).

5.31 Where sprinklers are fitted, there is no limit on the use of glazed screens that provide a minimum period of fire resistance of 30 minutes (integrity only), provided the glass is not of the type referred to as “modified toughened”.g

Firecode Glazing RestrictionsGlazed screens Fire hazard rooms and areas

gGlazed screens - Fire hazard rooms and areas

6.32 The maximum area of uninsulated glazing should be limited to 1000 mm² in any one room, and should only be provided in walls y , y penclosing the following fire hazard rooms:

a. dayrooms;

b. laboratories;

c. laundry – between supervising office and work area only.y p g y

6.33 There is no limit on the use of glazed screens which provide a minimum period of fire resistance of 30 minutes when tested to th l t t f BS 476 (i t it d i l ti ) BS ENthe relevant parts of BS 476 (integrity and insulation) or BS EN 12600.

Insulated Sandwich Panels Composite Panelsp

• PIR/PUR/mineral fibre

Overview of types and uses Overview of types and uses• cold rooms, kitchens, external insulation and cladding

Hazard notice reference NHS Estates IN(2003)02• Issued in 2003, provides further advice

Appendix F HTM05/02• Details on fire behaviour of insulating core panelseta s o e be a ou o su at g co e pa e s

• Recommends mineral fibre cores for most applications.

Insulated Sandwich PanelsInsulated Sandwich Panels• Importance of correct detailing and fixing installation• Importance of correct detailing and fixing installation

Fire performance – modern lpanels

PIR panel performed wellDid t t ib t t Did not contribute to the fire

Older panels Older panels problematic

Roseparkp