Series LF008PCQT Health Hazard, Anti-Siphon, Spill-Resistant Backflow Preventer  Sizes: 3  ⁄ 8", 1  ⁄ 2", 3  ⁄ 4" and 1" (10, 15, 20, 25mm) Series LF008PCQT is designed for indoor point-of-use applica- tions to prevent backsiphonage of contaminated water back into the potable water supply. Separation of the water supply from the air inlet is accomplished by means of a diaphragm seal. This feature protects against any spillage during start-up or operation. The LF008PCQT features Lead Free* construc- tion to comply with Lead Free* installation requirements. Features Standardly supplied with i nternal polymer coating Standardly supplied with Tee handle s Available less Tee handle with stem wrench flats. For use where space is limited Available in left-hande d or right-handed outlet Spill-resistant de sign for indoor use • Affordable design Modular cartridge for ease of service Vent uses an O-ring for reliable operati on Lead Free* cast copper silicon a lloy body for durability Compact space saving design Satin chrome f inish available Installation  The LF008PCQT is designed to be installed at the point- of-use. When factory installed deck/machine mounted on machines or equipment, the critical level of the LF008PCQT shall be not less than 1" (25mm) above the flood rim. If field applied for general plumbing applications, the critical level of the LF008PCQT shall be a minimum of 6" (150mm) above the flood rim. Specifications  A spill-resistant vacuum breake r (SVB) shall be installed, in accordance with the manufacturer’s instructions, as noted on the plans. The valve shall consist of a one-piece modu- lar check and float assembly made of engineered thermo- plastic and housed in a Lead Free* cast copper silicon alloy body. Springs shall be stainless steel. The Health Hazard,  Anti-Siphon, Spill Resistant Back flow Preventer shall be con- structed using Lead Free* materials. Lead Free* Health Hazard,  Anti-Siphon, Spill Resistant Back flow Preventer shall comply with state codes and standards, where applicable, requiring reduced lead content. The valve shall be constructed with a molded diaphragm separat ing the air inlet from the potable water supply to prevent spillage. The valve shall be a Watts Series LF008PCQT.  For Health Hazard and Continuo us Pressure Application s ES-LF008PCQT LF008PCQT LF008PCQT-L (Left Handed) LF008PCQT (Right Handed) FOR INDOOR USE! Hood Screws (2 Requred) Vent Sprng Ar Bleed Screw Bleed O-rng (not shown) Test Cock Shutoff Valve Assebly (2 Requred) Hood Bonnet O-rng Vent O-rng Body Retaner Check Assebly Size: 3  ⁄ 8", 1  ⁄ 2" (10, 15mm) Hood Bonnet O-rng Vent O-rng Body Retaner Check Assebly Hood Screw Vent Sprng Ar Bleed Screw Bleed O-rng (not shown) Test Cock Shutoff Valve Assebly (2 Requred) Size: 3  ⁄ 4", 1" (20, 25mm) Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, constructio n, specifications, or materials with- out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold. LEAD FREE *The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight. Job Name ––––––––––––––––––––––––––––––––––––––––––– Contractor –––––––––––––––––––––––––––––––––––––––––––– Job Location ––––––––––––––––––––––––––––––––––––––––– Approval ––––––––––––––––––––––––––––––––––––––––––––– Engineer ––––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––  Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative ––––––––––––––––––––––––––––––––––––––––

Series LF008PCQT Specification Sheet

  • Upload
    watts

  • View
    219

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Series LF008PCQT Specification Sheet

8/8/2019 Series LF008PCQT Specification Sheet

http://slidepdf.com/reader/full/series-lf008pcqt-specification-sheet 1/2

Series LF008PCQTHealth Hazard, Anti-Siphon,Spill-Resistant Backflow Preventer Sizes: 3 ⁄ 8", 1 ⁄ 2", 3 ⁄ 4" and 1" (10, 15, 20, 25mm)

Series LF008PCQT is designed for indoor point-of-use applica-tions to prevent backsiphonage of contaminated water back into the potable water supply. Separation of the water supplyfrom the air inlet is accomplished by means of a diaphragmseal. This feature protects against any spillage during start-upor operation. The LF008PCQT features Lead Free* construc-tion to comply with Lead Free* installation requirements.

Features• Standardly supplied with internal polymer coating• Standardly supplied with Tee handles• Available less Tee handle with stem wrench flats. For use

where space is limited• Available in left-handed or right-handed outlet• Spill-resistant design for indoor use• Affordable design• Modular cartridge for ease of service• Vent uses an O-ring for reliable operation• Lead Free* cast copper silicon alloy body for durability

• Compact space saving design• Satin chrome finish available

Installation The LF008PCQT is designed to be installed at the point-of-use. When factory installed deck/machine mounted onmachines or equipment, the critical level of the LF008PCQT shall be not less than 1" (25mm) above the flood rim. If fieldapplied for general plumbing applications, the critical level of the LF008PCQT shall be a minimum of 6" (150mm) above theflood rim.

Specifications A spill-resistant vacuum breaker (SVB) shall be installed, inaccordance with the manufacturer’s instructions, as notedon the plans. The valve shall consist of a one-piece modu-

lar check and float assembly made of engineered thermo-plastic and housed in a Lead Free* cast copper silicon alloybody. Springs shall be stainless steel. The Health Hazard,

 Anti-Siphon, Spill Resistant Backflow Preventer shall be con-structed using Lead Free* materials. Lead Free* Health Hazard,

 Anti-Siphon, Spill Resistant Backflow Preventer shall complywith state codes and standards, where applicable, requiringreduced lead content. The valve shall be constructed with amolded diaphragm separating the air inlet from the potablewater supply to prevent spillage. The valve shall be a WattsSeries LF008PCQT.

 For Health Hazard and Continuous Pressure Applications

ES-LF008PCQT

LF008PCQT

LF008PCQT-L (Left Handed

LF008PCQT (Right Handed

FOR INDOOR USE!

Hood Screws(2 Requred)

VentSprng Ar Bleed Screw

Bleed O-rng(not shown)

Test Cock 

ShutoffValve Assebly(2 Requred)

Hood

Bonnet

O-rng

VentO-rng

Body

Retaner

Check Assebly

Size: 3 ⁄ 8", 1 ⁄ 2" (10, 15mm)

Hood

Bonnet

O-rng

VentO-rng

Body

Retaner

Check Assebly

Hood Screw

VentSprng Ar Bleed Screw

Bleed O-rng(not shown)

Test Cock 

ShutoffValve Assebly(2 Requred)

Size: 3 ⁄ 4", 1" (20, 25mm)

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,

please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-

out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

LEAD FREE*

*The wetted surface of this product contacted by consumablewater contains less than 0.25% of lead by weight.

Job Name ––––––––––––––––––––––––––––––––––––––––––– Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location ––––––––––––––––––––––––––––––––––––––––– Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer ––––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

 Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative ––––––––––––––––––––––––––––––––––––––––

Page 2: Series LF008PCQT Specification Sheet

8/8/2019 Series LF008PCQT Specification Sheet

http://slidepdf.com/reader/full/series-lf008pcqt-specification-sheet 2/2

Materials

Springs: Stainless steel

Bonnet: PPO

 Vent Disc: EPDM

Disc Holder: PPO

Check Disc: Silicone rubber

Body: Lead Free* cast copper silicon alloy

Pressure – Temperature

 Temperature Range: 33°F – 180°F (0.5°C – 83°C)Maximum Working Pressure: 150psi (10.3 bar)

End Connections

Female NPT - Ball Valve shutoffs

Capacity

 As compiled from documented Foundation for Cross-ConnectionControl and Hydraulic Research at the University of SouthernCalifornia lab tests.

==Typical maximum system flow rate (7.5 feet/sec.)

 A strainer is recommended to be installed ahead of the backflow preventer to prevent the fouling of the check assembly

and resulting spillage from the valve during repressurization. Do not install in concealed locations or areas where water

leakage due to normal wear of the internal parts can cause damage.

Standards

Meets requirements of IAPMO.

 Approvals

D

E

2"

B

kPa ps

69 10

55 8

41 6

28 4

14 2

0 0

0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 gp 0 1.9 3.8 5.7 7.6 9.5 11.4 13.3 15.2  17.1 19 21 lp 

3 ⁄ 8" (10)

∆P

FLOW

kPa ps

97 14

83 12

69 10

55 8

41 628 4

14 2

0 0

0 1 2 3 4 5 6 7 8 9 10 gp 0 3.8 7.6 11.4 15.2 19 22.8 27 30 34 38 lp

7.5 fps2.3 ps 

==

∆P

FLOW

3 ⁄ 4" (20)kPa ps

69 10

55 8

41 6

28 4

14 2

0 00 5 10 15 20 25 30 gp 0 19 38 57 76 95 114 lp

7.5 fps 2.3 ps

∆P

FLOW

0 5 10 15 20 25 30 35 40 45 50 gp 0 19 38 57 76 95 114 135 152 171 190 lp

7.5 fps 2.3 ps

kPa ps

69 10

55 8

41 6

28 4

14 2

0 0

1" (25)

∆P

FLOW

Dimensions — Weights

LF008PCQT

SizE (DN) DimENSiONS WEigHT

B D E

in. mm in. mm in. mm in. mm lbs. kgs.

3 ⁄ 8 10 51 ⁄ 2 140 315 ⁄ 16 100 31 ⁄ 8 79 1.6 .731 ⁄ 2 15 53 ⁄ 4 146 43 ⁄ 16 106 33 ⁄ 8 86 1.7 .773 ⁄ 4 20 7 178 45 ⁄ 8 117 41 ⁄ 2 114 3.8 1.72

1 25 71 ⁄ 2 191 51 ⁄ 8 130 47 ⁄ 8 124 4.8 2.18

1056 B64.1.2

3 ⁄ 4" (20) HoseAdapter wthstraner washer

Supply Hose

Shutoff

Test cock 

Dspensng inducers

Solenod ValvesLF008PCQT-S Watts P60-m1Pressure Reducng Valve

Typical Installation

1" min.(25mm)

ES-LF008PCQT 1318 © 2013 Watts

USA: Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com

Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.watts.ca

 A Watts Water Technologies Company 

==

==

1 ⁄ 2" (15)

NOTICE