3
Series SS07F Stainless Steel Single Detector  Check Valves Sizes: 4" – 10" (100 – 250mm) Series SS07F Stainless Steel Single Detector Check Valves are designed to detect any leakage or unauthorized use of water from fire sprinkler systems. During times of minimal water flow, the valve clapper remains closed so that the water flows through a bypass meter (optional). When fire flow is required, the increased demand will open the clapper to allow full flow. Features • Lightest weight in the industry – reduces shipping and handling costs • Non-corrosive stainless steel construction – eliminates pin holes and voids associated with epoxy coated valves • Can be installed in horizontal/vertical positions • Optional meter bypass assembly (specify GPM or CFM). Required to detect leakage or theft of water • Optional sized bypass tappings available Specifications  The valve body shall be formed, welded un its, in 300 series stainless steel. The valve shall be hydrostatically tested in excess of 700psi. Valve construction shall eliminate any possi- bility of defects such as sand pits and blow holes which may occur in casting. All linkage parts shall be stainless steel. Each valve shall be individually tested before shipping. All 8" and 10" valve sizes shall be equipped with lifting lugs. Valve shall be Watts Regulator Company Series SS07F. Materials Body: 300 Series stainless steel Linkage Parts: stainless steel Pressure – Temperature Maximum Working Pressure: 175psi (12.06 bar)  T emperature Ra nge: 33°F-110°F (5°C-43°C) Standards Flange bolt pattern and hole diameter in accordance with ANSI B16.5 Class 125/AWWA C207 Class D. Body nameplate provides nominal size, direction of flow, psi rating, year of manufactur e and approval marks.  App roval s  For Fire Prote ction Applications ES-SS07F Job Name ––––––––––––––––––––––––––––––––––––––––––– Contractor –––––––––––––––––––––––––––––––––––––––––––– Job Location –––––––––––––––––––––––––––––––––––––––––  Approval ––––––––––––––––––––––––––––––––––––––––––––– Engineer ––––––––––––––––––––––––––––––––––––––––––––– Contract or’s P.O. No. –––––––––––––––––––––––––––––––––––  Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative –––––––––––––––––––––––––––––––––––––––– IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES FOR LOCAL INSTALLATION REQUIREMENTS SS07F 8", 10" SS07F 4", 6" (8" & 10" sizes only) ® Watts product specificatio ns in U.S. customary units and metric are approximate and are provided for reference only.For precise measurements, please contact W atts T echnical Service. Watts reserves th e right to change or modify produc t design, constructio n, specificati ons, or materials wit h- out prior notice and without incurring any obligation to make such changes and modificati ons on Watts products previously or subsequently sold.

Series SS07F Specification Sheet

  • Upload
    watts

  • View
    221

  • Download
    0

Embed Size (px)

Citation preview

8/8/2019 Series SS07F Specification Sheet

http://slidepdf.com/reader/full/series-ss07f-specification-sheet 1/2

Series SS07FStainless Steel Single Detector Check Valves

Sizes: 4" – 10" (100 – 250mm)

Series SS07F Stainless Steel Single Detector Check Valves aredesigned to detect any leakage or unauthorized use of waterfrom fire sprinkler systems. During times of minimal water flow,the valve clapper remains closed so that the water flowsthrough a bypass meter (optional). When fire flow is required,

the increased demand will open the clapper to allow full flow.

Features

• Lightest weight in the industry – reduces shippingand handling costs

• Non-corrosive stainless steel construction – eliminates pinholes and voids associated with epoxy coated valves

• Can be installed in horizontal/vertical positions

• Optional meter bypass assembly (specify GPM or CFM).Required to detect leakage or theft of water

• Optional sized bypass tappings available

Specifications

 The valve body shall be formed, welded units, in 300 seriesstainless steel. The valve shall be hydrostatically tested inexcess of 700psi. Valve construction shall eliminate any possi-bility of defects such as sand pits and blow holes which mayoccur in casting. All linkage parts shall be stainless steel. Eachvalve shall be individually tested before shipping. All 8" and 10"valve sizes shall be equipped with lifting lugs. Valve shall beWatts Regulator Company Series SS07F.

Materials

Body: 300 Series stainless steel

Linkage Parts: stainless steel

Pressure – Temperature

Maximum Working Pressure: 175psi (12.06 bar)

 Temperature Range: 33°F-110°F (5°C-43°C)

Standards

Flange bolt pattern and hole diameter in accordance with ANSIB16.5 Class 125/AWWA C207 Class D.

Body nameplate provides nominal size, direction of flow, psirating, year of manufacture and approval marks.

 Approvals

 For Fire Protection Applications

ES-SS07F

Job Name ––––––––––––––––––––––––––––––––––––––––––– Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––  Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer ––––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. –––––––––––––––––––––––––––––––––––

 Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative ––––––––––––––––––––––––––––––––––––––––

IMPORTANT:  INQUIRE WITH GOVERNING AUTHORITIES 

FOR LOCAL INSTALLATION REQUIREMENTS 

SS07F 8", 10"

SS07F 4", 6"

(8" & 10" sizes only)

®

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only.For precise measurements,

please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-

out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

8/8/2019 Series SS07F Specification Sheet

http://slidepdf.com/reader/full/series-ss07f-specification-sheet 2/2

Capacities

*Head loss at the UL rated flow

Dimensions — Weights

kPa psi69 10

55 8

41 6

28 4

14 2

0 0

0 200 400 600 800 1000 1200 gpm

0 760 1520 2280 3040 3800 4560 lpm

4" (100mm) kPa psi69 10

55 8

41 6

28 4

14 2

0 00 500 1000 1500 2000 gpm

0 1900 3800 5700 7600 lpm

6" (150mm)

kPa psi69 10

55 8

41 6

28 4

14 2

0 00 500 1000 1500 2000 2500 3000 gpm

0 1900 3800 5700 7600 9500 11400 lpm

8" (200mm) kPa psi69 10

55 8

41 6

28 4

14 2

0 00 1000 2000 3000 4000 5000 gpm

0 3800 7600 11400 15200 19000 lpm

10" (250mm)

L S

R

E

B

D

T

L S

R

E

B

D

T

SIZE (DN) DIMENSIONS WEIGHTS

B D E K (NPT) L R S T less Bypass with Bypass

in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm   lb. kg. lb. kg.

4" 100 111 / 2 292 41 / 2 114 127 / 8 327 1 / 2 13 161 / 2 419 8 203 9 229 5 / 8 16 30 13.6 35 15.9

6" 150 131 / 2 343 51 / 2 140 17 432 3 / 4 19 221 / 2 572 101 / 2 267 11 279 11 / 16 17 65 29.5 70 31.8

8" 200 151 / 2 394 63 / 4 171 211 / 4 540 2 51 261 / 2 673 121 / 4 311 131 / 2 343 11 / 16 17 143 64.9 153 69.3

10" 250 171 / 2 445 8 203 281 / 4 718 2 51 36 914 141 / 2 368 16 406 11 / 16 17 163 73.9 173 78.5

   P   r   e   s   s   u   r

   e

   L   o   s   s

Flow Rate Flow Rate

Flow RateFlow Rate

   P   r   e   s   s   u   r   e

   L   o   s   s

   P   r   e   s   s   u   r   e

   L   o   s   s

   P   r   e   s   s   u   r   e

   L   o   s   s

Sizes: 4", 6" Sizes: 8", 10"

ES-SS07F 0830 © Watts, 2008

USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com

Canada: 5435 North Service Rd., Burlington, ONT. L7L 5H7; www.wattscanada.ca

Backf low Prevent ion Products