Upload
marlon-boucaud
View
225
Download
0
Embed Size (px)
Citation preview
8/18/2019 Safety Reliability
1/13
MINIMUM ACCEPTABLE LEVELS
OF SAFETY & RELIABILITY
THE WIRING CODE OF TRINIDAD
AND TOBAGO
TTS 171 PART ONE
PRESENTED BY
• HAYDEN BATSON
• ELECTRICAL INSPECTOR 1
GOVERNMENT ELECTRICAL
INSPECTORATE
8/18/2019 Safety Reliability
2/13
Annex C
• Provides Sub-Circuit rating andrequirements.
• C.1 Gives the maximum sub-circuitratings for domestic, commercial andindustrial premises.
• C.2 Gives the sub-circuitrequirements.
Table C-1
8/18/2019 Safety Reliability
3/13
Section B gives those that are not
shown before
C.2.1
• Ground-fault Circuit Interrupter
protection shall be provided for
personnel (ref sec 210-8 NEC 1999)
in:
• a) Bathrooms
• b) Outdoor receptacles
• c) Garages
• d) Counter tops
• e) Other required locations.
8/18/2019 Safety Reliability
4/13
C.2.2
Additional requirements for
conformity.• Receptacle outlets shall be spaced
approx. 4M along walls in rooms.
• Receptacle outlet and lighting
circuits shall be separated except
by special permission of the CEI.
• The rating for a general purpose
domestic receptacle is 180 VA.
• The minimum height of the service
entrance connection shall be 4M,
observing the minimum clearance of6M over road ways.
• We will maintain the IEE color code.
8/18/2019 Safety Reliability
5/13
INSTALLATION METHODS
The exact current carrying
capacity of conductors isaffected by a number of factors
besides CSA, one of which is the
way they are installed.
Two examples are are shownusing table D.5.D.1
8/18/2019 Safety Reliability
6/13
Example 1
Installing a run of 10 mm2 XLPEinsulated multi-core armored cable:
Using Method 1, a 3 or 4 core cableconnected to a 3-ph ac supply will carry
73A.
Using Method 11, a 3 or 4 core cableconnected as above will carry 78A.
Example 2
Installing a run of 95mm2 XLPEinsulated mult i-core armoured cable.
Using Method 1, a 3 or 4 core cable
connected to a 3-ph ac supply willcarry 289A.
Using Method 11, a 3 or 4 core cableconnected to a 3-ph ac supply will
carry 304A.
8/18/2019 Safety Reliability
7/13
• When using cards with current
rating tables the method of
installation for those valuesmust be observed.
VOLTAGE DROPCONSIDERATIONS
Apart from voltage drop andinstallation methods, factors such as
– ambient temperature
– grouping – thermal insulation
– operating temperature
of the cable also weigh in cableselection.
8/18/2019 Safety Reliability
8/13
Emphasis however must be placedon voltage drop.
WHY?
This value should not exceed 3% inthe circuit of which that cable forms
apart.
Not more than 6.90 V for a
230V 1-ph circuit
Not more than 14.4V for a 480V
3-ph circuit.
8/18/2019 Safety Reliability
9/13
Note also that the maximumallowable drop from the POE to
fixed current using equipmentmust not exceed 4%.
VOLTAGE DROP TABLES
These are tabulated for a
current of 1 Amp and alength of 1 Metre along the
route taken.
8/18/2019 Safety Reliability
10/13
For a balanced 3-ph system the
tables relate to line voltage.
Therefore the total voltage drop per run
Vd = mV x I x L
1000
Where I = current in amps
L = length in metres
& mV = approx voltdrop/amp/metre.
8/18/2019 Safety Reliability
11/13
Example:
Consider a run of 200M to be
installed in air (ref method 13) tocarry a current of 100A from a supplyof 415V 3-ph ac, the cable being ofcopper conductor, XLPE insulated,
armoured and PVC sheathed.
Let mV be voltage drop inmillivolts
Then Vd = mV x I x L
1000
Transposing mV= Vd
x 1000
I x L
8/18/2019 Safety Reliability
12/13
Max permissible voltage drop= 3% of
415V
=12.45V
Inserting values for I, L and maxpermissible voltage drop
Then mV= 12.45 x 1000 =0.62 mV
100 x 200
Referring to the following table.
Select value = to or just less than 0.62mVi.e. 60mV.
8/18/2019 Safety Reliability
13/13
Apply current carrying capacity
table.
This shows that we may
have used a 25 mm2
cable without voltage
drop consideration.
THE END