Safety Reliability

Embed Size (px)

Citation preview

  • 8/18/2019 Safety Reliability

    1/13

    MINIMUM ACCEPTABLE LEVELS

    OF SAFETY & RELIABILITY

    THE WIRING CODE OF TRINIDAD

     AND TOBAGO

    TTS 171 PART ONE

    PRESENTED BY

    • HAYDEN BATSON

    • ELECTRICAL INSPECTOR 1

    GOVERNMENT ELECTRICAL

    INSPECTORATE

  • 8/18/2019 Safety Reliability

    2/13

     Annex C

    • Provides Sub-Circuit rating andrequirements.

    • C.1 Gives the maximum sub-circuitratings for domestic, commercial andindustrial premises.

    • C.2 Gives the sub-circuitrequirements.

    Table C-1

  • 8/18/2019 Safety Reliability

    3/13

    Section B gives those that are not

    shown before

    C.2.1

    • Ground-fault Circuit Interrupter

    protection shall be provided for

    personnel (ref sec 210-8 NEC 1999)

    in:

    • a) Bathrooms

    • b) Outdoor receptacles

    • c) Garages

    • d) Counter tops

    • e) Other required locations.

  • 8/18/2019 Safety Reliability

    4/13

    C.2.2

     Additional requirements for

    conformity.• Receptacle outlets shall be spaced

    approx. 4M along walls in rooms.

    • Receptacle outlet and lighting

    circuits shall be separated except

    by special permission of the CEI.

    • The rating for a general purpose

    domestic receptacle is 180 VA.

    • The minimum height of the service

    entrance connection shall be 4M,

    observing the minimum clearance of6M over road ways.

    • We will maintain the IEE color code.

  • 8/18/2019 Safety Reliability

    5/13

    INSTALLATION METHODS

    The exact current carrying

    capacity of conductors isaffected by a number of factors

    besides CSA, one of which is the

    way they are installed.

    Two examples are are shownusing table D.5.D.1

  • 8/18/2019 Safety Reliability

    6/13

    Example 1

    Installing a run of 10 mm2 XLPEinsulated multi-core armored cable:

    Using Method 1, a 3 or 4 core cableconnected to a 3-ph ac supply will carry

    73A.

    Using Method 11, a 3 or 4 core cableconnected as above will carry 78A.

    Example 2

    Installing a run of 95mm2 XLPEinsulated mult i-core armoured cable.

    Using Method 1, a 3 or 4 core cable

    connected to a 3-ph ac supply willcarry 289A.

    Using Method 11, a 3 or 4 core cableconnected to a 3-ph ac supply will

    carry 304A.

  • 8/18/2019 Safety Reliability

    7/13

    • When using cards with current

    rating tables the method of

    installation for those valuesmust be observed.

    VOLTAGE DROPCONSIDERATIONS

     Apart from voltage drop andinstallation methods, factors such as

     – ambient temperature

     – grouping – thermal insulation

     – operating temperature

    of the cable also weigh in cableselection.

  • 8/18/2019 Safety Reliability

    8/13

    Emphasis however must be placedon voltage drop.

    WHY?

    This value should not exceed 3% inthe circuit of which that cable forms

    apart.

    Not more than 6.90 V for a

    230V 1-ph circuit

    Not more than 14.4V for a 480V

    3-ph circuit.

  • 8/18/2019 Safety Reliability

    9/13

    Note also that the maximumallowable drop from the POE to

    fixed current using equipmentmust not exceed 4%.

    VOLTAGE DROP TABLES

    These are tabulated for a

    current of 1 Amp and alength of 1 Metre along the

    route taken.

  • 8/18/2019 Safety Reliability

    10/13

    For a balanced 3-ph system the

    tables relate to line voltage.

    Therefore the total voltage drop per run

    Vd = mV x I x L

    1000

    Where I = current in amps

    L = length in metres

    & mV = approx voltdrop/amp/metre.

  • 8/18/2019 Safety Reliability

    11/13

    Example:

    Consider a run of 200M to be

    installed in air (ref method 13) tocarry a current of 100A from a supplyof 415V 3-ph ac, the cable being ofcopper conductor, XLPE insulated,

    armoured and PVC sheathed.

    Let mV be voltage drop inmillivolts

    Then Vd = mV x I x L

    1000

    Transposing mV= Vd

    x 1000

    I x L

  • 8/18/2019 Safety Reliability

    12/13

    Max permissible voltage drop= 3% of

    415V

    =12.45V

    Inserting values for I, L and maxpermissible voltage drop

    Then mV= 12.45 x 1000 =0.62 mV

    100 x 200

    Referring to the following table.

    Select value = to or just less than 0.62mVi.e. 60mV.

  • 8/18/2019 Safety Reliability

    13/13

     Apply current carrying capacity

    table.

    This shows that we may

    have used a 25 mm2

    cable without voltage

    drop consideration.

     

    THE END