Upload
ivan-ivanov
View
1.235
Download
10
Embed Size (px)
Citation preview
Germanischer Lloyd / Checklist for Maintenance and Inspection of Safety Equipment 1 Revision 02/2006
Checklist for Maintenance and Inspection of Safety Equipment With this overview of recommendations for maintenance and inspection requirements and recommendations for safety equipment, Germanischer Lloyd provides a compact and practical tool for ship owners, operators and surveyors. New maintenance requirements for such equipment are published irregularly and in various IMO documents and chapters, which makes it cumbersome and time consuming to keep track of all changes. This list contains all requirements regarding safety equipment and includes also requirements and recommendations by Germanischer Lloyd. National requirements, if any, should be observed in addition.
The Use of this "Checklist for Maintenance and Inspection of Safety Equipment" is subject to the following terms:
Disclaimer
1. The information contained and accessed in this publication is provided by GL for general guidance and is intended to offer You general information of interest on a non-binding basis. GL owns all text, data, images and other materials in this publication (except those text, data, images and other materials referred to as “Others” in this publication being third parties contents for which item 2. and 3. below apply). GL has made every effort to ensure that the information contained herein is accurate and reliable. However, errors may sometimes occur. Therefore GL expressly disclaims all express or implied warranties of any kind as to any matter whatsoever relating to this publication. In no event shall GL be liable for any indirect or consequential loss or damage (whether for loss of profit or otherwise) arising out of or in connection with the use of this information. All content, functions, material and information accessed through this publication are provided "as is". GL makes no warranties of any kind whatsoever for the content, material, information and functions accessed through this publication.
All offers are not-binding and without obligation. Parts of or the complete publication including information might be extended, changed or partly or completely deleted by GL without separate announcement.
For the rest, GL can only be held liable for wilful or gross negligent acts and for claims brought under the German law on product liability. Except in case of breach by GL of an essential contractual obligation, liability of GL for negligent performance of its obligations towards clients shall be limited to either five times the remuneration of the individual obligation to which the breach relates or shall be limited to a maximum amount of € 500.000,-- whichever is applicable.
2. Despite the fact that this publication may refer to and/or provide information of third parties, the use of such information of third parties is entirely at own risk and GL is not responsible for loss, expense, claim or damage, whether direct, indirect or consequential, arising from the use of such other third parties information. GL does not adopt these third parties´ information made available through this publication as its own and is not responsible for their contents.
If any damage occurs by the use of information presented there, only the author of the respective pages might be liable, not the one who has referred to these pages.
3. The information contained in this publication is the exclusive property of GL or is licensed to GL and is protected by copyright and other proprietary rights. Nothing contained in this publication may be reproduced, distributed or edited in any manner without the prior written authorisation of GL.
This publication contains trademarks and other industrial property rights which are owned and registered by GL, to distinguish its services. No licence to use any of aforesaid rights is hereby granted or implied. No reproduction is permitted without specific written authorisation.
Germanischer Lloyd / Checklist for Maintenance and Inspection of Safety Equipment 2 Revision 02/2006
All mentioned and registered/protected trademarks of third parties in this publication are absolutely subject to the provisions of the respective effective trade mark and property rights of the respective registered owner. No conclusion can be drawn simply from mentioning in this publication that trade marks are not protected by third parties´ rights.
4. GL reserves the right to change and amend the content of this publication as well as this Disclaimer at any time. In this respect, please take notice of the respective applicable version.
5. Usage of this information is governed by German law. The exclusive place of jurisdiction for any legal action against GL is Hamburg, provided that the user is a merchant in the legal sense.
6. This disclaimer is to be regarded as part of the publication. If sections or individual terms of this statement are not legal or correct, the content or validity of the other parts remain uninfluenced by this fact. If you have any questions about this list or would like to have more details, please contact Germanischer Lloyd, Department NSF, Vorsetzen 35, 20459 Hamburg, Germany: Andreas Ullrich, phone +49(40) 36149-454, [email protected] Michael Oberländer, phone +49(40) 36149-7034, [email protected].
Table of Contents Page 1. Life Saving Appliances 4 2. Fire Fighting Equipment 9 3. Radio Equipment 12 4. Navigational Equipment 12 5. Others 13 Appendixes Bahamas – Maintenance of CO2 Fixed Fire Extinguishing Installations 14 Bahamas – Servicing of inflatable liferafts, inflatable life jackets, marine evacuation systems, inflated rescue boats and hydrostatic release units
15
Bahamas – Portable fire extinguishers: periodical examination and testing and carriage of spare charges
16
Greece – Distribution in the Market, Maintenance, Inspection and Refilling of Ships Fire Extinguishers
18
Hong Kong – Launching Appliances and On-Load Release Gear for Lifeboats and Rescue Boats
20
India – Guidelines for Periodic Servicing and Maintenance of Lifeboats, Launching Appliances and On-Load Release Gear
21
Isle of Man - Lifeboat and rescue boat davit testing and testing of on-load release gear
23
Isle of Man - Wire Rope Terminations for Falls used in Launching Lifeboats and other Survival Craft
27
Isle of Man - Periodic inspection, testing and maintenance of compressed gas cylinders, fire extinguishers and fixed fire-fighting systems
34
Italy – Maintenance/renewal of falls of life-saving appliances and inspection 42 Liberia – Maintenance and Inspection of Fire-Protection Systems and Appliances 44 Malaysia – Requirements for Fixed and Portable Fire Extinguishing Equipment 50 Malta – Fire Protection Systems and Appliances and Compressed Gas Cylinders 51 Marshall Islands - Maintenance and Inspection of Fire-Protection Systems and Appliances
60
Panama - Guidelines for the Maintenance and Inspection of Fire-Protection Systems and Appliances
68
Germanischer Lloyd / Checklist for Maintenance and Inspection of Safety Equipment 3 Revision 02/2006
Singapore – Maintenance, Testing and Inspections of Fire-Protection Systems and Fire-Fighting Systems and Appliances
73
Singapore – Guidelines for Periodic Servicing and Maintenance of Lifeboats, Launching Appliances and On-Load Release Gear
76
UK -- Servicing of inflatable Liferafts, Inflatable Boats, Rescue Boats, Fast Rescue Boats, Inflatable Lifejackets and Hydrostatic Release Units
79
Germanischer Lloyd / Checklist for Maintenance and Inspection of Safety Equipment 4 Revision 02/2006
1. Life Saving Appliances SOLAS Reg.
+ other Instruments Application Record Frequency / Interval
GL
C
arg
o
Sh
ips
Pa
ssen
ger
Ship
s
Log
Boo
k En
try
Serv
ice
Com
pany
1
Sh
ip's
C
rew
SOLAS Requirement
Requirement Recommendation
Survival craft, rescue boats and launching appliances (visual)
III/20.6.1, MSC/Circ. 1093
X X X X weekly
Test run of life- and rescue boat engines III/20.6.2, MSC/Circ. 1093
X X X X weekly
Davit launched lifeboats (moved from stowed position)
III/20.6.3, MSC.152(78)
X X X weekly
Testing of public address and general alarm system
III/20.6.4 X X X X weekly
X X X weekly (Passenger Vessel)
Testing of emergency lighting III/19.3.3.9
X X X monthly (Cargo Vessel) LSA incl. lifeboat equipment acc. to checklist III/20.7.2, MSC/Circ.
1047 X X X X monthly
Davit launched lifeboats (moved from stowed position)
III/20.7.1, MSC.152(78)
X X X X monthly
Germanischer Lloyd / Checklist for Maintenance and Inspection of Safety Equipment 5 Revision 02/2006
SOLAS Reg. + other Instruments Application Record Frequency / Interval
GL
C
arg
o
Sh
ips
Pa
ssen
ger
Ship
s
Log
Boo
k En
try
Serv
ice
Com
pany
Sh
ip's
C
rew
SOLAS Requirement
Requirement Recommendation
Immersion suits: - Shipboard inspection by crew - Air pressure test (seams and closures)
III/20.7, MSC/Circ.1047 MSC/Circ. 1114
X X
X X
X
X monthly 3 yearly
Inflatable liferafts, lifejackets, MES (by approved service station)
III/20.8.1.1 X X X 12 months (administration can allow extension up to 17 months)
Hydrostatic release units (non-disposable) III/20.9.1 X X X 12 months (administration can allow extension up to 17 months)
III/20.4.1 X X X X (X) End for end turning after 30 months and renewal latest after 5 years
Ships crew only if properly trained and familiar with these works
Maintenance of falls used in launching:
III/20.4.2 X X X X (X) Renewal latest after 4 years (+)(without end to end turning), periodic inspections; (+) permission of the Flag State Administration required
Ships crew only if properly trained and familiar with these works
Germanischer Lloyd / Checklist for Maintenance and Inspection of Safety Equipment 6 Revision 02/2006
SOLAS Reg. + other Instruments Application Record Frequency / Interval
GL
C
arg
o
Sh
ips
Pa
ssen
ger
Ship
s
Log
Boo
k En
try
Serv
ice
Com
pany
Sh
ip's
C
rew
SOLAS Requirement
Requirement Recommendation
Launching appliances (thorough examination and dynamic test of the winch brake)
III/20/11.1, MSC.152(78) LSA Code 6.1.2.5.2 MSC/Circ. 1093
X X X X
yearly
Lifeboat on-load release gear (thorough examination and test by properly trained personnel)
III/20.11.2.2 MSC/Circ. 1093
X X X X yearly
Lifeboat on-load release gear (overhauling + load test)
III/20.11.2.3 X X X X
5 yearly
Compressed air cylinders for lifeboats with selfcontained air support system (external inspection)
-- X X -- yearly
Compressed air cylinders for lifeboats with selfcontained air support system (hydrostatic testing)
-- X X -- 5 yearly
Compressed air cylinder in liferaft container (hydrostatic testing)
-- X X X -- 10 yearly
Line-throwing rockets III/18 LSA Code 1.2.3, 7.1
X X X Makers expiry date 3 yearly
Germanischer Lloyd / Checklist for Maintenance and Inspection of Safety Equipment 7 Revision 02/2006
SOLAS Reg. + other Instruments Application Record Frequency / Interval
GL
C
arg
o
Sh
ips
Pa
ssen
ger
Ship
s
Log
Boo
k En
try
Serv
ice
Com
pany
Sh
ip's
C
rew
SOLAS Requirement
Requirement Recommendation
Rocket parachute flares III/6.3 LSA Code 1.2.3, 3.1
X X X Makers expiry date 3 yearly
Smoke signals III/7.1.3 LSA Code 1.2.3, 3.3
X X X Makers expiry date 3 yearly
Lifebuoy lights (electric type) - battery replacement
III/7.1.3 LSA Code 1.2.3, 2.1.2
X X X Makers expiry date 1 yearly
Food rations of lifeboat equipment LSA Code 4.4.8.12 X X X Makers expiry date 5 yearly First-aid outfit of lifeboat equipment III/41.8.20
LSA Code 4.4.8.20 X X X Makers expiry date 1 yearly
Germanischer Lloyd / Checklist for Maintenance and Inspection of Safety Equipment 8 Revision 02/2006
2. Fire Fighting Equipment SOLAS Reg.
+ other Instruments Application Record Frequency / Interval
GL
C
arg
o
Sh
ips
Pa
ssen
ger
Ship
s
Log
Boo
k En
try
Serv
ice
Com
pany
Sh
ip's
C
rew
SOLAS Requirement
Requirement Recommendation
Cylinders of breathing apparatus (Check for leakages)
II-2/10.10.2.5, 19.3.6.2; MSC/Circ. 850
X X X X weekly
Fireman’s outfits, fire extinguishers, fire hydrants, hoses and nozzles in place, properly arranged and in proper condition
MSC/Circ. 850 X X X X monthly
Fixed fire fighting stop valves in proper open or closed position
MSC/Circ. 850 X X X X monthly
Check appropriate pressure of wet pipe sprinkler systems indicated by gauges
MSC/Circ. 850 X X X X monthly
Correct levels of water of sprinkler system pressure tanks indicated by glass gauges
MSC/Circ. 850 X X X X monthly
Sprinkler system pumps operate automatically on reduction of pressure
MSC/Circ. 850 X X X X monthly
Check operation of fire pumps MSC/Circ. 850 X X X X monthly Function test of all automatic alarms for sprinkler systems by using test valves for each section
MSC/Circ. 850 X X X X quarterly
Check condition of international shore connection
MSC/Circ. 850 X X X X quarterly
Germanischer Lloyd / Checklist for Maintenance and Inspection of Safety Equipment 9 Revision 02/2006
SOLAS Reg.
+ other Instruments Application Record Frequency / Interval
GL
C
arg
o
Sh
ips
Pa
ssen
ger
Ship
s
Log
Boo
k En
try
Serv
ice
Com
pany
Sh
ip's
C
rew
SOLAS Requirement
Requirement Recommendation
Test of fire doors and fire dampers for local operation
MSC/Circ. 850 X X X X quarterly
Portable fire extinguishers and mobile fire extinguishers – check for proper location, charging pressure and condition
II-2/10.3; MSC/Circ. 850 IMO Res.A.951(23)(1)
X X X X(2) yearly yearly
Fixed fire extinguishing systems,such as gas-, foam-, powder-, water spray or water mist - Inspection
II-2/10.4; FSS Code (IMO Res. MSC. 98(73))
X X X -- 2 yearly
Foam-water and water-spray fixed fire-fighting systems - operation test
MSC/Circ. 850 X X X X yearly
Test of fire detection system for proper operation
II-2/7.3.2; MSC/Circ. 850
X X X X yearly yearly
CO²-gas and halon cylinders, cylinders of fixed gas fire extinguishing systems - level check
II-2/14; MSC/Circ. 850
X X X -- 2 yearly
Test of fire doors and fire dampers for remote operation
MSC/Circ. 850 X X X X yearly
Fire hoses – hydrostatic test MSC/Circ. 850 X X X X yearly Flow test of fire pumps incl. sprinkler pumps for proper pressure and flow
MSC/Circ. 850 X X X X yearly
(1) for portable fire extinguisher (2) service to be undertaken by, or runder the supervision of, a person with demonstrable competence
Germanischer Lloyd / Checklist for Maintenance and Inspection of Safety Equipment 10 Revision 02/2006
SOLAS Reg. + other Instruments Application Record Frequency / Interval
GL
C
arg
o
Sh
ips
Pa
ssen
ger
Ship
s
Log
Boo
k En
try
Serv
ice
Com
pany
Sh
ip's
C
rew
SOLAS Requirement
Requirement Recommendation
Operation test of all hydrants MSC/Circ. 850 X X X X yearly Operation test of sprinkler system connections from the ship’s fire main
MSC/Circ. 850 X X X X yearly
Check of breathing apparatus air recharging systems for air quality
MSC/Circ. 850 X X X X yearly
Blow air through the piping of extinguishing gas systems
MSC/Circ. 850 X X X X yearly
Control valves of fixed fire-fighting systems – internal inspection
MSC/Circ. 850 X X X 5-yearly
SCBA Cylinders – hydrostatic testing MSC/Circ. 850 X X X 5-yearly Foam concentrate for fixed foam fire extinguishing systems
II-2/14; MSC/Circ. 850; MSC/Circ. 670
X X X 3 years after filling and yearly thereafter
Foam concentrate for portable foam applicator units
Class rules (1)(4) X X X --- 5-yearly
EEBD
MSC/Circ. 849, FSS Code (IMO Res.MSC.98(73))
X X Maintenance according to makers instructions
Germanischer Lloyd / Checklist for Maintenance and Inspection of Safety Equipment 11 Revision 02/2006
SOLAS Reg. + other Instruments Application Record Frequency / Interval
GL
C
arg
o
Sh
ips
Pa
ssen
ger
Ship
s
Log
Boo
k En
try
Serv
ice
Com
pany
Sh
ip's
C
rew
SOLAS Requirement
Requirement Recommendation
CO2 or other gas cylinders (hydrostatic pressure test and internal inspection)¹
Class rules (1)(2) X X X -- 10 yearly (at least 10 %)
Fire extinguishers and associates propellant gas cylinders - hydrostatic pressure test
MSC/Circ. 847 IMO Res.A.951(23)
X X X 10 yearly
CO2 hose assemblies - visual check Class rules (1)(3) X X X 2 yearly CO2 hose assemblies made of synthetic rubber to be replaced
Class rules (1)(3) X X X 10 yearly
¹ except halon cylinders (1) I Ship Technology 0 Classification and Surveys (2) Item B.1.5.5.3 (3) Item C.1.3.3.10.1 (4) Item C.1.1.4
Germanischer Lloyd / Checklist for Maintenance and Inspection of Safety Equipment 12 Revision 02/2006
3. Radio Equipment SOLAS Reg.
+ other Instruments Application Record Frequency / Interval
GL
C
arg
o
Sh
ips
Pa
ssen
ger
Ship
s
Log
Boo
k En
try
Serv
ice
Com
pany
Sh
ip's
C
rew
SOLAS Requirement
Requirement Recommendation
Satellite EPIRBs IV/15.9 X X X (1) X 5-yearly by approved shore-based maintenance facility
Satellite EPIRBs IV/15.9 X X X yearly by approved service supplier
Radio Battery IV/13.6.2 X X X X yearly by approved service supplier
4. Navigational Equipment
Voyage Data Recorder (VDR) V/18.8 X X X (1) (2) X yearly by testing facility
Steering gear V/26 X X X X 12 hours before departure
(1) Certificate of Compliance (2) Maintenance report
Germanischer Lloyd / Checklist for Maintenance and Inspection of Safety Equipment 13 Revision 02/2006
5. Others
SOLAS Reg. + other Instruments Application Record Frequency / Interval
GL
C
arg
o
Sh
ips
Pa
ssen
ger
Ship
s
Log
Boo
k En
try
Serv
ice
Com
pany
Sh
ip's
C
rew
SOLAS Requirement
Requirement Recommendation
Measurement of Low Location Lighting systems
ISO 15370, SOLAS II-2/13.3.2.5
X X 5-yearly by approved service supplier
Lightweight survey II-1/22.3 X X 5-yearly In Service Inclining Test system Class rules X X -- 5-yearly Medical Oxygen cylinders – hydraulic pressure test
-- X X X -- 5-yearly
Comment: Additional National requirements as far as known are contained in the attached summary
Bahamas Maritime Authority Instructions to Classification Societies
Date of issue: 20 April 01
Inspection and testing of CO2 cylinders 1. A visual inspection of all CO2 cylinders, forming part of the fixed fire extinguishing installation, is
to be carried out annually by:
a) A representative of a specialist testing/maintenance firm, approved for such purposes by one of our authorised classification societies, or;
b) A suitably qualified member of the Company’s shore-based personnel, e.g. superintendent engineer, or;
c) A suitably qualified member of the ship’s personnel, e.g. Second Engineer. 2. Records of annual inspections, deficiencies identified and corrective actions performed are to be
maintained on board. 3. Provided that annual visual inspections are carried out and recorded, all cylinders are to be
hydraulically tested after twenty (20) years from the date of manufacture, and every five (5) years thereafter.
4. If annual visual inspections are not carried out, or there is no record of them, then all cylinders are
to be hydraulically tested after ten (10) years and twenty (20) years from the date of manufacture and every five (5) years thereafter.
5. A record of the hydraulic pressure test should be legibly marked on the cylinders. 6. Any cylinder that has been discharged, or has a reduction in pressure of 10 % or more from its
original pressure as stamped on the cylinder, or shows signs of external corrosion, is to be hydraulically tested.
Maintenance of installations 7. In addition to the above requirements for CO2 all valves, wires, levers/pulls, pipework, markings
and operational instructions are to be maintained in a satisfactory condition. 8. Any aspects of the testing and maintenance of the system which is beyond the competence of the
Company’s and ship’s personnel should be carried out by an competent specialist maintenance firm.
9. Companies should ensure that that the inspection and maintenance of the whole system meets the
requirements of the classification society and any recommendations of the installation supplier. 10. Where the fixed CO2 installation is under maintenance and inoperable suitable provision should be
made for dealing with fires in the protected spaces.
Subject: Maintenance of CO2 Fixed Fire Extinguishing Installations
Regulation: SOLAS 1974, as amended
Chap II-2, Reg 5
Number 4
Effective Date: 1 March 2001
Revision: New
Bahamas Maritime Authority Instructions to Classification Societies
Date of issue: 8 February 2001
1. Regulations III/20.8.1 and III/20.9 require that inflatable liferafts, inflatable lifejackets, marine
evacuation systems, inflated rescue boats and hydrostatic release units be serviced at intervals not exceeding 12 months. Where this servicing cannot be carried out due to the lack of service stations in the ports to which ships are trading the period may be extended by up to 5 months.
2. Classification societies authorised to issue statutory certificates on behalf of the Bahamas
Maritime Authority are authorised to grant extensions of up to 5 months for the period of servicing this equipment where this is justified by operational considerations. In exercise of this authority, classifications societies should verify that the extension is justified and limit the period of extension to that which is reasonably necessary to carry out the required servicing.
3. Owners of Bahamian ships have been advised to approach classification societies directly
regarding the issue of these exemptions.
Subject: Servicing of inflatable liferafts, inflatable lifejackets, marine evacuation systems, inflated rescue boats and hydrostatic release units
Regulation: SOLAS Chapter III
Regulation 20.8.1 and 20.9
Number: 2
Effective Date: 8 February 2001
Revision: New
Bahamas Maritime Authority Instructions to Classification Societies
|Date of Issue: 20 April 2001
1. In determining the requirements for portable fire extinguishers classification societies should be
guided by the provisions of IMO Resolution A.602(15) and paragraph 6 of MSC Circular 847. Carriage of spare charges 2. The number of spare charges required by regulation 6.2 for portable extinguishers should be in
accordance with the provisions of MSC Circular 847, namely: (a) 100% for the first 10 extinguishers; and (b) 50% for the remaining extinguishers, subject to a maximum of 60. 3. Additional extinguishers of the same type and capacity should be carried in lieu of spare charges
for any extinguishers which cannot be charged on board ship, as determined in paragraph 2. 4. Instructions for recharging extinguishers should be carried on board ship and refills should be of
a type approved by the manufacturer of the extinguisher. Examination and testing of portable fire extinguishers 5. The extinguishers should be examined annually by a competent person. The Master, Chief Mate,
Chief Engineer or Second Engineer and similarly qualified and experienced persons are accepted by the Bahamas Maritime Authority as being competent to carry out these inspections.
6. The containers of permanently pressurised fire extinguishers, propellant bottles of non-
pressurised extinguishers and other extinguishers should be hydraulically pressure tested at intervals of 10 years. Containers of non-pressurised extinguishers should also be tested at intervals of 10 years.
Number portable fire extinguishers 7. The number of portable fire extinguishers required by regulation 6.7 is the number required to
satisfy classification society rules and in no case less than 5 for ships of 1000 gross tonnage and upwards.
Inspection and survey 8. If the loss of gas from a carbon dioxide extinguisher or propellant bottle of any other type of
extinguisher exceeds by 10% of the original charge as stamped on the extinguisher or bottle, the extinguisher or bottle should be recharged. Any extinguisher or bottle which has excessive external corrosion should be replaced.
9. In surveying the safety equipment on a vessel classification societies should verify that: (a) the manufacturer’s instructions for recharging extinguishers are on board;
(b) the extinguishers have been inspected and maintained in accordance with the
Subject: Portable fire extinguishers: periodical examination and testing and carriage of spare charges
Regulation: SOLAS 1974 as amended Chapter II-2 Regulation 6.2, 6.5 and 6.7
Number 6
Effective Date: 20.04.01
Revision: New
Bahamas Maritime Authority Instructions to Classification Societies
|Date of Issue: 20 April 2001
manufacturer’s instructions and the foregoing requirements; (c) records of inspections, maintenance and pressure tests are maintained; and (d) spare charges are provided in accordance with paragraphs 2 and 3. 10. Classification societies should refer to the Bahamas Maritime Authority, with relevant
recommendations, any Bahamian ship which does not satisfy the any of the foregoing requirements prior to the issue of a Safety Equipment Certificate or Passenger Safety Certificate.
MSN 2/1999
Hong Kong Merchant Shipping Notice
Five Yearly Testing of Launching Appliances and On-Load ReleaseGear for Lifeboats and Rescue Boats
Notice to Shipowners, Managers, Masters of Merchant Ships, Shipbuilders,Shiprepairers, Life-Saving Appliances Testing Houses, Life-Saving AppliancesManufacturers and Certifying Authorities
2. The coming into force of the 1996 amendments to SOLAS 1974 Chapter IIIRegulation 20, requires from the 1st July 1998 (amongst other things), that at leastonce every 5 years lifeboats and rescue boats shall be turned out and lowered withweights to simulate their full safe working load.
3. The following extracted details as they apply to the revised Chapter III ofSOLAS 74 from Resolution MSC.47 (66), outlines the requirements for the captionedtests.
Periodic servicing of launching appliances and on load release gear
11.1 Launching appliances:
.1 shall be serviced at recommended intervals in accordance withinstructions for on-board maintenance as required by Regulation36;
.2 shall be subjected to a thorough examination at intervals notexceeding 5 years; and
.3 shall upon completion of the examination in .2 be subjected to adynamic test of the winch brake in accordance with paragraph6.1.2.5.2 of the LSA Code; i.e. the winch brakes of a launchingappliance shall be of sufficient strength to withstand a dynamictest with a proof load of not less than 1.1 times the maximumworking load at maximum lowering speed.
11.2 Lifeboat on-load release gear shall be:
.1 serviced at recommended intervals in accordance withinstructions for on board maintenance as required by regulation36;
.2 subjected to a thorough examination and test during the surveysrequired by regulation I/7 and I/8 by properly trained personnelfamiliar with the system; and
.3 operationally tested under a load of 1.1 times the total mass ofthe lifeboat when loaded with its full complement of persons andequipment whenever the release gear is overhauled. Suchoverhauling and test shall be carried out at least once every fiveyears in accordance with the requirements of IMO Resolution A.689(17).
4. Further advice and details may be obtained from the Senior Surveyor/CargoShip Safety at Marine Department, Telephone: 2852 4510 or Facsimile: 2545 0556.
Marine DepartmentShipping Division
27 January 1999
Marine Administration 28/06/01
Page 1 of 4 Circular No. 4
Industry Circular No.
4
Amended 28th June 01
Government of the Isle of Man.
Department of Trade and Industry
Notice to Surveyors, Shipowners, Managers and Classification Societies
Lifeboat and rescue boat davit testing and testing of on-load release gear.
The 1996 amendments to SOLAS Ch. III, regulation 20, are included in the new Merchant Shipping (Lifesaving Appliances) Regulations 1999 for Isle of Man ships and require, amongst other things, that;
• launching appliances are subject to thorough examination at intervals not exceeding 5 years.
• launching appliances are tested dynamically to 110% operational weight at 5 yearly intervals on completion of the thorough examination.
• lifeboat on-load release gear is subjected to a thorough examination and test at each Cargo Safety Equipment survey or Passenger Ship certificate survey by properly trained personnel familiar with the system.
• lifeboat on-load release gear is tested at 110% operational load at intervals of at least 5 years.
These requirements apply to all ships from 1st July 1998. Instructions for the conduct of the 110% dynamic test can be found in IMO resolution A.689(17), 6.1.5.
During any renewal or periodical survey for a Cargo Ship Safety Equipment certificate, or a Passenger Ship Safety certificate in an Isle of Man ship, the surveyor should check for records on board of the last examination and 110% davit and winch test.
If the records show that an examination and test is due, or if no records are available, the surveyor should request an examination and test. If it is impractical
Marine Administration 28/06/01
Page 2 of 4 Circular No. 4
to arrange testing at the port of survey, the ship may be issued with a conditional certificate, requiring tests within three months.
The total load for conducting the 110% test is calculated from;
(a) the boat, plus
(b) its equipment, water, food, fuel and stores; plus
(c) a weight equivalent to the number of persons (at 75kg each) that the boat is certificated to carry; plus
(d) an additional weight equal to 10% of (a)+(b)+(c).
The test can be done by loading the boat itself in which case the test weights should be added to the boat from the point where persons would normally board, in the case of a boat lowered out of stowage to an embarkation deck then held in place by bowsing tackles, the weights should be added to the boat at this embarkation deck with the boat bowsed in and ready for boarding. When bowsing tackles are used they should be reversed for the test so that they may be released and paid out from the deck with the loaded boat unmanned.
In the case of a boat boarded and launched from stowage, the test weight should be added with the boat at that position.
Arrangements should be made to ensure the safety of persons loading the boat, in the event of a component failure. Weights should be spread out as evenly as possible in the boat to simulate the designed load condition and water bags, sandbags, or any suitable system of verifiable weight may be used.
The Marine Administration, however, is of the opinion that loading the actual boat in this manner can cause long term problems, especially with GRP boats, which may affect the strength of the boat and which may not manifest themselves for some time even though the boat shows no signs of deformation or damage at the time of test. It is a matter for each owner to decide on proceeding with a test in this manner.
If it is decided not to use the actual boat then it will be permissible to unship the boat and use a spreader beam with water bags or solid weights in lieu of the boat for the davit and winch dynamic test.
The 1996 amendments to SOLAS CH. III also require five yearly testing of lifeboat on-load release systems plus overhauling of the equipment. This test
Marine Administration 28/06/01
Page 3 of 4 Circular No. 4
can be carried out in conjunction with the 110% davit and winch test if the boat is used for this test , by stopping the loaded boat just at the water and boarding it from another craft to operate the release mechanism.
It may also be done in a workshop or from a crane if the boat is unshipped for the davit and winch test, by loading the boat to 110% and operating the release mechanism in a situation where the drop of the boat will not hazard the operator or the boat. The best situation for this is with the boat suspended over water with its keel just touching the water at the time of operating the on-load release.
Similar tests are required of liferaft davits and rescue boat davits and these can be done with a simulated weight.
Whenever tests are carried out the attending surveyor should provide a suitable form of documentary evidence of satisfactory test to be retained on board and should submit a copy of such documents to the Marine Administration. No special appointment is required from the Marine Administration for Classification Society exclusive surveyors witnessing these tests. On satisfactory completion, the attending surveyor should, in addition to supplying documentary evidence, make and stamp a hand-written entry in the ship’s record of safety equipment (Isle of Man Form C8.) to the effect of the test being done and the dates. In due course a revised Form C8 will be introduced with entry boxes for this information.
Owners and managers of ships with multiple lifeboat arrangements may wish to instigate a rolling programme of tests to spread the testing effort over a period of time.
A further requirement of the 1996 amendments is a:
thorough examination and test of lifeboat on-load release gear at each Cargo Ship Safety Equipment survey or Passenger Ship Safety Certificate survey by properly trained personnel familiar with the system.
The test in this case is not a loaded test and may be conducted with the light boat.
It is considered unlikely that external personnel who are properly trained and familiar with any particular ship’s system will be available in many of the ports where ships will present for survey. In such cases it will be acceptable for a suitably senior member of the ship’s staff who is provided with the manufacturers manuals, who has experience with the system, and who has been provided with instruction in the examination and use of the system and who has,
Marine Administration 28/06/01
Page 4 of 4 Circular No. 4
where possible, attended a manufacturers training programme, to undertake this examination and test. The test should be witnessed by the attending surveyor
The test should be carried out with the boat lowered just to the water
In some ports it may not be possible or permissible to carry out this test on one or both boats. In such cases the test may be postponed and carried out by ship’s staff within 3 months. When this approach is taken the ship will be required to provide confirmation to the Marine Administration in the form of a certificate signed by the Chief Engineer and the Master to confirm that the examination and test has been carried out with satisfactory results.
On board load testing for commissioning of new davits
New davits should arrive at the ship, fully certificated to verify that the production tests listed below have been carried out at the manufacturers’:
a) Static load test of 2.2 x SWL with the davit in its fully outboard position. In this test the weight should be suspended from the davit head.
b) Static load test of 1.5 x SWL to be held on the winch brakes
Attending surveyors should satisfy themselves that these certificates are on board and have been issued or endorsed by the ship’s classification society or a Government authority to indicate that the tests have been carried out. Where no evidence exists these tests will be required on board.
Once on board, in order to demonstrate that the attachments of the davits and winches to the ship’s structure are satisfactory, the following test is required:
A dynamic load test at 110% maximum working load to be carried out with the davit in the outboard position. The weight is to be suspended from the release hook or fall wire. When the maximum lowering speed is reached, the brakes are to be abruptly applied.
The maximum working load is to be calculated as described on page 2 of this circular.
Following the test the attending surveyor should carry out an examination of the structure and attachments, including non-destructive testing where necessary, to satisfy himself that the connections to the ship remain efficient.
Marine Administration
07/03/2001
Page. 1 of 7
Industry Circular No. 7
Government of the Isle of Man.
Department of Trade and Industry
Notice to Surveyors, Shipowners, Managers and Classification Societies
Wire Rope Terminations for Falls used in Launching Lifeboats and other Survival Craft
There is no applicable marine legislation that specifies the appropriate way to form the primary load bearing terminations of wire ropes used for life boat falls, recovery strops or hanging off pennants.
The Isle of Man Marine Administration recognises that there are a number of alternative methods used to form these terminations and that the suitability of each type of connection for the intended service is varied.
This circular is intended to illustrate the different types and recommended uses for the different terminations that are acceptable to the Isle of Man Marine Administration.
Acceptance by the Isle of Man Marine Administration of any of the terminations is conditional on them being designed, manufactured, installed and used in the correct manner.
The different types of terminations, their acceptability for use on Isle of Man ships and some guidelines on the method of use are set out in this circular. 1. Permanent Terminations
Marine Administration
07/03/2001
Page. 2 of 7
These are supplied already formed on the wire rope by the manufacturer or recognised firm. They are suitable for all LSA applications provided that they have been certified for the maximum safe working load to be encountered. Permanent terminations of these types must only be fitted or re fitted by a recognised company, experienced in their use.
SWAGED EYE STANDARD THIMBLE FERRULE SECURED
SPELTER SOCKET Maintenance When in service these particular terminations should be examined for broken strands or deformation of the wire where it emerges from the connection. 2. Reusable Terminations.
Marine Administration
07/03/2001
Page. 3 of 7
There are two main ways of forming wire rope terminations with this method, cable grips or wedge and socket fittings. They have the advantage that they can be fitted by competent ships staff and can be re-used when the falls are turned or replaced. 2.1 Bull Dog / Cable Grips Bull dog grips are not the best practice for the forming of eyes in wire rope. The Isle of Man Marine Administration can accept this type of method for the formation of eyes at the termination of the lifeboat falls as in the case of the centre join for continuous falls (as in Fig 3) but not for any other purpose. They are to be fitted as shown below in Fig 1.
Fig1. method of fitting bulldog clips Maintenance The grips should be regularly inspected and tightened, so that any change in wire diameter when under load will not loosen the grips. 2.2 Wedge and Socket Type
As a general rule the grips should be placed at intervals of 6 x Wire Rope diameter. The minimum number of grips is to be three. After an initial load the grips should be re tightened.
Marine Administration
07/03/2001
Page. 4 of 7
This type of fitting is also allowed by the Isle of Man Marine Administration for the formation of eyes at the termination for the lifeboat falls as shown in Fig 3. Their use is not recommended for cases where there is a possibility that the dead end of the termination can come into contact with an obstruction and loosen the wedge. When assembling the termination, the manufacturers instructions should be followed exactly. A general guide to their assembly is shown below in Fig 2
Fig 2 assembly of a typical wedge and socket type termination The dead end of the rope is to be not less than 15 x the rope diameter in length. The wedges and sockets are sized for a particular wire diameter and parts should never be mixed. Maintenance The sockets are to be periodically examined for tightness of the wedge and for cracks. The rope is to be examined for broken wires or deformation were it emerges from the socket. 3. Terminations of Lifeboat Falls
Marine Administration
07/03/2001
Page. 5 of 7
Fig 3 Example of the type of termination for lifeboat falls preferred by Isle of Man Marine Administration .
3.1 Unacceptable Terminations
Marine Administration
07/03/2001
Page. 6 of 7
Termination is by only two cable grips without a ferrule and the end of the wire rope is unsecured.
Marine Administration
07/03/2001
Page. 7 of 7
The ends have been joined together directly. They should either be formed into eyes with ferrules secured by at least 3 cable grips and linked with shackles, or wedge and socket terninations are to be used.
Marine Administration
31/01/01
Page. 1 of 7
Industry Circular No.
6
Government of the Isle of Man.
Department of Trade and Industry
Notice to Surveyors, Shipowners, Managers and Classification Societies
Periodic inspection, testing and maintenance of compressed gas cylinders, fire extinguishers and fixed fire-fighting systems.
Clarification is often sought as to the requirements for periodic servicing and testing of fire extinguishers, compressed gas cylinders and components of fixed fire-extinguishing systems on board Isle of Man registered vessels.
As the regulations within the SOLAS Convention leave the definition of the period and extent of inspection and testing for this equipment to the Administration, this circular aims to inform the industry of the current Isle of Man requirements.
For ease of reference, a table of service and test periods has been set out in appendix 1 to this notice.
1. Fire Extinguishers
Fire extinguishers includes portable and semi-portable units of all types.
Inspection
• all extinguishers should be examined annually by a competent person. • the competent person may be either a member of the ship’s crew who is
trained and assigned to carry out this work or an accredited service agent. • each extinguisher should be marked clearly to indicate the date upon which it
has been examined.
Marine Administration
31/01/01
Page. 2 of 7
Testing
the hydraulic test period for all types of fire extinguishers and propellant bottles is 5 years.
• hydraulic testing must be carried out by an accredited service agent or test facility.
• following the hydraulic testing, a thorough inspection and internal examination must be carried out prior to recharging.
• the test pressure and test date must be marked clearly on each extinguisher. Note: ‘hard-stamping’ is only acceptable for CO2 extinguishers and propellant bottles.
• test certificates or test records must be provided and retained on board for inspection.
2. Cylinders for SCBA , Medical Oxygen and Compressed Air Cylinders for survival craft air systems.
SCBA cylinders includes compressed air cylinders for all breathing apparatus, escape sets and rescue equipment.
Inspection
• all cylinders should be externally examined annually by a competent person.
• the competent person may be either a member of the ship’s crew who is trained and assigned to carry out this work or an accredited service agent.
Testing
• the maximum interval between hydraulic tests for solid drawn steel cylinders is 5 years. Composite cylinders may require more frequent testing - stipulated by manufacturers instructions.
• hydraulic testing must be carried out by an accredited service agent or test facility.
• following the hydraulic test, a thorough inspection and internal examination must be carried out prior to recharging.
• the test pressure and test date must be stamped clearly on each steel cylinder. Composite cylinders will require a permanent marking or tag.
• test certificates must be provided and retained on board for inspection.
Marine Administration
31/01/01
Page. 3 of 7
3. Cylinders for high-pressure fixed gas fire-extinguishing systems
(Note: for bulk CO2 systems – refer to Industry Notice No. 2)
Inspection
Annually the cylinders should be subject to a contents or level check by a competent person. The competent person may be either a member of the ship’s crew who is trained and assigned to carry out the task or an accredited service agent.
At least once every 2 years the cylinders should be subject to an inspection by an accredited service agent1, this inspection should be conducted in conjunction with the service for the entire system and will include:
• visual inspection of each cylinder, fittings and securing arrangements. • accurate determination of the contents and comparison with original
readings e.g. liquid level gauging, test weighing etc.
Any cylinders showing signs of mechanical damage, excessive corrosion, or loss of contents exceeding 10% of installed quantity for CO2 or 5% for Halon should be withdrawn from service and sent ashore for full periodic service and inspection. If more than 10 years have elapsed since initial pressure test at manufacture, they will require to be hydraulically tested before refilling.
Testing
The hydraulic pressure test period for these high-pressure cylinders is as follows:
• first pressure test within 20 years of initial pressure test at manufacture, provided annual tests have been carried out with satisfactory results.
• subsequent pressure tests every 5 years thereafter.
Note: Testing for High-Pressure Halogenated Hydrocarbon (Halon) systems
The Isle of Man Marine Administration strongly advises owners to consider replacing their existing Halon systems before the hydrostatic test of the cylinders is due. However, where problems arise the following may be considered for which special application must be made on a ship-by-ship basis:
Due to the environmental implications of emptying, testing and re-charging of these cylinders and the reduced risk of internal corrosion due to the absorption of moisture by the Nitrogen pressurisation gas,
1 On board inspection or test required by an accredited service agent, with the exception of pressure testing, may be carried out by a senior member of the ship’s staff who has been fully trained to carry out this work. In all cases, calibrated equipment must be used and all procedures and documentation must be in accordance with shipboard safety management systems.
Marine Administration
31/01/01
Page. 4 of 7
the Isle of Man will accept postponement of pressure testing providing the external condition of the cylinders remains acceptable.
In order to extend the cylinder test period beyond 20 years, the Isle of Man require a thorough examination of all cylinders be carried out by an accredited service agent. Where each cylinder is found to be in a satisfactory condition with no significant signs of pitting, corrosion, fretting or cracking, this Administration will permit the hydraulic test of all the cylinders to be postponed for a further 5 years, i.e. 25 years from initial test date for which a letter will be issued to the vessel upon receipt of the inspection report.
4. Cylinders containing refrigerant gases and gases for burning equipment
These cylinders are not normally considered to be part of the ship’s safety equipment. They are generally supplied full and exchanged or returned when empty. Ship’s staff should, prior to accepting the cylinder on board, check the date stamp on the cylinders and ensure that no more than 5 years have elapsed since the last hydraulic pressure test.
For cylinders remaining on board, arrangements should be made for an exchange cylinder from ashore if more than 5 years have elapsed since the last hydrostatic test.
5. Foam Systems
To include all foam types: FP; AFFF; FFFP; ARFFF
In addition to the regular shipboard inspections and where practicable the system should be tested to produce foam as often as possible in a drill scenario. Used concentrate should be replenished as required.
Foam sampling
An analysis of foam samples for fixed and portable systems must be undertaken after 2 Years from date of manufacture and annually thereafter.
samples should be:
• as representative as practical, e.g. taken from top, middle and bottom of tanks where arrangement permits.
• analysed by an independent or manufacturer’s laboratory and the results of analyses must be kept on board and readily available for inspection.
Marine Administration
31/01/01
Page. 5 of 7
6. Fixed Dry Powder Systems
Annually, the system should be inspected and the dry powder charge should be agitated with Nitrogen, using “bubbling” connections where provided. Note: due to the powder’s affinity for moisture, any Nitrogen gas introduced for agitation must be moisture free.
In addition to the regular shipboard inspections, the systems should be inspected at least once every two years by an accredited service1 agent. This inspection should include:
• blow-through with air to ensure associated pipes and nozzles are clear.
• operation test of local and remote controls and section valves.
• contents verification of propellant gas cylinders containing Nitrogen (including remote operating stations).
Note: the replenishment and test regime for these high-pressure Nitrogen cylinders is identical to that for CO2 cylinders for fixed-gas fire extinguishing systems.
7. Sprinkler and Fixed Pressure Water Spray Systems
No specific inspection or test regime exists for these systems outside of normal shipboard testing and statutory survey requirements. In the case of sprinkler systems protecting passenger accommodation, our surveyors will inspect and test the system as necessary during Passenger Ship Safety Certificate Renewal surveys.
8. Hydraulic Pressure Testing
The test pressure applied for all cylinders and extinguishers should be 1.5 x maximum working pressure, which should be held for at least one minute.
The test pressure should be clearly stamped on each compressed gas cylinder and clearly marked on each extinguisher.
Where cylinders are sent ashore for re-charging, the pressure test requirements for the Local Authority may override, but should not be less stringent, than the above requirements.
1 On board inspection or test required by an accredited service agent, with the exception of pressure testing, may be carried out by a senior member of the ship’s staff who has been fully trained to carry out this work. In all cases, calibrated equipment must be used and all procedures and documentation must be in accordance with shipboard safety management systems.
Marine Administration
31/01/01
Page. 6 of 7
9. Rejection
Extinguishers or cylinders failing any inspection or test shall be rendered unserviceable and disposed of accordingly.
An entry in the records must be made to show when any extinguisher or cylinder has been rejected.
10. Records
Records of inspection, maintenance and testing of all extinguishers and cylinders must be maintained and readily available on board for inspection.
These records should clearly identify each individual extinguisher or cylinder and its inspection status.
Marine Administration
31/01/01
Page. 7 of 7
Appendix 1
System or Appliance
Shipboard Inspection Periodic Inspection and
Service
Hydraulic Pressure Test
Marking and Documentation
Fire Extinguishers
(all types)
In accordance with SMS procedures and
manufacturer’s instructions
Annually by a competent person
(see Note 1)
5 Years (includes
propellant gas bottles)
Pressure Test date to be clearly marked (see Note 2).
Inspection and PT certificates on board
SCBA and Medical O2
cylinders
In accordance with SMS procedures and
manufacturer’s instructions
Annually by a competent person.
(see Note 1)
Steel - 5 years Composites -
see manufacturer
Pressure Test date to be hard-stamped on
cylinder. PT certificates on board
Air Cylinders for Survival Craft
(TEMPSC)
In accordance with SMS procedures and
manufacturer’s instructions.
Annually by a competent person
(see Note 1)
5 years
Pressure Test date to be hard-stamped on cylinder .PT certificates on board
CO2 High Pressure Cylinders - Fixed
Installations
Annual level check and function checks In accordance with SMS
procedures
Every 2 years by an accredited service
agent (see Note 3)
Within 20 years and every 5 years thereafter
Pressure Test date to be hard-stamped on
cylinder. Inspection and PT
certificates on board Halon High
Pressure Cylinders - Fixed Installations
Annual level check and function checks In accordance with SMS
procedures
Every 2 years by an accredited service
agent (see Note 3)
External examination at
20 years to extend to 25 years
(see note 4)
Pressure Test date to be hard-stamped on
cylinder. Inspection and PT
certificates on board
Cylinders for Refrigerant Gas
and Burning Equipment
Periodically check
condition
-
5 years
(see note 5)
Pressure test date to be hard-stamped on
cylinder.
Foam Systems
(fixed and portable)
In accordance with SMS procedures and
manufacturer’s instructions
Foam sample after 2 years then annually
thereafter. (see Note 6)
- Foam sample certificates on board.
Dry Powder
systems
Powder charge agitated annually (N2 blow-through)
& system inspected
Sample of dry powder and test for moisture absorption
every 2 years (see Note 6)
N2 Propellant cylinders -20 years then 5
years thereafter
Last sample date marked clearly. Powder sample
certificates on board
Notes: 1. The competent person may be a member of the ship’s crew who is trained and assigned to this
task or an accredited service agent. 2. Pressure test dates must be clearly marked. Hard-stamping is only permitted on CO2
extinguisher cylinders and propellant bottles. 3. On board inspection or test required by an accredited service agent, with the exception of
pressure testing, may be carried out by a senior member of the ship’s staff who has been fully trained to carry out this work. In all cases, calibrated equipment must be used and all procedures and documentation must be in accordance with shipboard safety management systems.
4. This relaxation from the 20 years test period is permitted on a ship by ship basis for which application must be made to the Administration. Any extension is granted subject to thorough examination (including NDT) by an accredited service agent , the details of which will be provided upon application.
Marine Administration
31/01/01
Page. 8 of 7
5. These cylinders are generally supplied full and exchanged when empty and as such are not considered as part of the ships safety equipment. Ship’s staff should , prior to acceptance, ensure no more than 5 years have elapsed since the last pressure test. Cylinders remaining on board should be exchanged ashore if more than 10 years have elapsed since last Pressure Test.
6. Sample analyses must be carried out by an accredited service agent ashore.
REPUBLIC OF LIBERIA
BUREAU OF
MARITIME AFFAIRS
Marine Notice
FIR-001Rev. 11/02
TO: ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF
MERCHANT SHIPS, AND AUTHORIZED CLASSIFICATION SOCIETIES
SUBJECT: Maintenance and Inspection of Fire-Protection Systems and Appliances. References: (a) Maritime Regulation 2.36
(b) SOLAS Chapter II-2 (c) MSC Circular 849 adopted 8 June 1998 (d) MSC Circular 850 adopted 8 June 1998 (e) International Code for Fire Safety Systems (FSS Code).
Supersedes: Marine Notice FIR-001 dated 6/01 PURPOSE:
This Notice provides Administration guidelines for the proper maintenance and inspection of fire protection systems, appliances, and emergency equipment. General guidelines applicable to all fire protection systems and appliances, and specific guidelines applicable to testing and examination of fixed and portable fire extinguishers, foam systems, and self-contained breathing apparatus are provided. It should be noted that the general guidelines contained in this Notice are not an all inclusive list of maintenance or inspection items for fire protection systems, fire fighting appliances, and emergency equipment. The specific guidelines contained in this Notice address areas where the Administration feels there is need for additional guidance or clarification. Vessel owners should be familiar with and follow the equipment manufacturers recommendations, as well as class society requirements and applicable requirements of SOLAS, except where these recommendations or requirements are superseded by this Notice. APPLICABILITY:
This Notice applies to all ships, MODUs and mobile offshore units (MOUs). GUIDELINES: 1.0 General Guidelines for the Maintenance and Inspection of Fire-Protection Systems
and Appliances. 1.1 Operational Readiness.
1 of 7 Inquiries concerning the subject of this Notice should be directed to the Office of the Deputy Commissioner, Republic of Liberia, the Liberian International Ship & Corporate Registry, LLC, 8619 Westwood Center Drive, Suite 300, Vienna, VA 22182, USA 11/02
All fire protection systems and appliances should at all times be in good order and available for immediate use while the ship is in service. If a fire protection system is under repair, then suitable arrangements acceptable to the vessel classification society and this Administration should be made to ensure safety is not diminished. Prior to sailing or in the case of MODUs and MOUs engaging in operations with a fire protection system under repairs, a dispensation must be obtained from the Administration.
1.2 Maintenance and Testing.
Instructions for on-board maintenance, not necessarily by the ship’s crew, and testing of active and passive fire protection systems and appliances should be easily understood, illustrated wherever possible, and, as appropriate, should include the following for each system or appliance:
.1 maintenance and repair instructions; .2 schedule of periodic maintenance; .3 list of replaceable parts; and .4 log for records of inspections and maintenance, listing identified non-conformities
and their targeted completion dates. 1.3 Weekly Testing and Inspections.
Weekly inspections should be carried out to ensure that:
.1 all public address systems and general alarm systems are functioning properly; and
.2 breathing apparatus cylinders do not present leakages. 1.4 Monthly Examinations and Inspections.
Ships officers are responsible for performing monthly examinations of firefighting system equipment and recording the examinations in the ship's official logbook. Monthly inspections should be carried out to ensure that:
.1 all fireman’s outfits, fire extinguishers, fire hydrants, hose and nozzles are in
place, properly arranged, and are in proper condition; .2 all fixed fire-fighting system stop valves are in the proper open or closed position,
dry pipe sprinkler systems have appropriate pressures as indicated by gauges; .3 sprinkler system pressure tanks have correct levels of water as indicated by glass
gauges; .4 all sprinkler system pumps automatically operate on reduction of pressure in the
systems; .5 all fire pumps are operated; and .6 all fixed fire-extinguishing installations using extinguishing gas are free from
leakage. 1.5 Quarterly Examinations and Inspections.
Ships officers are responsible for performing quarterly tests and examinations of the following firefighting system equipment and recording the test and examinations in the ship's official logbook. Quarterly inspections should be carried out to ensure that:
FIR-001 2 of 7 Rev. 11/02 The Republic of Liberia
.1 all automatic alarms for the sprinkler systems are tested using the test valves for
each section;
.2 the international shore connection is in proper condition;
.3 lockers providing storage for fire-fighting equipment contain proper inventory and equipment is in proper condition;
.4 all fire doors and fire dampers are tested for local operation; and
.5 all CO2 bottle connections for cable operating system clips should be checked for tightness on fixed fire-extinguishing installations.
1.6 Annual Testing and Inspections.
As part of the annual statutory survey for Safety Equipment Certification, the following inspections and tests should be carried out to ensure that:
.1 all fire extinguishers are checked for proper location, charging pressure, and
condition; .2 fire detection systems are tested for proper operation, as appropriate; .3 all fire doors and dampers are tested for remote operation; .4 all foam-water and water-spray fixed fire-fighting systems are tested for
operation; .5 all accessible components of fixed fire-fighting systems are visually inspected for
proper condition; .6 all fire pumps, including sprinkler system pumps, are flow tested for proper
pressures and flows; .7 all hydrants are tested for operation; .8 all antifreeze systems are tested for proper solutions; .9 sprinkler system connections from the ship’s fire main are tested for operation; .10 all fire hoses are hydrostatically tested; .11 breathing apparatus air recharging systems checked for air quality; .12 control valves of fixed fire-fighting systems should be inspected; and .13 air should be blown through the piping of extinguishing gas systems.
The verification of the examinations and tests described Section 1.2 thru 1.6 above are an integral part of the annual statutory surveys for the SOLAS Safety Equipment Certificate. The inspection and/or verification of the applicable items in Section 1.2 thru 1.7 shall be to the satisfaction of the attending classification society surveyor.
1.7 Five-year Service.
At least once every five years, the following inspection and test should be carried out:
• control valves of fixed fire-fighting systems should be internally inspected. 2.0 Fixed CO2 and Halon Systems. 2.1 Verification of Cylinder Contents.
Every two years the contents of the cylinders are verified by weight or isotropic measurement as part of the survey for issuance of the SOLAS Safety Equipment
FIR-001 3 of 7 Rev. 11/02 The Republic of Liberia
Certificate. Weigh scales may be used to verify cylinder contents and recharging is required if the loss in charge is 10 percent or more. Generally the weigh scales are included as part of the CO2 system equipment in order to satisfy SOLAS, Chapter II-2, Regulation 5.1.11.
2.2 Hydrostatic Testing.
All fixed CO2 and Halon cylinders must be hydrostatically tested as follows:
.1 after each 20 years of service,
.2 prior to recharging a discharged cylinder,
.3 or when visual inspection reveals a potential defect.
Hydrostatic test dates must be stamped on the cylinders. Hydrostatic testing must be performed by an authorized servicing facility which has been certified by a government agency or recognized classification society, and by extinguisher manufacturer to perform this type of work. The facility must be acceptable to the attending classification society surveyor. The same facility should recharge the cylinders after testing to demonstrate serviceability.
3.0 Portable Fire Extinguishers. 3.1 Annual Survey.
The examination of the fire extinguishers is an integral part of the annual statutory surveys for the SOLAS Safety Equipment Certification. The fire extinguishers should be examined and, if necessary, serviced annually. The annual servicing/examination of the portable fire extinguishers can be carried out by the crew, if the crew is properly trained and such servicing is acceptable to the vessel’s classification society, or by an authorized service facility. The classification society surveyor must be satisfied with the condition of the extinguishers.
3.2 Servicing of Fire Extinguishers by the Crew of a Vessel.
A vessel crew may service powder, foam, or water type portable fire extinguishers subject to the following:
.1 The equipment required to test, examine, and service the extinguishers is obtained
and maintained in a calibrated and serviceable condition. .2 The crew is properly trained in the testing and examination, and servicing of fire
extinguishers and the extinguisher manufacturer's servicing instructions are followed.
.3 The testing and inspection is carried out to the satisfaction of the attending classification society surveyor, and if required by the surveyor, in the presence of the surveyor.
3.3 Verification of Fire Extinguishers Contents.
Every two years in conjunction with the issuance of the SOLAS Safety Equipment Certificate the contents of the cylinders must be verified. Weighing of the portable CO2 cylinders in the presence of the classification society surveyor is an acceptable method of
FIR-001 4 of 7 Rev. 11/02 The Republic of Liberia
verification. Other methods of determining contents of the cylinders, such as isotropic measurement, may also be accepted provided the equipment is properly calibrated, the operator of the device is trained and qualified in its use, and the classification society surveyor is satisfied with the measurements. If an alternative method is use, spot checks of cylinder contents by weighing may be required to verify the accuracy and consistency of the measurement device.
3.4. Spare Charges, Additional Fire Extinguishers, and Refilling of Extinguishers.
.1 For fire extinguishers of the same type, capable of being recharged on board, the spare charges should be provided as follows: 100% for the first 10 extinguishers and 50% for the remaining extinguishers but not more than 60 (fractions to be rounded off to next whole number).
.2 For extinguishers which cannot be recharged by the crew, additional portable fire extinguishers of the same quantity, type, capacity and number as determined in paragraph a above should be provided in lieu of spare charges.
.3 Instructions for recharging the extinguishers should be carried on board. Periodic refilling of the cylinders should be in accordance with the manufacturer's recommendations. Lacking same, refill is required when the extinguishing media starts to lose effectiveness. Partially emptied extinguishers should also be recharged. Only refills approved for the fire extinguisher in question may be used for recharging.
3.5 Authorized Servicing Facilities.
The classification society surveyor may also accept a servicing certificate from an authorized servicing facility acceptable to the society for the annual and biannual examination, servicing and verification of the portable fire extinguishers.
3.6 Hydrostatic Testing of Portable Fire Extinguishers.
Portable fire extinguishers shall be hydrostatically tested as follows:
.1 Dry Powder Extinguishers every 10 years;
.2 CO2 Extinguishers every 10 years;
.3 Other Extinguishers every 10 years.
A hydrostatic test may also be required by the classification society surveyor or Liberian Nautical Inspector if visual examination indicates a potential defect in the cylinder. The hydrostatic test date must be permanently marked on the bottles.
3.7 Hydrostatic Testing Facilities.
Hydrostatic testing must be performed by a servicing facility which has been certified by a government agency or classification society, and by the extinguisher manufacturer to perform this type of work. The facility must be acceptable to the attending classification society surveyor. This same facility should recharge the cylinder after testing to demonstrate serviceability.
FIR-001 5 of 7 Rev. 11/02 The Republic of Liberia
4.0 Fixed Foam System. 4.1 Foam Analysis.
The first periodical test and analysis of foam concentrates stored on board should be performed after a period of three (3) years and, after that every year. The class society surveyor may require it at other times if there is cause to question the suitability of the foam or condition of the storage tank. A record of the age of the foam concentrates and of subsequent tests should be kept on board.
5.0 Self-Contained Breathing Apparatus (SCBA). 5.1 Annual Examination.
All SCBAs shall be examined at least annually as part of the annual statutory survey for the Safety Equipment Certificate (SEC) or MODU Code certificate. If applicable, the breathing apparatus air recharging systems should be checked for air quality as part of the annual statutory survey for the SEC or MODU Code certificate.
5.2 Hydrostatic Testing of Self-contained Breathing Apparatus Cylinders.
Hydrostatic testing of SCBA cylinders shall be carried out once every five years. The hydrostatic test date must be permanently marked on the bottles. Intervals for hydrostatically testing cylinders of the ultra lightweight type may vary and will depend upon the requirements of the cylinder manufacturer and the vessel’s classification society. Servicing of the cylinders must be performed to the satisfaction of the classification society surveyor.
5.3 Spare Charges and Recharging of Breathing Apparatus Air Cylinders.
.1 Two spare charges suitable for use with the breathing apparatus should be provided for each required apparatus.
.2 If passenger ships carrying not more than 36 passengers and cargo ships are equipped with suitably located means for fully recharging the air cylinders free from contamination, only one spare charge is required for each required apparatus.
6.0 Emergency Escape Breathing Devices (EEBDs) 6.1 Maintenance and Care
.1 The EEBD should be examined and maintained in accordance with the
manufacturer’s instructions. .2 The ship’s periodic safety appliance and equipment inspection and testing procedures
should be modified to incorporate the inspection of EEBDs. .3 Maintenance requirements, manufacturer’s trademark and serial number, shelf life
with accompanying manufacture date and name of approving authority should be printed on each EEBD.
FIR-001 6 of 7 Rev. 11/02 The Republic of Liberia
FIR-001 7 of 7 Rev. 11/02 The Republic of Liberia
.4 EEBDs, which have exceeded their service life as indicated by the manufacturer, should be discarded. Any unusable or damaged EEBDs should be promptly disposed of in accordance with manufacturers instructions.
.5 Liberia does not require periodic hydrostatic testing for EEBD cylinders.
6.2. Spare EEBDs
.1 Ships with ten or less EEBDs on board shall carry at least one spare devices. Ships with
11 to 20 EEBDs on board shall carry at least two spare devices. Ships with more than 20 EEBDs on board shall carry spares equal to at least 10% of the total EEBDs but no more than 4 spares will be required.
NATIONAL ADMINISTRATION REQUIREMENTS MALAYSIA
(Letter dated 23rd July, 2004 – (55) dlm IPL 6033 Jld 5)
Permanently Installed Fire Fighting Systems Fixed gas fire extinguishing systems The quantity of medium in containers must be inspected every 12 mo nths by authorized service agent or trained ships officers in charge of the equipments. Periodic hydrostatic testing of high-pressure containers must be carried out for not less than 10% of the containers during each 10 years period or 100% of the contain ers after reach 20 years from date of manufacture. Fixed Foam Extinguishing Systems Foam sample analysis shall be carried out after a period of 3 years of date manufacture and thereafter every year at an authorized service agent or manufacture's laborat ory. Notwithstanding the aforementioned, occasional foam sample analysis may be requested at the discretion of the attending surveyor during the safety equipment survey. Portable Fire Extinguishing All portable fire extinguishers shall be tested hydrostatically as follows: a) dry powder extinguishers - every 10 years from date of manufacture b) CO2 extinguishers - every 10 years from date of manufacture c) other extinguishers - every 10 years from date of manufacture and when visual inspection by a surveyor or trained ship's officer reveals a defect. Water and foam extinguishers must be refilled every 12 months by authorized services agent or deck or engine officer in charge of the equipments. Others extinguishers shall be inspected and recharged by authorized service agent every 2 years. Annual inspection by authorized service agent or deck or engine officer in charge of the equipments.
1 of 8 Inquiries concerning the subject of this Notice should be directed to the Office of the Maritime Administrator, Republic of the Marshall Islands, c/o Marshall Islands Maritime and Corporate Administrators, Inc., 11495 Commerce Park Drive, Reston, VA 20191-1507 USA.
MI-01, 01/97
REPUBLIC OF Marine Notice THE MARSHALL ISLANDS
No. 2-011-14 OFFICE OF THE
MARITIME ADMINISTRATOR Rev. 7/02
TO: ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF MERCHANT SHIPS, AND AUTHORIZED CLASSIFICATION SOCIETIES
SUBJECT: Maintenance and Inspection of Fire-Protection Systems and Appliances. Reference: (a) Maritime Regulation 2.11.
(b) SOLAS Chapter II-2. (c) International Code for Fire Safety Systems (FSS Code). (d) MSC Circular 849 adopted 8 June 1998. (e) MSC Circular 850 adopted 8 June 1998.
PURPOSE:
This Notice provides Administration guidelines for the proper maintenance and inspection of fire protection systems, appliances, and emergency equipment. General guidelines applicable to all fire protection systems and appliances, and specific guidelines applicable to testing and examination of fixed and portable fire extinguishers, foam systems, and self-contained breathing apparatus are provided. It should be noted that the general guidelines contained in this Notice are not an all inclusive list of maintenance or inspection items for fire protection systems fire fighting appliances, and emergency equipment. The specific guidelines contained in this Notice address areas where the Administration feels there is need for additional guidance or clarification. Vessel owners should be familiar with and follow the equipment manufacturers recommendations, as well as Classification Society requirements and applicable requirements of SOLAS, except where these recommendations or requirements are superseded by this Notice. APPLICABILITY:
This Notice applies to all ships, MODUs and mobile offshore units (MOUs). GUIDELINES 1.0 General Guidelines for the Maintenance and Inspection of Fire-Protection Systems and
Appliances. 1.1 Operational readiness.
All fire protection systems and appliances should at all times be in good order and available for immediate use while the vessel is in service. If a fire protection system is under repair, then suitable arrangements acceptable to the vessel Classification Society and this Administration should be
Rev. 7/02 2 of 8 2-011-14
The Republic of the Marshall Islands
made to ensure safety is not diminished. Prior to sailing or in the case of MODUs and MOUs engaging in operations with a fire protection system under repairs, a dispensation must be obtained from the Administration.
1.2 Maintenance and testing.
Instructions for on-board maintenance, not necessarily by the ship’s crew, and testing of active and passive fire protection systems and appliances should be easily understood, illustrated wherever possible, and, as appropriate, should include the following for each system or appliance:
.1 maintenance and repair instructions;
.2 schedule of periodic maintenance;
.3 list of replaceable parts; and
.4 log for records of inspections and maintenance, listing identified non-conformities and their
targeted completion dates. 1.3 Weekly testing and inspections.
Weekly inspections should be carried out to ensure that:
.1 all public address systems and general alarm systems are functioning properly; and
.2 breathing apparatus cylinders do not present leakages. 1.4 Monthly examinations and inspections.
Ships officers are responsible for performing monthly examinations of firefighting system equipment and recording the examinations in the ship's official log book. Monthly inspections should be carried out to ensure that:
.1 all fireman’s outfits, fire extinguishers, fire hydrants, hoses and nozzles are in place, properly
arranged, and are in proper condition;
.2 all fixed fire-fighting system stop valves are in the proper open or closed position, dry pipe sprinkler systems have appropriate pressures as indicated by gauges;
.3 sprinkler system pressure tanks have correct levels of water as indicated by glass gauges;
.4 all sprinkler system pumps automatically operate on reduction of pressure in the systems;
Rev. 7/02 3 of 8 2-011-14
The Republic of the Marshall Islands
.5 all fire pumps are operated; and
.6 all fixed fire-extinguishing installations using extinguishing gas are free from leakage. 1.5 Quarterly examinations and inspections.
Ships officers are responsible for performing quarterly tests and examinations of the following firefighting system equipment and recording the test and examinations in the ship's official log book. Quarterly inspections should be carried out to ensure that:
.1 all automatic alarms for the sprinkler systems are tested using the test valves for each
section;
.2 the international shore connection is in proper condition;
.3 fire stations and lockers providing storage for fire-fighting equipment contain proper inventory and that missing or unserviceable equipment is replaced*;
.4 all fire doors and fire dampers are tested for local operation; and
.5 all CO2 bottle connections for cable operating system clips should be checked for tightness
on fixed fire-extinguishing installations. 1.6 Annual testing and inspections.
As part of the annual statutory survey for Safety Equipment Certification, the following inspections and tests should be carried out to ensure that:
.1 all fire extinguishers are checked for proper location, charging pressure, and condition;
.2 fire detection systems are tested for proper operation, as appropriate;
.3 all fire doors and dampers are tested for remote operation;
.4 all foam-water and water-spray fixed fire-fighting systems are tested for operation;
.5 all accessible components of fixed fire-fighting systems are visually inspected for proper
condition;
* The minimum fire hose length is 10 meters. The length should not exceed 15 meters in machinery spaces and 20 meters in other compartments and on open decks (except that hoses of 25 meters in length may be used on open decks when the breadth of the ship is greater than 30 meters).
Rev. 7/02 4 of 8 2-011-14
The Republic of the Marshall Islands
.6 all fire pumps, including sprinkler system pumps, are flow tested for proper pressures and flows;
.7 all hydrants are tested for operation;
.8 all antifreeze systems are tested for proper solutions;
.9 sprinkler system connections from the ship’s fire main are tested for operation;
.10 all fire hoses are hydrostatically tested;
.11 breathing apparatus air recharging systems checked for air quality;
.12 control valves of fixed fire-fighting systems should be inspected; and
.13 air should be blown through the piping of extinguishing gas systems.
The verification of the examinations and tests described in Sections 1.2 thru 1.6 above are an integral part of the annual statutory surveys for the SOLAS Safety Equipment Certificate. The inspection and/or verification of the applicable items in Section 1.2 thru 1.7 shall be to the satisfaction of the attending Classification Society surveyor.
1.7 Five-year service.
At least once every five years, the following inspections and tests should be carried out:
• control valves of fixed fire-fighting systems should be internally inspected. 2.0 Fixed CO2 and Halon Systems. 2.1 Verification of Cylinder Contents.
Every two (2) years the contents of the cylinders are verified by weight or isotropic measurement as part of the survey for issuance of the SOLAS Safety Equipment Certificate. Weigh scales may be used to verify cylinder contents and recharging is required if the loss in charge is 10 percent or more. Generally the weigh scales are included as part of the CO2 system equipment in order to satisfy FSS Code, Regulation 5.2.1.1.3.
2.2 Hydrostatic Testing.
All fixed CO2 and Halon cylinders must be hydrostatically tested as follows:
.1 after each 20 years of service,
Rev. 7/02 5 of 8 2-011-14
The Republic of the Marshall Islands
.2 prior to recharging a discharged cylinder,
.3 or when visual inspection reveals a potential defect.
Hydrostatic test dates must be stamped on the cylinders. Hydrostatic testing must be performed by a authorized servicing facility which has been certified by a government agency, or Classification Society, and by extinguisher manufacturer to perform this type of work. The facility must be acceptable to the attending Classification Society surveyor. The same facility should recharge the cylinders after testing to demonstrate serviceability.
3.0 Portable Fire Extinguishers. 3.1 Annual Survey.
The examination of the fire extinguishers is an integral part of the annual statutory surveys for the SOLAS Safety Equipment Certification. The fire extinguishers should be examined and, if necessary, serviced annually. The annual servicing/examination of the portable fire extinguishers can be carried out by the crew, if the crew is properly trained and such servicing is acceptable to the vessel’s Classification Society, or by an authorized service facility. The Classification Society surveyor must be satisfied with the condition of the extinguishers.
3.2 Servicing of Fire Extinguishers by the Crew of a Vessel.
A vessel crew may service powder, foam, or water type portable fire extinguishers subject to the following:
.1 The equipment required to test, examine, and service the extinguishers is obtained and
maintained in a calibrated and serviceable condition.
.2 The crew is properly trained in the testing and examination, and servicing of fire extinguishers and the extinguisher manufacturer's servicing instructions are followed.
.3 The testing and inspection is carried out to the satisfaction of the attending Classification
Society surveyor, and if required by the surveyor, in the presence of the surveyor. 3.3 Verification of Fire Extinguishers Contents.
Every two years in conjunction with the issuance of the SOLAS Safety Equipment Certificate the contents of the cylinders must be verified. Weighing of the portable CO2 cylinders in the presence of the Classification Society surveyor is an acceptable method of verification. Other methods of determining contents of the cylinders, such as isotropic measurement, may also be accepted provided the equipment is properly calibrated, the operator of the device is trained and qualified in
Rev. 7/02 6 of 8 2-011-14
The Republic of the Marshall Islands
its use, and the Classification Society surveyor is satisfied with the measurements. If an alternative method is used, spot checks of cylinder contents by weighing may be required to verify the accuracy and consistency of the measurement device.
3.4. Spare Charges, Additional Fire Extinguishers, and Refilling of Extinguishers.
.1 For fire extinguishers of the same type, capable of being recharged on board, the spare charges should be provided as follows:
100% for the first 10 extinguishers and 50% for the remaining extinguishers but not more than 60 (fractions to be rounded off to next whole number).
.2 For extinguishers which cannot be recharged by the crew, additional portable fire
extinguishers of the same quantity, type, capacity and number as determined in paragraph a above should be provided in lieu of spare charges.
.3 Instructions for recharging the extinguishers should be carried on board. Periodic refilling of
the cylinders should be in accordance with the manufacturer's recommendations. Lacking same, refill is required when the extinguishing media starts to lose effectiveness. Partially emptied extinguishers should also be recharged. Only refills approved for the fire extinguisher in question may be used for recharging.
3.5 Authorized Servicing Facilities.
The Classification Society surveyor may also accept a servicing certificate from an authorized servicing facility acceptable to the society for both the annual and biannual examination, servicing and verification of the portable fire extinguishers.
3.6 Hydrostatic Testing of Portable Fire Extinguishers
All portable extinguishers shall be hydrostatically tested every 10 years; however, a hydrostatic test may also be required by the Classification Society surveyor or Marshall Islands Nautical Inspector if visual examination indicates a potential defect in the cylinder. The hydrostatic test date must be permanently marked on the bottles.
3.7 Hydrostatic Testing Facilities.
Hydrostatic testing must be performed by a servicing facility which has been certified by a government agency or Classification Society, and by the extinguisher manufacturer to perform this type of work. The facility must be acceptable to the attending Classification Society surveyor. This same facility should recharge the cylinder after testing to demonstrate serviceability.
Rev. 7/02 7 of 8 2-011-14
The Republic of the Marshall Islands
4.0 Fixed Foam System. 4.1 Foam Analysis.
Foam analysis is a part of the survey for issuance of the SOLAS Safety Equipment Certificate and thus is performed every two years. The Classification Society surveyor may require it at other times if there is cause to question the suitability of the foam or condition of the storage tank.
5.0 Self-Contained Breathing Apparatus (SCBA). 5.1 Annual Examination.
All SCBAs shall be examined at least annually as part of the annual statutory survey for the Safety Equipment Certificate (SEC) or MODU Code certificate. If applicable, the breathing apparatus air recharging systems should be checked for air quality as part of the annual statutory survey for the SEC or MODU Code certificate.
5.2 Hydrostatic Testing of Self-contained Breathing Apparatus Cylinders.
Hydrostatic testing of SCBA cylinders shall be carried out once every five years. The hydrostatic test date must be permanently marked on the bottles. Intervals for hydrostatically testing cylinders of the ultra lightweight type may vary and will depend upon the requirements of the cylinder manufacturer and the vessel’s Classification Society. Servicing of the cylinders must be performed to the satisfaction of the Classification Society surveyor.
5.3 Spare Charges and Recharging of Breathing Apparatus Air Cylinders.
.1 Two spare charges suitable for use with the breathing apparatus should be provided for each required apparatus.
.2 If passenger ships carrying not more than 36 passengers and cargo ships are equipped with
suitable located means for fully recharging the air cylinders free from contamination, only one spare charge is required for each required apparatus.
6.0 Emergency Escape Breathing Devices (EEBDs) 6.1 Number and Locations
.1 SOLAS requires at least two EEBDs to be located in the accommodations and additional EEBDs to be placed in the machinery spaces, The Administration considers “machinery spaces” to mean Category A Machinery Spaces such as engine rooms and boiler rooms. Auxiliary Machinery Spaces such as Steering Gear Compartments, Refrigeration Machinery Rooms, Bow Thruster Compartments, and alike do not have to be fitted with EEBDs.
Rev. 7/02 8 of 8 2-011-14
The Republic of the Marshall Islands
.2 Inasmuch as MSC/Circ.849 is referenced in SOLAS II-2/13.3.4 and 13.4.3, the
Administration is treating the guidelines contained in the Circular as mandatory.
.3 For compliance with the last sentence in Paragraph 4.6 of MSC/Circ.849, only those control spaces and workshops that are remotely located from the machinery space escape routes need be considered.
.4 In achieving compliance with paragraph 4.6 of MSC/Circ.849, a minimum of two EEBDs should be located on each level of the machinery space. If a machinery space contains an enclosed primary escape trunk having a door at each level, only one EEBD need be located on each level*.
6.2 Maintenance and Care
.1 The EEBD should be examined and maintained in accordance with the manufacturer’s
instructions. .2 Sufficient spare EEBDs should be kept on board to replace units that are used, reach their
expiry date, or otherwise become unserviceable. .3 Maintenance requirements, manufacturer’s trademark and serial number, shelf life with
accompanying manufacture date and name of approving authority should be printed on each EEBD.
* The term “level” should be interpreted as meaning a deck where watchstanding personnel reside, workshops and control stations are located, or the crew may be employed during routine maintenance. In essence, two EEBDs are required only on those deck “levels” where people are likely to be employed. Platform decks that serve to divide long ladders into segments and partial decks where personnel are not likely to be employed for any significant period of time are not considered as “levels” and do not require EEBDs.
Panama Maritime Authority Directorate General of Merchant Marine International Representative Office, New York
Merchant Marine Circular No. 122
Note: 11.1 revised April 2003 (see asterisk *) 1 Purpose
.1 This Merchant Marine Circular establishes new guidelines for the proper maintenance, testing, inspection and service of fixed and portable fire protection systems, appliances and emergency equipment. It replaces Merchant Marine Circular 96 and the following titles (with their respective requirements) on Merchant Marine Circulars 70 and 91: “SOLAS - Emergency Fire Pump,” “Testing of CO2 Cylinders ” and “Portable Fire Extinguishers.”
.2 This Merchant Marine Circular interprets item d on the Merchant Marine Circular 119
2 Application
.1 These Guidelines apply to all ships including Units under MODU Code or Technical Note MODU 1/83.
3 Operational readiness
.1 All fire protection systems and appliances shall at all times be in good order and available for immediate use while the ship is in service. If a fire protection system is under repair, then suitable arrangements acceptable to the Recognized Organization that issued the pertinent safety certificate shall be made to ensure safety is not diminished. Under this circumstance, prior to sailing, the ship shall obtain a short-term certificate authorized by this office to the pertinent Recognized Organization. Unless expressly provided here otherwise, these authorizations for temporary non-compliance shall be issued for 60 days as per Merchant Marine Circular 39 and Resolution 614-33-ALCN or as per the Merchant Marine Circular or Resolution that regulates authorizations for temporary non-compliance at that time.
4 Maintenance and testing
.1 Instructions for on-board maintenance, not necessarily by the ship's crew, and testing of active and passive fire protection systems and appliances shall be easily understood, illustrated wherever possible, and, as appropriate, shall include the following for each system or appliance:
To: Owners/Operators of Panamanian flag ships Recognized Organizations Subject: Guidelines for the Maintenance and Inspection of Fire-Protection Systems and Appliances. Interpretation of Merchant Marine Circular 119 (item d). References: Merchant Marine Circular 39 & Resolution No. 614-33-ALCN MSC/Circ.850, MSC/Circ. 847, MSC/Circ.582, 670 & 798 SOLAS 74, 2000 amendments and Merchant Marine Circulars 70, 91, 96 & 119 IMO Assembly Resolution A. 602(15), A.719(17), MSC/Circ.600 and MSC.27(61)
Seite 1 von 5Merchant Marine Circular No
2004-01-23file://F:\Data\Abt_BCS\02%20Allgemeine%20Vorgänge\2003-12-09%20Vermarktun...
a. maintenance and repair instructions; b. schedule of periodic maintenance; c. list of replaceable parts; and d. log for records of inspections and maintenance, listing identified non-conformities and their
targeted completion dates. 5 Weekly testing and inspections
.1 Weekly inspections shall be carried out to ensure that: a. all public address systems and general alarm systems are functioning properly; and b. breathing apparatus cylinders do not present leakages.
6 Monthly testing and inspections
.1 Monthly inspections shall be carried out to ensure that: a. all fireman's outfits, fire extinguishers, fire hydrants, hose and nozzles are in place, properly
arranged, and are in proper condition; b. all fixed fire-fighting system stop valves are in the proper open or closed position, dry pipe
sprinkler systems have appropriate pressures as indicated by gauges; c. sprinkler system pressure tanks have correct levels of water as indicated by glass gauges; d. all sprinkler system pumps automatically operate on reduction of pressure in the systems; e. all fire pumps are operated; and f. all fixed fire -extinguishing installation using extinguishing gas are free from leakage.
7 Quarterly testing and inspections
.1 Quarterly inspections shall be carried out to ensure that: a. all automatic alarms for the sprinkler systems are tested using the test valves for each section; b. the international shore connection is in proper condition according to the specifications of the
FSS Code; c. lockers providing storage for fire-fighting equipment contain proper inventory and equipment
is in proper condition; d. all fire doors and fire dampers are tested for local operation; and e. all CO2 bottle connections for cable operating system clips shall be checked for tightness on
fixed fire-extinguishing installations.
8 Annual testing and inspections
.1 Annual inspections shall be carried out to ensure that: a. all portable fire extinguishers are checked for proper location, charging pressure, and condition
according to the ship’s fire plan; b. fire detection systems are tested for proper operation, as appropriate; c. all fire doors and dampers are tested for remote operation; d. all foam-water and water -spray fixed fire-fighting systems are tested for operation; e. all accessible components of fixed fire-fighting systems are visually inspected for proper
condition; f. all fire pumps, including sprinkler system pumps, are flow tested for proper pressures and
flows; g. all hydrants are tested for operation; h. all antifreeze systems are tested for proper solutions; i. sprinkler system connections from the ship's fire main are tested for operation; j. all fire hoses are hydrostatically tested; k. All Self-contained breathing apparatus (including SCBA’s on lifeboats) should be checked for
external condition and air recharging systems checked for air quality;
Seite 2 von 5Merchant Marine Circular No
2004-01-23file://F:\Data\Abt_BCS\02%20Allgemeine%20Vorgänge\2003-12-09%20Vermarktun...
.2 Every two years, portable fire extinguishers and SCBA’s cylinders shall be checked by a service agent or facility certified by the manufacturer to perform this type of work and accepted by the Recognized
Organization issuing the pertinent safety certificate[§]
. Every other year, these checks shall be carried
out either by a service agent or facility (certified and accepted§) or by a deck or engine officer trained and assigned to this duty.
.3 Halon installations of fire–extinguishing systems on board ships, which keel was laid or at a similar stage of construction on or after October 1994, are prohibited. Moreover, full-scale tests of Halon fire-extinguishing systems on board ships are prohibited since January 1992 in accordance with Resolution A.719(17)/2(b). However, an annual leakage test shall be carried out, MSC/Circ.600. The Chief Engineer can carry out this test if provided with the proper equipment and training.
9 Two year service
.1 At least once every two years, the following inspections and tests shall be carried out:
a. CO2 Fixed System contents shall be verified at least every two years. b. Air shall be blown through the piping of extinguishing gas systems.
.2 The blow test (item 9.1(b)) shall be carried out by a service agent or facility certified by the manufacturer to perform this test and accepted by the Recognized Organization issuing the pertinent safety certificate.
10 Three year service
.1 Periodical controls of foam concentrates stored on board .2 The first periodical control of fixed foam fire-extinguishing system and foam concentrates stored on
board shall be performed after a period of 3 years (from the original installation date), after that, every year. A record of the age of the foam concentrates and of subsequent control should be kept on board readily available for inspection. Periodical controls or analysis will be performed by an independent or manufacturer ’s laboratory, which is accepted by the Recognized Organization issuing the pertinent safety certificate. Tests, controls or analysis of foam will be performed as per MSC/Circ.582, MSC/Circ. 670 and MSC/Circ.798.
11 Five-year service
.1 Hydrostatic testing for all SCBA's cylinders (*)
.2 Hydrostatic testing for all SCBA's cylinders shall be carried out by a servicing facility or agent certified by the manufacturer to perform this type of work and accepted by the Recognized Organization issuing the pertinent safety certificate. Test certificates must be provided and kept on board for inspections. Test date and pressure must be stamped or tagged on each cylinder. This test shall not be carried on board.
12 Ten-year Service
.1 At least once every ten years, the following inspections and tests should be carried out: a. Control valves of fixed fire-fighting systems shall be internally inspected. b. Hydrostatic Pressure Test of Portable Fire Extinguishers
.2 Hydrostatic Testing for all Portable Fire Extinguishers and internal inspection of control valves of the fixed fire-fighting systems shall be carried out by a servicing facility or agent certified by the manufacturer to perform this type of work and accepted by the Recognized Organization issuing the pertinent safety certificate.
.3 Portable Fire Extinguishers Test certificates must be provided and kept on board for inspections. Test date and pressure must be tagged on each bottle. This test shall not be carried on board.
Seite 3 von 5Merchant Marine Circular No
2004-01-23file://F:\Data\Abt_BCS\02%20Allgemeine%20Vorgänge\2003-12-09%20Vermarktun...
13 Twenty-year Service
.1 All (100%) CO2 cylinders from the fixed fire system shall be hydrostatically tested before 20 years
from the date of manufacture and the pressure test shall then be completed every ten years thereafter. Any percentage of CO2 bottles can be hydrostatically tested at any interval of time but all (100%) shall be hydrostatically pressure tested no later than the datelines already established.
.2 Hydrostatic testing for the fixed CO2 system shall be carried out by a servicing facility or agent which
has been certified by the manufacturer to perform this type of work and accepted by the Recognized Organization issuing the pertinent safety certificate. Test certificates must be provided and kept on board for inspections. Test date and pressure must be stamped on each bottle. This test shall not be carried on board.
.3 Ships (20 years or older) coming into our registry will be required to carry this test at the next scheduled dry-docking. However, no CO2 cylinder onboard our ships shall reach 20 years from the date of manufacture without being hydrostatically tested.
14 The verification of the examinations and tests until here mentioned shall be to the satisfaction of the attending surveyor of the Recognized Organization that will endorse or issue the pertinent safety certificate.
15 Fire Extinguishers Spare Charges
.1 Spare charges shall be provided for 100% of the first 10 extinguishers and 50% of the remaining fire extinguishers capable of being recharged on board. Not more than 60 total spare charges are required. Instructions for recharging should be carried out on board.
.2 For fire extinguishers which cannot be recharged onboard, additional portable fire extinguishers of the same quantity, type, capacity and number as determined in above paragraph shall be provided.
16 Fire Protection - Paint Lockers
.1 Paint lockers shall be protected by: a. a carbon dioxide system, designed to give a minimum volume of free gas equal to 40% of
the gross volume of the protected space; b. a dry powder system, designed for at least 0.5 kg powder/m 3;
c. a water spraying or sprinkler system, designed for 5 l/m2 min. Water spraying systems may be connected to the fire main of the ship; or
d. The fitting of a portable fire extinguisher immediately outside the entrance to the paint locker. The number of portable extinguishers is to be adequate to the size of the paint locker as determined by the Recognized Organization.
.2 In any case, the system shall be operable from outside the protected space
17 SOLAS - Emergency Fire Pump
.1 This Administration accepts gasoline engine driven portable emergency fire pumps on board cargo ships less than 2000 GRT. Proper precautions must be observed in the storage and handling of gasoline with this equipment.
18 Minimum Number of EEBD’s in Machinery Spaces.
20 Year Period 10 Yr.
Period
10 Yr.
Period
10 Yr.
Period
10 Yr.
Period
10 Yr.
Period
10 Yr.
Period
10 Yr.
Period
100% 100% 100% 100% 100% 100% 100% 100%
Seite 4 von 5Merchant Marine Circular No
2004-01-23file://F:\Data\Abt_BCS\02%20Allgemeine%20Vorgänge\2003-12-09%20Vermarktun...
.1 In reference to the item d on the Merchant Marine Circular 119, the maximum number of persons (i.e.
engineers and ratings) working during a normal day of operation shall be understood as the sum of ratings (from the engine department) and engineers on the ship’s Minimum Safe Manning Certificate. If this sum exceeds six persons, then six EEBD’s will be the minimum number required in machinery spaces.
January 2003 (*) Revised April 2003 Inquiries concerning the subject of this Circular or any request should be directed to: Directorate General of Merchant Marine, New York Office International Representative Office 6 West 48th Street, 11 th floor New York, NY 10036 U.S.A. Phone: ++1 (212) 869 -6440 Fax: ++1 (212) 575-2285/2288 www.segumar.com
[§] Whenever is stated “and accepted by the Recognized Organization issuing the pertinent safety certificate”it must be pointed out that this Administration recognizes the tests performed by an agent, facility or laboratory certified by any of her Recognized Organizations. Therefore, having the agreement of the Recognized Organization that issues the pertinent safety certificate, it is possible to hire the services of an agent, facility or laboratory certified by a Recognized Organization that no necessarily will issue or endorse the pertinent safety certificate.
Seite 5 von 5Merchant Marine Circular No
2004-01-23file://F:\Data\Abt_BCS\02%20Allgemeine%20Vorgänge\2003-12-09%20Vermarktun...
MARITIME AND PORT AUTHORITY OF SINGAPORE
MARINE CIRCULAR TO SHIPOWNERS NO. 4 OF 2003
Date: 19/3/03
MAINTENANCE, TESTING AND INSPECTIONS OF FIRE-PROTECTION SYSTEMS AND FIRE-FIGHTING SYSTEMS AND APPLIANCES
Regulation II-2/14.2.2 (Maintenance, testing and inspections) of the 2000 SOLAS Amendments requires maintenance, testing and inspections to be carried out based on MSC/Circ.850 (Guidelines for the Maintenance and Inspection of Fire-protection systems and appliances) dated 8 June 1998.
2 The maintenance plan should include, but not limited to, the following fire protection systems and fire-fighting systems and appliances, where installed: (a) fire mains, fire pumps and hydrants including hoses, nozzles and international shore connections; (b) fixed fire detection and fire alarm systems; (c) fixed fire-extinguishing systems and other fire extinguishing appliances; (d) automatic sprinkler, fire detection and fire alarm systems; (e) ventilation systems including fire and smoke dampers, fans and their controls; (f) emergency shut down of fuel supply; (g) fire doors including their controls; (h) general emergency alarm systems; (i) emergency escape breathing devices; (j) portable fire extinguishers including space charges; and (k) fire-fighter’s outfits.
3 In addition to the fire protection systems and appliances listed in paragraph 2, passenger ships are required to develop a maintenance plan for low-location lighting and public address systems.
4 In addition to the fire protection systems and appliances listed in paragraph 2, tankers are required to develop a maintenance plan for: (a) inert gas systems; (b) deck foam systems; (c) fire safety arrangements in cargo pump rooms; and (d) flammable gas detectors.
5 The following are supplementary to the guidelines in MSC/Circ.850: (a) Portable fire extinguishers (i) Portable fire extinguishers should be examined annually by a competent person; (ii) Each portable fire extinguisher should be provided with a sign indicating that it has been examined. (iii) Containers of permanently pressurized portable fire extinguishers and propellant bottles of non- pressurized portable fire extinguishers should be hydraulic pressure tested as follows: · powder extinguishers every 10 years;
Applicable to: Shipowners, shipmanagers, masters and officers of Singapore ships. This circular provides guidance for the maintenance and inspection of fire-protection systems and appliances.
Seite 1 von 3Maintenance,Testing and Inspections oF Fire-Protection Systems And Fire-Fighting ...
2004-01-23file://F:\Data\Abt_BCS\02%20Allgemeine%20Vorgänge\2003-12-09%20Vermarktun...
· CO2 extinguishers every 10 years; and · Other extinguishers every 10 years. (iv) Containers of non-permanently pressurized portable fire extinguishers should be hydraulic pressure tested every 10 years. (b) Fixed CO2 fire extinguishing installation (i) CO2 bottles of fixed CO2 fire extinguishing installation should be hydraulic pressure tested 20 years after the date on which the bottles were put into use, and every 5 years thereafter. (ii) The quantity of the medium in the CO2 bottles should be checked once every 4 years. This may be carried out in batches of 25% of the CO2 bottles annually, or 50% of the CO2 bottles biennially or in accordance with the ship’s maintenance so long as every CO2 bottle is checked once every 4 years. (iii) All stop valves should be checked monthly to ensure that they are in their proper open or closed position. (iv) The installation should be checked monthly to ensure that there is no leakage. (v) All CO2 bottle connections for cable operating system clips should be checked for tightness every 3 months. (vi) All control valves should be inspected annually and internally inspected every 5 years. (vii) Air should be blown through the piping of the installation annually
(c) Low pressure fixed CO2 fire extinguishing installation (i) The tanks, together with fittings shall be inspected externally every 5 years. (ii) At the external inspection, insulation material of the tank at points most likely to suffer corosion/ deterioration and considered necessary shall be removed to facilitate the external inspection. (iii) Pipes and valves at transitional points between insulated and uninsulated areas (cold-conductors) as well as tank supports, flange sockets and valves shall be included in the 5-yearly external inspection. (iv) The external inspection shall also include maintenance inspection stipulated in the manufacturer's operation and maintenance manual. (v) At least once a year, a thorough external inspection of the tank supports, flange sockets and valves mentioned in (c) shall be carried out. (vi) In addition to the 5-yearly external inspection, an internal inspection of the tanks shall be carried out every 10 years. (vii) Hydrostatic testing of the pipes and tanks may be required at the discretion of the attending surveyor, in cases of corrosion/deterioration or the external or internal proved prudent to do so. (viii) In any case, hydrostatic testing of the pipes and tanks shall be carried out after repairs to the tanks or pipes in cases of cracks or holes.
6 A copy of MSC/Circ.850 can be found in our website under “other notices” at:
Seite 2 von 3Maintenance,Testing and Inspections oF Fire-Protection Systems And Fire-Fighting ...
2004-01-23file://F:\Data\Abt_BCS\02%20Allgemeine%20Vorgänge\2003-12-09%20Vermarktun...
www.mpa.gov.sg/homepage/other-notices.html
7 This circular supersedes Marine Circular No. 7 of 2000 dated 9 June 2000.
8 Any queries relating to this circular should be directed to Mr. Tan Leong Beng at 6375 6207.
LEE SENG KONG DIRECTOR OF MARINE MARITIME AND PORT AUTHORITY OF SINGAPORE
Seite 3 von 3Maintenance,Testing and Inspections oF Fire-Protection Systems And Fire-Fighting ...
2004-01-23file://F:\Data\Abt_BCS\02%20Allgemeine%20Vorgänge\2003-12-09%20Vermarktun...
MARITIME AND PORT AUTHORITY OF SINGAPORE
MARINE CIRCULAR TO SHIPOWNERS NO.14 OF 2003
Date: 24/7/03
GUIDELINES FOR PERIODIC SERVICING AND MAINTENANCE OF LIFEBOATS, LAUNCHING APPLIANCES AND ON-LOAD RELEASE GEAR
Regulation III/20 (Operational readiness, maintenance and inspections) of SOLAS 74 requires instructions for on-board maintenance of life-saving appliances complying with the requirements of Regulation III/36 (Instructions for on-board maintenance) to be provided and maintenance to be carried out accordingly.
2 Section 10 (Maintenance of the Ship and Equipment) of the ISM Code requires a Company, as defined in Regulation IX/1.2 of SOLAS 74, to establish procedures to ensure that the ship is maintained in conformity with the provisions of the relevant rules and regulations.
3 For the purpose of the above requirements, the Guidelines for Periodic Servicing and Maintenance of Lifeboats, Launching Appliances and On-load Release Gear issued by IMO in MSC/Circ.1093 dated 17 June 2003 shall be complied with.
4 Companies should review the existing instructions for on-board maintenance of life-saving appliances and procedures relating thereto in the Safety Management System on board their ships to ensure that the guidelines are complied with.
5 A copy of MSC/Circ.1093 can be found in our website under “other notices” at: http://www.mpa.gov.sg/homepage/other-notices.html
6 Any queries relating to this circular should be directed to Mr. Tan Leong Beng at 6375 6207.
LEE SENG KONG DIRECTOR OF MARINE MARITIME AND PORT AUTHORITY OF SINGAPORE
Applicable to: Shipowners, shipmanagers, masters and officers of Singapore ships.
Seite 1 von 1Guidelines For Periodic Servicing and Maintenance of Lifeboats, Launching Applia...
2004-01-23file://F:\Data\Abt_BCS\02%20Allgemeine%20Vorgänge\2003-12-09%20Vermarktun...
S e rvicing of Inflatable Liferafts, Inflatable Boats,Rescue Boats, Fast Rescue Boats, InflatableLifejackets and Hydrostatic Release Units.
Notice to Owners, Operators and Masters of Merchant Ships, Owners and Skippers of FishingVessels, Code Vessels, Yachtsmen, Manufacturers and Service Station Personnel.
This Note supersedes Marine Guidance Note MGN 182 (M+F)
MARINE GUIDANCE NOTE
Summary
This note advises all owners, operators and seafarers of the need to have the above mentioned life-saving appliances regularly serviced at an approved service station.
Key Points:
All above mentioned life-saving appliances carried on UK ships, Code Vessels and fishing vessels arenormally required to be serviced annually, although if compliance is impracticable servicing may bedeferred for a period not exceeding 5 months.
Listed in the Appendices to this note are the names and addresses of the manufacturers of the abovementioned life-saving appliances and their currently appointed service station located in the UK.
Owners or Masters requiring details of overseas service stations or confirmation of continuedacceptance of any listed service station are requested to make contact with the individualmanufacturer.
An exception to annual servicing of liferafts indicated above, is that the Maritime and CoastguardAgency has introduced a scheme for extended servicing of open reversible liferafts (ORLs) fitted toClass III to VI(A) passenger vessels. These do not apply to ORLs fitted on high-speed craft or canopyliferafts fitted to the above classes of vessels.
National Administrations are responsible for the approval of servicing stations within their jurisdiction.
MGN 274 (M+F)
1
1. Shipowners, masters, skippers andyachtsmen are reminded of the need tohave inflatable liferafts, inflatable boats,rescue boats, fast rescue boats, inflatable lifejackets and hydrostatic release units, where applicable, which formpart of their vessel’s life-saving appliances,
regularly serviced at an approved service station.
2. Under the provisions of the followingRegulations, all inflatable liferafts, boats,rescue boats, fast rescue boats, inflatablelifejackets and hydrostatic release units
2
carried on United Kingdom ships andfishing vessels are required to be servicedat an approved service station:
• Regulation 11(7) of the Merc h a n tShipping (Life-Saving Appliances forPassenger Ships of Classes III to VI (A))Regulations 1999.
• Regulation 84 (7) of the Merc h a n tshipping (Life Saving Appliances forShips Other Than Ships of Classes III toVI(A)) Regulations 1999 as amended byM e rchant Shipping (Life-SavingAppliances for Ships Other Than Shipsof Classes III to VI(A)) (Amendment)Regulations 2000.
• Rule 85(2) of the Fishing Vessel (SafetyProvisions) Rules 1975.
• Regulation 5 of the Fishing Vessels (Life Saving A p p l i a n c e s )Regulations 1988.
• Sections 12.14 and 12.26.3 of the Surveyof Fishing Vessels (Instructions for theGuidance of Surveyors).
3. Such liferafts, lifejackets, inflatable boats,rescue boats, fast rescue boats andh y d rostatic release units are normallyrequired to be serviced annually and everyeffort should be made to ensure that it iscarried out (however see paragraph11 ) .When it is clearly impracticable to complywith this annual servicing requirement, theservicing may be deferred for a period notexceeding 5 months. In such cases mastersor owners are requested to apply to theMaritime and Coastguard Agency’s (MCA)Shipping Safety Branch, indicating theirreason for seeking their deferment.
4. It should also be noted that InternationalSailing Federation (ISAF) Offshore SpecialRegulations (OSR) Appendix A Part 2canister rafts, which are acceptable onsome vessels certified under the MCA’sCodes of Practice for vessels under 24m(Code Vessels), must be serviced accordingto the manufacture r’s instructions at amanufacturer‘s approved service station.
5. Inflatable lifejackets on Code Ve s s e l sshould be serviced at a service stationapproved by the manufacturer within onemonth either side of the Compliance,
Renewal and Intermediate examinations ofthe vessel. In the intervening years they a re to be examined annually to themanufacturer’s recommendation. Furtherinformation on inflatable liferaft andlifejacket servicing can be found in theCodes of Practice.
6. Listed in Appendix 1 to this Note arenames of the manufacturers of approvedliferafts, (including hydrostatic re l e a s eunits), lifejackets, inflatable boats, rescueboats and fast rescue boats and the namesand addresses of their currently appointedservice stations located in the UnitedKingdom. Owners or masters wishing toobtain details of the service stations locatedoverseas or to have confirmation of thecontinued acceptance of any station in theUnited Kingdom should make dire c tcontact with the individual manufacturer.M a n u f a c t u rers must provide the MCAwith details of any changes to theapproved service stations.
7. In recent years a number of cases involvingextremely poor servicing of liferafts havebeen reported. On further investigation itwas found that in many of these cases theservicing had been so inadequate that theraft would have been ineffective as a pieceof life-saving equipment. As aconsequence, it is recommended that priorto placing liferafts, lifejackets, hydrostaticrelease units, inflatable boats, rescue boatsor fast rescue boats in a service station,owners or masters should obtainconfirmation of the continued acceptanceof the station direct from the individualmanufacturer. Details of their agents arelisted in Appendix 2. With re g a rd toinflatable liferafts the re q u i rements foronboard stowage together with hydrostaticrelease units are contained in MarineGuidance Note MGN 104 (M+F).
8. The MCA has, since July 1993, conformedwith the servicing re q u i rements given in IMO Resolution A.761(18) -“Recommendations On Conditions ForThe Approval Of Servicing Stations ForInflatable Liferafts”- for it's appro v e dservice stations in the United Kingdom.For information an extract of this IMOResolution is shown at Appendix 3, whichindicates the frequency of the various testsnow carried out.
3
9. It should be noted that United Kingdomships are required to carry Wheelmarkedliferafts equipped to UK standards underthe requirements of the Marine EquipmentD i rective. At present, manufacturers ofapproved liferafts are required to have aservice network of at least six in the UK.H o w e v e r, this may not be possible incertain cases where a vessel is carrying aliferaft which needs servicing, but is notmanufactured by one of the companieswith a UK service station network. TheOwner, Master or Agent should, in thesecases, contact the manufacturer of theliferafts carried in order to establish thelocation of their approved service stations.
10. An exception to the annual servicing ofliferafts indicated above, is that for openreversible liferafts (ORLs) fitted to Class IIIto VI(A) passenger vessels, the MCA hasi n t roduced a scheme for extendedservicing i.e. to omit the second year,fourth year sixth year and eighth yearannual servicing interval. It should benoted that this extended servicingprocedure will not apply to ORLs fitted tohigh-speed craft or to canopy "SOLAS"type liferafts fitted to the above Classes of vessels. A general exemption from the re q u i rements of Regulation 11(7) of the Merchant Shipping (Life-SavingAppliances for Passenger Ships of ClassesIII to VI(A)) Regulations 1999 has beenissued and is shown in Appendix 4. Theschedule to this general exemption,attached as Appendix 5, specificallyindicates the particular servicing intervalsand test methods applicable to ORLs fittedon the above passenger ships.
11. A further exception to the annual servicingof inflatable liferafts has been accepted byMCA. This exception allows servicingintervals of up to 30 months for particularequipment when it is specially packed.Special packing systems have beendesigned and developed by the relevantmanufacturers, and these ensure that theliferafts can (i) be operated using thenormal control lines, and (ii) re m a i np rotected throughout the extendedservicing interval within a hermeticallysealed membrane which resists watervapour transmission. The arrangementsfall within the provisions of SOLAS 1974Chapter III, regulations 20.8.3 and 20.8.5, inrespect of which MCA has notified IMO of
the arrangements accepted on UnitedKingdom ships. Extracts from these IMOnotifications are attached at Appendices 6and 7 which describe the equipment andthe conditions attached to its use. It shouldbe noted that these specially packedliferafts may only be serviced at suitablyequipped, approved service stations, a listof which must be obtained from the liferaft manufacturer.
12. At every biennial servicing or servicingreferred to in paragraph 11, of a davitlaunched inflatable liferaft, inflatable boator inflatable rescue boat, a 10% overloadstatic load test is to be carried out with the liferaft or boat suspended f rom its lifting hook or bridle in a c c o rdance with the manufacture r’ sapproved servicing instructions.
13. With regard to hydrostatic release units(HRUs), at present there are typesa p p roved by the MCA which have anoperational life of two years without anintermediate service being required. In thiscase, when the operational life of theseparticular hydrostatic release units hase x p i red, they are to be returned to anauthorised service station where a functiontest is to be carried out.
14. In recent years an increasing incidence ofincorrectly installed HRUs has been notedby Surveyors carrying out Inspections,resulting in the float free arrangements forthe liferaft being compromised. A f t e rservicing of the liferaft and HRUs, whereapplicable, the liferaft and HRUs whenreturned on board should be installedstrictly in accordance with the approvedmanufacturer's instructions. Details of thec o r rect installation of the HRU to theliferaft should be provided with each unit supplied.
15. An ‘approved service station’ is one thathas been formally appointed by them a n u f a c t u rer of an approved type ofliferaft, boat or inflatable lifejacket and hasbeen accepted by the Secretary of State. Ithas certificated personnel who have beentrained to undertake servicing and repairs,and also to repack inflatable liferafts readyfor operational use; it carries genuinespares and is kept fully informed of thec u r rent servicing pro c e d u res by theapproved manufacturer.
Shipping Safety BranchMaritime and Coastguard AgencySpring Place105 Commercial RoadSO15 1EG
Telephone: 023 8032 9522Fax: 023 8032 9251E-Mail: [email protected]
General Enquiries: 24 Hour Info [email protected] 600 6505
MCA Website Address: Internet:http://www.mcga.gov.uk
File Ref: MS 3/14/862
Published: January 2005
© Crown Copyright 2005
Safer Lives, Safer Ships, Cleaner Seas
4
16. I n t e r n a t i o n a l l y, through the provisions of SOLAS 1974, National Administrationsa re responsible for the approval ofservicing stations within their jurisdictioni r respective of whether or not thatparticular administration has approved thesubject product.
17. Shipowners and masters are furtherreminded that it is an offence to carry aninflatable liferaft, inflatable boat, re s c u eboat, fast rescue boat, inflatable lifejacket orhydrostatic release unit which is known tobe defective, or which has not beenserviced at the intervals prescribed by the Regulations.
18. This MGN can be found on the MCAwebsite at www. m c g a . g o v.uk. A l t h o u g hthis MGN will be circulated as usual eachyear in hard copy, the service station andm a n u f a c t u rers address lists will beregularly updated on the website. In orderto keep this updated, please notify us at theaddress below of any changes or additions.These will be amended on the website andincluded in the new MGN next year.
SER
VIC
ING
OF
LIFE
RA
FTS,
BO
ATS
& L
IFEJ
AC
KET
S
SER
VIC
ING
OF
INFL
ATA
BLE
LR
/BO
ATS
/M.E
.S.
R.I.
BLI
FEJA
CK
ETS
OFF
SHO
RE
SER
VIC
E ST
ATI
ON
AD
DR
ESS
TEL
/ FA
X
Avon Inflatable Boats
Beaufort & Dunlop Inflatable Liferafts / Boats
CSM Liferafts (Shanghai Star Rubber Company)
DSB (Autoflug, Seetex, VEB Textil & TVB) Inflatable Liferafts / Boats
Eurovinil / Callegari Inflatable Liferafts
International Safety Group
Lifeguard Liferafts & Inflatable Boats
Liferaft Systems Australia
RFD Inflatable Liferafts / MES SystemsViking Inflatable Liferafts
Zodiac/Bombard Inflatable Liferafts / Boats
Harding Watercraft Rigid Inflatable Boats
Mulder and Rijke Rigid Inflatable Boats
Delta Rigid Inflatable Boats
DSB Rigid Inflatable Boats
Beaufort
Baltic
Crewsaver
Challenger
Mullion
Lifeguard
Remploy
RFD
Vacuum Reflex
Avon
Delta
Halmatic
Maritime Partner Craft
Norsafe
UFAS Norway
RTK
A B
Mar
ine
Lim
ited
Cas
tle W
alk,
St P
eter
Por
t, G
uern
sey,
C
hann
el Is
land
s G
Y1
1AU
0148
1 72
2378
/ 71
1080
XX
XX
XX
Abe
rdee
n In
flata
bles
Lim
ited
164a
Sin
clai
r Roa
d, T
orry
,
Abe
rdee
n A
B11
9P
S01
224
8909
22 /
8909
13X
AD
EC
Mar
ine
Saf
ety
Sur
viva
l Li
mite
d4
Mas
ons
Ave
nue,
Cro
ydon
,
S
urre
y C
R0
9XS
0208
686
971
7 /
680
9912
XA
DE
C M
arin
e S
afet
y S
urvi
val
Lim
ited
Uni
t 46,
Bar
king
Indu
stria
l Par
k,
Alfr
eds
Way
, Bar
king
, E
ssex
0208
591
255
2 /
591
2552
X*
XA
tlant
ic M
arin
e S
uppl
ies
Don
egal
Roa
d, K
illey
begs
, Co
Don
egal
, S
outh
ern
Irela
nd03
53 7
33 1
440
/ 73
3 16
99X
*X
*X
*X
Bal
tic S
afet
y P
rodu
cts
UK
Ltd
Uni
t 4, M
itche
ll P
oint
, Ens
ign
Way
, H
ambl
e, S
outh
ampt
on S
O31
4R
F02
3 80
45 7
272
/ 80
45 4
747
XB
eauf
ort A
ir-S
ea E
quip
men
t Li
mite
dB
eauf
ort R
oad,
Birk
enhe
ad,
Mer
seys
ide
L41
1HQ
0151
652
915
1 /
653
6639
XB
osto
n P
utfo
rd L
td28
, Com
mer
cial
Roa
d,
Low
esto
ft N
R32
2JG
0150
2 51
7545
XC
osal
t Int
erna
tiona
l Lim
ited
Sur
viva
l Hou
se, T
he D
ocks
,
Milf
ord
Hav
en,
Pem
brok
eshi
re S
A73
3A
F
0164
6 69
2394
/ 69
2523
XX
*X
*X
*X
X*
XX
XX
X
Cos
alt I
nter
natio
nal L
imite
dS
choo
l Roa
d In
dust
rial E
stat
e,
O
ulto
n B
road
, Low
esto
ft,
S
uffo
lk N
R33
9N
B
0150
2 51
6731
/ 50
0659
XX
*X
*X
X*
XX
XX
Cos
alt I
nter
natio
nal L
imite
dLi
fera
ft D
epar
tmen
t, W
icke
m R
oad,
G
rimsb
y Fi
sh D
ocks
,
N
orth
Eas
t Lin
coln
shire
DN
31 3
SL
0147
2 50
4300
/ 50
4314
XX
*X
*X
X*
XX
XX
XC
osal
t Int
erna
tiona
l Lim
ited
Uni
t 5, V
alia
nt W
ay,
Laird
side
Tec
hnol
ogy
Par
k,
O
ff N
ew C
hest
er R
oad,
Birk
enhe
ad,
Mer
seys
ide
CH
41 9
HS
0151
650
560
0 /
65
0 56
19X
X*
XX
*mX
XX
XX
X
Cos
alt I
nter
natio
nal L
imite
dH
arbo
ur R
oad,
New
lyn,
Pen
zanc
e,
Cor
nwal
l TR
18 5
HA
0173
6 36
3094
/ 35
1623
XX
XX
XX
XX
Cos
alt I
nter
natio
nal L
imite
dU
nits
1-3
Cas
tle B
uild
ings
, Gils
ton
Roa
d, S
alta
sh, C
ornw
all P
L12
6TW
0175
2 84
1752
/ 84
1834
XX
XX
XX
X
APP
END
IX 1
X*
= Fa
cilit
y to
load
test
dav
it la
unch
ed L
ifera
ftX
^ =
Ser
vice
Lei
sure
Raf
ts O
nly
Xm
= Fa
cilit
y to
Ser
vice
Mar
ine
Eva
cuat
ion
Sys
tem
SER
VIC
ING
OF
INFL
ATA
BLE
LR
/BO
ATS
/M.E
.S.
R.I.
BLI
FEJA
CK
ETS
OFF
SHO
RE
SER
VIC
E ST
ATI
ON
AD
DR
ESS
TEL
/ FA
X
Avon Inflatable Boats
Beaufort & Dunlop Inflatable Liferafts / Boats
CSM Liferafts (Shanghai Star Rubber Company)
DSB (Autoflug, Seetex, VEB Textil & TVB) Inflatable Liferafts / Boats
Eurovinil / Callegari Inflatable Liferafts
International Safety Group
Lifeguard Liferafts & Inflatable Boats
Liferaft Systems Australia
RFD Inflatable Liferafts / MES SystemsViking Inflatable Liferafts
Zodiac/Bombard Inflatable Liferafts / Boats
Harding Watercraft Rigid Inflatable Boats
Mulder and Rijke Rigid Inflatable Boats
Delta Rigid Inflatable Boats
DSB Rigid Inflatable Boats
Beaufort
Baltic
Crewsaver
Challenger
Mullion
Lifeguard
Remploy
RFD
Vacuum Reflex
Avon
Delta
Halmatic
Maritime Partner Craft
Norsafe
UFAS Norway
RTK
Cos
alt I
nter
natio
nal L
imite
d1
Lidd
ell S
treet
, N
orth
Shi
elds
, Tyn
e &
W
ear N
E30
1H
E01
91 2
5761
21 /
2961
431
XX
XX
XX
XX
Cos
alt I
nter
natio
nal L
imite
dU
nit 2
Cen
tral T
radi
ng E
stat
e,
M
arin
e P
arad
e, S
outh
ampt
on,
Ham
pshi
re S
O14
5JP
0238
0 63
2824
/ 23
2330
XX
X*m
X*m
XX
XX
X
Cos
alt I
nter
natio
nal L
imite
dM
ills
Hou
se, H
arbo
ur R
oad
Trad
ing
Est
ate,
Har
bour
Roa
d, P
ortis
head
, B
risto
l BS
20 7
BL
0127
5 84
8488
/ 84
8480
XX
*X
*X
*Xm
X*
XX
XX
Cos
alt S
ea-D
og L
ife S
avin
g A
pplia
nces
(Sco
tland
Ltd
)4
Alb
ert R
oad,
Edi
nbur
gh E
H6
7DP
0131
554
853
1 /
554
8061
XX
*X
*X
X*
XX
XX
Cos
alt S
ea-D
og L
ife S
avin
g A
pplia
nces
(Sco
tland
Ltd
)18
Pal
mer
ston
Roa
d, A
berd
een,
S
cotla
nd A
B11
5Q
N01
224
5883
27 /
5751
84X
*X
XmX
*mX
XX
XX
Dan
by M
ariti
me
Saf
ety
Lim
ited
Linc
ombe
Boa
tyar
d, L
inco
mbe
, S
alco
mbe
, Dev
on T
Q8
8NQ
0154
8 84
2777
XX
XD
enho
lm F
ishs
ellin
g Li
mite
d12
1 S
hore
Stre
et, F
rase
rbor
ough
, A
berd
eens
hire
, Sco
tland
AB
43 5
BR
0134
6 51
3211
/ 51
7649
XX
Fine
way
Lei
sure
Riv
ersi
de R
oad,
Hov
erto
n, N
orw
ich,
N
orfo
lk N
R12
8U
D01
603
7823
09 /
7848
38X
Gla
slyn
Mar
ine
The
Har
bour
, Por
thm
adog
, Gw
yned
d,
Wal
es L
L49
9AY
0176
6 51
3545
/ 51
5080
XG
rimsb
y In
flata
bles
Lim
ited
Roy
al C
ourt,
Roy
al D
ock,
Grim
sby
DN
31 3
TN01
472
2412
70X
XH
elen
sbur
gh C
ar &
C
omm
erci
al In
corp
orat
ing
R &
R
Mar
ine
Ser
vice
s
17 G
eorg
e S
treet
, Hel
ensb
urgh
G84
7P
R01
436
6759
99X
Hen
shaw
Infla
tabl
es L
imite
dS
outh
gate
Roa
d, W
inca
nton
, Som
erse
t
BA
9 9R
Z01
963
3323
7 /
34
578
XH
utto
ns In
tern
atio
nal L
tdM
arin
e &
Exp
ort l
ogis
tics,
633
/653
H
edon
Roa
d, H
ull,
Eas
t Yor
kshi
re H
U9
5LQ
0148
2 32
4093
/ 22
5347
XX
Infla
tabl
e B
oat S
ervi
ces
Lim
ited
89 N
orth
Par
ade,
Fal
mou
th, C
ornw
all
TR11
2TG
0132
6 31
3800
/ 31
3338
XX
Inte
rnat
iona
l Rib
Ser
vice
s Lt
d2
Sol
ent W
orks
, Nor
th C
lose
, Ly
min
gton
, Ham
pshi
re S
O41
9B
U01
590
6881
61 /
6102
53X
Jack
son
Yac
ht S
ervi
ces
Lond
on B
erth
War
ehou
se, V
icto
ria p
ier,
St.
Hel
ier,
Jers
ey, C
hann
el Is
land
s JE
2 3W
S
0153
4 43
819
/
4595
2X
X
X*
= Fa
cilit
y to
load
test
dav
it la
unch
ed L
ifera
ftX
^ =
Ser
vice
Lei
sure
Raf
ts O
nly
Xm
= Fa
cilit
y to
Ser
vice
Mar
ine
Eva
cuat
ion
Sys
tem
SER
VIC
ING
OF
INFL
ATA
BLE
LR
/BO
ATS
/M.E
.S.
R.I.
BLI
FEJA
CK
ETS
OFF
SHO
RE
SER
VIC
E ST
ATI
ON
AD
DR
ESS
TEL
/ FA
X
Avon Inflatable Boats
Beaufort & Dunlop Inflatable Liferafts / Boats
CSM Liferafts (Shanghai Star Rubber Company)
DSB (Autoflug, Seetex, VEB Textil & TVB) Inflatable Liferafts / Boats
Eurovinil / Callegari Inflatable Liferafts
International Safety Group
Lifeguard Liferafts & Inflatable Boats
Liferaft Systems Australia
RFD Inflatable Liferafts / MES SystemsViking Inflatable Liferafts
Zodiac/Bombard Inflatable Liferafts / Boats
Harding Watercraft Rigid Inflatable Boats
Mulder and Rijke Rigid Inflatable Boats
Delta Rigid Inflatable Boats
DSB Rigid Inflatable Boats
Beaufort
Baltic
Crewsaver
Challenger
Mullion
Lifeguard
Remploy
RFD
Vacuum Reflex
Avon
Delta
Halmatic
Maritime Partner Craft
Norsafe
UFAS Norway
RTK
Kilk
eel T
raw
ler S
uppl
ies
Sea
S
afet
yTh
e H
arbo
ur, K
ilkee
l, C
o D
own,
N
orth
ern
Irela
nd, B
T34
4AX
0284
1 76
2655
/ 76
4502
XX
XX
XX
XK
insa
le &
Kilm
acsi
mon
B
oaty
ard
Kilm
acsi
mon
Qua
y, B
ando
n, C
ount
y C
ork,
Sou
ther
n Ire
land
0035
321
7751
34
/ 775
405
XK
TS N
ewto
wna
rds
Scr
abo
Indu
stria
l Est
ate,
Jub
ilee
Roa
d,
New
tow
nard
s, C
o. D
own,
N. I
rela
nd02
8 91
82 8
405
/ 91
82 8
410
XX
^X
Lars
Knu
tsen
& C
lode
Lim
ited
Cha
ndle
ry H
ouse
, War
rior W
ay,
Pem
brok
e D
ock,
Pem
brok
eshi
re S
A72
6U
B
0164
6 68
6556
/ 68
1470
X
Life
raft
& In
flata
ble
Ser
vice
sU
nit 5
, Arth
ur B
rays
Yar
d,
Wes
t Qua
y R
oad,
Poo
le,
Dor
set B
H15
1H
T
0120
2 66
6447
X
Life
rafts
Inte
rnat
iona
lU
nit 6
A, H
umbe
r Brid
ge In
dust
rial
Est
ate,
Har
rier R
oad,
Bar
ton
Upo
n H
umbe
r, Li
ncs
DN
18 5
RP
0165
2 63
6970
/ 63
7012
XX
*
Life
rafts
Inte
rnat
iona
l Lim
ited
Sur
viva
l Hou
se, C
layh
ill E
stat
es,
Nes
ton,
Liv
erpo
ol L
64 3
RU
0151
336
274
0 /
336
7915
XX
*X
Mac
kay
Mar
ine
Ser
vice
s30
- 36
Virg
inia
Stre
et, A
berd
een,
G
ram
pian
, AB
11 5
AU
0122
4 57
5772
/ 57
5713
XX
XX
XM
alak
off a
nd M
oore
Nor
th N
ess,
Ler
wic
k, S
hetla
nd Z
E1
OLZ
0159
5 69
5544
/ 69
5720
XM
arin
e S
afet
y C
entre
Lim
ited
Uni
t 4, C
olvi
lle R
oad
Wor
ks,
C
olvi
lle R
oad,
Low
esto
ft,
Suf
folk
NR
33 9
QX
0150
2 50
0940
/ 50
0937
XX
X*
XX
Mar
ine
Saf
ety
Sup
plie
sU
nit 1
8, W
estfi
eld
Cou
rt, M
orris
Roa
d In
dust
rial E
stat
e, W
alls
end,
New
cast
le-
upon
-Tyn
e, N
E28
6B
Y
0191
263
019
1 /
263
0104
X
Mid
dlet
on M
arin
e Li
mite
dM
arin
e C
entre
, Car
ringt
on H
ill,
C
ount
y C
ork,
Sou
ther
n Ire
land
0035
321
8836
37
/ 883
553
XM
idla
nd C
raft
& L
eisu
re
Ser
vice
s13
3 M
ain
Stre
et, L
into
n, N
r Sw
adlin
cote
, S
outh
Der
bysh
ire D
E12
6Q
A
0128
3 76
2936
/ 76
2936
X
Mul
lion
Man
ufac
turin
g Lt
d.44
Nor
th F
arm
Roa
d, S
outh
Par
k In
dust
rial E
stat
e, S
cunt
horp
e,
N
orth
Lin
coln
shire
DN
17 2
AY
0172
4 28
0077
/ 28
0146
X
N.I.
F.P
.O. L
td1
Coa
st G
uard
Cot
tage
s, T
he H
arbo
ur,
Por
tavo
gie,
Co
Dow
n,
N. I
rela
nd B
T22
1EA
028
4277
194
6 /
4277
169
6X
X*
= Fa
cilit
y to
load
test
dav
it la
unch
ed L
ifera
ftX
^ =
Ser
vice
Lei
sure
Raf
ts O
nly
Xm
= Fa
cilit
y to
Ser
vice
Mar
ine
Eva
cuat
ion
Sys
tem
SER
VIC
ING
OF
INFL
ATA
BLE
LR
/BO
ATS
/M.E
.S.
R.I.
BLI
FEJA
CK
ETS
OFF
SHO
RE
SER
VIC
E ST
ATI
ON
AD
DR
ESS
TEL
/ FA
X
Avon Inflatable Boats
Beaufort & Dunlop Inflatable Liferafts / Boats
CSM Liferafts (Shanghai Star Rubber Company)
DSB (Autoflug, Seetex, VEB Textil & TVB) Inflatable Liferafts / Boats
Eurovinil / Callegari Inflatable Liferafts
International Safety Group
Lifeguard Liferafts & Inflatable Boats
Liferaft Systems Australia
RFD Inflatable Liferafts / MES SystemsViking Inflatable Liferafts
Zodiac/Bombard Inflatable Liferafts / Boats
Harding Watercraft Rigid Inflatable Boats
Mulder and Rijke Rigid Inflatable Boats
Delta Rigid Inflatable Boats
DSB Rigid Inflatable Boats
Beaufort
Baltic
Crewsaver
Challenger
Mullion
Lifeguard
Remploy
RFD
Vacuum Reflex
Avon
Delta
Halmatic
Maritime Partner Craft
Norsafe
UFAS Norway
RTK
Nor
wes
t Mar
ine
Lim
ited
Uni
cred
it H
ouse
, 6 C
otto
n S
treet
, Li
verp
ool L
3 7D
Y01
51 2
07 2
860
XX
XN
orth
Sta
r Shi
ppin
g (A
berd
een)
Li
mite
d20
7 A
lber
t Qua
y, A
berd
een,
Sco
tland
A
B11
5FS
0122
4 59
2206
/ 58
3198
XN
orth
Wal
es In
flata
ble
Boa
t &
RIB
Cen
treTh
e R
ound
Hou
se, F
erry
Far
m R
oad,
Ll
andu
dno
Junc
tion,
Con
wy
LL31
9S
G01
492
5833
22 /
5831
11X
Oce
an S
afet
y Li
mite
dS
axon
Wha
rf, L
ower
Yor
k S
treet
, S
outh
ampt
on, H
amps
hire
SO
14 5
QF
0238
0 72
0800
/ 72
0801
XX
*X
*X
XP
rem
ium
Life
raft
Ser
vice
s Li
mite
dLi
fera
ft H
ouse
, Bur
nham
Bus
ines
s P
ark
Est
ate,
Bur
nham
on
Cro
uch,
Ess
ex
CM
O 8
TE
0162
1 78
4858
/ 78
5934
XX
RFD
Nor
th W
ales
Lim
ited
Llan
ddeg
ai In
dust
rial E
stat
e, B
ango
r, G
wyn
edd
LL57
4H
S01
248
3603
30 /
3603
31X
XX
XmX
XX
Ric
hard
Irvi
n G
roup
Irvin
Gro
up C
ompl
ex, A
lber
t Qua
y,
Abe
rdee
n, S
cotla
nd A
B11
5E
S01
224
5762
80 /
5827
58X
*X
Ron
Hal
e M
arin
e94
-98
Hig
hlan
d R
oad,
Eas
tney
, P
orts
mou
th, H
amps
hire
PO
4 9N
Q02
392
7329
85 /
2960
65X
Ros
s S
urvi
val S
ervi
ces
Ltd
70 S
t Cle
men
ts S
treet
, Abe
rdee
n,
Sco
tland
AB
11 5
BD
0122
4 21
2114
/ 25
2234
XS
eaw
eath
er M
arin
e S
ervi
ces
Lim
ited
625-
649
Prin
ces
Roa
d, D
artfo
rd,
Ken
t DA
2 6E
F01
322
2755
13 /
2926
39X
*X
XmXm
XX
XX
Sea
Saf
e S
afet
y P
rodu
cts
1 S
herlo
ck L
ane,
Wal
lase
y, M
erse
ysid
e L4
4 4E
R01
51 6
38 7
999
/ 63
87 8
888
XS
M G
roup
Eur
ope
Ltd
Sal
t Qua
y H
ouse
, Nor
th E
ast Q
uay,
S
utto
n H
arbo
ur, P
lym
outh
,
Dev
on P
L4 0
RA
0175
2 66
2129
/ 22
2717
XX
X
Sol
as M
arin
e S
ervi
ces
The
Dry
Doc
ks, A
lexa
ndra
Roa
d, D
ublin
, S
outh
ern
Irela
nd00
3531
856
1320
/ 8
5613
21X
X
Sou
th E
aste
rn M
arin
e S
ervi
ces
Lim
ited
Uni
t 13/
25 O
lym
pic
Bus
ines
s C
entre
, P
ayco
cke
Roa
d, B
asild
on,
Ess
ex S
S14
3E
X
0126
8 53
4427
/ 28
1009
XX
Sou
th P
ier S
hipy
ard
St.
Hel
ier,
Jers
ey,
Cha
nnel
Isla
nds
JE2
3NB
0153
4 51
9700
/ 51
9701
XS
peed
ings
Lim
ited
Whi
ckha
m S
treet
, Rok
er, S
unde
rland
, Ty
ne &
Wea
r SR
6 O
ED
0191
565
752
5 /
514
7525
XS
uffo
lk S
ailin
gU
nit 7
5, C
layd
on In
dust
rial P
ark,
Ip
swic
h, S
uffo
lk IP
6 O
NL
0147
3 83
3010
/ 83
3020
XX
^X
* =
Faci
lity
to lo
ad te
st d
avit
laun
ched
Life
raft
X^
= S
ervi
ce L
eisu
re R
afts
Onl
yX
m =
Faci
lity
to S
ervi
ce M
arin
e E
vacu
atio
n S
yste
m
SER
VIC
ING
OF
INFL
ATA
BLE
LR
/BO
ATS
/M.E
.S.
R.I.
BLI
FEJA
CK
ETS
OFF
SHO
RE
SER
VIC
E ST
ATI
ON
AD
DR
ESS
TEL
/ FA
X
Avon Inflatable Boats
Beaufort & Dunlop Inflatable Liferafts / Boats
CSM Liferafts (Shanghai Star Rubber Company)
DSB (Autoflug, Seetex, VEB Textil & TVB) Inflatable Liferafts / Boats
Eurovinil / Callegari Inflatable Liferafts
International Safety Group
Lifeguard Liferafts & Inflatable Boats
Liferaft Systems Australia
RFD Inflatable Liferafts / MES SystemsViking Inflatable Liferafts
Zodiac/Bombard Inflatable Liferafts / Boats
Harding Watercraft Rigid Inflatable Boats
Mulder and Rijke Rigid Inflatable Boats
Delta Rigid Inflatable Boats
DSB Rigid Inflatable Boats
Beaufort
Baltic
Crewsaver
Challenger
Mullion
Lifeguard
Remploy
RFD
Vacuum Reflex
Avon
Delta
Halmatic
Maritime Partner Craft
Norsafe
UFAS Norway
RTK
Sur
viva
l Sys
tem
s In
tern
atio
nal
Vik
ing
Roa
d,
Gap
ton
Hal
l Ind
ustri
al E
stat
e,
Gre
at Y
arm
outh
, Nor
folk
NR
31 0
NU
0149
3 65
9411
/ 65
5425
X
Sw
an N
et-G
undr
yM
axw
ell P
lace
, Fra
serb
urgh
, AB
43 9
SX
0134
6 51
8449
/ 51
8996
XTe
dfor
ds (R
iggi
ng a
nd R
afts
)U
nit 2
4, O
rmea
u B
usin
ess
Par
k, (O
ld
Gas
Wor
ks S
ite),
8 C
rom
ac A
venu
e,
Bel
fast
, Nor
ther
n Ire
land
BT7
2JA
0289
0 32
6763
/ 23
4566
XX
^V
ikin
g Li
fe S
avin
g E
quip
men
t Li
mite
dU
nit 1
9 O
cean
Tra
de C
entre
, Min
to
Ave
nue,
Alte
ns, A
berd
een,
Sco
tland
A
B12
3JZ
0122
4 89
8969
/ 89
4565
XmX
Vik
ing
Life
-Sav
ing
Equ
ipm
ent
Lim
ited
Ham
ble
Cou
rt, H
ambl
e La
ne, H
ambl
e,
Sou
tham
pton
, Ham
pshi
re S
O31
4H
X02
380
4541
84 /
4542
84X
Xm
Vik
ing
Sta
ndby
Lim
ited
Ann
at H
ouse
, Sou
th Q
uay,
Fer
ryde
n,
Mon
trose
, Sco
tland
DD
10 9
UB
0167
4 67
3844
/ 67
2080
XX
XV
ulca
n M
arin
e Li
mite
dC
/o C
ount
y Ty
re S
ervi
ce, A
lphi
ngto
n S
treet
, Exe
ter,
Dev
on E
X2
8LR
0139
2 27
9292
/ 49
8826
XW
orm
ald
Oil
and
Gas
Hew
ett R
oad
Gap
ton
Hal
l Ind
ustri
al
Est
ate,
Gre
at Y
arm
outh
,
Nor
folk
NR
31 0
NN
0149
3 44
0500
/ 44
2639
X
Wor
mal
d S
afet
y &
Ser
vice
Oce
an T
rade
Cen
tre, M
into
Ave
nue,
A
ltens
Indu
stria
l Est
ate,
Abe
rdee
n,
Sco
tland
AB
12 3
JZ
0122
4 89
4292
/ 89
5870
X
X*
= Fa
cilit
y to
load
test
dav
it la
unch
ed L
ifera
ftX
^ =
Ser
vice
Lei
sure
Raf
ts O
nly
Xm
= Fa
cilit
y to
Ser
vice
Mar
ine
Eva
cuat
ion
Sys
tem
APPENDIX 2MANUFACTURERS & THEIR UK REPRESENTATIVES
Avon Inflatables Limited Dafan, Llanelli, Carmarthenshire SA14 8NATel./Fax. 01554 882000 / 741500
Baltic Safety Products AB Box 60, Algaras, S-545-02, SwedenTel./Fax. 00 46 5063 6990 / 5064 0196
UK Representative
Baltic Safety Products UK Ltd Unit 4, Mitchell Point, Ensign Way, Hamble,Southampton SO31 4RFTel./Fax. 023 8045 7272 / 8045 4747
Beaufort Air Sea Equipment (Dunlop Marine Safety Limited), Beaufort Road,Birkenhead, Merseyside L41 1HQTel./Fax. 0151 652 9151 / 653 6639
Crewsaver Limited Mumby Road, Gosport, Hampshire, PO12 1AQTel./Fax. 01705 528621 / 510905
Deutsche Schlauchbootfabrik (DSB) Hans Angerweg 5, D-37632 Eschershausen, GermanyScheibert GmbH & Co. KG (Autoflug, Seetex, Tel./Fax. 0049 5534 301212 / 301214VEB Textil and TVB)I C Brindle & Co 34 Lytchett Drive, Dorset, BH18 9LB
Tel./Fax. 01202 657814 / 693005Mulder & Rijke B.V. PO BOX 48, 1970 AA Ijmuiden, Netherlands
Tel./Fax. 00 31 255 519129 / 522642RFD Limited Kingsway, Dunmurry, Belfast, BT17 9AF
Tel./Fax. 01232 301531 / 621765Shark Sports Limited Nordstrom House, North Broomhill, Morpeth,
Northumberland NE65 9UJTel./Fax. 01670 760365 / 761343
Shanghai Star Rubber Products Co. Ltd. Maquiao, Minhang District, Shanghai, China
European Representative
Nautic Service Sauvetage Mr. M Connen, Z.A.C. deRogerville Oudale, BP60 76700 Harfleur, FranceTel./Fax. 33 02 3551 7530 / 3545 7085
Umoe Schat Harding Limited, (formally Harding Mumby Road, Gosport, Hampshire PO12 1AEWatercraft limited) Tel./Fax. 02392 581331 / 582565Vacuum Reflex Limited Barrack Square, Martlesham Industrial Estate,
Ipswich, Suffolk, IP5 7RF Tel./Fax. 01473 624080 / 622371Viking Life Saving Equipment A/S PO BOX 3060, 6710 Esbjerg V, Denmark
Tel./Fax. 0045 7611 81 00 / 01
UK Representative
Viking Life Saving Equipment Ltd De Vere House, 90 St. Faith House, Norwich, NR1 1NETel./Fax. 01603 767677 / 766700
Zodiac 58 Boulevard Gallieni, 92130 Issy Les Moulineaux,Cedex, France Tel./Fax. 00 33 1412 32323 / 46 487 524
Bombard Liferafts Angeviniere Marine, 58 Boulevard Gallieni, 92130 IssyLes Moulineaux, Cedex, FranceTel./Fax. 00 33 1412 32323 / 46 487 524
UK Representative
International Safety Group Limited Brunswick Place, Bank Hall, Liverpool L20 8NZTel./Fax. 0151 922 2202 / 922 5874
12
APPENDIX 3
FREQUENCY OF NAP TESTS, WORKING PRESSURE TESTS, GAS INFLATION TESTS AND FLOOR SEAM STRENGTH TESTS.
- extract from IMO Resolution A.761 (18)
Servicing intervals Test method
End of first year WP testEnd of second year WP testEnd of third year WP testEnd of fourth year WP testEnd of fifth year GI testEnd of sixth year WP testEnd of seventh year WP testEnd of eighth year WP testEnd of ninth year WP testEnd of tenth year GI test + FSEleventh to fourteenth year NAP test + FSFifteenth year GI test + NAP + FSSixteenth to nineteenth year NAP test + FSTwentieth year GI test + NAP + FSTwenty-first to twenty-fourth year NAP test + FSTwenty-fifth year GI test + NAP + FSEtc.
NAP - Necessary additional pressure testWP - Working pressure (compressed air)GI - Gas InflationFS - Floor seam test
13
APPENDIX 4 GENERAL EXEMPTION
THE MERCHANT SHIPPING (LIFE-SAVING APPLIANCES FOR PASSENGER SHIPS OF CLASSES III TO VI(A) REGULATIONS 1999
The Secretary of State in exercise of his power under regulation 23 of the Merchant Shipping (Life-Saving Appliances for Passenger Ships of Classes III to VI(A) Regulations 19991; hereby exempts ships to which the Regulations apply from the requirement of regulation 11(7) that open reversible liferafts, complying with the requirements of Schedule 4, Part II of the said Regulations, shall be serviced at a service station approved by the Secretary of State at intervals not exceeding 12 months, subject to the following conditions that: 1. such open reversible liferafts shall be serviced; (a) at intervals not exceeding two years; and (b) within the periods stated in the attached Schedule, such periods being
measured from the date of manufacture; and 2. the servicing includes the test methods stated in the attached Schedule
according to the age of the open reversible liferaft. This exemption shall not apply to open reversible liferafts carried on High Speed Craft. This exemption, which may be cancelled or modified at any time, shall remain in force until 31 May 2010. Dated this 20th day of May 2005 A. Fairney For the Secretary of State
1 SI 1999/2723
APPENDIX 5
SCHEDULE
SERVICING INTERVALS AND TEST METHODS FOR OPEN REVERSIBLE LIFERAFTS CARRIED ON PASSENGER SHIPS OF CLASSES III TO VI(A)
Servicing intervals Test method
End of first year WP testEnd of third year WP testEnd of fifth year GI testEnd of seventh year WP testEnd of ninth year WP testEnd of tenth year GI test + FSEleventh to fourteenth year NAP test + FSFifteenth year GI test + NAP + FSSixteenth to nineteenth year NAP test + FSTwentieth year GI test + NAP + FSTwenty-first to twenty-fourth year NAP test + FSTwenty-fifth year GI test + NAP + FSEtc. GI test + NAP + FS
NAP - Necessary additional pressure testWP - Working pressure (compressed air)GI - Gas InflationFS - Floor seam test
15
APPENDIX 6
EQUIVALENT ARRANGEMENT FOR EXTENDED SERVICING INTERVALS OF AN INFLATABLE LIFERAFT.
Equipment Type
RFD Endura 25 person davit launched/ roll-over canopied inflatable liferaft packed for extended serviceintervals. Packing consists of hermetically sealed foil bag within a GRP outer container.
The liferaft is type approved as indicated on Lloyds Register/ MCA type approval certificate MED0250139 in accordance with SOLAS 74, Chapter III regulations 4, 20.8.3 and 34 and Chapter X regulation3, and manufactured by Survitec Group Limited, Birkenhead, Merseyside L41 1HQ.
Conditions under which extended servicing intervals have been accepted
1. Servicing will be carried out at 30 month maximum intervals, only at approved servicing stationswhich have additionally been appointed for this purpose by Survitec Group Ltd.
2. The extended service intervals will apply over the first 10 years of a liferaft’s life.
3. Liferafts which are specially packed shall be repacked at each service using new packagingmaterials within the GRP outer container.
4. On loss of hermetic seal for any reason a raft will be serviced and repacked within 3 months, or30 months from previous repacking if sooner.
5. All servicing tests prescribed in A761(18) to be carried out, according to the age of the liferaft,during the period of the elapsed extended service interval will be carried out by the service stationprior to repacking.
6. Monitoring on board consists of regularly checking for moisture ingress by means of a specialindicator, and completion of an inspection log which remains aboard the ship; as indicated in theequipment type approval certificate.
7. Passenger ships equipped with liferafts specially packed as above will comply with SOLASregulation III 19.4.3 by carrying aboard, or having ready access to, a conventionally packedtraining raft of similar type and means of operation, or by carrying a visual training aid which cansimulate inflation and davit launching of such liferafts.
8. In addition to other required marks, the outer containers of specially packed Endura 25 D/Lliferafts within the extended servicing scheme carry the following label:
This RFD ‘Endura’ Liferaft has been designed and manufactured in accordance with the SOLAS 1996Amendments, regulation 20 paragraph 8.3 and the IMO ‘2000 HSC Code’, chapter 8 paragraph 8.9.9,which permit Extended Service Intervals of 30 months.
To comply with this, the liferaft must be inspected on board by a person certified for such purpose bySurvitec Group Ltd at intervals not exceeding 12 months. The record of such inspection must beentered on an Inspection Log Card.
The liferaft must be serviced at intervals of 30 months at a Survitec Group Ltd approved liferaftservice station in accordance with regulation 20, paragraph 8.1.2.
16
APPENDIX 7
EQUIVALENT ARRANGEMENT FOR EXTENDED SERVICING INTERVALS OF INFLATABLE LIFERAFTS
Equipment Type
Zodiac (or Bombard) inflatable liferafts with SOLAS ‘A’ and ‘B’ packs of the following models:
Throw over - 10, 25 and 50 persons;Throw over self righting – 6, 25, 37 and 50 persons;Davit launched - 25 and 37 persons;Davit launched self righting - 25 and 37 persons.
The liferafts are packed for extended service intervals by enclosure within a sealed membrane, locatedwithin the GRP outer container (the Extended Packing Service, EPS system).
The liferafts are manufactured by ZODIAC INTERNATIONAL, Issy-les-Moulineaux, France; typeapproved by Bureau Veritas in accordance with SOLAS 74, Chapter III, regulations 4, 20.8.3 and 34 andChapter X regulation 3; as evidenced by certificates Nos. 13298/A1 EC, 13300/A0 EC, 13301/A0 EC,13302/A1 EC, 13305/A1 EC, 13303/A1 EC, 12930/A0 EC, 13297/A0 EC, 13304/A0 EC, 13299/A0 EC,13148/A0 EC.
Conditions under which extended servicing intervals have been accepted on United Kingdom ships.
1. Servicing will be carried out at 30 month maximum intervals, only at approved servicing stationswhich have additionally been appointed for this purpose by Zodiac International.
2. Zodiac International will provide MCA with the results of comparative study on the ageing ofliferaft fabric and pressure seams, using material samples variously exposed, and tested at 2 1⁄2, 5,7 1⁄2 and 10 years of age.
3. EPS liferafts shall be repacked at each service using new packaging materials within the GRPouter container.
4. On deployment, or damage to membrane, or pressure within gas inflation cylinder falling belowa limit defined by the manufacturer, a raft will be serviced and repacked within 3 months, or 30months from a previous repacking, if sooner.
5. All servicing tests prescribed in A761(18) to be carried out, according to the age of the liferaft,during the period of the elapsed extended service interval will be carried out by the servicestation prior to repacking.
6. Monitoring on board by certified personnel consists of annually checking inflation gas pressureand temperature by means of a special indicator, and completion of an inspection card whichtravels with the liferaft.
7. Passenger ships equipped with any of the above EPS liferafts will comply with SOLAS regulationIII/ 19.4.3 by carrying aboard, or having ready access to, a conventionally packed training raft ofsimilar type and means of operation, or by carrying a visual training aid which can simulateinflation and davit launching of such liferafts.
8. In addition to other required marks, the outer containers of EPS liferafts which are serviced atextended intervals will be marked:
17