1 January 2011 • New Issue Service Information Voltage Regulators CL-6 Series Regulator Control Cooper Control Interface (CCI) Software and Microsoft ® Windows ® 7 Operating System Supplement S225-11-3 Table of Contents Safety Information 2 Product Information 3 Introduction 3 General Overview 3 Method A 4 Change VTS Compatibility Mode Property to Windows XP 4 Method B 6 Install XP Mode 6 Additional Information 8 Additional Assistance 8 Service Information 8 Figure 1. Cooper Control Interface (CCI) software Welcome screen.

s225!11!3, Instrucciones Para Instalar Cci en Windows 7

Embed Size (px)

DESCRIPTION

s225

Citation preview

Page 1: s225!11!3, Instrucciones Para Instalar Cci en Windows 7

1January 2011 • New Issue

Service Information

Voltage RegulatorsCL-6 Series Regulator ControlCooper Control Interface (CCI) Software and Microsoft® Windows® 7 Operating System Supplement S225-11-3

Table of ContentsSafety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Product Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3General Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Method A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Change VTS Compatibility Mode Property to Windows XP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Method B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Install XP Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Additional Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Service Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Figure 1.Cooper Control Interface (CCI) software Welcome screen.

Page 2: s225!11!3, Instrucciones Para Instalar Cci en Windows 7

2

CL-6 Series Regulator Control Cooper Control Interface (CCI) Software and Microsoft® Windows® 7 Operating System Supplement

The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described . Only competent technicians who are familiar with this equip-ment should install, operate, and service it .

A competent technician has these qualifications:

•Isthoroughlyfamiliarwiththeseinstructions.

•Istrainedinindustry-acceptedhigh-andlow-voltagesafeoperatingpracticesandprocedures.

•Is trained and authorized to energize, de-energize,clear,andgroundpowerdistributionequipment.

•Istrainedinthecareanduseofprotectiveequipmentsuch as flash clothing, safety glasses, face shield,hardhat,rubbergloves,hotstick,etc.

Following is important safety information . For safe instal-lation and operation of this equipment, be sure to read and under stand all cautions and warnings .

Safety InstructionsFollowing are general caution and warning statements that apply to this equipment . Additional statements, related to specific tasks and procedures, are located throughout the manual .

SAFETY INFORMATION

!SAFETYFOR LIFE SAFETY FOR LIFE

!SAFETYFOR LIFE

Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety . We active-ly promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing, and service .

We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment and support our “Safety For Life” mission .

This manual may contain four types of hazard statements:

DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in

death or serious injury.

WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in

death or serious injury.

CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in

minor or moderate injury.

CAUTION: Indicates a potentially hazardous situa-tion which, if not avoided, may result in equipment damage only.

Hazard Statement Definitions

WARNING:This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury, and equipment damage. G102.1

WARNING:Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling, or maintenance can result in death, severe personal injury, and equipment damage. G101.0

WARNING:Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety proce-dures. These instructions are written for such personnel and are not a substitute for adequate training and expe-rience in safety procedures. Failure to properly select, install, or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3

DANGER:Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. G103.3

Page 3: s225!11!3, Instrucciones Para Instalar Cci en Windows 7

IntroductionService Information S225-11-3 provides supplemental infor-mation and instructions regarding the use of the CL-6 series voltage regulator control Cooper Control Interface (CCI) software with the Microsoft® Windows® 7 operating system. The CCI software interface is a customer interface developed upon the VTSTM platform.

These instructions apply to all CL-6 series voltage regula-tor controls that the CCI software has the ability to connect to and are to be used in conjunction with the programming instructions for your CL-6A and/or CL-6B control:

• ServiceInformationS225-11-2CL-6Series Microprocessor-BasedRegulatorControl CooperControlInterface4.0UsersGuide

Read This Manual First

Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment.

Additional Information

These instructions cannot cover all details or vari ations in the equipment, procedures, or process described, nor provide directions for meeting every possible contin gency during instal-lation, operation, or maintenance. When additional information is desired to satisfy a problem not cov ered sufficiently for the user’s purpose, contact your Cooper Power Systems representative.

General OverviewThe CCI interface software may not start or operate properly on some Windows® 7 operating systems:

• The user interface may not display properly.

• An error message may appear stating there is an error in the CPS DNP Layer and prompt the user to close the program.

Determine System TypeMethods to resolve this situations are primarily dependent upon the system type: 32-bit or 64-bit.

If the CCI interface software does not start or operate prop-erly on your Windows® 7 operating systems, determine your system type before proceeding further:

1. Open a Windows Explorer browser and navigate to the location of the VTS.exe file.

2. Left-click on Start in the lower-left corner of your screen.

3. Right-click on Computer.

4. Select Properties.

5. Under System a System type: field will identify if your computer is a 64-bit or 32-bit system-type.

3

S225-11-3!

SAFETYFOR LIFE

Product Information

Page 4: s225!11!3, Instrucciones Para Instalar Cci en Windows 7

Change VTS Compatibility Mode Property to Windows XP

Method A (Primary): 32-bit SystemMethod B (Secondary): 64-bit System

These instructions primarily apply to computers running the CCI interface software on a Windows® 7 operating system with a 32-bit system-type.

If your computer has a 64-bit system-type, refer to Method B, before attempting Method A.

Note: If Method B, which includes the primary instructions for com-puters running the CCI interface software on a Windows® 7 operating system with a 64-bit system-type, does not resolve the CCI software start and operating issues, Method A is then recommended as a secondary alternative.

On some Windows® 7 operating systems the CCI interface software may not start or operate properly. This may cause an error message stating there is an error in the CPS DNP Layer and prompt the user to close the program.

If this issue occurs when launching the CCI interface software for the CL-6 voltage regulator control it is recommended the compatibility mode property of the VTS.exe file be changed.

Follow these instructions to change the compatibility mode property of the VTS.exe file in the Windows® 7 operating sys-tem, so that it runs in compatibility mode for the Windows® XP operating system.

1. Open a Windows Explorer browser and navigate to the location of the VTS.exe file.

• The default location is: C:\CL6\Software\source\VTS.

4

CL-6 Series Regulator Control Cooper Control Interface (CCI) Software and Microsoft® Windows® 7 Operating System Supplement

Method A

Page 5: s225!11!3, Instrucciones Para Instalar Cci en Windows 7

2. Right-click on the VTS.exe file and select Properties from the resulting drop-down menu.

3. Select the Compatibility tab in the Properties window.

4. In the Compatibility mode section proceed as follows:

A. Select Windows XP (Service Pack 3) from the drop-down list.

B. Check the “Run this program in compatibility mode for” checkbox.

C. Click the Apply button.

D. Click on the OK button.

5. Launch the CCI interface software. Refer to Service InformationS225-11-2CL-6SeriesMicroprocessor-BasedRegulatorControlCooperControlInterface4.0UsersGuide for additional information.

If the error message stating there is an error in the CPS DNP Layer appears and prompts the user to close the pro-gram, refer to Method B section in this manual for a sec-ondary procedure.

If neither method resolves the issue, contact your Cooper Power Systems representative.

5

S225-11-3!

SAFETYFOR LIFE

Page 6: s225!11!3, Instrucciones Para Instalar Cci en Windows 7

Install XP ModeMethod B (Primary): 64-bit SystemMethod A (Secondary): 32-bit System

These instructions primarily apply to computers running the CCI interface software on a Windows® 7 operating system with a 64-bit system-type.

If your computer has a 32-bit system-type, refer to Method A, before attempting Method B.

Note: If Method A, which includes the primary instructions for com-puters running the CCI interface software on a Windows® 7 operating system with a 32-bit system-type, does not resolve the CCI software start and operating issues, Method B is then recommended as a secondary alternative.

On some Windows® 7 operating systems the CCI interface software may not start or operate properly. This may cause the following to occur:

• The user interface may not display properly.

• An error message may appear stating there is an error in the CPS DNP Layer and prompt the user to close the program.

If either of these issues occur when launching the CCI inter-face software for the CL-6 voltage regulator control it is rec-ommended to install XP Mode.

Follow these instructions to install XP Mode, configure it, install the CCI software (VTS) on the XP virtual machine, and launch the software.

Note: Administrator privileges are required to install XP Mode. Each user of the CCI software on a specific computer are required to complete steps 2 through 8 if a separate log-in is required.

1. Install XP mode for the Windows® 7 operating system.

http://www.microsoft.com/windows/virtual-pc/down-load.aspx

2. Launch XP Mode.

Note: If you are unable to find the XP Mode start, open the Start icon and in the search area enter “Windows XP Mode.”

3. Configure XP Mode (virtual machine). Select Tools>Settings on the virtual machine window.

6

CL-6 Series Regulator Control Cooper Control Interface (CCI) Software and Microsoft® Windows® 7 Operating System Supplement

Method B

Page 7: s225!11!3, Instrucciones Para Instalar Cci en Windows 7

• If you are using a serial port to communicate with the CL-6 control proceed as follows:

A. Enable a communication port on the virtual machine by selecting “COM1” or “COM2”, which ever you are using.

B. Select “Physical serial port.”

• If you are using a networked environment for communication to a CL-6 control, you will need to enable the virtual machine to have its own IP address. Proceed as follows:

A. Select “Networking.”

B. Change “Adapter 1:” to the physical network adapter hardware that you will be using

4. Restart the Virtual Machine by selecting Action>Close.

5. Launch XP Mode.

7

S225-11-3!

SAFETYFOR LIFE

Page 8: s225!11!3, Instrucciones Para Instalar Cci en Windows 7

6. Install the CCI Interface software (VTS) on the Virtual XP machine. Proceed as follows:

A. Place the installation package on a CD-ROM or a USB storage device.

B. From within the XP Mode Virtual Machine, open a Windows file and explore to the location of the installation package.

C. Start the setup.exe installations file.

D. Install the CCI Interface software (VTS) on the Virtual XP machine.

7. Close the Virtual Machine by selecting Action>Close.

8. Start the CCI Interface software (VTS).

A. Search in the Start menu for “VTS (Windows XP Mode).”

B. Start the application.

Note: An alternate method to start the CCI Interface software (VTS) is to launch the XP Mode Virtual Machine and then select the appropriate desktop icon.

If either of the following occur, change the VTS compatibility mode properties to Windows XP:

• The user interface may not display properly.

• An error message may appear stating there is an error in the CPS DNP Layer and prompt the user to close the program.

Refer to Method A section in this manual for a secondary procedure.

If neither method resolves the issue, contact your Cooper Power Systems representative.

8

CL-6 Series Regulator Control Cooper Control Interface (CCI) Software and Microsoft® Windows® 7 Operating System Supplement

©2011 Cooper Industries. All Rights Reserved.Cooper Power Systems, CCI, and Cooper Control Interface are valuable trade-marks of Cooper Industries in the U.S. and other countries. You are not permitted to use Cooper trademarks without the prior written consent of Cooper Industries.Microsoft® Windows® are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries.VTS™ is a trademark of Trihedral Engineering Limited.

2300 Badger DriveWaukesha, WI 53188www.cooperpower.com

!SAFETYFOR LIFE

Additional AssistanceIf additional assistance or information is required, all inquiries should be directed to Voltage Regulator Technical Support:

Direct contact: 1-866-975-7347

For International calls: 262-896-2591

Email: [email protected]

Contact hours: Standard hours 8:00 am to 5:00 pm Central Standard Time.

Service InformationRefer to the Service Information that was pro-vided with your CL-6 voltage regulator control (ServiceInformationS225-11-#series) for addi-tional information regarding control features, installation, accessories, and testing.