3
DATE: DESCRIPTION PROJECT: TAG: NOMINAL COOLING (Ton): 6.0 Compressor No./Type: 1/ Scroll Refrigerant: R-22 Total Cooling Capacity [Btuh]: 69,200 Energy Efficiency Ratio (EER): 12.4 Filter No. / Size: 1/25x20x1, 1/20x20x1 Condensate Drain Connection: 3/4" NPT Shipping Weight [lbs.]: 355 Indoor Blower, Direct Drive: CENTRIFUGAL Diameter x Width [in]: 10 x 10 0 0 2 2 : M F C n g i s e D Motor HP / Speeds: 1.0 / 3 Indoor Coil: Copper tubes, Aluminum Fins 0 0 . 5 ) . t f . q s ( a e r A e c a F Rows / FPI : 3 / 14 Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice Condense Type: CO-AXIAL Number Used / Tons Capacity: 1 / 6.0 Nominal Water Flow Rate [gpm]: 18.0 Condenser Water Connections: 1" FPT *Tested in Accordance with ARI Standard 390-2003. Cooling rating conditions are 80 o F DB/67 o F WB EAT-Indoor Coil, 95 o F EAT-Outdoor Coil, Standard Design CFM’s. Heating rating conditions are 47 o F DB/43 o F WB EAT-Outdoor Coil, 70 o F EAT-Indoor Coil, Standard Design CFM’s. Total Heating Capacity [Btuh]: 69,200 2 . 4 : P O C ELECTRICAL DATA MIN. CCT. MAX FUSE / QTY RLA LRA HP FLA AMPACITY CCT. BKR. AMP 208-230/1/60 1 @ 28.8 148.0 1.00 5.1 41.10 40 208-230/3/60 1 @ 17.3 137.0 1.00 5.1 26.73 25 460/3/60 1 @ 8.2 62.0 1.00 3.2 13.45 15 575/3/60 1 @ 7.1 50.0 1.00 2.6 11.48 15 VOLTAGE COMPRESSOR EVAPORATOR FAN SUPPLY AIR BLOWER PERFORMANCE 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Low - - 1680 1670 1650 1620 1595 1500 1440 Med 2020 2005 1980 1940 1900 1860 1795 1710 1610 High 2400 2320 2260 2200 2120 2040 1920 1840 1700 RPH070 MODEL Speed CFM @ EXTERNAL STATIC PRESSURE - Inches W.C. June 2008 RPH070 HORIZONTAL WATER SOURCE HEAT PUMP Form 145.16-PA11 (608) 1 of 3

RPH070 Horizontal Water Source Heat Pump Data Sheet

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: RPH070 Horizontal Water Source Heat Pump Data Sheet

DATE:

DESCRIPTION

PROJECT: TAG:

NOMINAL COOLING (Ton): 6.0 Compressor No./Type: 1/ ScrollRefrigerant: R-22

Total Cooling Capacity [Btuh]: 69,200

Energy Efficiency Ratio (EER): 12.4

Filter No. / Size: 1/25x20x1, 1/20x20x1Condensate Drain Connection: 3/4" NPT

Shipping Weight [lbs.]: 355

Indoor Blower, Direct Drive: CENTRIFUGALDiameter x Width [in]: 10 x 10

0022:MFC ngiseDMotor HP / Speeds: 1.0 / 3

Indoor Coil: Copper tubes, Aluminum Fins00.5).tf .qs( aerA ecaF

Rows / FPI : 3 / 14

Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice

Condense Type: CO-AXIALNumber Used / Tons Capacity: 1 / 6.0

Nominal Water Flow Rate [gpm]: 18.0Condenser Water Connections: 1" FPT

*Tested in Accordance with ARI Standard 390-2003. Cooling rating conditions are 80oF DB/67oF WB EAT-Indoor Coil, 95oF EAT-Outdoor Coil, StandardDesign CFM’s. Heating rating conditions are 47oF DB/43oF WB EAT-Outdoor Coil, 70oF EAT-Indoor Coil, Standard Design CFM’s.

Total Heating Capacity [Btuh]: 69,2002.4:POC

ELECTRICAL DATAMIN. CCT. MAX FUSE /

QTY RLA LRA HP FLA AMPACITYCCT. BKR.

AMP208-230/1/60 1 @ 28.8 148.0 1.00 5.1 41.10 40208-230/3/60 1 @ 17.3 137.0 1.00 5.1 26.73 25

460/3/60 1 @ 8.2 62.0 1.00 3.2 13.45 15575/3/60 1 @ 7.1 50.0 1.00 2.6 11.48 15

VOLTAGECOMPRESSOR EVAPORATOR FAN

SUPPLY AIR BLOWER PERFORMANCE

0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8Low - - 1680 1670 1650 1620 1595 1500 1440Med 2020 2005 1980 1940 1900 1860 1795 1710 1610High 2400 2320 2260 2200 2120 2040 1920 1840 1700

RPH070

MODEL Speed CFM @ EXTERNAL STATIC PRESSURE - Inches W.C.

June 2008

RPH070 HORIZONTALWATER SOURCE HEAT PUMP

Form 145.16-PA11 (608)

1 of 3

Page 2: RPH070 Horizontal Water Source Heat Pump Data Sheet

DATE:

DESCRIPTION

PROJECT: TAG:

Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice

GENERALAll models 1-6 ton ship as factory-charged packages. Horizontal (RPH) units are designed for suspended ceiling mounting. RPHmodels are shipped with ‘straight-through’ evaporator fan discharge as standard. Fan orientation is field convertible to sidedischarge.

Vertical (RPV) units are designed for free -standing floor mounting. All units are completely factory wired and pre-piped. Watersupply, water outlet, and condensate drain connections are via female pipe thread fittings.

CABINETAll cabinets are completely constructed of corrosion resistant "Galvanized" coated steel. The RPH units are complete with integralhanger channels. The entire unit interior ( both evaporator and condensing section ) is insulated with 1/2" thick, 2 lb densityinsulation. Service panels are equipped with lifting handles for ease of removal and handling. All units provide service access to thereversing valve, thermal expansion valve, and compressor with the unit remaining in location. An integral duct collar is provided onthe blower discharge opening. An optional ‘free discharge’ plenum is available for Vertical RPV models.

REFRIGERATION CIRCUITSAll models utilize high efficiency rotary, hermetic reciprocating or scroll compressors. Compressors are mounted on rubber isolatorsto minimize vibration transmission. Internal overload protection is provided. External high pressure and low pressure cutout switchesare included in each compressor control circuit. Each refrigeration circuit includes an adjustable bi-flow thermal expansion valve(with external equalizer), bi-flow liquid line filter drier, and service gauge ports. The reversing valve is a pilot operated, sliding pistontype with a replaceable magnetic solenoid coil.

The refrigerant-to-air heat transfer coils are constructed of internally enhanced copper tubes mechanically bonded to enhancedaluminum plate fins. The evaporator coil is employed in a draw-through configuration. Large evaporator coil face area minimizespotential water blow-off.

The coaxial refrigerant-to-water heat exchangers feature a convoluted inner tube design for high heat transfer efficiency. Standardmodels feature a copper inner tube surrounded by a steel outer tube, and carry a 400 psig water side working pressure rating.

INDOOR FANForward curved, double inlet and double width, direct-drive centrifugal blowers are used for air movement. Large diameter wheelsare employed to provide required airflow performance at minimum noise levels. Blower wheels are fabricated of galvanized steel.Fan motors are PSC type, with minimum three speeds. The PSC motors feature permanently lubricated bearings and internalthermal overload protection.

ELECTRICAL/CONTROLSAll units are completely factory wired with all necessary operating controls. A 24 volt control circuit, with oversize transformer, isprovided for field connection. Units are designed to operate with conventional heat pump thermostat control interface. The reversingvalve solenoid coil shall be energized in cooling mode only. A manual reset is provided on each compressor control circuit in theevent of high/low pressure cutout. A time delay relay for anti-short cycle protection is standard in all units. An optional condensateoverflow switch is available, complete with an alarm output contact. An optional remote management package allows the unit to becontrolled by an external source.

FILTERSAll models are shipped with 1-inch thick throwaway filters, factory installed. Filters are accessible from either side of unit.

June 2008

RPH070 HORIZONTALWATER SOURCE HEAT PUMP

Form 145.16-PA11 (608)

2 of 3

GENERAL MECHANICAL SPECIFICATIONS

Page 3: RPH070 Horizontal Water Source Heat Pump Data Sheet

June 2008

DIMENSIONAL DATARPH070 HORIZONTAL

WATER SOURCE HEAT PUMP

Form 145.16-PA11 (608)

3 of 3

RPHRPH

RPHRPHRPHRPHRPHRPH