Product Overview & Reference GuideROOM CONTROLLER ASHRAE 90.1-2010
California
Compliant24TITLE
- - -
- -
- -
- - -
- - - - - - - - - - - - - - -
to provide the flexibility and cost savings needed in today’s competitive lighting controls market. It’s designed for stand-alone room applications, but can also be networked to a Dialog controller for centralized control of an entire floor or building.” Brad Stevenson - Vice President, Sales Douglas Lighting Controls
“The Dialog Room Controller* is the right product...
* Patent Pending1
Dialog Room Controller introduces specifiers and contractors to a versatile solution for stand-alone or networked lighting control applications. The Dialog Room Controller, manages classrooms, offices, conference rooms or small rooms to meet local and national lighting requirements such as ASHRAE 90.1-2010, California Title 24, and New York Local Law 48.
The Dialog Room Controller incorporates 2 sections – the Room Controller and the UL924 Relay Expansion Pack. The Room Controller is the main device and it includes 4 relays, 4 independent dimming
channels and the capability to connect to a Douglas Lighting Controls Dialog or BACnet network. When the need for emergency lighting control or additional relays arises because of room size or lighting requirements, the Room Controller UL924 / Relay Expansion Pack is easily added by clipping it to the bottom of the room controller and connecting to the appropriate loads. The expansion pack provides two additional relays that are certified for emergency lighting operation or can be used for additional lighting loads.
Dialog Room Controller is offered as in a packaged kit for specific room applications. Each kit is Plug ‘N ControlTM ready out of the box for fast installation. Kits can include the Room Controller, the UL924 Expansion Pack, occupancy sensors, switch stations, and daylight sensors depending on the application.
An added feature is the Dialog Room Controller can also be used in a centralized Dialog system to create a globally controlled network that is faster to install, requires less long wire/conduit runs, and provides room-by-room testing before complete system start-up.
ROOM CONTROLLER®
2
DIMENSIONS
2.1” (54mm)
6.1” (155mm)
4.3” (109mm)
5.7”(144mm)
6.3”(159mm) WEIGHT 1.15lbs (0.52kg)
3
FEATURES
CIRCUIT TEST BUTTONSRJ45 PORT FOR BACNET IP CONNECTIVITY
STATUS & LOCATOR LED LABELED LOW VOLTAGE WIRING COMPARTMENT
EASY BREAK WIRING KNOCKOUTS
& ACCESS TABS
PUSH-CONNECT DIMMING AND DATA
TERMINALSWIRE COLOR MATCHING RELAY LABELS WIRING INSTRUCTIONS½ INCH CHASE NIPPLES
½ INCH CHASE NIPPLES
COLOR CODED WIRESCLIP CONNECT RELAY
EXPANSION/UL924 EMERGENCY
LIGHTING PACK
4
ARCHITECTURE
In this example, Dialog Room Controller supports the requirements of a single classroom by taking commands from wall switches and sensors. The functionality of the lighting in this classroom is independent of lighting controls in other classrooms or across the facility. The Dialog Room Controller can be connected to a BMS/EMS via BACnet IP to receive demand response commands, share information on occupancy status, provide central time control, and allow for energy monitoring.
STAND-ALONE ARCHITECTURE
Entry Station
Teacher Station
Dialog Room Contoller
NATURAL LIGHT
Dialog Room Controller is designed for versatility. There are two common architectures for the Dialog Room Controller: Stand-alone or Networked
Occupancy/Vacancy Sensor
Daylight Sensor
5
ARCHITECTURE
In this example the Dialog Room Controller supports the requirements of one classroom by taking commands from wall switches and sensors in that classroom. Additionally, each Room Controller is networked to a centralized Dialog LCU (lighting control unit) through a low cost, polarity neutral, 2-wire data line. The LCU is programmed with schedules for controlling lights across the entire facility. Demand response functionality can also be initiated across the entire network.
NATURAL LIGHT
NATURAL LIGHT
DIALOG NETWORK CONTROLLERS
WLC-3150
Dialog Global Web Server for Master Level Control and/or Graphics Based User Experience
ROUTER LAN
LANDIALOG NETWORK
CONTROLLERSWLC-3150
NETWORKED ARCHITECTUREDialog Room Controller is designed for versatility. There are two common architectures for the Dialog Room Controller: Stand-alone or Networked
6
in identifying market challenges and then developing solutions that solve those challenges. We designed the Dialog Room Controller to eliminate wiring complications, ensure code compliance, simplify control systems, and improve the commissioning experience - common challenges that are found across our industry.” Rob Mahaffey, Director Product Market Development
“Douglas Lighting Controls continues to
provide leadership...
7
DRC 01 N S - - -1 S 1 2 1 2 N
01 = One Room System02 = Two Room System
1 = One 2-button Classroom Entry Station2 = Two 2-button Classroom Entry Stations3 = One 2-button Office Entry Station4 = Two 2-button Office Entry Stations
E = UL924 Relay Expansion PackN = None
1 = One 4-button Teacher Master Station2 = Two 4-button Teacher Master Stations3 = One 4-button Office Master Station4 = One 4-button Office Master Station + One 4-button Office Pre-set Station
1 = One Interior Daylight Sensor2 = Two Interior Daylight Sensors
1 = all relays Auto ON/Auto OFF3 = relays 1, 2, 3 Manual ON/Auto OFF. Relay 4 (receptacle) Auto ON/Auto OFF
N = No Teaching/Presentation WallO = Teaching/Presentation Wall Opposite WindowsP = Teaching/Presentation Wall Perpendicular to Windows
S = Single Daylight SourceM = Multiple Daylight Sources (Skylights)
1 = One Dual Tech Occupancy Sensor2 = Two Dual Tech Occupancy Sensors
S = standard range lensX = extended range lens
A key advantage of the Dialog Room Controller is the “kit” system. With many office and classrooms having common lighting control requirements, standardizing kits help make project design and installation easier. For extra cost and installation time saving, kits 9, 10, 15 are designed to control 2 similar rooms with only one Room Controller.
SENSOR ADDITIONSOccupancy sensors can be added to a total of 4 sensors per room controller.
SWITCH ADDITIONSDuplicate switches can be added to a total of 6 switch stations per
room controller
TITLE 24 DIMMING SWITCH ADDITIONS
For Title 24 requirements, dimming switches can be added to a total of
6 switch stations
1. Find a classroom or office layout that best suits your application on the following pages.2. Select the kit part number from the 4 options listed on the specific Kit page.
MODIFICATIONS:In some cases, specific applications may need kit modifications. For these instances, first find the kit that best suits your application, then review the modifications available below. Then call or email us.
DIALOG ROOM CONTROLLER KIT PART NUMBER OVERVIEW
LET US HELP YOU. [email protected] • 877-873-2797 ext. 607
• Removal of the Occupancy/ Vacancy Sensor• Removal of the Interior Daylight Sensor• Removal of the Entry Stations• Removal of the Teachers Station
• Addition of Occupancy/Vacancy Sensors, up to 4 per Dialog Room Controller
• Addition of duplicate wall switch stations (total of 6)
WRC-TS-1Teachers Stations
WRC-ES-1Entry Station
WRC-OF-PSPresent Station
WRC-OF-A1Entry Station
OF-TGLOffice Station
WRC-TS-8
Teaching General 50% R1 Toggle
General On Meeting 100% R2 ToggleGeneral On
A/V Presentation R3 Lights R3 ToggleAll Off
Quiet Mode All Off All Off All Off
WRC-DS-0
General
WRC-DS-F
Front
WRC-DS-R
Rear
WRC-DS-Z1
Zone 1
WRC-DS-Z2
Zone 2
WRC-DS-Z3
Zone 3
ORDERING
8
KIT #1
DimmingZone 1
Dimming Zone 3
Relay 3 White Board / Presentation Wall Lights
Window
D/S O/S
Relay 1
Dimmer 1
Dialog RoomController
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 1
Dimmer 1
Relay 2
Dimmer 4
Relay 2
Dimmer 4
Relay 2
Dimmer 4
Relay 2
Dimmer 4
Relay 2
Dimmer 3
Relay 2
Dimmer 3
EntryStation
EntryStation
TeacherStation
Relay 4Receptacle
Relay 1
Dimmer 2
Relay 1
Dimmer 2
DimmingZone 2
DimmingZone 4
Classroom• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Entry Station and Teacher Station provide manual control
of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and
Teacher Station
Secondary Daylight ZonePrimary Daylight Zone
9
CLASSROOMPROJECT NAME: ___________________________________________________________________ DATE: __________________
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOT
NEUTRAL
NEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 4Dim 3
Occupancy Sensor(up to 4)
Daylight Sensor
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
Teachers Station
Entry Station Entry Station
KIT#1
Kit Ordering Numbers:
DRC01PS-1S11-12-NDRC01PS-1X11-12-NDRC01PS-1S31-12-NDRC01PS-1X31-12-N
Primary Daylight Zone Secondary Daylight Zone
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Whiteboard Light(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station
Dialog Room Controller
10
KIT #2
DimmingZone 1
Dimming Zone 3
Relay 3 White Board / Presentation Wall Lights
Window
D/S O/S
Relay 1
Dimmer 1
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 5Dimmer 1
EMERGENCY
Relay 2
Dimmer 4
Relay 2
Dimmer 4
Relay 2
Dimmer 4
Relay 6Dimmer 4
EMERGENCY
Relay 2
Dimmer 3
Relay 2
Dimmer 3
EntryStation
EntryStation
TeacherStation
Relay 4Receptacle
Relay 1
Dimmer 2
Relay 1
Dimmer 2
DimmingZone 2
DimmingZone 4
Classroom with Emergency Lighting• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Entry Station and Teacher Station provide manual control
of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and
Teacher Station• During power failure UL924 listed relays are automatically
switched ON by back-up power source switching designated emergency lights ON and to full-bright. Emergency lights remain ON with all controls disabled until primary power is restored.
Dialog RoomController
Secondary Daylight ZonePrimary Daylight Zone
11
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
CLASSROOM + EMERGENCY
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
ORANGE
ORANGE
GREY
GREY
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
ORANGE
ORANGE
GREY
GREY
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOT
NEUTRAL
(EM) LIGHTING LOAD 5
(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6
(EM) LIGHTING HOT
NEUTRAL
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
Classroom Front(Relay 1)
N
N
Classroom Rear(Relay 2)N
N
Front EM Light(Relay 5)N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Classroom Front(Relay 1)
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 1
Dim 4
Occupancy Sensor(up to 4)
Daylight Sensor
Teachers Station
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Entry Station
KIT#2
Kit Ordering Numbers:
DRC01PS-1S11-12-EDRC01PS-1X11-12-EDRC01PS-1S31-12-EDRC01PS-1X31-12-E
Entry Station
Classroom Rear(Relay 2)
Dim 1 Dim 2
Dim 4Dim 3
Primary Daylight Zone Secondary Daylight Zone
Rear EM Light(Relay 6)
Whiteboard Light(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom with Emergency Lighting• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station• During power failure UL924 listed relays are
automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.
Dialog Room Controller
12
KIT #3Primary Daylight Zone
Secondary Daylight Zone
Dimming Zone 1
Dimming Zone 2
Window
D/S
O/S
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 4Receptacle
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Classroom• Windows Opposite to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Entry Station and Teacher Station provide manual control
of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and
Teacher Station
Dimming Zone 3
Relay 3 White Board / Presentation Wall LightsEntry
StationEntry
StationTeacherStation
Dialog RoomController
13
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
CLASSROOM
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOT
NEUTRAL
NEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
Whiteboard LightRelay 3N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 2
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 1Dim 1
Occupancy Sensor(up to 4)
Daylight Sensor
RoomController(WRC-3160)
Building Controlvia
BACnet IP or Dialog Network
Teachers Station
Entry Station Entry Station
KIT#3
Kit Ordering Numbers:
DRC01OS-1S11-12-NDRC01OS-1X11-12-NDRC01OS-1S31-12-NDRC01OS-1X31-12-N
Primary Daylight Zone Secondary Daylight Zone
Classroom Front(Relay 1)
Classroom RearRelay 2
Classroom Front(Relay 1)
Classroom RearRelay 2
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom• Windows Opposite to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station.
Dialog Room Controller
14
KIT #4Classroom with Emergency Lighting• Windows Opposite to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control zones (3 zones)• Receptacle Control• Dimming Control (3 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Entry Station and Teacher Station provide manual control
of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and
Teacher Station• During power failure UL924 listed relays are automatically
switched ON by back-up power source switching designated emergency lights ON and to full-bright. Emergency lights remain ON with all controls disabled until primary power is restored.
Primary Daylight Zone
Secondary Daylight Zone
Dimming Zone 1
Dimming Zone 2
Window
D/S
O/S
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Relay 6Dimmer 1
EMERGENCY
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 5Dimmer 2
EMERGENCY
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 4Receptacle
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Dimming Zone 3
Relay 3 White Board / Presentation Wall LightsEntry
StationEntry
StationTeacherStation
Dialog RoomController
15
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
CLASSROOM + EMERGENCY
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
ORANGE
ORANGE
GREY
GREY
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
ORANGE
ORANGE
GREY
GREY
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOT
NEUTRAL
(EM) LIGHTING LOAD 5
(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6
(EM) LIGHTING HOT
NEUTRAL
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 2
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 1Dim 1
Dim 2
Dim 1
Occupancy Sensor(up to 4)
Daylight Sensor
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Teachers Station
Entry Station Entry Station
KIT#4
Kit Ordering Numbers:
DRC01OS-1S11-12-EDRC01OS-1X11-12-EDRC01OS-1S31-12-EDRC01OS-1X31-12-E
Primary Daylight Zone Secondary Daylight Zone
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Front EM Light(Relay 5)
Rear EM Light(Relay 6)
Whiteboard Light(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom with Emergency Lighting• Windows Opposite to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control zones (3 zones)• Receptacle Control• Dimming Control (3 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station• During power failure UL924 listed relays are
automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.
Dialog Room Controller
16
KIT #5
Secondary Daylight ZonePrimary Daylight Zone
DimmingZone 1
Dimming Zone 3
Relay 3 White Board / Presentation Wall Lights
Window
O/S
Relay 1
Dimmer 1
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 1
Dimmer 1
Relay 2
Dimmer 4
Relay 2
Dimmer 4
Relay 2
Dimmer 4
Relay 2
Dimmer 4
Relay 2
Dimmer 3
Relay 2
Dimmer 3
EntryStation
EntryStation
TeacherStation
Relay 4Receptacle
Relay 1
Dimmer 2
Relay 1
Dimmer 2
DimmingZone 2
DimmingZone 4
Classroom• Windows Perpendicular to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Entry Station and Teacher Station provide manual control
of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and
Teacher Station
D/SD/S Skylight
Dialog RoomController
17
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
CLASSROOM
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOT
NEUTRAL
NEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 4Dim 3
Daylight SensorZone 2
RoomController(WRC-3160)
Occupancy Sensor(up to 4)
Daylight SensorZone 1
Building Controlvia
BACnet IP or Dialog Network
Teachers Station
Entry Station Entry Station
KIT#5
Kit Ordering Numbers:
DRC01PM-1S12-12-NDRC01PM-1X12-12-NDRC01PM-1S32-12-NDRC01PM-1X32-12-N
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Window Daylight Zone Skylight Daylight Zone
Whiteboard Light(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom• Windows Perpendicular to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station
Dialog Room Controller
18
KIT #6
DimmingZone 1
Dimming Zone 3
Relay 3 White Board / Presentation Wall Lights
Window
O/S
Relay 1
Dimmer 1
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 5Dimmer 1
EMERGENCY
Relay 2
Dimmer 4
Relay 2
Dimmer 4
Relay 2
Dimmer 4
Relay 6Dimmer 4
EMERGENCY
Relay 2
Dimmer 3
Relay 2
Dimmer 3
EntryStation
EntryStation
TeacherStation
Relay 4Receptacle
Relay 1
Dimmer 2
Relay 1
Dimmer 2
DimmingZone 2
DimmingZone 4
Classroom with Emergency Power• Windows Perpendicular to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Entry Station and Teacher Station provide manual control
of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and
Teacher Station• During power failure UL924 listed relays are automatically
switched ON by back-up power source switching designated emergency lights ON and to full-bright. Emergency lights remain ON with all controls disabled until primary power is restored.
D/SD/S
Secondary Daylight ZonePrimary Daylight Zone
Skylight
Dialog RoomController
19
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
CLASSROOM + EMERGENCY
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
ORANGE
ORANGE
GREY
GREY
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
ORANGE
ORANGE
GREY
GREY
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOT
NEUTRAL
(EM) LIGHTING LOAD 5
(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6
(EM) LIGHTING HOT
NEUTRAL
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 4Dim 3
Dim 1
Dim 4
Daylight SensorZone 2
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Occupancy Sensor(up to 4)
Daylight SensorZone 1
Teachers Station
Entry Station Entry Station
KIT#6
Kit Ordering Numbers:
DRC01PM-1S12-12-EDRC01PM-1X12-12-EDRC01PM-1S32-12-EDRC01PM-1X32-12-E
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Front EM Light(Relay 5)
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Window Daylight Zone Skylight Daylight Zone
Rear EM Light(Relay 6)
Whiteboard Light(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom with Emergency Power• Windows Perpendicular to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station• During power failure UL924 listed relays are
automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.
Dialog Room Controller
20
KIT #7Classroom• Windows Opposite to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Entry Station and Teacher Station provide manual control
of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and
Teacher Station
Primary Daylight Zone
Secondary Daylight Zone
Dimming Zone 1
Dimming Zone 2
Dimming Zone 3
Relay 3 White Board / Presentation Wall Lights
Window
D/SA
D/SB
O/S
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 1
Dimmer 2
EntryStation
EntryStation
TeacherStation
Relay 4Receptacle
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Skylight
Dialog RoomController
21
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
CLASSROOM
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOT
NEUTRAL
NEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 1
Dim 2Dim 2
RoomController(WRC-3160) Daylight Sensor
Zone 2
Occupancy Sensor(up to 4)
Daylight SensorZone 1
Building Controlvia
BACnet IP or Dialog Network
Teachers Station
Entry Station Entry Station
KIT#7
Kit Ordering Numbers:
DRC01OM-1S12-12-NDRC01OM-1X12-12-NDRC01OM-1S32-12-NDRC01OM-1X32-12-N
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Whiteboard Light(Relay 3)
Window Daylight Zone Skylight Daylight Zone
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom• Windows Opposite to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station
Dialog Room Controller
22
KIT #8Classroom with Emergency Lighting• Windows Opposite to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Entry Station and Teacher Station provide manual control
of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and
Teacher Station• During power failure UL924 listed relays are automatically
switched ON by back-up power source switching designated emergency lights ON and to full-bright. Emergency lights remain ON with all controls disabled until primary power is restored.
Primary Daylight Zone
Secondary Daylight Zone
Dimming Zone 1
Dimming Zone 2
Dimming Zone 3
Relay 3 White Board / Presentation Wall Lights
Window
D/SA
D/SB
O/S
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Relay 6Dimmer 1
EMERGENCY
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 1
Dimmer 2
Relay 5Dimmer 2
EMERGENCY
Relay 1
Dimmer 2
Relay 1
Dimmer 2
EntryStation
EntryStation
TeacherStation
Relay 4Receptacle
Relay 2
Dimmer 1
Relay 2
Dimmer 1
Skylight
Dialog RoomController
23
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
CLASSROOM + EMERGENCY
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
ORANGE
ORANGE
GREY
GREY
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
ORANGE
ORANGE
GREY
GREY
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOT
NEUTRAL
(EM) LIGHTING LOAD 5
(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6
(EM) LIGHTING HOT
NEUTRAL
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 2
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 1Dim 1
Dim 2
Dim 1
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Daylight SensorZone 2
Occupancy Sensor(up to 4)
Daylight SensorZone 1
Teachers Station
Entry Station Entry Station
KIT#8
Kit Ordering Numbers:
DRC01OM-1S12-12-EDRC01OM-1X12-12-EDRC01OM-1S32-12-EDRC01OM-1X32-12-E
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Front EM Light(Relay 5)
Rear EM Light(Relay 6)
Whiteboard Light(Relay 3)
Window Daylight Zone Skylight Daylight Zone
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom with Emergency Lighting• Windows Opposite to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station• During power failure UL924 listed relays are
automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.
Dialog Room Controller
24
KIT #9Double Classroom• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones per room)• Light Control (2 zones per room)• Dimming Control (2 zones per room)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Entry Station (ON/OFF) and Teacher Station (GENERAL,
TEACHING, A/V, ALL, DIMMING) provide manual control of lights
• Upon Exit and after Occupancy sensor times out, lights and receptacles switched OFF
• Lights can be switched OFF manually at Entry Station and Teacher Station
Primary Daylight Zone A Primary Daylight Zone B
Secondary Daylight Zone A Secondary Daylight Zone B
Dimming Zone 1 Dimming Zone 2
Dimming Zone 3 Dimming Zone 4
Window Window
D/SA
D/SB
O/SA
O/SB
Relay 1 Dimmer 1 Relay 2 Dimmer 2
Relay 1 Dimmer 3 Relay 2 Dimmer 4
EntryStation A
EntryStation B
TeacherStation A
TeacherStation B
Relay 3 W
hite Bo
ard / P
resentation W
all Lights
Dialog Room
Controller
Rel
ay 4
Whi
te B
oar
d /
Pre
sent
atio
n W
all L
ight
s25
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
DOUBLE CLASSROOM
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
LIGHTING LOAD 4
LIGHTING HOT LOAD 4
LIGHTING HOT
NEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 4Dim 3
Daylight SensorClassroom B
RoomController(WRC-3160)
Occupancy SensorClassroom A
Daylight SensorClassroom A
N
N
N
Occupancy SensorClassroom B
Building Controlvia
BACnet IP or Dialog Network
Entry Station(s)Classroom B
Teachers StationClassroom B
Entry Station(s)Classroom A
Teachers StationClassroom A
KIT#9
Kit Ordering Numbers:
DRC02PS-2S12-22-NDRC02PS-2X12-22-NDRC02PS-2S32-22-NDRC02PS-2X32-22-N
Near Window(Relay 1)
Classroom B
Primary Daylight Zone Primary Daylight Zone
Near Window(Relay 2)
Secondary Daylight Zone Secondary Daylight Zone
Interior(Relay 1)
Interior(Relay 2)
Classroom A
Whiteboard Light(Relay 3)
Whiteboard Light((Relay 4))
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Double Classroom• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones per room)• Light Control (2 zones per room)• Dimming Control (2 zones per room)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station (ON/OFF) and Teacher Station
(GENERAL, TEACHING, A/V, ALL, DIMMING) providemanual control of lights
• Upon Exit and after Occupancy sensor times out,lights and receptacles switched OFF.
• Lights can be switched OFF manually at EntryStation and Teacher Station
Dialog Room Controller
26
KIT #10Double Classroom with Emergency Lighting(Requires UL924 Relay Expansion Pack)
• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones per room)• Light Control (3 zones per room)• Dimming Control (2 per room)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Entry Station and Teacher Station provide manual control
of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and
Teacher Station• During power failure UL924 listed relays are automatically
switched ON by back-up power source switching designated emergency lights ON and to full-bright. Emergency lights remain ON with all controls disabled until primary power is restored.
Primary Daylight Zone A Primary Daylight Zone B
Secondary Daylight Zone A Secondary Daylight Zone B
Dimming Zone 1 Dimming Zone 2
Dimming Zone 3 Dimming Zone 4
Relay 3 W
hite Bo
ard / P
resentation W
all Lights R
elay
4 W
hite
Bo
ard
/ P
rese
ntat
ion
Wal
l Lig
hts
Window Window
D/SA
D/SB
O/SA
O/SB
Relay 1 Dimmer 1 Relay 2 Dimmer 2
Relay 5 Dimmer 3 EMERGENCY Relay 6 Dimmer 4 EMERGENCY
EntryStation A
EntryStation B
TeacherStation A
TeacherStation B
Dialog Room
Controller
27
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
DOUBLE CLASSROOM + EMERGENCY
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
ORANGE
ORANGE
GREY
GREY
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
ORANGE
ORANGE
GREY
GREY
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
LIGHTING LOAD 4
LIGHTING HOT LOAD 4
LIGHTING HOT
NEUTRAL
(EM) LIGHTING LOAD 5
(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6
(EM) LIGHTING HOT
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Near Window(Relay 1)N
Interior(Relay 5)N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 4Dim 3
Daylight SensorClassroom B
Entry Station(s)Classroom B
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924) Teachers Station
Classroom B
Occupancy SensorClassroom A
Daylight SensorClassroom A
N
N
N
Classroom A Classroom B
Occupancy SensorClassroom B
Entry Station(s)Classroom A
Teachers StationClassroom A
KIT#10
Kit Ordering Numbers:
DRC02PS-2S12-22-NDRC02PS-2X12-22-NDRC02PS-2S32-22-NDRC02PS-2X32-22-N
Primary Daylight Zone Primary Daylight Zone
Near Window(Relay 2)
Interior(Relay 6)
Secondary Daylight Zone Secondary Daylight Zone
Whiteboard Light(Relay 3)
Whiteboard Light((Relay 4))
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Double Classroom with Emergency Lighting• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones per room)• Light Control (3 zones per room)• Dimming Control (2 per room)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station• During power failure UL924 listed relays are
automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.
Dialog Room Controller
28
DRC02PS-2S12-22-EDRC02PS-2X12-22-EDRC02PS-2S32-22-EDRC02PS-2X32-22-E
KIT #11Office• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (General ON/ALL OFF)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF• Lights can be switched OFF manually at Office Wall
Station
Primary Daylight Zone
Secondary Daylight Zone
Dimming Zone 1
Dimming Zone 2
O/S
Relay 2
Dimmer 1
Relay 1
Dimmer 2
WallStation
Relay 4Receptacle
D/SDimming Zone 3
*Optional
Relay 3Dimmer 3
Relay 3Dimmer 3
Relay 3Dimmer 3
Relay 3Dimmer 3
Window
Dialog RoomController
29
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
OFFICE
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
NEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 2
0-10V Dimming(18/2 per channel)
Dim 1
RoomController(WRC-3160)
Local Room Dataline (18/2)
Occupancy Sensor(up to 4)
Daylight Sensor
NDim 3
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOT
NEUTRAL
Building Controlvia
BACnet IP or Dialog Network
Entry Station
KIT#11
Kit Ordering Numbers:
DRC01NS-1S11-03-NDRC01NS-1X11-03-NDRC01NS-1S31-03-NDRC01NS-1X31-03-N
Interior(Relay 1)
Secondary Daylight Zone
Display / Track(Relay 3)
Near Window(Relay 2)
Primary Daylight Zone
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Office• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (General ON/ALL OFF)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Office Wall
Station
Dialog Room Controller
30
KIT #12Office with Emergency Lighting• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (General ON/ALL OFF)
Emergency Lighting Control (EMRG)• UL924 Relay Expansion Pack Required• (1 zone - Orange)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF• Lights can be switched OFF manually at Office Wall
Station• During power failure UL924 listed relays are automatically
switched ON by back-up power source switching designated emergency lights ON and to full-bright. Emergency lights remain ON with all controls disabled until primary power is restored.
Primary Daylight Zone
Secondary Daylight Zone
Dimming Zone 1
Dimming Zone 2
O/S
Relay 2Dimmer 1
Relay 5Dimmer 2
EMERGENCY
WallStation
Relay 4Receptacle
D/S
Window
Dimming Zone 3
*Optional
Relay 3Dimmer 3
Relay 3Dimmer 3
Relay 3Dimmer 3
Relay 3Dimmer 3
Dialog RoomController
31
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
OFFICE + EMERGENCY
32
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
ORANGE
ORANGE
GREY
GREY
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
ORANGE
ORANGE
GREY
GREY
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOT
NEUTRAL
(EM) LIGHTING LOAD 5
(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6
(EM) LIGHTING HOT
NEUTRAL
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
0-10V Dimming(18/2 per channel)
Dim 1
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Local Room Dataline (18/2)
Occupancy Sensor(up to 4)
Daylight Sensor
NDim 3
Interior EM(Relay 5)N
Dim 2
Entry Station
KIT#12
Kit Ordering Numbers:
DRC01NS-1S11-03-EDRC01NS-1X11-03-EDRC01NS-1S31-03-EDRC01NS-1X31-03-E
Near Window(Relay 2)
Primary Daylight Zone
Secondary Daylight Zone
Display / Track(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28')
Office with Emergency Lighting• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (General ON/ALL OFF)
• Emergency Lighting Control (1 zones Orange)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Office Wall
Station• During power failure UL924 listed relays are
automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.
Dialog Room Controller
DRC01NS-1S11-30-EDRC01NS-1X11-30-EDRC01NS-1S31-30-EDRC01NS-1X31-30-E
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
ORANGE
ORANGE
GREY
GREY
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
ORANGE
ORANGE
GREY
GREY
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOT
NEUTRAL
(EM) LIGHTING LOAD 5
(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6
(EM) LIGHTING HOT
NEUTRAL
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
0-10V Dimming(18/2 per channel)
Dim 1
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Local Room Dataline (18/2)
Occupancy Sensor(up to 4)
Daylight Sensor
NDim 3
Interior EM(Relay 5)N
Dim 2
Entry Station
KIT#12
Kit Ordering Numbers:
DRC01NS-1S11-03-EDRC01NS-1X11-03-EDRC01NS-1S31-03-EDRC01NS-1X31-03-E
Near Window(Relay 2)
Primary Daylight Zone
Secondary Daylight Zone
Display / Track(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28')
Office with Emergency Lighting• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (General ON/ALL OFF)
• Emergency Lighting Control (1 zones Orange)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Office Wall
Station• During power failure UL924 listed relays are
automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.
Dialog Room Controller
KIT #13Office• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (4-button toggle)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
• Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF• Lights and receptacle can be switched OFF manually at
Wall Station
Primary Daylight Zone &Dimmer Zone 1
Dimming Zone 1
Window
O/S
Relay 1
Dimmer 1
Relay 1
Dimmer 1
WallStation
Relay 4Receptacle
D/S
Relay 2 D
imm
er 2
Dimming Zone 3 Dimming Zone 2
*Optional *Optional
Relay 3Dimmer 3
Relay 3Dimmer 3
Relay 3Dimmer 3
Relay 3Dimmer 3
Dialog RoomController
33
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
OFFICE
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
NEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
General Lighting(Relay 1)
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Dim 2
RoomController(WRC-3160)
Local Room Dataline (18/2)
Occupancy Sensor(up to 4)
Daylight Sensor
Office Toggle Station
Preset Station(Optional)
NDim 3
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOT
NEUTRAL
Building Controlvia
BACnet IP or Dialog Network
KIT#13
Kit Ordering Numbers:
DRC01PS-1S11-30-NDRC01PS-1X11-30-NDRC01PS-1S31-30-NDRC01PS-1X31-30-N
Primary Daylight Zone
Display / Track(Relay 2)
Display / Track(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Office• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (4-button toggle)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights and receptacle can be switched OFF
manually at Wall Station
Dialog Room Controller
34
DRC01NS-1S11-30-NDRC01NS-1X11-30-NDRC01NS-1S31-30-NDRC01NS-1X31-30-N
KIT #14Office with Emergency Lighting• Requires UL924 Relay Expansion Pack (orange)• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (4-button)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF• Lights and receptacle can be switched OFF manually at
Wall Station• During power failure UL924 listed relays are automatically
switched ON by back-up power source switching designated emergency lights ON and to full-bright.
• Emergency lights remain ON with all controls disabled until primary power is restored.
Primary Daylight Zone &Dimmer Zone 1
Dimming Zone 1
Window
O/S
Relay 1
Dimmer 1
Relay 5Dimmer 1
EMERGENCY
WallStation
Relay 4Receptacle
D/S
Relay 2 D
imm
er 2
Dimming Zone 3 Dimming Zone 2
*Optional *Optional
Relay 3Dimmer 3
Relay 3Dimmer 3
Relay 3Dimmer 3
Relay 3Dimmer 3
Dialog RoomController
35
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
OFFICE + EMERGENCY
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
ORANGE
ORANGE
GREY
GREY
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
ORANGE
ORANGE
GREY
GREY
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOT
NEUTRAL
(EM) LIGHTING LOAD 5
(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6
(EM) LIGHTING HOT
NEUTRAL
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Dim 2
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Local Room Dataline (18/2)
Occupancy Sensor(up to 4)
Daylight Sensor
Office Toggle Station
Preset Station(Optional)
NDim 3
Genreal Ltg EM(Relay 5)N
Dim 1
KIT#14
Kit Ordering Numbers:
DRC01PS-1S11-30-EDRC01PS-1X11-30-EDRC01PS-1S31-30-EDRC01PS-1X31-30-E
General Lighting(Relay 1)
Primary Daylight Zone
Display / Track(Relay 2)
Display / Track(Relay 3)
Primary Daylight Zone
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Office with Emergency Lighting• Requires UL924 Relay Expansion Pack (orange)• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (4-button)
• Emergency Lighting Control (1 zones Orange)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights and receptacle can be switched OFF
manually at Wall Station
• During power failure UL924 listed relays areautomatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright.
• Emergency lights remain ON with all controlsdisabled until primary power is restored.
Dialog Room Controller
36
DRC01NS-1S11-30-EDRC01NS-1X11-30-EDRC01NS-1S31-30-EDRC01NS-1X31-30-E
KIT #15Two Offices, One Dialog Room Controller• UL924 Relay Expansion Pack used for additional light
loads (not Emergency Lighting)• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (1 zones per room)• Light Control (2 zones per room)• Receptacle Control• Dimming Control (1 zones per room)• Wall Station (ON/OFF)
Options• Additional Occupancy Sensors (Max. 4 per system)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light level
pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out, lights
and receptacles switched OFF • Lights can be switched OFF manually at Wall Station
Primary Daylight Zone A Primary Daylight Zone B
Dimming Zone 1 Dimming Zone 2
Window Window
D/S D/S
O/S O/S
Relay 1 Dimmer 1 Relay 3 Dimmer 2
Relay 2 Dimmer 1 Relay 4 Dimmer 2
WallStation A
WallStation B
Relay 5Receptacle
Relay 6Receptacle
Dialog Room
Controller
37
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
PROJECT NAME: ___________________________________________________________________ DATE: __________________
TWO OFFICES, ONE DRC
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLE
RED
YELLOW
BLUE
BLUE
WHITE
BLACK
ORANGE
ORANGE
GREY
GREY
PURPLE
RED
YELLOW
BLUE
BLUE
BLACK
WHITE
ORANGE
ORANGE
GREY
GREY
LIGHTING LOAD 1
LIGHTING LOAD 2
LIGHTING LOAD 3
LIGHTING LOAD 4
LIGHTING HOT LOAD 4
LIGHTING HOT
NEUTRAL
(EM) RECEPTACLE LOAD 5
(EM) RECEPTACLE HOT
(EM) RECEPTACLE LOAD 6
(EM) RECEPTACLE HOT
NEUTRAL
Receptacle120Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Office A(Relay 3)N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Office B((Relay 4))
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2Dim 1
Daylight SensorClassroom B
Entry Station(s)Office B
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Occupancy SensorClassroom A
Daylight SensorClassroom A
N
Office A Office B
Occupancy SensorClassroom B
Entry Station(s)Office A
Receptacle(Relay 5)
N
Receptacle(Relay 6)
N
KIT#15
Kit Ordering Numbers:
DRC02NS-2S12-04-NDRC02NS-2X12-04-NDRC02NS-2S32-04-NDRC02NS-2X32-04-N
Primary Daylight Zone Primary Daylight Zone
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Two Offices, One Dialog Room Controller• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (1 zones per room)• Light Control (2 zones per room)• Receptacle Control• Dimming Control (1 zones per room)• Wall Station (ON/OFF)
• UL924 Relay Expansion for additional light load(2 zones Orange & Grey)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station
Dialog Room Controller
38
4
1
2
3
1.0 BASIC INSTALLATION 3.0 EMERGENCY INSTALLATION
4.0 EMERGENCY + RECEPTACLE INSTALLATION
2.0 RECEPTACLE
Loads Line Voltage (lights) Daylight Sensor
2-Wire Network
Occupancy Sensor Wall Switches
BASIC INSTALLATION
Dimming Zone 1
Dimming Zone 2
Dimming Zone 3
Dimming Zone 4
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
39
Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor
www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details
14040500-ALine Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor
www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details
14040500-A
1.0 BASIC INSTALLATION 3.0 EMERGENCY INSTALLATION
4.0 EMERGENCY + RECEPTACLE INSTALLATION
2.0 RECEPTACLE
Loads Line Voltage (lights)
Line Voltage (lights) with emergency backup power
BASIC + EMERGENCY LIGHTING
Daylight Sensor
2-Wire Network
Occupancy Sensor Wall Switches
Dimming Zone 1
Dimming Zone 2
Dimming Zone 3
Dimming Zone 4
4
1
2
3
EM1
EM2
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
40
Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor
www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details
14040500-ALine Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor
www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details
14040500-A
BASIC + RECEPTACLE
1.0 BASIC INSTALLATION 3.0 EMERGENCY INSTALLATION
4.0 EMERGENCY + RECEPTACLE INSTALLATION
2.0 RECEPTACLELoads Line Voltage (receptacle)
Line Voltage (lights)
Daylight Sensor
2-Wire Network
Occupancy Sensor Wall Switches
Dimming Zone 1
Dimming Zone 2
Dimming Zone 3
Dimming Zone 4
1
2
3
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
41
Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor
www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details
14040500-ALine Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor
www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details
14040500-A
BASIC + RECEPTACLE + EMERGENCY
4.0 EMERGENCY + RECEPTACLE INSTALLATIONDaylight Sensor
2-Wire Network
Occupancy Sensor Wall SwitchesLoads
Dimming Zone 1
Dimming Zone 2
Dimming Zone 3
Dimming Zone 4EM1
EM2
3
2
1
Line Voltage (receptacle)Line Voltage (lights)
Line Voltage (lights) with emergency backup power
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
42
Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor
www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details
14040500-ALine Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor
www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details
14040500-A
EMERGENCY (REMOTE MOUNT)
Loads
EM1
EM2
Line Voltage (lights) with emergency backup power
2-wire network to Dialog Room Controller
Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.
43
WRC-TS-1Teachers Stations
WRC-ES-1Entry Station
WRC-OF-PSPresent Station
WRC-OF-A1Entry Station
OF-TGLOffice Station
WRC-TS-8
WRC-DS-0 WRC-DS-R WRC-DS-Z2WRC-DS-F WRC-DS-Z1 WRC-DS-Z3
Switch Option Summary Dimmer Switch: Optinal Dimming Control
Standard naming ShownCan be Customized at Site or At Customer Request
Device Type Description PNDialog Room Controller Digital 4 Channel ON/OFF Room Controller w/ Receptacle Control, BACNet WRC-3160
Dialog Room Controller UL924 / Relay Expansion Pack Digital 2 Channel UL924 Emergency Lighting Controller / Relay Expansion Pack WUL-3924
Digital Occupancy Sensor Recessed Ceiling Standard Range Lens w/ Time Delay Dial & Aux Relay WORSDG1-R-T
Digital Occupancy Sensor Recessed Ceiling Extended Range Lens w/ Time Delay Dial & Aux Relay WORXDG1-R-T
Digital Vacancy Sensor Recessed Ceiling Standard Range Lens w/ Time Delay Dial & Aux Relay WVRSDG1-R-T
Digital Vacancy Sensor Recessed Ceiling Extended Range Lens w/ Time Delay Dial & Aux Relay WVRXDG1-R-T
Closed Loop Daylight Sensor Interior Daylight Sensor for Closed Loop Controlled dimming (on-board dial) WPP-INT
Digital Dimmer & Switch, 1 Channel, O Type Digital Dimmer & Switch, ALL Up/Down & On/Off WRC-DS-O
Digital Dimmer & Switch, 1 Channel, F Type Digital Dimmer & Switch, FRONT Up/Down & On/Off WRC-DS-F
Digital Dimmer & Switch, 1 Channel, R Type Digital Dimmer & Switch, REAR Up/Down & On/Off WRC-DS-R
Digital Dimmer & Switch, 1 Channel, Zone 1 Type Digital Dimmer & Switch, Zone 1 UP/Down & On/Off WRC-DS-Z1
Digital Dimmer & Switch, 1 Channel, Zone 2 Type Digital Dimmer & Switch, Zone 2 Up/Down & On/Off WRC-DS-Z2
Digital Dimmer & Switch, 1 Channel, Zone 3 Type Digital Dimmer & Switch, Zone 3 Up/Down & On/Off WRC-DS-Z3
4 Button Teacher Switch Station Digital 1 Gang 4 Button Switch WRC-TS-1
2 Button Classroom Entry Switch Station Digital 1 Gang 2 Button Switch WRC-ES-1
4 Button Office Switch Station Toggle Control Digital 1 Gang 4 Button Switch WRC-OF-TGL
4 Button Office Switch Station Preset Control Digital 1 Gang 4 Button Switch WRC-OF-PS
4 Button Office Entry Switch Station Digital 1 Gang 4 Button Switch WRC-OF-ES1
2 Button Office Entry Switch Station Digital 1 Gang 2 Button Switch WRC-OF-ES2
8 Button Dimmer Control Digital 1 Gang 8 Button Switch (dimming & ON/OFF) WRC-TS-8
KIT COMPONENTS
Teaching General 50% R1 Toggle
General On Meeting 100% R2 ToggleGeneral On
A/V Presentation R3 Lights R3 ToggleAll Off
Quiet Mode All Off All Off All Off General Front Rear Zone 1 Zone 2 Zone 3
44
FAQ - DIALOG ROOM CONTROLLER
QUESTION: How does the Expansion Pack connect to Dialog Room Controller?
ANSWER: The Expansion Pack can be connected directly to the Room controller via an integrated clip attachment.
• If the Expansion Pack is connected with the Room Controller, then the units communicate through a Dialog protocol connection.
ANSWER: If the Expansion Pack is remotely mounted from the Room Controller, then a 2-wire connection is needed to communicate through a Dialog protocol. The remote mount kit includes a Conduit Adapter and Connector.
QUESTION: What power can the relays support?
ANSWER: There are two 20A circuits coming into the Room Controller, Hot on #1, #2, #3 and Hot on 4.
• #1, #2, #3 are rated for 20A (combined).• #4 is rated for 20A by itself.• There are 2 circuits so different voltages can be used.• Expansion pack can add 2 more 20A Circuits (#5 and #6)
QUESTION: Do the relays support 120VAC, 277VAC and 347VAC?
ANSWER: Yes.
QUESTION: When using Dialog WLC-3150 and Dialog Room Controller and the Dialog WLC-3150 goes down, will the Dialog Room Controller function as a stand-alone?
ANSWER: Yes.
QUESTION: Does Dialog Room Controller work with a GUI?
ANSWER: Graphical UI would be for a centralized system. To drive graphics, a Dialog WLC-3150 and GWS are required.
QUESTION: Do Dialog devices work with Dialog Room Controller?
ANSWER: No. Dialog Room Controller is sold as a kit and includes sensors and switches configured for the specific room applications.
QUESTION: Is the 0-10V dimming isolated?
ANSWER: Yes, each of the four 0-10V dimming outputs are independent channels. 100mA sinking per channel.
QUESTION: What is the maximum number of devices on a room controller?
ANSWER: Dimming: Calculation required based on 100mA per channel of dimming. This will depend on LED driver sinking current requirements. Each DRC is designed to handle up to four Occupancy Sensors and 2 Daylight Sensors plus switches and is limited by the 250mA output of the Dialog Room Controller.
QUESTION: Can Dialog Room Controller provide partition control?
ANSWER: No, it is designed for room control. Partition Control requires WLC-3150 and appropriate firmware version.
QUESTION: How many Dialog Room Controllers on WLC-3150?
ANSWER: WLC-3150 can support up to 64 Dialog Room Controllers. Please contact us for your specific project.
QUESTION: Why or when should I use the expansion pack?
ANSWER: If the room requires a UL924 emergency lighting circuit.ANSWER: If you need to support additional loads.
QUESTION: How does the emergency lighting work when a 0-10v dimmer channel is controlling the fixture/zone?
ANSWER: When power is lost to the room controller, the dimming circuit acts as an open circuit so dimming control is no longer present, while the expansion pack automatically latches both internal relays to ON position. When emergency power is provided, power goes through the UL924 expansion pack and the fixture will turn on at full brightness. – see wiring diagram.
45
Since 1962, Douglas Lighting Controls has been solving lighting control challenges by providing convenient and efficient solutions to buildings throughout North America. Their products effectively operate facility lighting while minimizing energy consumption. With over 50 years of providing lighting control solutions, customers trust Douglas Lighting Controls’ experience and product quality.
• Best-in-Class Pre-Sales, Quote, & Design Services• Exceptional Post-Sales Site & Technical Support• 1,500 Projects Annually
• 100% Project Quality Control• Industry Best Practices for Design & Testing• Make use of Highest Performing Components
• Over 50 Years of Proven Experience• Unwavering Commitment to Successful Outcomes• Backed by a Global Leader - Panasonic