HASTINGS PARK GARDEN AUDITORIUMROOF REPLACEMENT
2901 EAST HASTINGS STREET,VANCOUVER, B.C.
COVER PAGE
R-0.0 0
DMN
AMa N.T.S.
HASTINGS PARK GARDENAUDITORIUM ROOFREPLACEMENT
Sheet Title
Project Name
Drawn By
Designed By
RJC Project Number
Sheet Number Revision
MARCH 14, 2018Date
Scale
VAN.100502.0005
2901 EAST HASTINGS,VANCOUVER, B.C.
No. Revision Date By
amachula P:\VAN\100500\VAN.100502.0005 - Hastings Park Garden Auditorium Roof Replacement\Drafting\VAN.100502.0005 (I) R-0.0 CP.dwg 18-03-14 13:47:40
Seal
All drawings, plans, models, designs, specifications and other documentsprepared by Read Jones Christoffersen Ltd. ("RJC") and used in connectionwith this project are instruments of service for the work shown in them (the"Work") and as such are and remain the property of RJC whether the Workis executed or not, and RJC reserves the copyright in them and in the Workexecuted from them, and they shall not be used for any other work or project.
These drawings are "design drawings" only. They may not be suitable foruse as shop drawings. Use of these drawings as base drawings for "shopdrawings" is not permitted unless written permission containing certainconditions and limitations is obtained from RJC. The work "as constructed"may vary from what is shown on these drawings.
Use of these drawings is limited to that identified in the Revision column.Do not construct from these drawings unless marked "Issued forConstruction" by RJC in the Revision column, and then only for the partsnoted. The drawings shall not be used for "pricing", "costing", or "tender"unless so indicated in the Revision column. "Pricing" or "Costing" drawingsare not complete and any prices based on such drawings must allow for this.
3.
2.
1.
Drawing Notes
Read Jones Christoffersen Ltd.
1285 West Broadway, Suite 300Vancouver, BC V6H 3X8 Canada
604-738-0048604-738-1107
Engineersrjc.ca
telfax
ISSUED FOR CLIENT REVIEW DEC 08/17 DMN
ISSUED FOR 100% CLIENTREVIEW FEB 01/18 DMN
ISSUED FOR BUILDING PERMIT FEB 07/18 DMN
ISSUED FOR BID MAR 14/18 DMN
WOOD FRAMING
GENERAL NOTES
DESIGN PARAMETERS
NON-BUILDING ENVELOPE ELEMENTS
FIELD REVIEW BY RJC
GENERAL SCOPE OF WORK
ABBREVIATIONS
STAGING
HASTINGS PARK GARDENAUDITORIUM ROOFREPLACEMENT
Sheet Title
Project Name
Drawn By
Designed By
RJC Project Number
Sheet Number Revision
MARCH 14, 2018Date
Scale
VAN.100502.0005
2901 EAST HASTINGS,VANCOUVER, B.C.
No. Revision Date By
amachula P:\VAN\100500\VAN.100502.0005 - Hastings Park Garden Auditorium Roof Replacement\Drafting\VAN.100502.0005 (I) R-1.1 SPAGN.dwg 18-03-14 13:47:58
Seal
All drawings, plans, models, designs, specifications and other documentsprepared by Read Jones Christoffersen Ltd. ("RJC") and used in connectionwith this project are instruments of service for the work shown in them (the"Work") and as such are and remain the property of RJC whether the Workis executed or not, and RJC reserves the copyright in them and in the Workexecuted from them, and they shall not be used for any other work or project.
These drawings are "design drawings" only. They may not be suitable foruse as shop drawings. Use of these drawings as base drawings for "shopdrawings" is not permitted unless written permission containing certainconditions and limitations is obtained from RJC. The work "as constructed"may vary from what is shown on these drawings.
Use of these drawings is limited to that identified in the Revision column.Do not construct from these drawings unless marked "Issued forConstruction" by RJC in the Revision column, and then only for the partsnoted. The drawings shall not be used for "pricing", "costing", or "tender"unless so indicated in the Revision column. "Pricing" or "Costing" drawingsare not complete and any prices based on such drawings must allow for this.
3.
2.
1.
Drawing Notes
Read Jones Christoffersen Ltd.
1285 West Broadway, Suite 300Vancouver, BC V6H 3X8 Canada
604-738-0048604-738-1107
Engineersrjc.ca
telfax
SITE PLAN AND GENERALNOTES
R-1.1 0
DMN
AMa N.T.S.
ISSUED FOR CLIENT REVIEW DEC 08/17 DMN
ISSUED FOR 100% CLIENTREVIEW FEB 01/18 DMN
ISSUED FOR BUILDING PERMIT FEB 07/18 DMN
ISSUED FOR BID MAR 14/18 DMN
HASTINGS PARK GARDENAUDITORIUM ROOFREPLACEMENT
Sheet Title
Project Name
Drawn By
Designed By
RJC Project Number
Sheet Number Revision
MARCH 14, 2018Date
Scale
VAN.100502.0005
2901 EAST HASTINGS,VANCOUVER, B.C.
No. Revision Date By
amachula P:\VAN\100500\VAN.100502.0005 - Hastings Park Garden Auditorium Roof Replacement\Drafting\VAN.100502.0005 (I) R-2.1 RP.dwg 18-03-14 13:24:49
Seal
All drawings, plans, models, designs, specifications and other documentsprepared by Read Jones Christoffersen Ltd. ("RJC") and used in connectionwith this project are instruments of service for the work shown in them (the"Work") and as such are and remain the property of RJC whether the Workis executed or not, and RJC reserves the copyright in them and in the Workexecuted from them, and they shall not be used for any other work or project.
These drawings are "design drawings" only. They may not be suitable foruse as shop drawings. Use of these drawings as base drawings for "shopdrawings" is not permitted unless written permission containing certainconditions and limitations is obtained from RJC. The work "as constructed"may vary from what is shown on these drawings.
Use of these drawings is limited to that identified in the Revision column.Do not construct from these drawings unless marked "Issued forConstruction" by RJC in the Revision column, and then only for the partsnoted. The drawings shall not be used for "pricing", "costing", or "tender"unless so indicated in the Revision column. "Pricing" or "Costing" drawingsare not complete and any prices based on such drawings must allow for this.
3.
2.
1.
Drawing Notes
Read Jones Christoffersen Ltd.
1285 West Broadway, Suite 300Vancouver, BC V6H 3X8 Canada
604-738-0048604-738-1107
Engineersrjc.ca
telfax
ROOF PLAN
R-2.1 0
DMN
AMa 1/8"=1'-0"
ISSUED FOR CLIENT REVIEW DEC 08/17 DMN
ISSUED FOR 100% CLIENTREVIEW FEB 01/18 DMN
ISSUED FOR BUILDING PERMIT FEB 07/18 DMN
ISSUED FOR BID MAR 14/18 DMN
SECTION
SECTION
HASTINGS PARK GARDENAUDITORIUM ROOFREPLACEMENT
Sheet Title
Project Name
Drawn By
Designed By
RJC Project Number
Sheet Number Revision
MARCH 14, 2018Date
Scale
VAN.100502.0005
2901 EAST HASTINGS,VANCOUVER, B.C.
No. Revision Date By
amachula P:\VAN\100500\VAN.100502.0005 - Hastings Park Garden Auditorium Roof Replacement\Drafting\VAN.100502.0005 (I) R-3.1 BS.dwg 18-03-14 13:25:05
Seal
All drawings, plans, models, designs, specifications and other documentsprepared by Read Jones Christoffersen Ltd. ("RJC") and used in connectionwith this project are instruments of service for the work shown in them (the"Work") and as such are and remain the property of RJC whether the Workis executed or not, and RJC reserves the copyright in them and in the Workexecuted from them, and they shall not be used for any other work or project.
These drawings are "design drawings" only. They may not be suitable foruse as shop drawings. Use of these drawings as base drawings for "shopdrawings" is not permitted unless written permission containing certainconditions and limitations is obtained from RJC. The work "as constructed"may vary from what is shown on these drawings.
Use of these drawings is limited to that identified in the Revision column.Do not construct from these drawings unless marked "Issued forConstruction" by RJC in the Revision column, and then only for the partsnoted. The drawings shall not be used for "pricing", "costing", or "tender"unless so indicated in the Revision column. "Pricing" or "Costing" drawingsare not complete and any prices based on such drawings must allow for this.
3.
2.
1.
Drawing Notes
Read Jones Christoffersen Ltd.
1285 West Broadway, Suite 300Vancouver, BC V6H 3X8 Canada
604-738-0048604-738-1107
Engineersrjc.ca
telfax
BUILDING SECTIONS
R-3.1 0
DMN
AMa 1/8"=1'-0"
ISSUED FOR CLIENT REVIEW DEC 08/17 DMN
ISSUED FOR 100% CLIENTREVIEW FEB 01/18 DMN
ISSUED FOR BUILDING PERMIT FEB 07/18 DMN
ISSUED FOR BID MAR 14/18 DMN
TYPICAL INTERNAL GUTTER
TYPICAL ROOF DRAIN
TYPICAL SCUPPER DETAIL AT GUTTER
TYPICAL LOW SLOPE ROOF MEMBRANEWATERPROOFING ASSEMBLY
TYPICAL ELECTRICAL CABLE PENETRATION
HASTINGS PARK GARDENAUDITORIUM ROOFREPLACEMENT
Sheet Title
Project Name
Drawn By
Designed By
RJC Project Number
Sheet Number Revision
MARCH 14, 2018Date
Scale
VAN.100502.0005
2901 EAST HASTINGS,VANCOUVER, B.C.
No. Revision Date By
amachula P:\VAN\100500\VAN.100502.0005 - Hastings Park Garden Auditorium Roof Replacement\Drafting\VAN.100502.0005 (I) R-4.1 D.dwg 18-03-14 13:54:08
Seal
All drawings, plans, models, designs, specifications and other documentsprepared by Read Jones Christoffersen Ltd. ("RJC") and used in connectionwith this project are instruments of service for the work shown in them (the"Work") and as such are and remain the property of RJC whether the Workis executed or not, and RJC reserves the copyright in them and in the Workexecuted from them, and they shall not be used for any other work or project.
These drawings are "design drawings" only. They may not be suitable foruse as shop drawings. Use of these drawings as base drawings for "shopdrawings" is not permitted unless written permission containing certainconditions and limitations is obtained from RJC. The work "as constructed"may vary from what is shown on these drawings.
Use of these drawings is limited to that identified in the Revision column.Do not construct from these drawings unless marked "Issued forConstruction" by RJC in the Revision column, and then only for the partsnoted. The drawings shall not be used for "pricing", "costing", or "tender"unless so indicated in the Revision column. "Pricing" or "Costing" drawingsare not complete and any prices based on such drawings must allow for this.
3.
2.
1.
Drawing Notes
Read Jones Christoffersen Ltd.
1285 West Broadway, Suite 300Vancouver, BC V6H 3X8 Canada
604-738-0048604-738-1107
Engineersrjc.ca
telfax
TYPICAL DETAILS
R-4.1 0
DMN
KJB/AMa AS SHOWN
ISSUED FOR CLIENT REVIEW DEC 08/17 DMN
ISSUED FOR 100% CLIENTREVIEW FEB 01/18 DMN
ISSUED FOR BUILDING PERMIT FEB 07/18 DMN
ISSUED FOR BID MAR 14/18 DMN
TYPICAL STEEP SLOPE ROOF ASSEMBLY
TYPICAL VENT STACK FLASHINGAT STEEP SLOPE ROOF
TYPICAL FLASHING DETAIL AT CURB JUNCTIONTYPICAL FLASHING DETAIL AT CORNERTYPICAL SADDLE FLASHING JOINTS
ROOF HATCH DETAIL
HASTINGS PARK GARDENAUDITORIUM ROOFREPLACEMENT
Sheet Title
Project Name
Drawn By
Designed By
RJC Project Number
Sheet Number Revision
MARCH 14, 2018Date
Scale
VAN.100502.0005
2901 EAST HASTINGS,VANCOUVER, B.C.
No. Revision Date By
amachula P:\VAN\100500\VAN.100502.0005 - Hastings Park Garden Auditorium Roof Replacement\Drafting\VAN.100502.0005 (I) R-4.2 TD.dwg 18-03-14 13:25:39
Seal
All drawings, plans, models, designs, specifications and other documentsprepared by Read Jones Christoffersen Ltd. ("RJC") and used in connectionwith this project are instruments of service for the work shown in them (the"Work") and as such are and remain the property of RJC whether the Workis executed or not, and RJC reserves the copyright in them and in the Workexecuted from them, and they shall not be used for any other work or project.
These drawings are "design drawings" only. They may not be suitable foruse as shop drawings. Use of these drawings as base drawings for "shopdrawings" is not permitted unless written permission containing certainconditions and limitations is obtained from RJC. The work "as constructed"may vary from what is shown on these drawings.
Use of these drawings is limited to that identified in the Revision column.Do not construct from these drawings unless marked "Issued forConstruction" by RJC in the Revision column, and then only for the partsnoted. The drawings shall not be used for "pricing", "costing", or "tender"unless so indicated in the Revision column. "Pricing" or "Costing" drawingsare not complete and any prices based on such drawings must allow for this.
3.
2.
1.
Drawing Notes
Read Jones Christoffersen Ltd.
1285 West Broadway, Suite 300Vancouver, BC V6H 3X8 Canada
604-738-0048604-738-1107
Engineersrjc.ca
telfax
TYPICAL DETAILS
R-4.2 0
DMN
AMa/KJB AS SHOWN
ISSUED FOR CLIENT REVIEW DEC 08/17 DMN
ISSUED FOR 100% CLIENTREVIEW FEB 01/18 DMN
ISSUED FOR BUILDING PERMIT FEB 07/18 DMN
ISSUED FOR BID MAR 14/18 DMN
LOW SLOPE TO STEEP SLOPE TRANSITION
GUTTER TRAY
LOWER CANOPY SECTION
CURVED CAP FLASHING AT LOWER CANOPY
BOX VENT AT SLOPED ROOF
HASTINGS PARK GARDENAUDITORIUM ROOFREPLACEMENT
Sheet Title
Project Name
Drawn By
Designed By
RJC Project Number
Sheet Number Revision
MARCH 14, 2018Date
Scale
VAN.100502.0005
2901 EAST HASTINGS,VANCOUVER, B.C.
No. Revision Date By
amachula P:\VAN\100500\VAN.100502.0005 - Hastings Park Garden Auditorium Roof Replacement\Drafting\VAN.100502.0005 (I) R-4.3 TD.dwg 18-03-14 13:25:59
Seal
All drawings, plans, models, designs, specifications and other documentsprepared by Read Jones Christoffersen Ltd. ("RJC") and used in connectionwith this project are instruments of service for the work shown in them (the"Work") and as such are and remain the property of RJC whether the Workis executed or not, and RJC reserves the copyright in them and in the Workexecuted from them, and they shall not be used for any other work or project.
These drawings are "design drawings" only. They may not be suitable foruse as shop drawings. Use of these drawings as base drawings for "shopdrawings" is not permitted unless written permission containing certainconditions and limitations is obtained from RJC. The work "as constructed"may vary from what is shown on these drawings.
Use of these drawings is limited to that identified in the Revision column.Do not construct from these drawings unless marked "Issued forConstruction" by RJC in the Revision column, and then only for the partsnoted. The drawings shall not be used for "pricing", "costing", or "tender"unless so indicated in the Revision column. "Pricing" or "Costing" drawingsare not complete and any prices based on such drawings must allow for this.
3.
2.
1.
Drawing Notes
Read Jones Christoffersen Ltd.
1285 West Broadway, Suite 300Vancouver, BC V6H 3X8 Canada
604-738-0048604-738-1107
Engineersrjc.ca
telfax
TYPICAL DETAILS
R-4.3 0
DMN
AMa AS SHOWN
ISSUED FOR CLIENT REVIEW DEC 08/17 DMN
ISSUED FOR 100% CLIENTREVIEW FEB 01/18 DMN
ISSUED FOR BUILDING PERMIT FEB 07/18 DMN
ISSUED FOR BID MAR 14/18 DMN
TYPICAL STACK VENT AT LOW SLOPE ROOFTYPICAL EXHAUST PENETRATION DETAIL
SECTION AT RIDGE
FLASHING DETAIL AT CHIMNEY
PARAPET AT CAST COPING - SOUTH ROOFCURB AT SOUTH ROOF
HASTINGS PARK GARDENAUDITORIUM ROOFREPLACEMENT
Sheet Title
Project Name
Drawn By
Designed By
RJC Project Number
Sheet Number Revision
MARCH 14, 2018Date
Scale
VAN.100502.0005
2901 EAST HASTINGS,VANCOUVER, B.C.
No. Revision Date By
amachula P:\VAN\100500\VAN.100502.0005 - Hastings Park Garden Auditorium Roof Replacement\Drafting\VAN.100502.0005 (I) R-4.4 TD.dwg 18-03-14 13:26:19
Seal
All drawings, plans, models, designs, specifications and other documentsprepared by Read Jones Christoffersen Ltd. ("RJC") and used in connectionwith this project are instruments of service for the work shown in them (the"Work") and as such are and remain the property of RJC whether the Workis executed or not, and RJC reserves the copyright in them and in the Workexecuted from them, and they shall not be used for any other work or project.
These drawings are "design drawings" only. They may not be suitable foruse as shop drawings. Use of these drawings as base drawings for "shopdrawings" is not permitted unless written permission containing certainconditions and limitations is obtained from RJC. The work "as constructed"may vary from what is shown on these drawings.
Use of these drawings is limited to that identified in the Revision column.Do not construct from these drawings unless marked "Issued forConstruction" by RJC in the Revision column, and then only for the partsnoted. The drawings shall not be used for "pricing", "costing", or "tender"unless so indicated in the Revision column. "Pricing" or "Costing" drawingsare not complete and any prices based on such drawings must allow for this.
3.
2.
1.
Drawing Notes
Read Jones Christoffersen Ltd.
1285 West Broadway, Suite 300Vancouver, BC V6H 3X8 Canada
604-738-0048604-738-1107
Engineersrjc.ca
telfax
TYPICAL DETAILS
R-4.4 0
DMN
AMa/KJB AS SHOWN
ISSUED FOR CLIENT REVIEW DEC 08/17 DMN
ISSUED FOR 100% CLIENTREVIEW FEB 01/18 DMN
ISSUED FOR BUILDING PERMIT FEB 07/18 DMN
ISSUED FOR BID MAR 14/18 DMN
SKYLIGHT AT SOUTH ROOF
CURVED PARAPET FLASHING AT SOUTH ROOFCURVED PARAPET FLASHING AT GUTTER
PARAPET ROOF ASSEMBLY AT ELECTRICAL ROOMBASE OF WALL AT ELECTRICAL ROOM ROOFDRAIN AT ELECTRICAL ROOM ROOF
TYPICAL DETAILS
R-4.5 0
DMN
AMa AS SHOWN
HASTINGS PARK GARDENAUDITORIUM ROOFREPLACEMENT
Sheet Title
Project Name
Drawn By
Designed By
RJC Project Number
Sheet Number Revision
MARCH 14, 2018Date
Scale
VAN.100502.0005
2901 EAST HASTINGS,VANCOUVER, B.C.
No. Revision Date By
amachula P:\VAN\100500\VAN.100502.0005 - Hastings Park Garden Auditorium Roof Replacement\Drafting\VAN.100502.0005 (I) R-4.5 TD.dwg 18-03-14 13:26:37
Seal
All drawings, plans, models, designs, specifications and other documentsprepared by Read Jones Christoffersen Ltd. ("RJC") and used in connectionwith this project are instruments of service for the work shown in them (the"Work") and as such are and remain the property of RJC whether the Workis executed or not, and RJC reserves the copyright in them and in the Workexecuted from them, and they shall not be used for any other work or project.
These drawings are "design drawings" only. They may not be suitable foruse as shop drawings. Use of these drawings as base drawings for "shopdrawings" is not permitted unless written permission containing certainconditions and limitations is obtained from RJC. The work "as constructed"may vary from what is shown on these drawings.
Use of these drawings is limited to that identified in the Revision column.Do not construct from these drawings unless marked "Issued forConstruction" by RJC in the Revision column, and then only for the partsnoted. The drawings shall not be used for "pricing", "costing", or "tender"unless so indicated in the Revision column. "Pricing" or "Costing" drawingsare not complete and any prices based on such drawings must allow for this.
3.
2.
1.
Drawing Notes
Read Jones Christoffersen Ltd.
1285 West Broadway, Suite 300Vancouver, BC V6H 3X8 Canada
604-738-0048604-738-1107
Engineersrjc.ca
telfax
ISSUED FOR CLIENT REVIEW DEC 08/17 DMN
ISSUED FOR 100% CLIENTREVIEW FEB 01/18 DMN
ISSUED FOR BUILDING PERMIT FEB 07/18 DMN
ISSUED FOR BID MAR 14/18 DMN
LIST OF STRUCTURAL DRAWINGS
DRAWINGS
GENERAL
ANALYSIS AND DESIGN CRITERIA
RENOVATIONSWOOD FRAMING
DESIGN LOADS
STRUCTURAL STEEL
STEEL DECK
PLYWOOD OVERLAY - LOWER LAYER
PLYWOOD OVERLAY - UPPER LAYER
TYPICAL PLYWOOD NAILING PATTERN
STRUCTURALGENERAL NOTES
Sheet Title
Project Name
Drawn By
Designed By
RJC Project Number
Sheet Number
S1.1 .Revision
JMH
HMB N/A
NOVEMBER, 2017Date
Scale
VAN.107371.0007
2901 EAST HASTINGS,VANCOUVER, B.C.
No. Revision Date By
KMills P:\VAN\107300\VAN.107371.0007 - City of Vancouver Roof Replacement Diaphragm Upgrades\Drafting\Hastings Park Garden\Hastings Park Garden - Sheets.dwg 18-03-14 10:44:19
Seal
All drawings, plans, models, designs, specifications and other documentsprepared by Read Jones Christoffersen Ltd. ("RJC") and used in connectionwith this project are instruments of service for the work shown in them (the"Work") and as such are and remain the property of RJC whether the Workis executed or not, and RJC reserves the copyright in them and in the Workexecuted from them, and they shall not be used for any other work or project.
These drawings are "design drawings" only. They may not be suitable foruse as shop drawings. Use of these drawings as base drawings for "shopdrawings" is not permitted unless written permission containing certainconditions and limitations is obtained from RJC. The work "as constructed"may vary from what is shown on these drawings.
Use of these drawings is limited to that identified in the Revision column.Do not construct from these drawings unless marked "Issued forConstruction" by RJC in the Revision column, and then only for the partsnoted. The drawings shall not be used for "pricing", "costing", or "tender"unless so indicated in the Revision column. "Pricing" or "Costing" drawingsare not complete and any prices based on such drawings must allow for this.
3.
2.
1.
Drawing Notes
Read Jones Christoffersen Ltd.
1285 West Broadway, Suite 300Vancouver, BC V6H 3X8 Canada
604-738-0048604-738-1107
Engineersrjc.ca
telfax
COORDINATION NOV 17/17 JMH
HASTINGS PARK GARDENAUDITORIUMROOF REPLACEMENT
ISSUED FOR REVIEW DEC 08/17 JMH
ISSUED FOR BUILDING PERMIT FEB 07/18 JMH
ISSUED FOR BID MAR 14/18 JMH
KEY NOTES
ROOF NOTES
DIMENSIONS
ROOF PLAN
ROOF PLANSSheet Title
Project Name
Drawn By
Designed By
RJC Project Number
Sheet Number
S2.1 .Revision
HMB 3/32"=1'-0"
Date
Scale
VAN.107371.0007
No. Revision Date By
KMills P:\VAN\107300\VAN.107371.0007 - City of Vancouver Roof Replacement Diaphragm Upgrades\Drafting\Hastings Park Garden\Hastings Park Garden - Sheets.dwg 18-03-14 10:44:19
Seal
All drawings, plans, models, designs, specifications and other documentsprepared by Read Jones Christoffersen Ltd. ("RJC") and used in connectionwith this project are instruments of service for the work shown in them (the"Work") and as such are and remain the property of RJC whether the Workis executed or not, and RJC reserves the copyright in them and in the Workexecuted from them, and they shall not be used for any other work or project.
These drawings are "design drawings" only. They may not be suitable foruse as shop drawings. Use of these drawings as base drawings for "shopdrawings" is not permitted unless written permission containing certainconditions and limitations is obtained from RJC. The work "as constructed"may vary from what is shown on these drawings.
Use of these drawings is limited to that identified in the Revision column.Do not construct from these drawings unless marked "Issued forConstruction" by RJC in the Revision column, and then only for the partsnoted. The drawings shall not be used for "pricing", "costing", or "tender"unless so indicated in the Revision column. "Pricing" or "Costing" drawingsare not complete and any prices based on such drawings must allow for this.
3.
2.
1.
Drawing Notes
Read Jones Christoffersen Ltd.
1285 West Broadway, Suite 300Vancouver, BC V6H 3X8 Canada
604-738-0048604-738-1107
Engineersrjc.ca
telfax
JMH NOVEMBER, 2017
2901 EAST HASTINGS,VANCOUVER, B.C.
COORDINATION NOV 17/17 JMH
ISSUED FOR REVIEW DEC 08/17 JMH
ISSUED FOR BUILDING PERMIT FEB 07/18 JMH
HASTINGS PARK GARDENAUDITORIUMROOF REPLACEMENT
ISSUED FOR BID MAR 14/18 JMH
SECTIONSECTION
TYPICAL INTERNAL GUTTERINTERNAL GUTTERISOMETRIC VIEW
BUILDING SECTIONSSheet Title
Project Name
Drawn By
Designed By
RJC Project Number
Sheet Number
S3.1 .Revision
HMB 1/8"=1'-0"
Date
Scale
VAN.107371.0007
No. Revision Date By
KMills P:\VAN\107300\VAN.107371.0007 - City of Vancouver Roof Replacement Diaphragm Upgrades\Drafting\Hastings Park Garden\Hastings Park Garden - Sheets.dwg 18-03-14 10:44:19
Seal
All drawings, plans, models, designs, specifications and other documentsprepared by Read Jones Christoffersen Ltd. ("RJC") and used in connectionwith this project are instruments of service for the work shown in them (the"Work") and as such are and remain the property of RJC whether the Workis executed or not, and RJC reserves the copyright in them and in the Workexecuted from them, and they shall not be used for any other work or project.
These drawings are "design drawings" only. They may not be suitable foruse as shop drawings. Use of these drawings as base drawings for "shopdrawings" is not permitted unless written permission containing certainconditions and limitations is obtained from RJC. The work "as constructed"may vary from what is shown on these drawings.
Use of these drawings is limited to that identified in the Revision column.Do not construct from these drawings unless marked "Issued forConstruction" by RJC in the Revision column, and then only for the partsnoted. The drawings shall not be used for "pricing", "costing", or "tender"unless so indicated in the Revision column. "Pricing" or "Costing" drawingsare not complete and any prices based on such drawings must allow for this.
3.
2.
1.
Drawing Notes
Read Jones Christoffersen Ltd.
1285 West Broadway, Suite 300Vancouver, BC V6H 3X8 Canada
604-738-0048604-738-1107
Engineersrjc.ca
telfax
JMH NOVEMBER, 2017
2901 EAST HASTINGS,VANCOUVER, B.C.
COORDINATION NOV 17/17 JMH
ISSUED FOR REVIEW DEC 08/17 JMH
ISSUED FOR BUILDING PERMIT FEB 07/18 JMH
HASTINGS PARK GARDENAUDITORIUMROOF REPLACEMENT
ISSUED FOR BID MAR 14/18 JMH