17
A Yes No B Yes No C Yes No D Yes No N/A E Yes No N/A F Yes No N/A G Yes No N/A H Yes No N/A I Yes No N/A J Yes No N/A Mircom Company 19-991812 Identification Number of Primary or Supervising Technician Conducting the Verification RAMSEY ELECTRIC Company Identification Number of Technician Conducting the Verification LULLABOO CHILDCARE BRIAN D UHLE KEVIN RIVERS Printed Name of Primary or Supervising Date: September 8, 2016 Job #: A copy of this report will be given to the following, who is the owner or owner's representative for this building: - Address: Site #: This is to certify that the information contained in this Fire Alarm System Verification Report is correct and complete. - - - The entire fire alarm system has been verified in accordance with CAN/ULC-S537-04, Verification of Fire Alarm Systems. The fire alarm system has deficiencies noted on the pages attached. Technician Conducting the Verification The fire alarm system is fully functional. System provides single-stage operation System provides two-stage operation K The fire alarm system documentation is on site and includes a description of the system. This is a partial verification for partial occupancy. This is a verification of a portion of an existing fire alarm system verified in accordance with Section 6, system modifications This is a partial verification for a fire alarm system that has been replaced in stages. Signature of Primary or Supervising No The fire alarm system has notes & recommendations noted on the pages attached. Yes VERIFICATION REPORT the Verification Printed Name of Technician Conducting Technician Conducting the Verification MIRCOM 1454 QUEENS ST W BRAMPTON, ON Building Name: Model Number: FA-1000 System Manufacturer: KEVIN @ RAMSEY ELECTRIC Signature of Technician Conducting the Verification Page 1

Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

A Yes No

B Yes No

C Yes No

D Yes No N/A

E Yes No N/A

F Yes No N/A

G Yes No N/A

H Yes No N/A

I Yes No N/A

J Yes No N/A

MircomCompany

19-991812Identification Number of Primary or Supervising

Technician Conducting the Verification

RAMSEY ELECTRICCompany

Identification Number of TechnicianConducting the Verification

LULLABOO CHILDCARE

BRIAN D UHLE

KEVIN RIVERS

Printed Name of Primary or Supervising

Date: September 8, 2016

Job #:

A copy of this report will be given to the following, who is the owner or owner's representative

for this building: -

Address:

Site #:

This is to certify that the information contained in this Fire Alarm System Verification Report is correct and complete.

-

-

-The entire fire alarm system has been verified in accordance with CAN/ULC-S537-04, Verification of Fire

Alarm Systems.

The fire alarm system has deficiencies noted on the pages attached.

Technician Conducting the Verification

The fire alarm system is fully functional.

System provides single-stage operation

System provides two-stage operation

K

The fire alarm system documentation is on site and includes a description of the system.

This is a partial verification for partial occupancy.

This is a verification of a portion of an existing fire alarm system verified in accordance with Section 6,

system modifications

This is a partial verification for a fire alarm system that has been replaced in stages.

Signature of Primary or Supervising

No

The fire alarm system has notes & recommendations noted on the pages attached.

Yes

VERIFICATION REPORT

the VerificationPrinted Name of Technician Conducting

Technician Conducting the Verification

MIRCOM

1454 QUEENS ST W

BRAMPTON, ON

Building Name:

Model Number: FA-1000System Manufacturer:

KEVIN @ RAMSEY ELECTRIC

Signature of Technician Conductingthe Verification

Page 1

Page 2: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

Notes:

Deficiencies:

Recommendations:

MONITORING COMPANY NOT ON SITE DURING VERIFICATION - SYSTEM NOT MONITORED AT THIS TIME

DOOR HOLD OPEN DEVICES NOT INSTALLED AT TIME OF VERIFICATION - RELAY OPERATION ONLY CONFIRMED

REMARKS

Page 2

Page 3: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

DEVICE LEGEND

Device Description Manufacturer Model Number

M Manual Pull Station MIRCOM MS-401

GA General Alarm

RHT Heat Detector, Restorable

HT Heat Detector, Non-Restorable SYSTEM SENSOR 5603A

S Smoke Detector SYSTEM SENSOR C2W-BA

S Smoke Detector SYSTEM SENSOR 2151A

DS Duct Smoke Detector

RI Remote Indicator Unit

SP Speaker

V Visual Signal Device

SPV Speaker Strobe

H Horn

H/V Horn Strobe MIRCOM FHS-340R

B Bell

ET Emergency Telephone

EOL End-of-Line Resistor MIRCOM EL-300

FS Sprinkler Flow Switch

SS Sprinkler Supervisory Device

PS Sprinkler Low Pressure Device

MON Monitor Module

REL Relay Module MIRCOM RM-1008A

ISO Fault Isolation Module

FCM Control Module

RLY-B RELAY BASE SYSTEM SENSOR B116LPA

Page 3

Page 4: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

FIRE ALARM SYSTEM DEVICE RECORD

BUILDING NAME: LULLABOO NURSERY AND CHILD CAREDATE: September 7, 2017

Loca

tion

of D

evic

e

Dev

ice

Type

Dev

ice

Add

ress

or

Circ

uit N

umbe

rCo

rrec

tly

Inst

alle

d

Ala

rm, S

uper

viso

ry o

r

Func

tion

Con

firm

ed

Ann

unci

atio

n Co

nfir

med

Supe

rvis

ion

& G

roun

d

Faul

t Det

ecti

on

Smok

e Se

nsit

ivit

y (%

)

Duc

t Sm

oke

Pres

sure

Diff

eren

tial

(Pas

cal)

Wat

er fl

ow D

elay

(sec

)

Mag

lock

Ope

rati

on

Notes

2ND FLOOR

2ND FL - CORRIDOR SOUTH STAIR EXIT M 1 a a a a2ND FL - CORRIDOR SOUTH S 1 a a a a 2.402ND FL - CORRIDOR CENTER S 1 a a a a 2.402ND FL - ELEVATOR LOBBY S 3 a a a a 2.40 RELAY BASE2ND FL - CORRIDOR NORTH S 1 a a a a 2.40

2ND FL - CORRIDOR NORTH STAIR EXIT M 1 a a a a2ND FL - CORRIDOR NORTH STAIR EXIT EOL 1 a a a a2ND FL - CLASSROOM S.W S 3 a a a a 2.40

2ND FL - CLASSROOM S.W + S.CNTR CLOSET S 3 a a a a 2.40

2ND FL - CLASSROOM W.CNTR S 3 a a a a 2.40

2ND FL - CLASSROOM N.W S 3 a a a a 2.40

2ND FL - CLASSROOM N.W CLOSET S 3 a a a a 2.40

2ND FL - CLASSROOM N.E S 3 a a a a 2.40

2ND FL - CLASSROOM N.E CLOSET S 3 a a a a 2.40

2ND FL - CLASSROOM N.E CLOSET EOL 3 a a a a2ND FL - CLASSROOM N.E CLOSET EOL 2 a a a a2ND FL - CLASSROOM S.E S 3 a a a a 2.40

2ND FL - CLASSROOM S.E CLOSET S 3 a a a a 2.40

2ND FL - UTILITY ROOM EAST S 7 a a a a2ND FL - UTILITY ROOM EAST EOL 7 a a a a2ND FL - UTILITY ROOM EWEST S 6 a a a a2ND FL - UTILITY ROOM WEST EOL 6 a a a a

ELEVATOR TOP OF SHAFT S 2 a a a a 2.40

TOP OF NORTH STAIR S 4 a a a a 2.40

TOP OF NORTH STAIR EOL 4 a a a aTOP OF SOUTH STAIR S 5 a a a a 2.40

TOP OF SOUTH STAIR EOL 5 a a a a

Device Record Page 4

Page 5: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

FIRE ALARM SYSTEM DEVICE RECORD

BUILDING NAME: LULLABOO NURSERY AND CHILD CAREDATE: September 7, 2017

Loca

tion

of D

evic

e

Dev

ice

Type

Dev

ice

Add

ress

or

Circ

uit N

umbe

rCo

rrec

tly

Inst

alle

d

Ala

rm, S

uper

viso

ry o

r

Func

tion

Con

firm

ed

Ann

unci

atio

n Co

nfir

med

Supe

rvis

ion

& G

roun

d

Faul

t Det

ecti

on

Smok

e Se

nsit

ivit

y (%

)

Duc

t Sm

oke

Pres

sure

Diff

eren

tial

(Pas

cal)

Wat

er fl

ow D

elay

(sec

)

Mag

lock

Ope

rati

on

Notes

2ND FL - CORRIDOR SOUTH H/V SIG5 a a a2ND FL - CORRIDOR SOUTH EOL SIG5 a a a2ND FL - CORRIDOR NORTH H/V SIG6 a a a2ND FL - CORRIDOR NORTH EOL SIG6 a a a

1ST FLOOR

1ST FL - CORRIDOR SOUTH STAIR EXIT M 9 a a a a1ST FL - CORRIDOR SOUTH S 9 a a a a 2.40

1ST FL - CORRIDOR WEST AT OFFICES S 9 a a a a 2.40

1ST FL - ELEVATOR LOBBY S 13 a a a a 2.40 RELAY BASE

1ST FL - CORRIDOR NORTH S 9 a a a a 2.40

1ST FL - CORRIDOR NORTH STAIR EXIT M 9 a a a a1ST FL - CORRIDOR NORTH STAIR EXIT EOL 9 a a a a1ST FL - UTILITY ROOM AT STAFF WASHROOM S 15 a a a a 2.40

1ST FL - UTILITY ROOM AT STAFF WASHROOM EOL 15 a a a a1ST FL - UTILITY ROOM WEST S 16 a a a a 2.40

1ST FL - UTILITY ROOM WEST EOL 16 a a a a1ST FL - KITCHEN HT 12 a a a a1ST FL - KITCHEN EOL 12 a a a a1ST FL - CLASSROOM S.W S 13 a a a a 2.40

1ST FL - CLASSROOM N.W S 13 a a a a 2.40

1ST FL - CLASSROOM N.W SLEEPING AREA S 13 a a a a 2.40

1ST FL - CLASSROOM N.CNTR S 13 a a a a 2.40

Device Record Page 5

Page 6: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

FIRE ALARM SYSTEM DEVICE RECORD

BUILDING NAME: LULLABOO NURSERY AND CHILD CAREDATE: September 7, 2017

Loca

tion

of D

evic

e

Dev

ice

Type

Dev

ice

Add

ress

or

Circ

uit N

umbe

rCo

rrec

tly

Inst

alle

d

Ala

rm, S

uper

viso

ry o

r

Func

tion

Con

firm

ed

Ann

unci

atio

n Co

nfir

med

Supe

rvis

ion

& G

roun

d

Faul

t Det

ecti

on

Smok

e Se

nsit

ivit

y (%

)

Duc

t Sm

oke

Pres

sure

Diff

eren

tial

(Pas

cal)

Wat

er fl

ow D

elay

(sec

)

Mag

lock

Ope

rati

on

Notes

1ST FL - CLASSROOM N.CNTR SLEEPING AREA S 13 a a a a 2.40

1ST FL - CLASSROOM E.CNTR S 13 a a a a 2.40

1ST FL - CLASSROOM E.CNTR + S.E CLOSET S 13 a a a a 2.40

1ST FL - CLASSROOM S.E S 13 a a a a 2.40

1ST FL - UTILITY ROOM EAST S 11 a a a a 2.40

1ST FL - UTILITY ROOM EAST EOL 11 a a a a

1ST FL - CORRIDOR SOUTH H/V SIG3 a a a1ST FL - CORRIDOR SOUTH EOL SIG3 a a a1ST FL - CORRIDOR NORTH H/V SIG4 a a a1ST FL - CORRIDOR NORTH EOL SIG4 a a a

BASEMENT

BSMNT - CORRIDOR SOUTH STAIR EXIT M 19 a a a aBSMNT - CORRIDOR SOUTH S 19 a a a a 2.40

BSMNT - ELEVATOR LOBBY S 19 a a a a 2.40 RELAY BASE

BSMNT - CORRIDOR NORTH S 19 a a a a 2.40

BSMNT - CORRIDOR NORTH STAIR EXIT M 19 a a a aBSMNT - CORRIDOR NORTH STAIR EXIT EOL 19 a a a aBSMNT - MAIIN ELECTRICAL ROOM S 18 a a a a 2.40

BSMNT - CLASSROOM S.W S 17 a a a a 2.40

BSMNT - CLASSROOM S.W CLOSET S 17 a a a a 2.40

BSMNT - STAFF KITCHEN S 17 a a a a 2.40

BSMNT - STAFF KITCHEN CLOSET S 17 a a a a 2.40

BSMNT - STAFF MEETING ROOM S 17 a a a a 2.40

BSMNT - STAFF MEETING ROOM CLOSET S 17 a a a a 2.40

Device Record Page 6

Page 7: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

FIRE ALARM SYSTEM DEVICE RECORD

BUILDING NAME: LULLABOO NURSERY AND CHILD CAREDATE: September 7, 2017

Loca

tion

of D

evic

e

Dev

ice

Type

Dev

ice

Add

ress

or

Circ

uit N

umbe

rCo

rrec

tly

Inst

alle

d

Ala

rm, S

uper

viso

ry o

r

Func

tion

Con

firm

ed

Ann

unci

atio

n Co

nfir

med

Supe

rvis

ion

& G

roun

d

Faul

t Det

ecti

on

Smok

e Se

nsit

ivit

y (%

)

Duc

t Sm

oke

Pres

sure

Diff

eren

tial

(Pas

cal)

Wat

er fl

ow D

elay

(sec

)

Mag

lock

Ope

rati

on

Notes

BSMNT - SUMP PUMP ROOM S 17 a a a a 2.40

BSMNT - NORTH STAIR LOBBY S 17 a a a a 2.40

BSMNT - CLASSROOM N.E S 17 a a a a 2.40

BSMNT - CLOSET BENEATH SOUTH STAIR S 17 a a a a 2.40

BSMNT - CLASSROOM S.E S 17 a a a a 2.40

BSMNT - CLASSROOM S.E CLOSET S 17 a a a a 2.40

BSMNT - CLASSROOM S.E CLOSET EOL 17 a a a aBSMNT - ELEVATOR PIT S 21 a a a a 2.40

BSMNT - ELEVATOR MACHINE ROOM S 20 a a a a 2.40

BSMNT - ELEVATOR MACHINE ROOM EOL 21 a a a aBSMNT - ELEVATOR MACHINE ROOM EOL 20 a a a a

BSMNT - CORRIDOR SOUTH H/V SIG2 a a aBSMNT - CORRIDOR SOUTH EOL SIG2 a a aBSMNT - CORRIDOR CENTER H/V SIG1 a a aBSMNT - CORRIDOR NORTH STAIRWELL H/V SIG1 a a aBSMNT - CORRIDOR NORTH STAIRWELL EOL SIG1 a a a

Device Record Page 7

Page 8: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

A Yes No N/A

B Yes No N/A

C Yes No N/A

D Yes No N/A

E Yes No N/A

F Yes No N/A

G Yes No N/A

H Yes No N/A

I Yes No N/A

J Yes No N/A

K Yes No N/A

L Yes No N/A

M Yes No N/A

N Yes No N/A

O Yes No N/A

P

Q Yes No N/A

R Yes No N/A

S Yes No N/A

T Yes No N/A

U Yes No N/A

V Yes No N/A

W Yes No N/A

X Yes No N/A

Y Yes No N/A

Z Yes No N/A

AA Yes No N/A

BB Yes No N/A

CC Yes No N/A

DD Yes No N/A

EE Yes No N/A

FF Yes No N/A

GG Yes No N/A

HH Yes No N/A

JJ Yes No N/A

Input circuit supervision fault causes a trouble indication.

Alarm signal silence automatic cut-out timer.

Common audible trouble signal operates.

Common visual trouble signal operates.

Audible and visual alert and alarm signals operate per design and specification.

II

N/A

Ancillary device by-pass results in trouble signal.

Trouble signal silence switch operates.

Alarm signal manual silence operates.

Ground fault tested on positive and negative initiates trouble signal.

Main power supply failure trouble signal operates.

Alarm signal, when silenced, automatically reinitiates upon subsequent alarm.

Alarm signal silence visual indication operates.

Automatic transfer from alert signal to alarm signal cancelled when system is acknowledged on a

two-stage system.

Visual indicator test (lamp test) operates.

Output circuit supervision fault causes a trouble indication.

Alarm signal silence inhibit function operates. 1 MINUTE

Manually transfers from alert signal to alarm signal operates (two-stage system)

Automatically transfers from alert signal to alarm signal operates (two-stage system)

CONTROL UNIT OR TRANSPONDER RECORD

NOT MONITOREDPhone #: N/A

Operation of the fire signal receiving centre disconnect results in a specific trouble indication at

the control unit or transponder and transmits a trouble signal to the remote fire signal receiving

centre.

Confirm that the alarm transmission to the remote fire signal receiving centre is

received.

Time:

Main power supply to emergency power supply transfer operates.

Fire alarm system reset operates.

Ancillary device control circuit is rated for the intended purpose

Confirm that the supervisory transmission to the remote fire signal receiving centre is

received.

Control unit or transponder bonded to ground

Input circuits programmed to operate output circuits (including ancillary devices)

operate as per design and specification.

Status change confirmation feature (smoke detectors only) verified.

Input circuit, alarm & supervisory operation (including visual indicator) operates.

Confirm that the trouble transmission to the remote fire signal receiving centre is

received.

If connected, record the name and telephone number of the fire signal receiving centre.Name:

Control Unit or Transponder Location:

Control Unit or Transponder Identification:

SOUTH MAIN ENTRANCE

MAIN FACP

Coded signal sequences are not interrupted by subsequent alarms.

Coded signal sequences operate not less than the required number of times and the

correct alarm signal operates thereafter.

Output circuit alarm indicators operates.

Power 'On' visual indicator operates.

Alarm signal operates.

Alert signal operates.

Nodes Page 8

Page 9: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

A Yes No N/A

B Yes No N/A

C Yes No N/A

D Yes No N/A

E Yes No N/A

F Yes No N/A

G Yes No N/A

H Yes No N/A

I Yes No N/A

J Yes No N/A

K Yes No N/A

L Yes No N/A

M Yes No N/A

N Yes No N/A

O Yes No N/A

P Yes No N/A

A Yes No N/A

B Yes No N/A

C Yes No N/A

D Yes No N/A

E Yes No N/A

Rev: Ver:

G Yes No N/A

H Yes No N/A

I Yes No N/A

J Yes No N/A

K Yes No N/A

L Yes No N/A

M Yes No N/A

N Yes No N/A

O Yes No N/A

VOICE COMMUNICATION TEST

Common visual trouble signal operates.

Common audible trouble signal operates.

Trouble signal silence switch operates.

Output circuits for selective voice paging trouble operation, including visual indication, operates.

Correct designations for common control functions and indicators.

Record the date, revision and version of firmware and software

Microphone, including press to talk switch, operates.

Operation of voice paging does not interfere with initial inhibit time of alert signal or alarm signal.

Circuits for emergency telephones operate and two-way voice communication operates.

Plug-in components and modules securely in place.

ALL CALL voice paging, including visual indicator, operates.

Output circuits for selective voice paging, including visual indication, operates.

Power 'On' visual indicator operates.

1.0

ALL CALL voice paging operates on emergency power supply.

Upon failure of one amplifier, system automatically transfers to backup amplifier(s).

Circuits for emergency telephone call-in operation operates audible and visual indicators.

Input circuit designations correctly identified in relation to connected field devices.

Output circuit designations correctly identified in relation to connected field devices.

Circuits for emergency telephone trouble operate and visual indication operates.

Emergency telephone verbal communication operates.

Emergency telephone 'operable' or 'in-use' tone at handset operates.

CONTROL UNIT OR TRANSPONDER INSPECTION

F8/1/2016

2.1.13

Date:

Plug-in cables securely in place.

Verify control units or transponders with stand alone capability serves the same area for both

input circuits and output circuits.Control units or transponders which operate with stand alone capability have signal silence, reset,

and trouble silence switches with visual indicators, degraded mode capability and stand alone

capability indicators.

Control unit or transponder visual indicators comply with the visual indicators colour code.

Control unit and transponder is clean and free of dust and dirt.

Control unit or transponder power disconnects in accordance with C22.1, Safety

Standard for Electrical Installations, Canadian Electrical Code, Part 1.

Main power supply feed wiring in accordance with manufacturer's specifications.

Fuses are in accordance with manufacturer's specification.

Termination points, from wiring to field devices, is secure.

Control unit or transponder lock is functional.

Nodes Page 9

Page 10: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

A Yes No N/A

B Yes No N/A

C Yes No N/A

D Yes No N/A

- - -

Yes No N/A

Yes No N/A

Yes No N/A

Yes No N/A

A Yes No N/A

B Yes No N/A

C Yes No N/A

D Yes No N/A

E Yes No N/A

F Yes No N/A

Adequate to meet the requirements of the system.

ii) Maintain synchronization of control units or transponders for alert signals and alarm

signals

Fused in accordance with the manufacturer's marked rating of the system.

POWER SUPPLY INSPECTION

Conforms with the requirements of CAN/ULC-S524, Standard for the Installation of Fire

Alarms Systems; and C22.1 Safety Standard for Electrical Installations, Canadian

Electrical Code, Part I, Section 32.

Equipped with the identified disconnect means.

E

i) Operate the alarm signals in accordance with the system operating sequence;

Verify control units or transponders serve the same area for both input circuits and output circuits

iii) Operate local relays in control units or transponders connected to ancillary devices; as required

iv) Confirm the operation of acknowledge, signal silence, reset and trouble silence switches with

visual indicators, degraded mode capability and stand alone capability indicators, are functional

for each network segment.

Ancillary devices, which are powered from the control unit or transponder, are recorded

Verify control units or transponders with stand alone capability have signal silence, reset and

trouble silence switches with visual indicators, degraded mode capability and stand alone

capability indicators

Confirm that between any nodes a single open circuit fault, wire-to-wire short circuit fault, or

ground fault on the network results in a trouble signal at each node and continued alarm receipt

capability at each node under these conditions.

LARGE SCALE NETWORK SYSTEMS

Power for ancillary devices is taken from a source separate from the fire alarm system

control unit or transponder power supply.

To test stand alone capability, create a condition of data communication link failure, and confirm

each control unit or transponder is capable of receiving an alarm initiation and provides output

operation in the area as served by the control unit or transponder degraded mode.

To test degraded mode capability, create a condition of data communication link failure

in two separate locations creating two network segments, and confirm each segment of

the network have the following operation:

Nodes Page 10

Page 11: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

A Yes No N/A

B Yes No N/A

C

D

E

F

G Yes No -

H Yes No N/A

I Yes No N/A

J Yes No N/A

K Yes No N/A

L Yes No N/A

M Yes No N/A

N

O Yes No N/A

Yes No -

Yes No -

Yes No -

Q

R

S Yes No N/A

T Yes No N/A

U Yes No N/A

See battery summary

EMERGENCY POWER SUPPLY TEST & INSPECTION

See battery summary

See battery summary

(i) Required supervisory load for 24 hours followed by the required full load operation;

or

Trouble condition at the emergency generator shall result in an audible common trouble signal

and a visual indication at the required annunciator.

Battery voltage not less than 85% of its rating after the tests.

See battery summary

See battery summary

P

Record calculated battery capacity

Record battery terminal voltage after completion of tests.

Generator provides power to the AC circuit serving the fire alarm system.

See battery summary

Terminals are cleaned and lubricated.

See battery summary

(iii) Silent accelerated test (batery capacity meter test)

Battery voltage with main power supply 'on'

Battery voltage and current with main power supply 'off' and fire alarm system in

supervisory condition.

Correct battery type as recommended by manufacturer

Type of battery test performed:

Specific gravity of electrolyte is within manufacturer's specifications.

Batteries show signs of physical damage.

Electrolyte leakage.

Terminals clamped tightly.

(ii) A silent test by using the load resistor method may be used for the full duration test;

or

Correct electrolyte level.

Correct battery rating as determined by battery calculations based on full system load.

Adequately ventilation.

Record manufacture's date code or in-service date

Disconnection causes trouble signal

Battery voltage and current with main power supply 'off' and fire alarm system in full

load alarm condition.

Charging current.

Nodes Page 11

Page 12: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

A Yes No N/A

B Yes No N/A

C Yes No N/A

D Yes No N/A

E Yes No N/A

F Yes No N/A

Class BTSTTTT

LEGENDT = Trouble indication at the control unit or transponder.S = Trouble indication at the control unit or transponder and alarm receipt

capability during abnormal operation.

* = Same link.

Loss of Carrier T T

Wire-to-Wire Short Circuit Fault & Ground Fault*

S

T S*Open Circuit Fault and Ground Fault* S S*

DATA COMMUNICATION LINK TEST

S

Where fault isolation in data communication links is provided between control units or

transponders, the field wiring shorted between each pair of control units or transponders, the

turn, annunciation of the fault confirmed and operation outside the shorted section confirmed.

Where fault isolation modules are installed in data communication links serving field devices,

wiring shorted on the isolated side, annunciation of the fault confirmed, and then a device on the

source side operated, and activation confirmed at the control unit or transponder.

Each system abnormal condition specified in Table below was tested for each data communication

link at the

control unit or transponder.

Where a data communication link serves devices on more than one floor area, an imposed wire-to-

wire short circuit fault within each floor area results in the receipt of a trouble and alarm

condition from another floor area.

Each conductor in a data communication link, Class A (DCLA) tested for the capability of providing

an alarm signal on each side of a single open circuit fault condition.

Tests for alarm and trouble received under a single ground fault condition conducted on each

conductor of that data communication link independently.

SYSTEM STYLESYSTEM ABNORMAL CONDITION

Wire-to-Wire Short Circuit Fault T S

Single Open Circuit FaultSingle Ground Fault S

Class A Class RS

Nodes Page 12

Page 13: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

Annunciator or remote trouble signal unit location:

Annunciator or remote trouble signal unit identification:

A Yes No N/A

B Yes No N/A

C Yes No N/A

D Yes No N/A

E Yes No N/A

F Yes No N/A

G Yes No N/A

H Yes No N/A

I Yes No N/A

J Yes No N/A

K Yes No N/A

L Yes No N/A

M Yes No N/A

N Yes No N/A

Annunciator or sequential display location:

Annunciator or sequential display identification:

A Yes No N/A

Yes No N/A

Yes No N/A

Yes No N/A

C Yes No N/A

D Yes No N/A

E Yes No N/A

F Yes No N/A

G Yes No N/A

H Yes No N/A

I Yes No N/A

J Yes No N/A

K Yes No N/A

B

ANNUNCIATOR & REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION

Displays are visible in installed location.

Operates on emergency power.

Ancillary functions visual indicators operate.

Power 'ON' indicator operates.

Manual activation of alarm signal and indication operates.

NORTH ENTRANCE

Visual indicator test (lamp test) operates.

Input wiring from control unit or transponder is supervised.

Individual alarm and supervisory zone indication operates.

Exception: Operation of each individual alarm and supervisory zone indication gives the identical

indication, or lights the identical indicators at the other annunciator(s) and sequential display(s).

Specify Method of confirmation: ONE ALARM PER ZONE

Multi-line sequential display operates as per 'ANNUNCIATORS or SEQUENTIAL

DISPLAYS', where utilized.

Alarm signal silence visual indicator operates.

ANNUNCIATORS OR SEQUENTIAL DISPLAYS

Switches for ancillary functions operate as per design and specification.

Visual indicators comply with Table 3 - visual indicators colour code

MAIN ANNUNCIATOR

Individual alarm, and supervisory input zones clearly indicated and separately

designated.

Individual alarm, and supervisory input zone designation labels are properly identified.

Common trouble signal operates.

NORTH ENTRANCE

Displays are visible in installed location.

Common trouble signal operates.

Visual indicator test (lamp test) operates.

Input wiring from control unit or transponder is supervised.

Alarm signal silence visual indicator operates.

Individual alarm and supervisory zone designation labels are properly identified.

Minimum of one alarm zone and one supervisory zoned tested per annunciator or sequential

display to confirm operation.

Power 'ON' indicator operates.

Switches for ancillary functions operate as per design and specification.

Ancillary function visual indicators operate.

Manual activation of alarm signal and indication operates.

General Page 13

Page 14: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

Remote Trouble Signal Unit Location:

Remote Trouble Signal Unit Identification:

A Yes No N/A

B Yes No N/A

C Yes No N/A

D Yes No N/A

Printer Location:

Printer Identification:

A Yes No N/A

B Yes No N/A

C Yes No N/A

A Yes No N/A

B Yes No N/A

C Yes No N/A

D Yes No N/A

E Yes No N/A

F Yes No N/A

A

B

C

D

E Yes No N/A

F Yes No N/A

G Yes No N/A

H Yes No N/A

I Yes No N/A

J Yes No N/A

Replaceable over-current devices are of correct rating on circuits using fire alarm system power.

Wire type and gauge at all termination points is in accordance with equipment

manufacturer's installation wiring requirements.

An active field device or supporting device results in a trouble signal when the device is

removed from the circuit.Refer to Device Record pages

If using a field verifying device, upon completion of circuit testing, one field device (in each circuit

with contact devices) shall be tested for annunciation at the control unit.

Each Class A circuit, serving conventional field devices, have been tested for the capability of

providing an alarm signal on each side of an open circuit fault connection at an electrically

remote point in the circuit.

Correct field termination and wiring size

DOCUMENTATION

Each circuit has been tested at the electrically furthest field device for ground fault indication at

the control unit. This ground fault does not result in a normal to off-normal status change

indication on the circuit tested.

For circuits using fire alarm system power, tested the field device at the electrically furthest point

from the power source (in every circuit) receives rated operating power as per rated

characteristics in accordance with manufacturer's specification.

Correct circuit polarities Refer to Device Record pages

A conventional device tested and inspected for an open circuit fault results in a trouble signal Refer to Device Record pages

Refer to Device Record pages

FIELD DEVICE AND RELATED CIRCUITS - TEST AND INSPECTION

Description of the function of each operating control and indicator on the control unit

Instructions for silencing the trouble signal and action to be taken when the trouble

signals sound

Instruction for resetting the system and silencing alarm signals

Description of the area or fire zone protected by each detection circuit (ex: zone list or

plan drawing)

Description of alarm signal operation.

Description of ancillary equipment controlled by the fire alarm system

Rated voltage is present.

Operates as per design and specification.

Zone of each alarm initiating device is correctly printed.

Audible trouble signal operates.

Audible trouble signal silence operates.

Visual trouble signal operates.

Input wiring from control unit or transponder is supervised.

PRINTER TEST

REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION

General Page 14

Page 15: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

Yes No

Yes No

B Yes No N/A

C Yes No N/A

Yes No

Yes No

Yes No N/A

Yes No N/A

Yes No N/A

Yes No N/A

1 Yes No

2 Yes No

3 Yes No

4 Yes No

5 Yes No

DOOR HOLD OPEN DEVICES VIA RELAY IN PANEL - RELAY OPERATION ONLY -

-

-

-

F

Ancillary circuits operated within 10 seconds from the activation of an alarm contact

device.

Ancillary circuits operated within 30 seconds from a subsequent activation of an alarm

contact device.

ANCILLARY DEVICE CIRCUIT TEST

Record Specific Type of Ancillary Circuit Operation Confirmed

D

Required annunciation operated within 10 seconds from the activation of an alarm

contact device.-

Required annunciation operated within 10 seconds from a subsequent activation of an

alarm contact device.-

-

E

Required central alarm and control facility operated within 10 seconds from the

activation of an alarm contact device.

Required central alarm and control facility operated within 10 seconds from a

subsequent activation of an alarm contact device.

Audible signal devices and visual signal devices operate within 10 seconds from the

activation of an alarm contact device.-

Audible signal devices and visual signal devices operate within 10 seconds from a

subsequent activation of an alarm contact device.-

Releasing device start of sequence operate within 10 seconds from the activation of an

alarm contact device.

Remote connection (fire signal receiving centre) operate within 10 seconds from the

activation of an alarm contact device.

REQUIRED SYSTEM RESPONSE TIMES

A

General Page 15

Page 16: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

BATTERY SUMMARY

BUILDING NAME:DATE:

DGP/Transponder Location/No: Date / Date Code:

AC Breaker Location/No: Size:

0.40 AMPS 1.23 AMPS

Lead Acid

Gel Cell

Nickel Cad

DGP/Transponder Location/No: Date / Date Code:

AC Breaker Location/No: Size:

AMPS AMPS

Lead AcidGel Cell

Nickel Cad

DGP/Transponder Location/No: Date / Date Code:

AC Breaker Location/No: Size:

AMPS AMPS

Lead AcidGel Cell

Nickel Cad

DGP/Transponder Location/No: Date / Date Code:

AC Breaker Location/No: Size:

AMPS AMPS

Lead AcidGel Cell

Nickel Cad

DGP/Transponder Location/No: Date / Date Code:

AC Breaker Location/No: Size:

AMPS AMPS

Lead Acid

Gel Cell

Nickel Cad

Amp Hour

0.00 AH

AMPS

CHARGING CURRENT BATTERY TYPE

MIN. REQUIRED SIZEVDC

AC POWER OFF FULL LOAD TEST

LEFT

BATTERY

AC POWER ON

VDC

VDC

VDC

VDC

RIGHT

BATTERYVDC

BATTERY TYPE

RIGHT

BATTERYVDC

VDC

Amp Hour

BATTERY TYPE

Amp Hour

AC POWER ON AC POWER OFF FULL LOAD TEST

VDC VDCRIGHT

BATTERY

VDCLEFT

BATTERYVDC

MIN. REQUIRED SIZE

CHARGING CURRENT

AH

AC POWER OFF FULL LOAD TEST CHARGING CURRENT

VDC 0.00

VDCVDCMIN. REQUIRED SIZE

AMPS

12.98 12.45VDC

LEFT

BATTERY13.45 VDC

LEFT

BATTERYVDC

RIGHT

BATTERY13.45 VDC

AC POWER OFF FULL LOAD TEST

AC POWER ON

12.98 VDC 12.45 VDC

VDC

AMPS

September 8, 2016

12.06 AH

AMPS

12V18A

9/8/2016

MIN. REQUIRED SIZE

SOUTH MAIN ENTRANCE

OFFICE CLOSET BRKR#26

CHARGING CURRENT BATTERY TYPE

18.00

AC POWER ON

Amp Hour1.67

AHVDC VDC

AC POWER ON AC POWER OFF FULL LOAD TEST

LEFT

BATTERYVDC

LULLABOO CHILDCARE

MIN. REQUIRED SIZEVDC VDC

0.00

CHARGING CURRENT BATTERY TYPE

AH

AMPS Amp Hour

VDC 0.00RIGHT

BATTERYVDC VDC

Battery Summary Page 16

Page 17: Robinson Solutions Fire Alarm Inspection · 2019-05-03 · fire alarm system device record building name: lullaboo nursery and child care date: september 7, 2017 e pe on ber d d d

SIGNALLIING SOUND LEVEL MEASUREMENT

BUILDING NAME: LULLABOO CHILDCAREDATE: September 8, 2016

Location

Ambient

(dBA)

Alarm Signal

(dBA) Remarks

2ND FLOOR

2ND FL - CLASSROOM W.CNTR 43.5 72.6

2ND FL - CLASSROOM N.W 42.3 73.6

2ND FL - CLASSROOM S.W 42.3 74.7

2ND FL - CLASSROOM N.E 44.5 73.6

2ND FL - CLASSROOM S.E 43.5 72.6

2ND FL - CORRIDOR SOUTH 45.8 74.3

2ND FL - CORRIDOR CENTER 46.7 73.6

2ND FL - ELEVATOR LOBBY 45.8 74.7

2ND FL - CORRIDOR NORTH 46.7 74.3

1ST FLOOR

1ST FL - CORRIDOR SOUTH 45.8 74.7

1ST FL - CORRIDOR CENTER 46.7 74.7

1ST FL - ELEVATOR LOBBY 45.8 73.6

1ST FL - CORRIDOR NORTH 45.8 74.3

1ST FL - CLASSROOM S.W 43.5 72.6

1ST FL - CLASSROOM N.W 43.5 74.7

1ST FL - CLASSROOM N.W SLEEP AREA 44.5 73.6

1ST FL - CLASSROOM N.CNTR 42.3 74.3

1ST FL - CLASSROOM N.CNTR SLEEP AREA 43.5 72.6

1ST FL - CLASSROOM E.CNTR 42.3 74.7

1ST FL - CLASSROOM S.E 43.5 72.6

BASEMENT

BSMNT - CORRIDOR SOUTH 46.7 74.7

BSMNT - ELEVATOR LOBBY 45.8 73.6

BSMNT - CORRIDOR NORTH 46.7 74.7

BSMNT - MAIIN ELECTRICAL ROOM 44.5 74.3

BSMNT - CLASSROOM S.W 43.5 74.3

BSMNT - STAFF KITCHEN 42.3 73.6

BSMNT - STAFF MEETING ROOM 42.3 72.6

BSMNT - CLASSROOM N.E 43.5 72.6

BSMNT - CLASSROOM S.E 43.5 72.6

Sound Level Page 17