Upload
thilinanit
View
158
Download
11
Embed Size (px)
Citation preview
FIRE ALARM & BILDGE ALARM SYSTEM
1
EA IV TA SENEVIRATHNAAL 104219SRI LANKA NAVY
2
FIRE ALARM SYSTEMS
EA IV TA SENEVIRATHNA
3
WHY ARE FIRE DETECTION AND ALARM SYSTEMS REQUIRED?
Detect fire in the areas.Notify building occupants to take evasive action to escape the dangers of a
hostile fire.Summon organized assistance to initiate or assist in fire control activities. Initiate automatic fire control & suppression systems & to sound alarm.Supervise fire control & suppression systems to assure operational status is
maintained Initiate auxiliary functions involving environmental, utility & process controls
Systems may incorporate one or all of these functions
EA IV TA SENEVIRATHNA
BLOCK DIAGRAM OF SYSTEM
4EA IV TA SENEVIRATHNA
5
FIRE ALARM SYSTEM DIAGRAM
EA IV TA SENEVIRATHNA
6
FIRE ALARM PANEL
EA IV TA SENEVIRATHNA
7
HEAT DETECTORS
1. fixed temp type heat detector
2. rate-of-rise type heat detector
SMOKE DETECTORS
1. Photoelectric
2. Ionization
FLAME DETECTORS
1. Ultraviolet light (UV)
2. Infrared (IR)
FIRE-GAS DETECTORS
INPUT DEVICES
EA IV TA SENEVIRATHNA
8
INPUT DEVICES
Heat Detectors Smoke Detectors
EA IV TA SENEVIRATHNA
9EA IV TA SENEVIRATHNA
10
INPUT DEVICES
Manual call pointWhen shorted trips an alarm (usually fire) Installed in the normal exit path
Types of manual call pointsSingle Action
Pull handle onceBreak Glass
Glass rod or plate is broken
EA IV TA SENEVIRATHNA
11
TYPES OF MANUAL CALL POINTS
BREAK GLASS PULL HANDLE ONCE
EA IV TA SENEVIRATHNA
12
PHOTOELECTRIC SMOKE DETECTORUses a photocell coupled with a specific light source.Basically smoke entering the smoke detector chamber
disrupts the light beam causing an alarm signal to be initiated.More sensitive to smoldering fires
1: Optical Chamber2: Cover3: Case Moulding4: Photodiode (Detector)5: Infrared LED
EA IV TA SENEVIRATHNA
13
AUDIBLE OUTPUT DEVICES
An audible alarm signal lets people know the alarm system has
been activated
Devices may be mounted inside or outside based on level of
protection required
May consist of: Sirens
Bells
Buzzers
Horns
Voice Drivers EA IV TA SENEVIRATHNA
14
VISUAL OUTPUT DEVICES
A visual signal lets users know the status of the alarm system if
activated
Visual devices may be mounted inside or outside
May consist of...
Strobe lights
LED’s
EA IV TA SENEVIRATHNA
15
DETERMINING LAYOUT OF THE FIRE DETECTORS
• The design, construction and operational features of all types of detectors shall be in accordance with relevant standards.
• The number of fire detectors to be installed is governed by• total area to be protected• type of ship construction• air movement & air velocity• panelling obstructions• concentration of equipment in the area covered• sensitivity required
• Area is divided into zones to be protected• The zones of individual detectors should overlap and no blind
zone should be left.
EA IV TA SENEVIRATHNA
15
• Areas above false ceiling and below false flooring shall be considered as separate zones.
• Under ideal conditions of smooth ceiling and average room size, one detector is recommended to protect the area.
• Ionisation type detectors should be located where the largest combustible gas concentration can be expected.
• In the air conditioned areas both ionisation and optical type smoke detectors are used.
• Detectors must always installed at the highest point of the ceiling and minimum coverage indicated by manufacture shall be considered.
• The number of detectors and their location should be so selected that complete coverage is obtained
EA IV TA SENEVIRATHNA
17
BILDGE ALARM SYSTEMS
EA IV TA SENEVIRATHNA
18
WHY ARE BILDGE ALARM SYSTEMS REQUIRED?
Detect flooding situations in the areas.Summon organized assistance to initiate or assist in fire control
activities.Initiate automatic bildge control & suppression systems & to
sound alarm.Supervise bildge control & suppression systems to assure
operational status is maintained initiate auxiliary functions involving environmental, utility & process controls
Systems may incorporate one or all of these functions
EA IV TA SENEVIRATHNA
19
SIMPLE BLOCK DIAGRAM OF BILDGE ALARM SYSTEMS
EA IV TA SENEVIRATHNA
20
BILDGE ALARM PANEL
EA IV TA SENEVIRATHNA
21
BILDGE ALARM PANEL INPUT & OUTPUT TERMINALS
EA IV TA SENEVIRATHNA
22
INPUT DEVICES
FLOATER SWITCH
EA IV TA SENEVIRATHNA
23
AUDIBLE OUTPUT DEVICES
An audible alarm signal lets people know the bildge alarm system has been activated
Devices may be mounted inside or outside based on level of protection required
May consist of:SirensBells BuzzersHorns Voice Drivers
EA IV TA SENEVIRATHNA
24
VISUAL OUTPUT DEVICES
A visual signal lets users know the status of the alarm system if activated
Visual devices may be mounted inside or outsideMay consist of...
Strobe lightsLED’s
EA IV TA SENEVIRATHNA
25
QUESTIONS???
EA IV TA SENEVIRATHNA