42
Page 1 5/30/2013 RIVERSIDE CENTER CONSTRUCTION RULES & REGULATIONS

RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 1 5/30/2013

       

RIVERSIDE  CENTER       CONSTRUCTION     RULES  &  REGULATIONS    

 

 

 

 

 

 

 

 

 

 

 

   

Page 2: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 2 5/30/2013

This   document,   titled   “Riverside   Center   Construction   Rules   and   Regulations”   is  intended   to   protect   the   continuity   of   services   provided   to   the   occupants   of   these  facilities,  maintenance  of  building  standards  and  safety  of  all  those  affected  by  these  processes.   As   such,   strict   adherence   to   the   requirements   of   this   document   is   a  condition  of  Contractor’s  presence  while  performing  work  in  this  facility.    

RIVERSIDE  CENTER  

  CONSTRUCTION     RULES  &  REGULATIONS  

  TABLE  OF  CONTENTS  

I.   Introduction  to  Manual   4  

II.   Tenant  Design  and  Construction   5  

III.   Pre-­‐Construction  Planning   6  

IV.   Development  of  Tenant  Plans   8  

V.   Construction  Requirements   9  

VI.   Other  Items  for  Tenant's  Consideration   11  

VII.   Building  Information  

  A.   Glossary  of  Terms  and  Acronyms   13  

  B.   Minimum  Information  Requirements  for  Architectural/  Engineering  

15  

  C   Minimum  Requirements  for  Tenant  Plans   18  

  D.   Coordination  Drawings  for  Above-­‐Ceiling  Work    

  E.   Indoor  Air  Quality  Specifications   20  

  F.   Tenant  Extra  Improvements  Cost  Considerations   24  

  G.   Landlord  Review  Checklist   26  

 

   

 

   

Page 3: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 3 5/30/2013

APPENDIX  

 

Exhibit   Title   Page  

A   Indemnity  Agreement   33  

B   Insurance  Agreement     34  

C   Contractor  Pass  Application  Form     38  

D   Fire  Alarm  Test  Notification   39  

E   Indoor  Air  Quality  Compliance  Table   40  

F   Indoor  Air  Quality  Checklist       41  

G   Welding/Burning  Permit  Letter  from  Landlord   42  

     

Page 4: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 4 5/30/2013

RIVERSIDE  CENTER  

CONSTRUCTION  RULES  &  REGULATIONS    

I.    INTRODUCTION  TO  MANUAL  The  purpose  of   this  Manual   is   to  describe   the  process  and  considerations   involved   in  the   Landlord   Review   phase   of   a   tenant   construction   project,   including   each   party’s  responsibilities  associated  with  a  successful  project.  The  Landlord  Review  Checklist  (Section  G):  

• Provides   a   guide   for   those   responsible   ensuring   the   project   meets   Landlord  requirements.      

• Is  to  be  carefully  considered  prior  to  creation  of  construction  documents.  

• Addresses  architectural,  mechanical,  electrical,  and  plumbing  considerations.      

• Facilitates   fulfillment   of   specific   construction   requirements   such   as   proper  permits,  inspections,  approvals  and  insurance.  

Tenant  Extra  Improvements  Cost  Considerations  (Section  F):  

• Emphasizes   planning   by   the   Tenant   and   Tenant’s   consultants   potentially  resulting  in  project  cost  savings.      

• Landlord’s  Review  shall  include  a  list  of  items  and  their  potential  impact  on  the  design  and  construction  of  the  Tenant  Improvements.    

• These   considerations   may   affect   Tenant   expenses,   comfort   and   long-­‐term  enjoyment  of  the  space  as  well  as  affect  base  building  operating  expenses.  

The  Tenant  is  required  to  factor  into  the  improvement  design  and  execution  the  items  described  in  Section  VI,  "Other  Items  for  Tenant's  Consideration":  

• Comprehensive   design   phase   planning   and   coordination   minimizes   change  orders   during   construction   resulting   in   project   delays   and   increased   Tenant  Improvement  costs.    

Section   VI   describes   the   Tenant's   role   in   managing   the   work   associated   with   the  following  systems:  

  •   Telephone/Data  Communication  Equipment  

•   Furniture  Systems  

•   Security  Systems  

The  Tenant  and  Tenant’s  Architect  are  required  to:  

• Coordinate  all  Base  Building  modifications  with  the  Landlord.    

• Incorporate  all  modifications  into  “as  built”  building  plans  at  Tenant’s  expense.  

Page 5: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 5 5/30/2013

• Changes/modification   to   be   recorded   include   but   are   not   limited   to   Tenant  stairs,   slab   penetrations,   HVAC,   Electrical,   plumbing,   architectural,   structural,  etc.  

The  Lease  requires  that  the  Landlord  may  be  obligated  to  perform  certain  services  for  the   Tenant   as   part   of   the   Tenant   Design   and   Construction   Process.     This   manual   is  intended  to  address  Landlord’s  obligations  associated  with  Landlord  Review.      Capitalized  terms  used  herein  are  defined  in  the  Glossary  of  Terms,  (Section  A).  

 

II.  TENANT  DESIGN  AND  CONSTRUCTION  The  primary  elements  of  the  design  and  construction  process  are  as  follows:  

1.   Tenant  Construction  Documents  (CDs)  

A. Tenant  will  engage  the  services  of  an  architectural   firm  licensed  to  do  business   in  the   City   of   Newton   ("Tenant's   Architect")   and   an   engineering   firm   ("Tenant's  Engineer")   to   complete   the   architectural   and   engineering   working   drawings   and  specifications   for   the   Tenant   Improvements   ("Tenant   CDs").   During   the   design  phase,   all   information   required   to   insure   proper   design   and   compliance   with  requirements   of   this   document   are   to   be   field   verified   by   the   design   architect,  engineer   or   approved   tenant   representative.   The   Tenant   CDs   will   include   all  information   necessary   to   construct   the   Tenant   Improvements   and   obtain   all  necessary  building  and  occupancy  permits  in  City  of  Newton.    The  Tenant  CDs  will  be  submitted   to   the  Landlord   for  Landlord's   review  and  comments  as  set   forth   in  Tenant's  Lease  prior  to  pricing  and  construction.  

2. Landlord’s  Review  

Landlord  will  review  the  plans  submitted  by  the  Tenant  and  provide  comments  and  recommendations   to   the   Tenant.     Landlord's   review   includes   managing   the  compatibility   of   Tenant's   design   with   the   Base   Building   systems   and   assisting  Tenant  in  providing  information  to  the  contractors  who  will  price  the  documents  so  that  costs  are  minimized  and  maximum  value  obtained.  Landlord’s  Review  of  these  plans  may   include,   at   Landlord’s   option   and   Tenant’s   expense,   contracted   review  services  by  Landlord’s  Architect  and/or  Landlord’s  Engineer.  Refer  to  the  Landlord  Review  Checklist,  (Section  G)  as  a  guide  for  the  review  process  to  ensure  that  all  potential  considerations  are  thoroughly  addressed.  

Tenant  CDs  must  not  be  changed  following  review  and  comment  without  Tenant's  and  Landlord’s  review  and  issuance  of  corresponding  change  orders.  

Landlords  review  and  comment  shall  not  constitute  approval  of  any  sort.  3.   Construction  Schedule  

Tenant,   Tenant’s   Architect,   and   Contractor   will   develop   a   construction   schedule  identifying   each   phase   of   construction   to   allow   for   effective   planning   and  coordination.     This   schedule   must   be   delivered   to   Landlord   to   allow   effective  

Page 6: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 6 5/30/2013

planning   and   monitoring   of   construction   activities.     Work   potentially   impacting  building  services  or  other  tenants  must  be  properly  coordinated  with  Landlord.  

4. Contractor  

Tenant   must   submit   selected   Contractor   qualifications,   references,   necessary  certificates  and  insurance  requirements  to  Landlord  for  review  and  acceptance.    The  Tenant  and  Contractor  shall  acknowledge  that  they  have  read  and  shall  comply  with  the  Rules  of  Site  (Section  H),  prior  to  commencement  of  work.  

5. Construction  

Upon   Landlord’s   review   of   the   Tenant’s   Contractor,   CDs,   Construction   Schedule,  Contractor’s   acceptance   of   the   Rules   of   the   Site   and   delivery   of   the   appropriate  building   permits   and   insurance   certificates,   the   Contractor   will   be   authorized   by  Tenant  to  commence  construction  of  the  Tenant  Improvements  in  accordance  with  the  Tenant  Plans.  The  Contractor  will  be  responsible  for  following  the  punchlist  and  project   close-­‐out   requirements   (Section   V).     Tenant   or   Contractor   may   request  coordination   services  of   the  Landlord   for   certain   construction   activities   occurring  during   normal   or   after   working   hours.   Expenses   associated   with   Landlord’s  coordination  may  be  billed  back  to  the  Tenant.  

 III.  PRE-­‐CONSTRUCTION  PLANNING  

1.   Introductory  Meeting  This  meeting  with  the  Tenant,  Tenant's  Architect,  and  the  Landlord  should  be  held  to  discuss  procedural  issues  and  general  circumstances  important  to  the  design  and  construction  process.  Based  on  critical  dates,  a  design  and  construction  schedule  for  the  Tenant   Improvements  will   be  proposed  by   the  Tenant   and  Tenant’s  Architect  outlining  completion  dates  for  the  major  phases  of  construction  in  order  to  ensure  timely  completion  of  the  project.    

The  Base  Building  systems  are  designed  to  meet  certain  criteria  which  the  Tenant's  Architect  and  Tenant's  Engineer  will  be  expected  to  adhere  to  in  their  design  for  the  Tenant   Improvements.     The  Landlord  will   distribute,   as   required   and   if   available,  Base  Building  drawings  necessary  for  the  Tenant's  Architect  and  Tenant's  Engineer  to   prepare   the   Tenant   Plans.     More   detailed   information   can   be   obtained   by  reviewing   the   complete   Base   Building   Plans   &   Specifications   available   from   the  Landlord.      At   the   meeting,   the   Landlord   should   provide   the   following   full-­‐size   sets   of   Base  Building  plans  of  the  construction  area  to  the  Tenant:  

a) Floor  Plan  (Tenant  floors)  b) Reflected  Ceiling  Plan  

c) Base  Building  Mechanical,  Electrical,  and  Plumbing  Plans  d) Structural  Plans  and  Loading  Drawing  

Page 7: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 7 5/30/2013

Landlord  recommends  that  Tenant’s  Architect  use  this  information  to  produce  their  own  base  sheets,  thereby  minimizing  inaccuracies  caused  by  repeated  reproduction  of  the  Base  Building  plans.  

2.   Tenant's  Budget  In   accordance   with   budget   guidelines   supplied   by   Tenant,   it   is   typically   the  responsibility  of  Tenant's  Architect  to  prepare,   for  Tenant's  review,  an  estimate  of  the  costs  associated  with  the  design  and  construction  of  the  Tenant  Improvements  ("Tenant's  Budget").    Landlord  strongly  advises  the  Tenant  to  confirm  that  Tenant's  Architect   has   an   accurate   understanding   of   the   provisions   set   forth   in   Tenant's  Lease  regarding  use  of  Building  Standard  Tenant  Improvements,   if  applicable,  and  their   potential   impact   on   the   pricing   of   Tenant   Plans.     Misrepresentations   often  occur  in  Tenant's  Budget  based  on  incorrect  assumptions  regarding  the  intent  of  the  Lease.  

3.   Tenant  Space  Plan  

Landlord  recommends  that  a  Tenant  Space  Plan  be  developed  in  such  a  manner  so  as   to   convey   all   information   necessary   for   Tenant   to   approve   the   layout   and   to  establish  the  scope  of  the  proposed  Tenant  Improvements.      

It   is   the   Landlord's   experience   that   substantial   savings   can   be   realized   through  careful  consideration  by  Tenant  and  Tenant's  Architect  of  the  information  set  forth  under  Section  F,  "Tenant  Extra  Improvements  Cost  Considerations".  Tenant   and   Tenant's   Architect   are   advised   to   consult   with   Landlord   when  developing  the  space  plan  to  coordinate  tenant  engineering  requirements  with  the  Base  Building,  and  to  address  any  potential  conflicts  as  early  in  the  design  process  as  possible.  

4.   Interim  Tenant  Space  Plan  Review  An   interim   review   of   the   Tenant   Space   Plan   will   be   performed   by   Landlord,   at  Tenant's   request,   to   assist   Tenant   with   the   compatibility   of   the   Tenant  Improvements  with  the  Base  Building  design  parameters.  

5.   Rules  of  the  Site  

The  Landlord  will  provide   the  Architect  a  copy  of   the  Rules  of   the  Site  during   the  Introductory   Meeting.     The   Landlord   requests   that   the   Architect   refer   to   the  obligations  of  the  Rules  of  the  Site  in  the  notes  section  of  the  Tenant  Plans,  and  also  state   that   the   Contractor   will   be   required   to   sign   the   Rules   of   the   Site   prior   to  commencement  of  any  work.    During  the  bidding  process,  this  will  inform  potential  Contractors   of   all   procedures   and   obligations   associated   with   working   in   the  building.    The  Tenant  will  also  be  required  to  sign  the  Rules  of  the  Site,  as  well  as  any  other  contractors  not  working  as  a  subcontractor  for  the  Contractor.  

     

Page 8: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 8 5/30/2013

IV.  DEVELOPMENT  OF  TENANT  PLANS  

1.   Engineering  Information  Package  Following  approval  of   the  Tenant  Space  Plan  by   the  Tenant,  but  prior   to  Tenant’s  submission   of   plans   for   Landlord   Review,   Tenant's   Architect   should   complete   a  package  of  engineering-­‐related  information  for  purposes  of  coordinating  the  Tenant  Improvements  with  the  Base  Building  systems  and  for  use  by  Tenant's  Engineer  in  preparing  engineering  working  drawings.    An  outline  of  the  minimum  information  normally   required   by   Tenant's   Engineer   is   attached   as   Section   B,   "Minimum  Requirements   for   Engineering   Information   Package”.     If   required,   additional  information  will  be  requested  of  the  Tenant,  Tenant's  Architect,  or  Landlord.  

2.   Architectural  and  Engineering  Working  Drawings  

Based  on  the  approved  Tenant  Space  Plan,  Tenant's  Architect  and  Tenant's  Engineer  will  proceed  to  complete  the  Tenant  Plans  which  consist  of  a  complete  package  of  architectural   and   engineering   drawings,   specifications,   and   other   information  necessary   to   review   the   Tenant   Improvements   and   to   obtain   all   the   necessary  building  permits.  

It   is   the   responsibility   of   Tenant's   Architect   to   coordinate   all   information   in   the  Tenant  Plans  for  both  accuracy  and  completeness.     Incomplete  documents  that  do  not  include  all  of  the  details  needed  to  complete  Tenant’s  design  intent  may  result  in  additional   costs   to   Tenant.     Tenant’s   Architect   should   include,   at   a  minimum,   the  information   outlined   in   Section   C   of   this   document   pertaining   to   the   “Minimum  Requirements   for  Tenant  Plans”.     In   addition,  Tenant’s  Architect   should   include   a  note  in  the  Tenant  Plans  that  specifically  requires  the  Contractor  to  strictly  adhere  to  the  Rules  of  the  Site  established  for  the  building.    The  Tenant’s  Architect  shall  also  include   a   note   to   require   the   coordination   of   the   documentation   provided   by  Tenant's  Engineer  and  any  other  outside  consultants  who  are  under  direct  contract  to   Tenant,   Tenant's   Architect,   or   Landlord,   and   coordinate   with   all   architectural,  structural,  mechanical,  electrical,  and  plumbing  aspects  of  the  Base  Building.  It  is  the  further  responsibility  of  Tenant's  Architect  to  ensure  that  the  Tenant  Plans  are  in  compliance  with  all  governing  codes  and  life  safety  regulations.  

Tenant  and  Tenant's  Architect  must  carefully  coordinate  the  Tenant  Plans  with  the  Base   Building   plans   and   any   existing   conditions,   and   to   identify   and   resolve  potential  ceiling  plenum  or  partition  and  lighting  layout  conflicts  before  they  arise  during   construction.     Landlord   strongly   recommends   that,   in   response   to   typical  characteristics  of  "flat  slab"  construction,  Tenant's  Architect  and  Tenant's  Engineer  make  allowances   to   include  one   inch  (1")  potential  slab  deflection   in  all  areas.     In  order   to   accommodate   Tenant   Improvements   which   require   more   critical   floor  tolerances,  and  to  minimize  potential  additional  costs  of  the  Tenant  Improvements  resulting  from  slab  deflection,  Tenant's  Architect  should  specify  that  any  millwork  items   (i.e.   secretarial   stations,   wall   base)   and   such   other   items   of   Tenant  Improvements  or  furniture  requiring  a  level  floor  be  fabricated  such  that  they  can  be  scribed  a  minimum  of  one-­‐inch  (1").  

Page 9: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 9 5/30/2013

It  is  extremely  important  for  the  Tenant's  Architect  and  Tenant's  Engineer  to  review  existing  field  conditions  as  well  as  the  Base  Building  plans  and  specifications  so  that  any  potential  conflicts  can  be  avoided.    Slab  penetration  location  and  sizes,  column  locations  and  sizes,  and  existing  MEP  systems  are  a  critical  part  of  that  review.  

  For   coordination   and   review   purposes,   Landlord   recommends   that   Tenant's  Architect   and   Tenant's   Engineer   exchange   "in-­‐progress"   working   drawings   when  they  are  30%,  60%,  and  90%  complete.  To  ensure  that  adequate  coordination  of  above-­‐ceiling  work  is  implemented  during  construction,   specification   information   requiring   that   the   Contractor   prepare   and  submit   ¼-­‐inch   “Scale   Coordination   Drawings"   for   above-­‐ceiling   work   should   be  included  in  both  the  architectural  and  engineering  portions  of  the  Tenant  Plans.    It  should   be   strongly   recommended   that   the   language   in   Section   D   "Coordination  Drawings  for  Above-­‐Ceiling  Work"  be  utilized  for  this  purpose.  

3.   Mechanical,  Electrical,  and  Plumbing  Specifications  

The   Base   Building   plans   and   specifications  must   be   included   by   reference   in   the  Tenant   Plans.     Tenant's   Architect   and   Tenant's   Engineer   should   carefully   review  these   plans   and   specifications   prior   to   beginning   the   Tenant   Plans   in   order   to  ensure   that   the  Tenant   Improvements   are   fully   integrated  with   the   base   building  systems.     A   copy   of   these   documents  will   also   be   available   to   any   contractor   for  review   as   part   of   the   pricing   process.   Landlord   should   strongly   encourage   the  Tenant’s  Architect  and  Tenant’s  Engineer  to  field  verify  existing  conditions  that  are  represented  in  the  Base  Building  plans  to  ensure  that  conflicts  are  avoided.  

4.   General  Conditions  The   General   Conditions   noted   on   the   Base   Building   plans   will   also   apply   to   the  construction   of   the   Tenant   Improvements.     The   Tenant's   Architect   and   Tenant's  Engineer  should  carefully  review  these  General  Conditions  to  verify  that  no  conflict  exists   between   these   documents   and   requirements   included   in   the   Tenant   Plans.    The   Tenant   will   be   responsible   for   any   additional   costs   related   to   its   additional  requirements.  

5.   Landlord  Review  

Upon  completion,  approval,  and  release  by  Tenant,  copies  of  the  Tenant  Plans  will  be   submitted   to   the   Landlord   for   review   and   comment.     In   accordance   with   the  terms  of  Tenant's  Lease,  Tenant  must  secure  written  Landlord  permission  prior  to  commencing  construction.  

 

V.    CONSTRUCTION  REQUIREMENTS  1. Contractor  Approval  

Landlord   requests   the   following   as   part   of   the   review   process   for   the   proposed  Contractor:  

  -­‐  References  for  similar  commercial  projects  

Page 10: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 10 5/30/2013

    -­‐  Insurance  certificate  in  accordance  with  Attachment  A  of  the  Rules  of  the  Site  

    -­‐  Signed  Rules  of  the  Site  Construction  should  not  be  allowed  to  commence  until  the  Contractor  has  provided  the  above  and  has  been  approved  by  the  Landlord.  

2.   Construction  Administration  

As   discussed   previously,   a   construction   schedule   is   required   by   the   Landlord   to  allow  for  effective  monitoring  of  construction  activities.    For  coordination  purposes,  Landlord  agrees  to  participate  in  progress  meetings  if  requested  by  the  Tenant.  

3.   Record  Drawings  

Throughout   the   construction   process,   Tenant's   Architect   and   Tenant's   Engineer  should   be   responsible   for   maintaining   a   record   set   of   drawings   (“as-­‐builts”)  incorporating  all  changes,  as  they  occur,  into  the  original  Tenant  Plans  and  will  be  responsible  for  submitting  copies  of  these  drawings  and  updated  CAD  disk(s)  to  the  Landlord  at  the  end  of  construction.  

4.   LEED  Requirements    Building   management   requires   a   minimum   of   75%   of   the   demolition   debris   be  diverted   from   landfills.    Please  provide   adequate  documentation   as   proof   of   this  diversion  that  would  meet  LEED  requirements.  Water   consumption   requirements   for   all   new   plumbing   fixtures   must   be   in  compliance  with  the  most  current  UPC/IPC  codes.      

5.   Field  Observation  

Tenant's   Architect   and   Tenant's   Engineer   should   be   conducting   periodic   field  inspections   of   the   construction   in   accordance   with   Tenant's   contracts   with   such  consultants.     In  addition,  Landlord  will  also   tour   the   job  site  on  a   regular  basis   to  ensure   that   the   Contractor   is   not   deviating   from   the   Tenant   Plans,   with   specific  focus  on  work  related  to  base  building  systems.    

The   following   requirements   are   associated  with   the   close-­‐out   of   the   construction  project:  

6.   Engineering  Field  Reports  

Prior   to   ceiling   close-­‐in   and   again   at   Substantial   Completion   of   the   Tenant  Improvements   (which   will   be   documented   by   the   Architectural   Punchlist),   but  following   the   completion   of   the   mechanical,   electrical,   and   plumbing   work,  punchlists   will   be   developed   from   Landlord’s   visual   inspection   and   from   field  observations   by   the  Tenant's   Engineer   documenting   unsatisfactory   or   incomplete  mechanical,   electrical,   and   plumbing   items,   or   work   not   in   accordance   with   the  Tenant   Plans.     These   lists   are   known   as   Engineering   Field   Reports.     Subsequent  reviews   by   the   Tenant's   Engineer   for   corrective   work   verification   will   be  documented   in   this  Engineering  Field  Report   format,  until  satisfactory  completion  has   been   achieved   by   the   Contractor.     All   Engineering   Field   Reports   must   be  submitted  to  Landlord  for  review.  

Page 11: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 11 5/30/2013

7.   Architectural  Punchlist  

Upon   Substantial   Completion   of   construction,   and   prior   to   Tenant's   occupancy,   a  single   list   of   unsatisfactory   or   incomplete   architectural   items,   or   work   not   in  accordance   with   the   Tenant   Plans,   should   be   prepared   jointly   by   Tenant   and  Tenant's  Architect.    Landlord  should  receive  a  copy  of  this  punchlist  for  review.  

8.   Air  Balance  Report  

The  requirement  for  a  certified  air  balance  report  must  be  specified  in  the  Tenant  Plans.     This   document   will   be   generated   by   a   Landlord-­‐approved   air   balancing  subcontractor  hired  by  the  Tenant  or  Contractor,  and  certified  by  three  parties:  the  air  balance  subcontractor  performing  the  work,  the  mechanical  subcontractor,  and  the   Contractor.     Final   review   for   compliance  with   the   original  mechanical   design  criteria  for  the  Project  and  the  Tenant  Plans  will  be  by  the  Tenant's  Engineer.    The  Landlord  requires  a  copy  of  this  report.  

9.   Operating  and  Maintenance  Manuals  

The   requirement   for   submission   of   operating   and   maintenance   manuals   for  mechanical  and  electrical  equipment  installed  in  accordance  with  the  Tenant  Plans  and   which   may   or   may   not   be   maintained   by   Property   Management   (i.e.  supplemental  HVAC  equipment,  pantry  equipment,  or  electrical  upgrades),  must  be  specified   in   the   Tenant   Plans.     Prior   to   submission   to   the   Landlord,   the  manuals  must  be  reviewed  and  accepted  by  the  Tenant's  Engineer   for  compliance  with  the  Tenant  Plans.  

10.  As-­‐Built  Drawings  

As-­‐built  drawings  or  updated  CAD  plans  must  be  delivered  to  Landlord  at  the  end  of   construction.     The   requirement   for   one   stamped   as-­‐built   drawing   for   each  portion  of  the  work  (architectural,  mechanical,  electrical,  plumbing,  and  sprinkler)  must  be  specified   in   the  Tenant  Plans.    A  CAD  drawing  of  each  drawing  must  be  stamped  by  the  appropriate  subcontractor  and  the  Contractor  to  certify  accuracy.    All  as-­‐built  MEP  drawings  must  be  reviewed  by  the  Tenant's  Engineer  for  design  compliance.    As  part  of  the  electrical  as-­‐built  requirement,  a  panel  directory  must  be  prepared  indicating  all  circuit  numbers  and  the  item(s)  being  served.  

 

VI.  OTHER  ITEMS  FOR  TENANT'S  CONSIDERATION  

The   following   is  a   list  of  other   items  pertaining   to   the  design  and  construction  of   the  space.  1.   Tenant  Direct  Contracts  

Please  be  aware   that   items  such  as   communication  equipment,   furniture   systems,  and   security   devices   are   typically   supplied   and   installed   by   Tenant's   vendors  independently  of  the  Tenant  Improvements  installed  by  the  Contractor.    Scheduling  information   pertaining   to   these   vendors   must   be   provided   to   Landlord   for  coordination   purposes.     Tenant's   contractor(s)   will   be   responsible   for   complying  

Page 12: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 12 5/30/2013

with   the   Landlord's   Rules   of   the   Site   and   Insurance   Requirements,   attached   as  Section  H.  

2.   Telephone/Data  Communications  Systems  

Given  the  numerous  sophisticated  telecommunications  alternatives  from  which  the  Tenant   may   choose,   Tenant's   selection   of   data   and   telephone   systems   can   be  extremely   time   consuming.     The   selection   of   telephone   and  data   communications  equipment   may   impact   the   design   of   the   Tenant   Improvements   in   terms   of  allocation  of  space  for  that  equipment  and  corresponding  mechanical,  electrical,  and  structural   considerations.     Tenant   should   begin   its   analysis   and   selection   process  very  early  in  the  design  phase  so  that  special  requirements  can  be  incorporated  in  the  Tenant   Space  Plan   and  Tenant   Plans.     All   of   the  Tenant's   equipment  must   be  located  within  the  Leased  Premises,  and  not  in  the  Base  Building  telephone  closets.  Tenant  shall  be  solely  responsible  for  the  delivery  and  installation  of  all  telephone  or  data  communications  systems,  and  shall  bear  all  scheduling  risk  associated  with  this  work.  

3.   Permit  Process  

Adequate  time  should  be  allowed  in  the  schedule  for  the  permit  process.    Landlord  has  no  obligation   in   this  process,   except   to   ensure   that   a  proper  permit  has  been  obtained  prior  to  the  commencement  of  any  work.  

4.   Keying  Schedule  The   schedule   of   all   keying   requirements   should   be   submitted   to   the   Landlord   in  order   to   ensure   compatibility   with   the   base   building   keying   system.     This  information  should  be  conveyed  in  the  Tenant  Plans.  

5.   Move-­‐In  

The   establishment   of  move-­‐in   date(s)   and   access   to   the   loading   dock   and   freight  elevator  must  be   coordinated  with   the  Landlord,   in   advance  of  Tenant's   intended  move-­‐in  date(s).    Tenant  and  all  subcontractors  or  vendors  are  required  to  comply  with  the  Rules  of  the  Site  during  the  move-­‐in  phase.      

6. Incidental  Costs  

a. Overtime   air   conditioning   may   be   required   to   facilitate   the   installation   of  millwork  

 

   

   

Page 13: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 13 5/30/2013

SECTION  A  

GLOSSARY  OF  TERMS  AND  ACRONYMS  Architectural   Punchlist   is   a   document   prepared   at   Substantial   Completion   by   the  Tenant's  Architect,  in  conjunction  with  Tenant,  Contractor,  and  Construction  Manager,  and  shall  consist  of  a  list  of  unsatisfactory,  incomplete,  or  any  unacceptable  work  which  is  not  in  accordance  with  the  Tenant  Plans.  

Base  Building   refers   to   the   infrastructure   of   the   entire   building   as   described  by   the  Plans   and   Specifications   including   but   not   limited   to:   the   building   exterior;   concrete  structure;   electrical,   plumbing,   heating,   ventilation,   and   air   conditioning   systems;   the  fire  protection/sprinkler  system;  and  life  safety  systems.  Building   Engineer   refers   to   the   representative(s)   of   Hines   Interests   Limited  Partnership  responsible   for   the  engineering   functions  of   the  building  and  mechanical,  electrical,  and  plumbing  review  of  the  Tenant  Improvements.  

Building   Standard   Improvements   are   those   Tenant   Improvements   delineated   in  Section  E,  "Building  Standard  Tenant  Improvements”.  Construction   Manager   refers   to   the   representative   of   the   Tenant   responsible   for  assistance   with   the   coordination   of   the   design,   administration   of   the   contractor   bid  process,  and  administration  of  the  construction  contract  for  the  Tenant  Improvements.  Contractor   is   the   construction   firm   engaged   by   the   Tenant   to   construct   the   Tenant  Improvements.  Engineering  Field  Report  is  prepared  by  Tenant's  Engineer  and  shall  consist  of  a  list  of  unsatisfactory  or  incomplete  mechanical,  electrical,  or  plumbing  items  which  are  not  in  accordance  with  the  Tenant  Plans.  Landlord  refers  to  the  Building  Owner  as  represented  by  Hines.  

Landlord's  Architect   is   the  architectural   firm(s)  retained  by  Landlord,   if  required,   to  perform   architectural   review   services   of   the   Tenant   Plans.     These   services   would  include  a   review  of   the  space  design  and  material   finishes   to  ensure   that  a   first-­‐class  appearance  of  the  premises  is  maintained  and  that  the  space  does  not  detract  from  the  general  architectural  concepts  for  the  building.  

Landlord's   Engineer   is   the   engineering   firm(s)   retained  by   Landlord,   if   required,   to  perform   mechanical,   electrical,   and   plumbing   review   services   (Landlord's  Mechanical/Electrical/Plumbing   Engineer)   or   structural   review   services   (Landlord's  Structural  Engineer)  of  the  Base  Building.  Landlord   Review   is   the   process   by   which   the   Landlord   reviews   the   Tenant   Plans  submitted   by   Tenant   and   the   Tenant’s   Architect  with   the   intent   to   identify   required  modifications  to  the  plans,  make  recommendations  that  could  potentially  result  in  cost  savings   or   enhanced   space   efficiency,   and   to   confirm   the   compatibility   of   Tenant’s  design  with  the  Base  Building.    The  Landlord  will  ultimately  provide  authorization  for  the   work   to   commence   following   review   of   tenant   construction   documents.     Upon  commencement  of  the  work,  the  Landlord  will  assist  in  the  coordination  of  construction  

Page 14: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 14 5/30/2013

related  activities  that  affect  base  building  operations  or  other  Tenants  in  the  building,  and   also   participate   in   meetings   or   discussions,   as   required,   to   help   facilitate   the  construction  process.  

Property  Manager  refers   to   the   representative  of  Hines   responsible   for   the  building  management.  

Tenant   refers   to   the  party  defined   in   the  Lease  as   the  Tenant  or  Tenant's  authorized  representative   for   matters   pertaining   to   the   design   and   construction   of   the   Tenant  Improvements.  

Tenant's  Architect   is   the   interior  design  or   architectural   firm   retained  by  Tenant   to  design  the  Tenant  Improvements,  prepare  the  architectural  portion  of  the  Tenant  Plans,  and  coordinate  the  architectural  with  the  engineering  or  other  consultants'  documents.  

Tenant's   Engineer   is   the   firm(s)   retained   by   Tenant   to   design   the   mechanical,  electrical,   plumbing,   and/or   structural   portions   of   the   Tenant   Improvements,   and   to  prepare  Tenant  Plans  for  this  work.  

Tenant   Extra   Improvements   are   Improvements   which   exceed   Building   Standard  Improvements  (if  any)  as  defined  in  the  Lease.  

Tenant  Improvements  are  the  Building  Standard  Improvements  (if  any)  and  Tenant  Extra  Improvements  to  be  constructed  within  the  Leased  Premises.  Tenant   Plans   are   the   detailed   drawings   and   specifications   produced   by   Tenant's  Architect   and   Tenant's   Engineer(s)   which   are   necessary   to   price   and   construct   the  Tenant  Improvements  and  to  obtain  the  necessary  building  and  occupancy  permits.  

Tenant  Space  Plan   is   the  document  prepared  by  Tenant's  Architect  representing  the  scope  of  the  Tenant  Improvements,  and  should  contain,  at  a  minimum,  the  information  required  by  the  Tenant  to  approve  the  layout  and  authorize  preparation  of  the  Tenant  Plans.  Abbreviated  Terms    

AHU:  Air  Handler  Unit  

BMS:  Building  Management  System  BTU:  British  Thermal  Unit  

CAV:    Constant  Air  Volume  

CDW:  Condenser  Water  CFM:  Cubic  Feet  Per  Minute  

CHW:  Chilled  Water  FAS:  Fire  Alarm  System  

FPTU:  Fan  Powered  Terminal  Units  

HVAC:  Heating,  Ventilation  &  Air  Conditioning  MSDS:  Material  Safety  Data  Sheet  

OSHA:  Occupational  Safety  &  Health  Administration  PMG:  Hines  Interests  Property  Management  TSAC:  Tenant  Supplemental  Air  Conditioning  

VAV:  Variable  Air  Volume  

 

Page 15: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 15 5/30/2013

SECTION  B  

MINIMUM  INFORMATION  REQUIREMENTS  FOR  ARCHITECTURAL  AND    ENGINEERING  PLANS  AND  SPECS  

The  following  information  should  be  clearly  identified  in  the  Tenant  Plans  submitted  to  the  Landlord.  

A.   Architectural  Information  

  1.   Location  and  type  of  all  partitions.     2.   Room  numbers  for  each  area.  

  3.   Location,  height,  and  swing  of  all  doors.     4.   Ceiling  heights  or  the  location  and  extent  of  drywall  ceiling  (if  any).  

  5.   Special  alignment  of   fixtures  with  diffusers,   if   required.    Specific   location  of  downlights  in  the  ceiling.  

  6.   Architectural   or   structural   elements   to   be   located   above   the   ceiling   (i.e.  recessed  projection  screens,  overhead  security  grills,  structural  supports  for  special  architectural  details,  or  items  of  a  similar  nature).  

  7.   CAD  disk  or  wash-­‐off  Mylars  showing  final  layout  of  Tenant  space.    Quantity  and  type  of  base  sheets  will  be  determined  by  Tenant's  Engineer.  

B.   Electrical  and  Telephone  Information  

  1.   Location  of  wall-­‐mounted  electrical   and   telephone  outlets.    No  electrical   or  telephone/data  outlets  may  be  located  along  the  exterior  wall  of  the  building.  

  2.   Floor-­‐mounted   electrical   and   telephone   outlets.     Dimensions   must   be  coordinated   with   the   building   structural,   HVAC,   sprinkler,   and   electrical  systems.    Note:    If  applicable,  Landlord’s  structural  engineer  must  review  and  approve,  at  Tenant’s  expense,  core  drill  locations.  Landlord  must  be  notified  of   any   core   drilling   requirements   prior   to  work.     Landlord  may   require   X-­‐rays  of  slab  at  Tenant’s  expense  prior  to  drilling.  

  3.   Location,  power  requirements,  and  specifications  for  special  receptacles  and  separate   circuits.     Provide   manufacturers'   specifications   for   all   special  equipment   including   appliances,   copiers,   computer   equipment,   and   word  processing  equipment.  

  4.   Description   of   the   space   requirements   and   electrical   and   mechanical  requirements   (i.e.   heat   rejection,   temperature,   hours   of   operation)   for   all  telephone   or   computer   equipment   within   the   Leased   Premises.       Note:   All  telephone   and   security   equipment   shall   be   located   within   the   Leased  Premises.  

  5.   Indicate   the   requirement   for   any   emergency  disconnect   switches   or   power  for  any  data  processing  equipment.  

    6.   Electrical  load  calculations  to  Landlord  prior  to  Construction.  

Page 16: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 16 5/30/2013

7. All  new  telephone  services  shall  be  properly  routed,  supported  and  identified.  

C.   Lighting  Information     1.   Locate   and   identify   fixtures   and   provide   specifications   for   all   fixtures.   The  

locations  of  fixtures  must  be  coordinated  with  the  building  structural,  HVAC,  sprinkler,   and   electrical   systems.   This   coordination   is   the   responsibility   of  the  Tenant's  Architect.  

  2.   Indicate  any  special  foot  candle  requirements.     3.   Locate  and  zone  all  switches,  dimmers,  and  other  lighting  control  devices.  

4.   Indicate  the  location  of  all  exit  lights  and  all  emergency  lighting  as  required  by  applicable  codes.  

  5.   Indicate   locations  of  occupancy  sensors.  Note:  Occupancy  sensors  are   to  be  used   throughout   the   premises.   Architect   to   coordinate   location   with  furniture  layout.  

D.   Mechanical  Information  

1. Kitchenette  Special  HVAC  Requirements  In  order  to  provide  acceptable  indoor  air  quality  to  occupants,  new  tenant  fit  outs  must   include  exhaust  air  connected  to  the  toilet  exhaust  riser  or  other  exhaust  vent  exiting  the  building  for  kitchens,  kitchenettes,  and  printing  area  per  ASHRAE  62.1-­‐2007.    A  kitchen  is  defined  as  a  space  for  cooking,  storing,  and   heating   food   that   includes   an   oven   or   stove,   microwave,   and  refrigerator.     A   kitchenette   is   defined   as   a   space   for   cooking,   storing,   and  heating   food   that   includes   a   refrigerator   and   one   food-­‐heating   or  warming  device  (toaster,  microwave,  etc.).    Building  Management  reserves  the  right  to  mandate  or  delete  exhaust  over  special  equipment  if  they  believe  indoor  air  quality   may   be   adversely   affected   or   meets   the   general   intent   of   the  requirements  listed  above.  

2. Printing  Area  Special  HVAC  Requirements  

In  order  to  provide  acceptable  indoor  air  quality  to  occupants,  new  tenant  fit  outs  must   include  exhaust  air  connected  to  the  toilet  exhaust  riser  or  other  exhaust  vent  exiting  the  building  for  printing  areas  per  ASHRAE  62.1-­‐2007.    A  printing  area  is  defined  as  any  space  200  sqft  or  less  that  has  at  least  three  printing,  faxing,  or  copying  machines.    A  printing  area  can  also  be  defined  as  any  room  or  space  whose  expected  average  printing  or  copying  rate  exceeds  120  pages  per  hour  in  an  eight  hour  day.    Building  Management  reserves  the  right   to   mandate   or   delete   exhaust   over   special   equipment   if   they   believe  indoor  air  quality  may  be  adversely  affected  or  meets   the  general   intent  of  the  requirements  listed  above.  

3. Identify  the  high  density  occupancy  areas  and  describe  the  occupant  load  to  be   used   in   designing   the  HVAC   system.     Note:   This   information   is   used   by  Tenant's   Engineers   in   determining   air   conditioning   requirements.    Occupancy   in   excess   of   design   load   may   result   in   temperature   control  

Page 17: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 17 5/30/2013

problems  during   the   periods   of   excess   occupancy.     Typically,   a   copy   of   the  furniture  layout  will  convey  this  information.  

4. Identify   all   non-­‐standard   HVAC   and   special   exhaust   requirements,   such   as  conference,  word  processing,  and  computer  rooms,  including  idling  and  start  up  heat  outputs  and  the  percentage  of  time  each  machine  runs  in  each  area.    Indicate   any   requirements   for   additional   cooling   (i.e.,   24-­‐hour   cooling   or  weekend  cooling)  at  times  when  the  building  systems  are  not  in  operation.  

5. Provide  chilled  water  usage  calculations  for  the  space.  

  6.   Specify   materials   and   installation   procedures   which   meet   the   criteria   for  maintenance   of   the   Base   Building   standards   for   Indoor   Air   Quality   (i.e.   no  internal  duct  insulation).  

Specify  kWh  and  BTU  meters  for  all  TSAC.  Manufacturer:  Omnicom  5. Specify  air  flow  volumes  for  all  terminal  devices  and  reconcile  quantities  with  

source  equipment  capacities  

E.   Plumbing  Information     1.   Provide  the  location  and  specifications  for  sinks  or  other  plumbing  fixtures.  

  2.   Indicate   the   location   of   water   supplies   for   appliances   and   drains   from  appliances.  

  3.   Coordinate   the   location   of   plumbing   fixtures   with   the   Base   Building  structural,   HVAC,   sprinkler,   and   electrical   systems   and   existing   Tenant  conditions.  

  4.   If   applicable,   the   review   of   all   core   drill   locations   by   Landlord   approved  structural  engineer  prior  to  performance  of  work.  

 

   

Page 18: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 18 5/30/2013

SECTION  C  

MINIMUM  REQUIREMENTS  FOR  TENANT  PLANS  In   addition   to   the   engineering   information   outlined   in   Section   B,   the   following  minimum  information  should  be  included  in  the  Tenant  Plans:  A.                General  

    1.   Base   Building  mechanical,   electrical,   and   plumbing   specifications   for   the  Tenant  Improvements,  and  any  supplementary  specifications  prepared  by  Tenant's   Engineer   should   be   incorporated   by   reference   into   the   Tenant  Plans  by  Tenant's  Architect.  

    2.   Landlord  requires  the  use  of   low  or  no  VOC  products  when  designing  the  Tenant   space.   Compliance   with   Landlord’s   “Indoor   Air   Quality  Specifications”  as  outlined  in  Section  E.  

B.     Architectural  Information  

    1.   Indicate   the   location   and   types   of   partitions.   Landlord   encourages  Architect   not   to   split   perimeter   windows,   but   instead   partition   them   at  window  mullions.  

    2.   All  dimensions  necessary  to  lay  out  space  as  designed.  Critical  dimensions  must  be  clearly  indicated  along  with  the  angle  of  any  diagonal  partitions  or  radii   of   any   curved   partitions.     Provide   dimensions   and   details   for   any  cased  openings.  

    3.   Indicate   dimensions,   if   required,   for   the   location  of   outlets   and   switches.    Building   Standard   telephone   or   data   outlets   require   the   Tenant's   use   of  plenum   rated   cable   and   interduct.   If   conduit   is   required   for   Tenant's  cabling,  the  conduit  will  be  installed  at  Tenant's  expense  and  should  be  so  indicated  on  the  Tenant's  Plans.  

    4.   Indicate   the   location,   swing,   and   specification   for   all   doors,   door   frames,  and   hardware.     Unless   otherwise   indicated,   the   Contractor   will   assume  Building  Standard  latch  sets  at  interior  doors  and  locksets  with  closures  at  public  corridor  doors,  and  will  price  the  work  accordingly.    Include  Tenant  keying  schedule.  

    5.   Tenant's  Architect  should  be  aware  that  above-­‐standard  ceiling  treatments  will   need   to   include   provisions   for   ceiling   access   to   air   distribution  equipment,  electrical  junction  boxes,  and  any  other  areas  above  the  ceiling  for  which  access  is  required  either  by  code  or  for  maintenance.  

  6.   Provide  and  indicate  locations  of  accommodations  for  above  ceiling  access  for  service  and  maintenance  of  above  ceiling  systems  and  equipment.      

  7.   Indicate   locations,   including   dimensions   where   necessary,   for   all   light  fixtures.    Indicate  ceiling  grid  start  points  necessary  to  achieve  the  desired  lighting  layout.  

  8.   Indicate   locations   and   dimensions   (including   height)   where   appropriate  for   all   electrical   and   telephone   and   data   outlets   (the   engineering  

Page 19: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 19 5/30/2013

documents  typically  do  not  include  dimensions).    Location  of  these  devices  is  not  permitted  in  the  exterior  wall.  

  9.   Indicate  the  location  of  any  millwork  and  provide  elevation,  sections,  and  details   sufficient   to   clearly   describe   all   requirements,   including   in   wall  blocking  to  support  wall  hung  cabinetry.  

  10.  Provide   support   framing   details   for   special   walls,   doors,   wall-­‐mounted  millwork  and  bookshelves,  and  any  ceiling-­‐mounted  equipment.  

  11.  Provide   a   finish   schedule   and   finish   legend   clearly   indicating   the   room  number,   wall   finishes,   floor   finish,   and   ceiling   finish   (if   different   from  Building  Standard).  

  12.  Indicate   the   location   and   specification   for   all   paints,   wall   coverings,   or  other  wall   finishes.    Where  wall   covering   is  desired,  Tenant  should  make  certain   that   the   material   is   available   in   accordance   with   design   and  construction  schedule.  

  13.  Provide   locations   and   complete   specifications   for   all   floor   coverings,  including  transition  strips.  

  14.  Indicate   the   weight,   description,   and   location   of   exceptionally   heavy  equipment  (such  as  library  shelving,  filing  cabinets,  safes,  UPS  batteries,  or  other  large  equipment)  which  exceed  80  psf  live  load,  plus  20  psf  partition  load   as   well   as   any   contemplated   floor   penetrations.     Provide  corresponding  structural  details  where  applicable.  

  15.  Designate  areas  requiring  critical  slab  levelness  for  items  such  as  specialty  millwork,  files,  or  wood  flooring.  

  16.  All   entrance   details   on  multi-­‐tenant   public   corridors,   including   graphics,  must  be  those  reviewed  by  Landlord.  

  17.  All  modifications  to  the  Base  Building  (slab  penetrations,  ceiling  elevation  modifications,  for  example)  must  be  reviewed  and  approved  by  Landlord.  

  18.  Tenant’s   Architect   must   specify   and   locate   the   Base   Building   linear  diffusers  in  the  reflected  ceiling  plan.  The  Base  Building  linear  diffusers  are  to  be  installed  centered  on  the  window  and  tight  to  the  window  head.  

C.     Sprinklers  

    1.   The  fire  protection  subcontractor  must  locate  all  sprinkler  heads  based  on  the  Tenant's  reflected  ceiling  plan.    The  heads  must  be  located  to  conform  with   the   building   fire   protection   system   and   Local   Jurisdiction   code  requirements.     The   Tenant's   Architect   will   review   and   approve   the  sprinkler  shop  drawings  before  the  work  is  released  for  construction.  

2. The  sprinkler  heads  should  not  be  shown  on  the  Tenant  Plans  unless  the  Tenant  has   special   design   requirements.    Any  area  which  must   receive   a  non-­‐standard  fire  protection  system  (pre-­‐action  system)  must  be  shown.  

   

Page 20: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 20 5/30/2013

SECTION  E  

INDOOR  AIR  QUALITY  SPECIFICATIONS  ASHRAE   62-­‐89   Ventilation   Standard   for   Acceptable   Indoor   Air   Quality   has   been  used   as   a   guideline   for   this   document   in   establishing  minimum   IAQ   standards   in  addition  to  those  required  by  local  codes.  

A.   General  

1.   The   purpose   of   this   section   is   to   protect   the   indoor   air   quality   in   the   area  under   renovation   and   in   all   surrounding   areas,  which  may   be   impacted   by  the  construction  activities  associated  with  the  Tenant  Contractor’s  work.  People   affected   by   this   include   building   occupants   and   visitors   in   adjacent  areas  to  your  worksite  as  well  as  workmen  within  the  area  being  renovated.    It  is  the  (Tenant  Contractor’s)  responsibility  to  ensure  the  following:  

• that  indoor  air  quality  is  maintained  at  all  times  

• that  no  dust,  debris,  fumes  or  other  harmful  contaminants  are  introduced  to  the  building  in  a  way  that  may  potentially  impact  good  indoor  quality  

• that  no  dust,  debris,  fumes  or  other  harmful  contaminants  are  introduced  to   the  HVAC  air  pathways   including  C.A.V.  units,   ductwork,   air  handling  units,  and  return  plenums.    

• that  no  dust,  debris,  fumes  or  other  harmful  contaminants  remain  within  the  air  pathways  and  space  that  may  be  occupied  after  construction.    This  may  require  thorough  internal  duct  cleaning,  return  plenum  cleaning  and  future  tenant  space  cleaning  at  the  contractor’s  expense.  

The  Landlord  may  make  available  some  equipment  including  ventilation  fans  and   filter  media   to   assist   the  Tenant’s   Contractor   in  meeting   this   goal   as   a  courtesy  only.    Additional  equipment  needed  to  meet  this  requirement  is  to  be   provided   by   Tenant   Contractor’s   at   their   expense   and   may   include  additional   ventilation   fans,   filters   “clean   air   machines”,   air   handling  equipment  and  HVAC  equipment.  

2. Adequate   ventilation   during   the   construction   process   is   the   key   to  maintaining  acceptable   indoor  air  quality.     It   is  during  Tenant   construction  that  the  largest  quantity  of  air  borne  chemicals  is  likely  to  be  released.  

3. Materials   and   finishes   should   be   selected   and   specified   which   produce   a  minimum  amount  of  chemical  emissions.    A   list  of  some  manufacturers  and  their   products  who  meet   established   pollutant   standards   is   available   upon  request.  

4.   The   construction   schedule  must   include   adequate   time   after   installation   of  materials   and   finishes   for   the   removal   of   toxic   emissions   (“off-­‐gassing”)  which  are  present  in  many  construction  materials,  finishes,  and  furnishings.    New   carpet   should   be   unrolled   at   the   warehouse   and   off-­‐gassed   for   a  minimum  of  48  hours  prior  to  installation.  

Page 21: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 21 5/30/2013

5.   All  building  HVAC  equipment  located  in  areas  that  could  be  contaminated  by  construction  related  activities  must  be  protected  prior  to  the  commencement  of  any  work.    The  returns  on  all  fan  powered  terminal  units  must  be  closed,  all   return  plenums  or   return  duct  work  must  be   sealed,   and  any  open  duct  that   could   be   contaminated   by   construction   activities   must   be   sealed.     If  demolition   or   construction   begins   prior   to   initiation   of   these   protective  requirements,   the   Contractor   will   be   required   to   clean,   at   their   cost,   all  related   HVAC   system   components   and   duct   that   could   have   been  contaminated.  

B.   Requirements  

1.   The   HVAC   system   should   be   designed   to   include   sufficient   air   volume  distribution   to   the   occupants,   adequate   outside   air   delivered   to   the  occupants,  ease  of  air  system  balance,  and  adequate  start-­‐up  commissioning  with   follow-­‐up   documentation   and   verification.     HVAC  ducts,   plenums,   and  equipment   shall   be   designed,   constructed,   and   installed   to   minimize   or  prohibit  the  growth  or  dissemination  of  microorganisms.  

Such  design  shall  include:  ·   External  thermal  duct  insulation;  

·   Dual  wall  construction  of  equipment  handling  air;  

·   Stainless  steel  components  inside  air  handling  equipment;  and  ·   Air   filtration   to   minimize   the   introduction   of   dirt   and   to   clean  

recirculated  air.  

Follows   is   a   brief   outline   of   these   requirements.   Refer   to   the   guideline   for  complete   information   and   details.     Two   methods   of   controlling   IAQ   are  offered:  

2. Renovation  when  following  Pollutant  Specification  

• Requires  a  minimum  of  one  filtered  air  change  per  hour.  This  may  require  modification  of  OA  supply  duct.  

• Local  exhaust  is  required.  

• Seal   all   return   plenums   between   construction   area   and   occupied   area.    This  may  require  ducting  of  return  air  between  occupied  area  and  AHU.  

• Re-­‐balancing  of  AHU  to  provide  proper  amounts  of  OA  and  re-­‐circulated  air  to  construction  and  occupied  area.  

3. Renovation  when  not  following  Pollutant  Specification  

• Requires  a  minimum  of  two  (2)  air  changes  of  outside  air  per  hour  in  the  construction   area   and   enclose   the   construction   area  when   construction  begins,  i.e.,  grinding  concrete  floors,  sanding  sheet  rock,  or  application  of  wet   products   like   painting,   sealing,   etc.     Supply   fans  must   be   operated  only  during  hours  of  actual  construction,  not  24  hours  a  day.    Supply  fan  operation  must   be   programmed   to   use   outside   air   in   lieu   of   return   air.    Caution  must  be  exercised  in  extremely  cold  weather.  

Page 22: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 22 5/30/2013

• Provide  a  minimum  of  two  (2)  air  changes  of  outside  air,  twenty-­‐four  (24)  hours   per   day   commencing  with   installation   of   floor   covering  products,  and   continuing   until   the   last   day   before   occupancy.     Caution   must   be  exercised  in  extremely  cold  weather.  

• Local  exhaust  is  required.  

• Seal   all   return   plenums   between   construction   area   and   occupied   area.    This  may  require  ducting  of  return  air  between  occupied  area  and  AHU.  

• Re-­‐balancing  of  AHU  to  provide  proper  amounts  of  OA  and  re-­‐circulated  air  to  construction  and  occupied  area.  

The   Pollutant   Specification   describes   those  materials   used   in   construction,  which   tend   to   introduce  pollutants   at   or  below   specific   target   levels   and   is  included   in   the   Hines’   guideline   “Indoor   Construction   and   Indoor   Air  Quality”.    Use  the  checklist  in  appendix;  Exhibit  J  to  assist  in  section  of  these  materials.  

Similar  measures  are  required  for  new  construction  and  are  also  described  in  the  guideline.    See  Chart  on  next  page  for  Summary  of  requirements:  

4. Contractor,  at  Tenant’s  expense,  will   install  and  operate   temporary  exhaust  fans,   equal   to   one   fan   for   every   5,000   to   6,000   square   feet   of   area   under  construction,   in   order   to   exhaust   air   through   the  windows   at   a   rate   of   one  hundred   percent   (100%)   of   the   outside   air   plus   ten   percent   (10%).    Operation  of  exhaust  fans  should  begin  simultaneously  with  #2  or  #3  above.    Exhaust  fans  must  be  removed  prior  to  occupancy.    All  building  return  air  to  the  air  handling  unit  will  be  temporarily  sealed,  to  the  extent  feasible.    Toilet  exhaust  will  remain  open.    Careful  coordination  with  the  Property  Manager  is  essential.  

5.   Contractor   should,   whenever   feasible,   allow   wet   applications   to   dry  completely  before  installing  dry  materials  and  furnishings.  

6.   Prior  to  commencing  work,  Contractor  must  provide  Property  Manager  with  Material  Safety  Data  Sheets  (MSDS)  for  all  applicable  materials  and  products.    Specific  installation  criteria  will  be  approved  based  upon  this  information.  

7.   Contractor   shall   be   required   to  minimize   the   air   concentrations   of   volatile  organic  compounds  (VOC’s)  by  controlling  their  source  and  selecting  building  materials  based  in  part  on  their  favorable  air  quality  characteristics.  

8. Contractor   shall   minimize,   whenever   possible,   the   on-­‐site   use   of   wet  materials   producing   VOC’s   such   as   lacquer,   adhesives,   paints,   etc.     Factory  application  of  these  finishes  should  be  specified  whenever  possible.    On-­‐site  work  with  materials   that   produce  VOC’s  must   be   approved   by   Landlord   in  advance  and  performed  after  normal  operating  hours.  

9. Asbestos  -­‐  all  EPA,  OSHA  and   local  regulations   including  310  CMR  7.09  and  4.00   regarding   the   surveying,   identification   and   handling   of   asbestos  containing  materials  (ACM),  suspected  asbestos  containing  materials  (SACM)  and  presumed  asbestos  containing  materials   (PACM)  are   to  be   followed.    A  

Page 23: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 23 5/30/2013

survey  prior  to  demolition  is  required,  according  to  OSHA  regulations  1410.1  and  1426.1101.    Other  forms  of  proof  that  no  asbestos  containing  materials  are   present   may   be   used   such   as   MSDS,   or   Architect   Certification.    Completion   of   MA   form   BWP   AQ   06   is   required.     See   the   Hines   Asbestos  Guideline   for   details   and   procedures.   Environmental   Health   Inc.   is   a   pre-­‐approved  testing  contractor.    Contact  Cathy  Coe  at  603.465.7284  to  arrange  

10. Prior  to  commencing  work,  Contractor  must  provide  Property  Manager  with  a   completed   asbestos   survey   in   a   format   to   be   provided   to   Contractor   by  Landlord.  

11. Prior  to  commencing  work,  Contractor  must  provide  Property  Manager  with  certification  indicating  non-­‐asbestos  containing  materials  which  will  be  used  in  the  renovation/build-­‐out.  

   

 

 

 

 

 

 

 

   

Page 24: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 24 5/30/2013

SECTION  F  

TENANT  EXTRA  IMPROVEMENTS  COST  CONSIDERATIONS  A. General  

1. Coordination  of  activities  outside  leased  area.  Some  construction  activities  such   as   coring,   cable   routing   requires   entry   to   other   tenant’s   leased   areas.  These   activities  may   require   special   security   escorts   or   direct   support   form  affected  tenants.  Potential  costs  for  these  added  services  should  be  factored.  

B.   Mechanical  

  1.   Heat  Load/Incandescent  Lighting.    Tenant's  use  of  special  lighting  systems,  in   particular   incandescent   lighting,   may   require   additional   air   conditioning  and   ventilation   due   to   the   increased   heat   load.     Additional   costs   may   be  minimized  by  avoiding  concentrations  of  incandescent  fixtures.      

  2.   Heat  Load/Office  Equipment.    Special  equipment  such  as  copiers,  computers,  word  processing  equipment,  and  telephone  equipment  may  require  additional  air  conditioning  and  ventilation.    Tenant's  Engineer  should  be  provided  with  the   equipment   voltage   and   amperage   requirements   (manufacturer's  specifications),  as  well  as  a  statement  concerning  the  anticipated  usage  of  the  equipment.    With   this   information,   the  Tenant's  Engineer   can  provide  an  air  conditioning   and   ventilation   system   which   satisfies   the   Tenant's   needs   and  minimizes  the  cost  of  Tenant  Extra  Improvements.  Office  equipment  shall  not  be  placed  directly  under  thermostats.  

  3.   Conference/LAN/Computer  Room  HVAC.    Conference   rooms  often  require  special   air   conditioning   and   separate   zoning,   and   in   some   cases,   exhaust  ventilation.     Additional   costs  may   be   anticipated   for   rooms  which   regularly  exceed   a   capacity   of   one   person   per   100   square   feet   of   Usable   Area.     To  minimize   these   additional   costs,   conference   rooms   should   be   located   near  existing   VAV   boxes.     Supplemental   AC   units   shall   be   monitored   at   Tenant’s  expense  with  a  Kwh  meter  tied  into  the  building  management  system.  

  4.   Recessed  Lighting  Locations  and  Ductwork.    The  Tenant's  Architect  and  Tenant's  Engineer  must  coordinate  the  location  of  recessed  lighting  whose  height  might  conflict  with  existing  Base  Building  ductwork.    Recessed  light  fixtures  should  be  located  clear  of  ductwork  and  sprinkler  lines  in  order  to  avoid  the  additional  cost  of  ductwork  relocation  or  modification.    In  all  cases,  Landlord  recommends  the  use  of  low  profile  light  fixtures.  

C.   Electrical  

  1.   Dedicated  Circuits.     Certain   equipment   such  as   copiers,   telephone   switches  and  computer  equipment  often  require  dedicated  circuits.    Therefore,  in  order  to   minimize   additional   costs,   dedicated   circuits   should   be   used   only   where  necessary.  

  2.   Floor   Outlet   Locations.     The   Tenant   Architect   must   coordinate   the   use   of  "poke-­‐through"  type  floor  outlets  with  the  structural  and  mechanical  drawings  in   order   to   avoid   a   conflict   with   the   structure,   Base   Building   ductwork,   or  existing   Tenant  work   below.     The   installation   cost   to   Tenant   of   this   type   of  

Page 25: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 25 5/30/2013

outlet   will   also   include   the   review   and   comment   by   a   Landlord   approved  structural   engineer   and   Landlord.     There   will   also   be   additional   costs   to  examine  the  slab  prior  to  installation.  

  3.   Electrical   Power   Capacity.     Sufficient   electrical   capacity   is   furnished   for  incandescent   lighting   and   for   120   volt   equipment   such   as   computers,  calculators,   and   other   machines   with   low   electrical   power   consumption,  provided  the  demand  load  does  not  exceed  3.5  watts  per  square  foot  of  Usable  Area.     Tenant’s   Engineer   is   to   calculate   and   provide   Landlord   with   power  consumption  calculations.  If  a  Tenant's  electrical  requirements  exceed  the  capacity  of  the  Base  Building  electrical   distribution   panel   boards   and/or   transformers   (or   pro   rata   share  thereof  on  a  multi-­‐tenant   floor)   then   the  costs  associated  with  providing   the  additional   capacity   will   be   at   Tenant's   expense.     “High   Capacity   Electrical  Equipment”   as   defined   in   the   Lease   shall   be   separately  metered   at   Tenant’s  expense.    

D.   Plumbing  

  1.   Special  plumbing  requirements  such  as  labs,  lavatories,  toilets,  dishwashers,  and   icemakers   should   be   located   near   the   Base   Building   plumbing   risers  which  are  available  for  Tenant  connections  of  domestic  water,  sanitary,  vent  and   exhaust   in   order   to   minimize   the   length   (and   therefore   the   cost)   of  Tenant  service  lines.    As  indicated  on  the  Base  Building  drawings,  these  stub-­‐outs  for  waste,  vent,  and  cold  water  are  available  on  each  floor.  

2. Landlord  advises  careful   consideration  of   the  requirement   for   toilet   facilities  within   the   Leased   Premises.     The   size   of   the   waste   line   combined  with   the  required   drainage   slope   to   the   nearest   wet   stack   can   be   costly   due   to  coordination  of  this  waste  line  with  existing  work.    Additionally,  the  location  of  the  slab  penetration  for  a  floor  mounted  toilet  does  not  allow  for  adjustment  due  to  structural  constraints.    A  wall  mounted  toilet  is  somewhat  more  flexible.  

3. Landlord  will   require  Tenant’s  architect   to   specify  a  waterproof  membrane  in  all  restrooms  contained  within  Tenant’s  space.  

4. Tenant’s  Engineer  is  to  calculate  and  provide  Landlord  with  condenser  water  consumption  calculations.  

5. Shut  off  valves  must  be  provided  at  all  sinks  and  equipment  supplied  by  the  domestic  water  system.  

6. All   hot   or   cold   piping   must   be   insulated.   Proper   access   for   all   valves   and  cleanouts  is  to  be  provided.  

7. All  new  plumbing  is  to  be  pressure  leak  tested.  

8. All  water  heaters   are   to  be  equipped  with  drain  pans  piped   to   a  drain   in   a  professional   manner.     Water   heaters   are   also   to   be   equipped   with   “First  Smart”  Sensor  Leak  Detector  System  model  number  FSS-­‐IZMS.  

   

Page 26: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 26 5/30/2013

SECTION  G  

LANDLORD  REVIEW  CHECKLIST  This  checklist  is  to  be  used  as  a  tool  for  to  track  certain  required  events  in  the  project  and   is   intended   to   be   complementary   to   the   balance   of   this   document   such   that  anything  uniquely  required  in  this  table  or  the  balance  of  the  document  shall  be  as  if  required  by  both.            

DESIGN  AND  CONSTRUCTION  TEAM  RESPONSIBILITIES  

 

The  Landlord’s  Team  

Landlord   Property  Manager   Engineering  Manager  

   

Phone:    

Fax:    

 

Phone:    

Fax:    

 

The  Tenant’s  Team  

Tenant’s  Representative   Tenant’s  Architect   Tenant’s  Engineer  

     

 

 

 

The  Contractor  

Main  Office   Project  Manager    

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

Page 27: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 27 5/30/2013

PRE-­‐CONSTRUCTION  PLANNING  

Introductory  Meeting  

  Agenda  

  Establish  schedule  of  ongoing  coordination  meetings  

  Base  Building  Plans  and  Specifications  to  Tenant/Tenant’s  Architect  (Provided  by  Landlord)  

  Landlord’s  names  and  contact  numbers  for  Base  Building  Architect/Engineer  (Provided  by  Landlord)  

  Base  Building  General  Conditions  (Provided  by  Landlord)  

  Landlord  Review  Procedures  and  Rules  of  the  Site  (Provided  by  Landlord)  

  Request  Indemnification  (see  Exhibit  A)  

  Request  Insurance  Agreement  (Exhibit  B)  

  Request  Certificates  of  Insurance  from  all  Contractors  (Exhibit  B)  

  Request  Bond  from  Contractor(s)  

  Request  Lien  Waiver    

  Request  Pest  Control  Plan  

  Proposed  design  and  construction  schedule  (Provided  by  Tenant/Tenant’s  Architect)  

  Landlord  to  suggest  review  of  Lease  obligations  by  Tenant’s  Architect  

  Landlord  to  suggest  development  of  a  Tenant  Space  Plan  

  Landlord  to  suggest  Tenant  review  potential  cost  savings  in  Section  F  

  Terminal  Unit/EMS  LAN  documentation  proving  system  integrity  prior  to  demo  (Provided  by  Landlord)  

Tenant  Space  Plan  

  Interim  review  of  Tenant  Space  Plan  by  Landlord  

  Review  of  the  Tenant  Space  Plan  

Other  Items  for  Tenant’s  Consideration  

  The  Tenant's  Architect  properly  labeled  all  sets  of  proposed  permit  drawings    

  The  Tenant  Improvements  have  been  designed  in  accordance  with  code  

  Landlord  to  suggest  that  long  lead  items  be  identified  by  Tenant  

  Changes  made  to  the  Tenant's  Plans  after  review  to  be  resubmitted  to  Landlord  

Page 28: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 28 5/30/2013

  Tenant  direct  contracts  identified  and  planned  for  (i.e.  telephone,  furniture,  security,  etc.)  

Development  of  the  Tenant  Plans  

  Landlord  to  deliver,  “Minimum  Requirements  for  Engineering”  Information  Package  

  Engineering  Information  Package  completed  by  Tenant’s  Architect  

  Architectural  and  Engineering  Working  Drawings  

  Codes  and  regulations  confirmed  by  Tenant  

TENANT  PLANS  

Architectural Drawings

  Indicate  the  location  and  types  of  partitions  

  All  dimensions  necessary  to  lay  out  space  as  designed  

  Dimensions  indicated  for  the  location  of  outlets  and  switches  

  The  location,  swing,  and  specification  for  all  doors,  doorframes,  and  hardware  are  indicated  

  Any  modifications  to  the  standard  acoustical  tile  ceiling  are  indicated  

  Locations  including  dimensions  for  all  light  fixtures.    Ceiling  grid  start  points  that  are  necessary  to  achieve  the  desired  lighting  layout  are  indicated  

  Locations  and  dimensions  (including  height)  indicated  for  all  electrical,  telephone  and  data  outlets  

  Location,  elevation,  sections,  and  details  of  any  millwork    

  Support-­‐framing  details  for  special  walls,  doors,  wall-­‐mounted  millwork  and  bookshelves,  and  any  ceiling-­‐mounted  equipment  is  provided  

  Finish  schedules  and  finish  legend  provided  

  All  paints,  wall  coverings,  or  other  wall  finishes  location  and  specification  indicated  

  Locations  and  complete  specifications  for  all  floor  coverings,  including  transition  strips  

  Indicate  the  weight,  description,  and  location  of  exceptionally  heavy  equipment.    Structural  loading  to  be  verified  by  Tenant  

  All  entrance  details  on  multi-­‐tenant  public  corridors,  including  graphics  

  All  modifications  to  the  Base  Building  

 Electrical  Drawings  

  Location  of  wall-­‐mounted  electrical  and  telephone  outlets  

  Floor-­‐mounted  electrical  and  telephone  outlets  

Page 29: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 29 5/30/2013

  Location,  power  requirements,  and  specifications  for  special  receptacles  and  separate  circuits  

  Description  of  requirements  all  telephone  or  computer  equipment    

  Design  for  and  install  sub  metering  as  required.    

  Indicate  the  requirement  for  any  emergency  disconnect  switches  or  power    

  All  Building  Standard  and  non-­‐Building  Standard  light  fixtures  located  and  identified  

  Specifications  for  all    light  fixtures  provided  

  Special  foot  candle  requirements  identified  

  All  switches,  dimmers,  and  other  lighting  control  devices  located  and  zoned  

  Location  of  all  exit  lights  and  all  emergency  lighting  indicated  

  Tie-­‐in  to  building  system.    Verify  that  existing  panels  are  adequate  for  the  new  loads  

Mechanical  Information      

  Heavy  occupancy  areas  identified  

  Identify  all  non-­‐standard  HVAC  and  special  exhaust  requirements  

  Specified  materials  and  installation  procedures  to  maintain  building  Indoor  Air  Quality.    Review  procedures  with  the  building  engineer.    Confirm  IAQ  requirements  for  multi-­‐tenant  floors  

  Located  and  specified  all  sinks  or  other  plumbing  fixtures  

  Location  of  water  supplies  for  appliances  and  drains  from  appliances  

  Drawings  coordinated  with  Architectural,  Structural,  and  Base  Building  

  All  sprinkler  heads  located  by  FS  subcontractor  

  Areas  receiving  a  nonstandard  fire  protection  system  are  shown  and  specified  

Required  Inclusions  in  Tenant  Specifications  

  Keying  Schedule  

  Tenant  Furnishings  

  Air  Balance  Report  

  Operating  and  Maintenance  Manuals  

  As-­‐Built  Drawings  

Page 30: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 30 5/30/2013

 RULES  OF  THE  SITE  

  Landlord  has  approved  the  Tenant’s  Contractor  

  Tenant  has  signed  the  Rules  of  the  Site  

  Contractor  has  signed  the  Rules  of  the  Site  

  Receive/approve  Indemnification  (see  Exhibit  A)  

  Receive/approve  Insurance  Agreement  (Exhibit  B)  

  Receive/approve  Certificates  of  Insurance  from  all  Contractors  (Exhibit  B)  

  Receive/approve  Bond  from  Contractor(s)  

  Receive/approve  Lien  Waiver    

  Site  Logistics  Plan  received  by  Property  Manager  

  The  Contractor  has  submitted  names  to  Property  Manager  of  its  quick  response  team.  

  Contractor  and  Property  Manager  have  reviewed  the  existing  condition  of  the  site    

  The  Contractor  has  created  a  videotape  or  photographic  documentation  of  the  construction  area  prior  to  the  start  of  construction  

  Contractor  has  received  written  permission  to  move  onto  site  

  Contractor  has  instituted  a  Safety  Plan  

  Contractors  has  supplied  the  Property  Manager  with  the  following  materials  48  hours  before  work  commences  

  Asbestos  survey  complete  

  Contractor  certification  that  non-­‐asbestos  containing  materials  are  being  used  

  A  copy  of  their  Hazard  Communication  standard  Program  as  required  by  OSHA  

  “Materials  Safety  Data  Sheets”  provided  by  Contractor  

  Contractor  to  provide  electrical  load  calculations  to  Landlord  

  All  concrete  “cores”  identified  and  properly  X-­‐rayed  

  Landlord  to  approve  all  “wet-­‐taps”  of  the  condenser  water  system  

  A  list  of  products  and  their  hazardous  substances  which  the  Contractor  plans  to  use  

  Landlord  to  approve  all  modifications  to  the  building  control  system  

  Landlord  to  approve  the  relocation  of  any  temperature  sensors  

Page 31: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 31 5/30/2013

  Temporary  ventilation  plan  for  removal  of  VOC/fumes  from  space  (see  Section  E,  “IAQ  Specifications”)  

  Written  notification  of  the  use  of  welding  or  open-­‐flame  equipment  

  Contractor  has  arranged  for  air  balance    

  Air  balance  reports  submitted  in  format  approved  by  Tenant’s  MEP  Engineer  and  as  per  Exhibit  E  of  BR&R  

  Contractor  conducts  weekly  job  progress  meetings  with  agenda,  change  order  drafts,  updated  schedules,  long  lead  items  identified  and  submittal  schedules.  

  Contractor  provides  reasonable  notice  for  building  system  shutdowns  

  Contractor  to  submit  schedule  for  loading  dock  use  

CONSTRUCTION    

Administration  

  Tenant  Plans  conceptually  reviewed  and  commented  upon  and  letter  with  Notice  to  Proceed  Issued  

  Permits  Received:  

□ Demolition  □ Construction  □ Electrical  □ Plumbing  □ Welding/burning  □ Fire  Dept/Alterations/Construction  □ Fire  watch(es)  □ Smoke  detector  bypass/bagging  □ Indoor  Air  Quality  -­‐  BWP-­‐AQ-­‐06  

  Contract  signed  

  Tenant’s  Schedule  received  

  Contractor  Schedules  received  

  Receive/approve  Construction  Schedule    

  Receive/approve  Pest  Control  Plan  

  Trash  dumpster  approval  by  Landlord  

  Badging  or  identification  system  implemented  by  Contractor  

Page 32: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 32 5/30/2013

  Parking  procedures  implemented  by  Contractor  

Quality  

  Quality  Program  received  from  Contractor  

  Site  Visits  procedures  established  

  Engineering  Field  Reports  formats  decided,  procedures  in  place  

  Daily  trash  removal  plan  in  place  

Close-­‐Out  

  Record  Drawings  received  by  Property  Manager  

  Certificate  of  Occupancy    (New  Space  only)  

  Architectural  Punchlist  completed  by  Tenant  Architect,  Construction  Manager,  and  Building  Engineer  

  Engineering  Punchlist  completed  by  Tenant  Engineers,  Construction  Manager,  and  Building  Engineer  

  Punchlist  Completed  by  Contractor  

  Operating  and  Maintenance  (O&M)  Manuals  received  by  Property  Manager  

  As-­‐Built  Drawings  received  by  Property  Manager  

□ Black,  blue  line  or  sepia  □ Electronic/CAD  

o Architectural  

o Electrical  

o Mechanical  

o Plumbing  

o Structural  

  Electrical  Panel  Schedules  

  Property  Accountant  notified  of  all  billable  items  to  Tenant  or  General  Contracts  

  Property  Accountant  receives  back-­‐up  for  payment  of  Tenant  Allowance  

  Rent  start  letter  sent  to  Tenant  

  Initialize  electric  metering  with  Energenix  

  Air  balance  reports  

 

   

Page 33: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 33 5/30/2013

EXHIBIT  A  

Indemnity  Agreement  The  Contractor  agrees  to  indemnify  and  save  harmless  Owner,   its  partners  and  their   officers,   agents,   servants,   employees,   and   the  Architect   and   each  of   them  (hereinafter   individually   and   collectively   the   "Indemnities"),   from   and   against  any   and   all   claims  made   or   asserted   for   any   damage   or   injury   of   any   kind   or  nature   whatsoever   (including   death   resulting   therefrom)   to   any   person   or  property   including,   without   limitation,   claims   for   damage   or   injury   to   any  employees  of   the  Contractor,  his  subcontractors  or  otherwise  which  claims  are  resulting  from  or  arising  out  of  the  execution  of  this  Work,  whether  or  not  such  claims  are  based  upon  indemnities  alleged  active  or  passive  negligence,  alleged  strict  liability  in  tort  or  participation  in  the  wrong  or  upon  any  alleged  breach  of  any   statutory   duty   or   obligation   on   the   part   of   indemnities   (regardless   of   the  percentage  or  degree  that  the  conduct  of   indemnities  contributed  to  the  loss  in  question)  and  further  from  and  against  all  loss,  cost,  expense,  liability,  damage  or  injury,   including   legal   fees,   that   Indemnities  may  directly   or   indirectly   sustain,  suffer  or  incur  as  a  result  thereof  and  the  Contractor  agrees  to  and  does  hereby  assume   on   behalf   of   Indemnities   the   defense   of   any   action   at   law  or   in   equity  which  may  be  brought  against  Indemnities  by  reason  of  such  claims  and  to  pay  on  behalf  of   Indemnities  upon   their  demand,   the  amount  of  any   judgment   that  may   be   entered   against   Indemnities   in   any   such   action.     Notwithstanding  anything  to  the  contrary  herein,  this  Indemnity  shall  not  extend  to  Indemnities  in  the  event,  and  only  in  the  event,  injury  or  damages  are  sustained  by  reason  of  the  intentional  torts  of  Indemnities  or  solely  by  reason  of  the  negligent  conduct  of  Indemnities.    

APPROVED  AND  ACCEPTED  THIS  __________  DAY  OF  __________,  __________.  

   

 

BY:    

   

   

   

TITLE:    

   

 

   

Page 34: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 34 5/30/2013

EXHIBIT  B  

Insurance  Agreement  

TENANT:    

   

TENANT  CONTRACTOR:    

   

SUBCONTRACTOR  NUMBER:    

   

SUBCONTRACT  DATE:    

 This  Agreement  shall  evidence  the  obligation  of  Tenant's  Contractor  to  be  bound  by  the  terms  of  this  Agreement  as  a  condition  to  being  permitted  to  perform  the  work   for   Tenant.     Although   Hines   Global   REIT   Riverside   Center   LLC   has   not  signed   this  Agreement,   the  Tenant's  Contractor  agrees   that   the  Owner  shall  be  entitled   to   the   benefits   of   this   Agreement   and  may   enforce   it   directly   against  Tenant's  Contractor.  Tenant's  Contractor  shall  be  bound  by   the  build-­‐out   requirements  as  amended  from  time  to  time,  a  copy  of  which  has  been  provided  to  Tenant's  Contractor.  Tenant's   Contractor   shall,   at   its   own   expense,   maintain   in   effect   at   all   times  during   the   performance   of   the  work   not   less   than   the   following   coverage   and  limits  of  insurance,  which  shall  be  maintained  with  insurers  and  under  forms  of  policies  satisfactory  to  the  Owner.  

A. Comprehensive  Automobile  Liability   Insurance   to   include   non-­‐owned,   hired,   rented,   as   well   as   owned  vehicles.  

1. Bodily  Injury              $500,000  for  each  person                  $1,000,000  aggregate  for  each  occurrence  

 2. Property  Damage   $500,000  for  each  accident  

    $1,000,000  aggregate  B. Fire  or  Extended  Coverage  

Insurance  on  equipment  tools  and  materials  owned  or  rented  by  Contractor.  Amount   to  be  determined  by  Contractor   to  be  necessary   to  protect   against  liability.  

Page 35: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 35 5/30/2013

The  Fire   and  Extended  Coverage   Insurance  policy   shall   include  a  waiver  of  subrogation  clause     as   follows:     "It   is   agreed   that   in   no   event   shall   this  Insurance  company  have  any  right  of  recovery  against  Owner  or  Architect."  

C.   Workmen's  Compensation  and  Occupational  Diseases  Employer's  Liability  is  $500,000.  

D.   Comprehensive  General  Liability  Insurance  

1. Bodily  Injury     $500,000  for  each  person         $1,000,000  aggregate  

2. Broad  Form  Property  Damage     $500,000  for  each  person         $1,000,000  aggregate  

3. Contractual  Liability  Coverage     $500,000  for  each  person  

      $1,000,000  aggregate  4. Contractor's  Protective  Liability       $500,000  for  each  person  

      $1,000,000  aggregate  

5. Explosion,  collapse  and     $500,000  for  each  person              damage  to  underground  utilities     $1,000,000  aggregate  

6. Completed  operations  coverage  for     $500,000  for  each  person    a  period  of  ten  (10)  years  after  final     $1,000,000  aggregate  

acceptance  of  the  Work.  

All  Subcontractors'  policies  shall  contain  an  endorsement  providing  that  written  notice  shall  be  given  to  the  Owner  at  least  thirty  (30)  days  prior  to  termination,  cancellation,  or  reduction  or  material  change  of  coverage  in  the  policy.  

The   Bodily   Injury   and   Property   Damage   Liability   policies   shall   contain   the  following:  A.   Provisions   or   endorsement   naming   the  Owner,   Development  Manager,   and  

Lender   as   additional   insured   as   respects   liabilities   arising   out   of   Tenant  Contractor's  performance  of   the  work  at   the  project  site  and  providing  that  such   insurance   as   respects   the   interest   of   the   Owner   and   that   any   other  insurance  maintained  by  the  Owner  is  excess  and  not  contributing  insurance  with  the  required  hereunder.  

B.   "Cross  Liability"  or  "Severability  of  Interest"  clause.  

C.   Elimination  of  any  exclusion  regarding  loss  or  damage  to  property  caused  by  explosion  or  resulting  from  collapse  of  buildings  or  structures  or  damage  to  property   underground,   commonly   referred   to   by   insurers   as   the   "XCU"  hazards.  

D.   Provision  or  endorsement  stating  that  such  insurance,  subject  to  all     of   its  other   terms   and   conditions,   applies   to   the   liability   assumed   by   Tenant's  

Page 36: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 36 5/30/2013

Contractor  under  the  Rules  of  the  Site  or  under  the  contract  between  Tenant  and  Tenant's  Contractor.  

E.   Provision   or   endorsement   waiving   any   rights   of   subrogation   against   the  Owner,  Development  Manager,  and  Lender.  

F.   Provision   or   endorsements   confirming   coverage   for   complete   continual  liability  and  broad  form  property  damage.  

Prior  to  commencement  of  work,  Tenant's  Contractor  shall  return  two  of  the  attached   Insurance   Certificates   properly   executed   and   signed   by   an  authorized   representative   on   behalf   of   the   insurer(s)   evidencing   the   above  coverage  and  conditions  to  the  Owner  and  Development  Manager.    Tenant's  Contractor   further   agrees,   upon   written   request   by   the   Owner   and  Development   Manager   to   furnish   copies   of   such   policies,   certified   by   an  authorized  representative  of  the  insurer(s).  

It   is  understood   that   the  Tenant's  Contractor   is   responsible   for   compliance  with   the   requirements   under   the  Williams-­‐Steiger   Occupational   Safety   and  Health  Act  of  1970.  

 APPROVED  AND  ACCEPTED  THIS  __________  DAY  OF  __________,  __________.  

 

BY:    

   

   

   

TITLE:    

   

 

OWNER:   Hines   Global   REIT   Riverside   Center   LLC,   and   Hines  Interests  Limited  Partnership  

Page 37: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 37 5/30/2013

CERTIFICATE  OF  INSURANCE  

The  following  is  the   information  you  requested,  regarding  insurance  forms.    When  contracting   for   service,   please   insure   that   your   vendor   provides   Hines   (fax  617.969.7400)  with  a  certificate  of  insurance  BEFORE  work  begins.    Please  call  with  any  questions  or  concerns.    Thank  you.  

 

ADDITIONAL  INSURED  

Hines  Global  REIT  Riverside  Center  LLC  Hines  Interests  Limited  Partnership    

   

ISSUED  TO    

Certificate  Holder:  

Hines  Global  REIT  Riverside  Center  LLC  

c/o  Hines  Interests  Limited  Partnership  

275  Grove  Street  

Newton,  MA  02466  

 

 

NAMED  INSURED   Hines  Global  REIT  Riverside  Center  LLC  

   

DESCRIPTION  OF  PROJECT  OR  OPERATIONS  

Office  Space  275  Grove  Street  

Newton,  Massachusetts  02466  

This   is   to   certify   that   the   insurance   company(s)   shown   below   has   (have)   issued  policies  of  insurance,  as  described  below  to  the  insured  named  above,  and  to  certify  that  such  policies  are   in   full   force  and  effect  at   this   time.     It   is  agreed  that  none  of  these  policies  will  be  canceled  or  changed  so  as  to  affect  insurance  described  by  this  certificate  until  thirty  (30)  days  after  written  notice  of  such  cancellation  or  change  has  been  delivered  to  the  insured  and  named  insured  at  the  addresses  shown  above.  

 

Page 38: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 38 5/30/2013

EXHIBIT  C  

Contractor  Pass  Applications  Form  

• Each   contractor   will   be   assigned   a   contractor   badge   to   be   kept  through  the  duration  of  the  construction  project.  

• All  contractors  are  required  to  wear  badges  when  on  site.  

• Badges  should  be  visible  on  outer  clothing  at  chest  level.  

• Contractors  found  on  site  without  a  badge  will  be  asked  to  vacate  the  premises.  

• Each  contractor  is  responsible  for  his/her  badge.  

• Lost  or  stolen  badge  should  be  reported  to  security  immediately.  

• Anyone  wearing  a  badge,  which  has  been  reported  lost  or  stolen  will  be  asked  to  leave  the  premises.  

NAME  (PRINT):    

   

SIGNATURE:    

   

COMPANY:    

 

PROJECT  SUPERVISOR/  FOREMAN:  

 

   

PASS  NUMBER:    

   

DATE:    

   

   

   

Page 39: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 39 5/30/2013

EXHIBIT  D  

FIRE  ALARM  TEST  NOTIFICATION  

To:   Hines  

  David  Estes,  Engineering  Manager     Jen  Gless,  Administrative  Assistant  

From:   Electrician    

     

  Superintendent    

     

  Date/Time    

    (must   be   a  minimum   of   three   working   days   prior   to   test  date)  

Re:   Fire  Alarm  Testing  

    Floor:    

     

    Tenant:    

     

    Building:    

 On  __________  (day)  the  __________  (date)  at  __________  am/pm  we  would  like  to  schedule  a  fire  alarm  test  for  the  ________  floor  of  Building  1  /  2  /  3  of  Riverside  Center.    Please  meet   the   building   engineer   at   the   Fire   Command   Center   on   the   ground   floor   of  Building  1  /  2  /  3  that  morning.    Thank  you.  

 NOTE:  

The  General  Contractor  is  responsible  for  confirming  that  this  is  acceptable  to  all  parties.  

Page 40: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 40 5/30/2013

 EXHIBIT  E  

 INDOOR  AIR  QUALITY  COMPLIANCE  TABLE  

CONSTRUCTION  MATERIALS,  FINISHES  AND  FURNISHINGS  

PRODUCT  NAME    

SUBMITTED  BY    

   

DOES  PRODUCT  COMPLY  WITH  FOLLOWING  

STANDARDS  

 

YES  

 

NO  

PREDICTED  AIR  CONCENTRATION  

30  DAYS  (UG/M3)  

EMISSION  RATE  

30  DAYS  

(UG/M3  –  HR)  

TIME  TO  COMPLIANCE  

(DAYS  +-­‐  0.1)  

1.   Formaldehyde  

  60  ug/m3  

         

2.   Total  VOC     500  ug/m3  

         

3.   Total  Particulate     50  ug/m3  

         

4.   4-­‐PC  

  6.5  ug/m3  

         

   

  YES   NO     YES   NO   SUBMITTALS  

NAAQS  Complaint             Product  Description  

            Test  Protocol  

1/10  TLV  Compliant             Graphs,  tables,  supporting  data  

            Laboratory  name,  address,  phone  

Note:    If  answers  to  1  through  4  above  are  Yes,  then  the  product  meets  the  Hines  target  guideline.  

   

Page 41: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 41 5/30/2013

EXHIBIT  F  

CONSTRUCTION  IAQ  CHECKLIST    

Include  IAQ  protection  measures  in  proposals  and  all  pre-­‐construction  meetings.  Make  sure  on  site  supervision  is  familiar  with  requirements  and  procedures.  

Use  construction  practices  that  minimize  dust  and  fumes.  

 Prevent  dust  infiltration  to  all  air  conveyance  equipment:  

Shut  off  all  CAV  units  and  AHUs.  Cover  all  CAV  induction  ports.  

Cover  all  open  duct  work.  

Check  frequently  to  ensure  these  measures  remain  in  place.    

Create  negative  pressure  work  zone:  

Install  barriers  on  partially  occupied  floors.  Install  ventilation  fans  to  create  negative  pressure  zone.  

Verify  that  fans  remain  in  operation  during  construction  process.    

 

   

 

   

   

 

   

   

   

Page 42: RIVERSIDECENTER! ! CONSTRUCTION! ! RULES&REGULATIONS! · 2020. 4. 21. · Page 6 5/30/2013 planning and% monitoring%of construction activities. % Work% potentially impact ing

Page 42 5/30/2013

EXHIBIT  G  

 WELDING/BURNING  PERMIT  LETTER  FROM  LANDLORD  

 Date  

 

Mechanical  Contractors    Newton,  MA    02466  

 Re:    Riverside  Center  

 

Dear  Sir  or  Madam:    

_________  has  notified  this  office   that  you  are  their  designated  subcontractor   for   the  welding  to  be  performed  _______.        

We  understand  that  welding,  cutting  and  burning  may  be  required.    

Please   let   this   letter   serve   as   authorization   for   welding,   cutting   and   burning   as  required  to  complete  the  HVAC  work.    We  understand  that  we  are  issuing  this  letter  so   that   you   may   obtain   the   necessary   permit   from   the   City   of   Newton   and   the  Newton  Fire  Department.        Please  understand  you  are  bound  to  observe  all  building  regulations  as  well  as  state  and   local  codes  with  regard  to  the  safe  conduct  of   this  work.  

 Regards,  

 

   

David  Pete  Property  Manager  

 

C. Gregory  Brown,  Vice  President  Property  Management  David  Estes,  Engineering  Manager