Upload
doantram
View
226
Download
1
Embed Size (px)
Citation preview
Meter Loop Detail
Residential and Commercial 100 to 200 Amp Meter Loops
esidential and commercial meter loops are typically
used when constructing facilities for permanent
service. It is important that all guidelines outlined in this
document be followed by your contractor or electrician.
The member shall be in compliance with the National
Electric Code (NEC). PEC is in compliance with the
National Electric Safety Code (NESC). For your
protection, PEC urges you or your electrician to use only
NEC approved procedures and materials. All meter
loops must be sized according to the load to be served
and NEC guidelines.
PEC will refuse service where a known hazardous
condition exists and/or if connections do not meet the
specifications outlined in this document. We urge you to
use a qualified electrician to prevent safety hazards,
additional costs, and delays. PEC requires that all
construction meet or exceed these specifications prior to
service connection.
Member will be responsible for any replacement and
repair of the meter loop, including the meter socket.
Electric service disconnects, regardless of the number of
circuit breakers, must have a weatherproof main
disconnect on the exterior of the service area. There will
be no more than two loops on any one pole. For more
information on higher amperage, contact PEC at
1-888-554-4732 or visit our website at www.pec.coop
Weather head
Neutral conductor must be electrically
continuous through the meter socket to the
main panel and must be attached to the
meter socket. Neutral shall be of equal size
or one standard size smaller. See page 3
for wiring guidelines.
*Note: Electrically Continuous
Electric contractor has the option of
terminating neutral at the meter socket lug.
Main panels will be terminated at the meter
socket lugs.
Must have at least
6 inches of drip
loop and 30 inch
tails
Weatherproof fused or
breaker protected main
disconnect panel will
have a main disconnect
on the outside of the
building, regardless of
the number of circuit
breakers.
Maximum 6 feet
Minimum 5 feet
#6 Copper
ground wire
Conduit nipple and
weatherproof hub
Service raceway will be
SCH 40 electrical grade
PVC, EMT, IMC, or
galvanized rigid pipe.
Only galvanized rigid pipe
can be used if raceway
extends through the roof
Watertight connector
5/8" x 8' copper clad
driven ground rod
with clamp per NEC
R
UL approved overhead meter
socket supplied by member.
6"
4"
date:approveddrawn:
Page 1
REB MJB
UL approved Overhead Meter base
supplied by member.
Service raceway will be
SCH 40 electrical grade
PVC, EMT, IMC, or
galvanized rigid pipe
Weatherproof fused or breaker
protected main disconnect panel will
have a main disconnect on the
outside of the building, regardless of
the number of circuit breakers
#6 copper ground
wire
Weather head
Min. 10 feet
in residential
use
Maximum 6 feet
Minimum 5 feet
Residential and Commercial 100 to 200 Amp Meter Loops
Construction on Residence/Commercial Location
Must have at least 6 inches of
drip loop out of weather cap and
30 inches of tails. Neutral shall
be of equal size or one standard
size smaller.
5/8 inch x 8 foot copper
clad driven ground rod with
clamp per NEC
Minimum 12 feet
over spaces
subject to
pedestrians where
animal riders and
vehicles are less
than 8 foot.
Minimum 16 feet
over driveways,
parking lots, and
other areas subject
to truck traffic.
NESC Table 232-1
This type of construction is the most common in areas where distance to poles is not a problem.
Construction must meet or exceed these specifications prior to service connection.
PEC wire
esidential and commercial meter loops are typically
used when constructing facilities for permanent
service. It is important that all guidelines outlined in this
document be followed by your contractor or electrician.
The member shall be in compliance with the National
Electric Code (NEC). PEC is in compliance with the
National Electric Safety Code (NESC). For your
protection, PEC urges you or your electrician to
use only NEC approved procedures and materials. All
meter loops must be sized according to the load to be
served and NEC guidelines.
PEC will refuse service where a known hazardous
condition exists and/or if connections do not meet the
specifications outlined in this document. We urge you to
use a qualified electrician to prevent safety hazards,
R
additional costs, and delays. PEC requires that all
construction meet or exceed these specifications prior to
service connection.
Member will be responsible for any replacement and
repair of meter loop, including meter socket.
Electric service disconnects, regardless of the number of
circuit breakers, must have a weatherproof main
disconnect on the exterior of the service area. There will
be no more than two loops on any one pole. Neutral
conductor must be electrically continuous through the
meter socket to the main panel and must be attached to
the meter socket. See note on page 1. See page 3 for
wiring guidelines. For more information on higher
amperages, contact PEC at 1-888-554-4732 or visit our
website at www.pec.coop.
XXXXX-PEC
date:approveddrawn:
Page 2
REB MJB
Minimum of #6
copper wire
UL approved
Overhead
Meter base
supplied by
member.
Weatherproof
fused or
breaker
protected main
disconnect
panel will have
a main
disconnect on
the pole,
regardless of
the number of
circuit
breakers
Service raceway
will be SCH 40
electrical grade
PVC, EMT, IMC,
or galvanized
rigid pipe
30 inch
tails
This type of construction is used when this choice is more
advantageous. Meter bases are not permitted on primary
poles. No member owned facilities on PEC poles other
than meter loops. There will no more than two loops on
any one pole.
2 Inch visible
galvanized rigid
metal conduit
only (not IMC or
EMT)
UL approved
Overhead Meter
base supplied by
member.
Weatherproof fused
or breaker protected
main disconnect
panel will have a
main disconnect on
the outside of the
building, regardless
of the number of
circuit breakers
#6 copper ground
wire
Weather head
This type of construction is appropriate when the existing
structure does not allow for proper ground clearance.
30 inch
tails
5/8" x 8' copper clad
driven ground rod
with clamp per NEC
5/8" x 8' copper clad
driven ground rod
with clamp per NEC
Wiring Guidelines
Minimum 12 feet
over spaces
subject to
pedestrians where
animal riders and
vehicles are less
than 8 foot in
height.
Minimum 16 feet
over driveways,
parking lots,
and other areas
subject to
truck traffic.
NESC Table 232-1
Max.
23 inches
for
200 amp
Min. 10 feet
in residential
use
Maximum 6 feet
Minimum 5 feet
Maximum 6 feet
Minimum 5 feet
Neutral conductor must be electrically continuous
through the meter socket to the main panel and
must be attached to the meter socket. See note on
page 1. Neutral shall be of equal size or one
standard size smaller
Mast Type Construction Through Roof
Construction of Meter Poles
Do not extend above pole
with weather head
PEC wire
PEC wire
Meter Base Size Breaker Size
Copper Wire
THW
Aluminum Wire
THW
100-200 amp 60 amp
#6 #4
100-200 amp 100 amp
#4 #2
150-200 amp 125 amp
#2 #1/0
150-200 amp 150 amp
#1 #2/0
Meter Base
Size
Breaker Size
Copper Wire
THW
Aluminum
Wire THW
200 amp 200 amp
#2/0 #4/0
200 amp
200 amp
commercial
#3/0 250
6"
6"
drip loop
18" - 24 "
date:approveddrawn:
Page 3 REB MJB
5' to 6' to center
of meter socket
Typical URD Loop on the Side of a House
5/8" X 10'
Ground Rod
#6 Copper minimum
UL
Approved
Main
Panel
UL Approved
Underground
Meter Socket
See Note 1
Note 1: Incoming conduit
must attach to the
opposite side of the
meter can from
disconnect.
date:approveddrawn:
Page 5
JBS MJB
Wire size is based on the
guidelines provided on page 3 with
30" of tails out of the weatherhead.
Neutral conductor must be
electrically continuous through the
meter socket to the main panel
and must be attached to the meter
socket.
#6 Copper
minimum
200A
Main
Disconnect
Member shall purchase and install
4" Galvanized pipe 4' in ground and
cemented with 16' of pipe exposed.
Watertight
connector
200A
Meter
Socket
200A Single Phase Loop Top to Bottom
Member to supply and install eyebolt
for service attachment. It should be
installed 4" to 6" from top of pipe.
13' Minimum
5' Minimum
6' Maximum
Member shall
purchase meter
socket. Member will
be responsible for
replacement and
repair of meter loop,
including meter
socket.
Height of the wire between PEC's
pole and 4" pipe must meet
pedestrian ground clearance per
Table 232.1 of the NESC of 12 feet.
PEC shall provide and install a service wire drop to the member's meter loop. The member shall own the meter rack, and
shall be solely responsible for the construction, installation and maintenance of all electrical and structural components.
PEC retains full discretion to refuse or disconnect service to any member owned meter rack that PEC deems to structurally
unsound or hazardous. The member shall be in compliance with the National Electric Code (NEC).
Weatherhead to be within
12" from top of pipe.
4" Threaded, galvanized
and rigid cap
2" Schedule 40 rigid pipe, IMC,
or EMT with weather tight
connectors or electrical grade PVC
Note: Installation of 4" pipe should not be more than 40' from PEC pole. Beyond that could violate NESC clearance and create an
extreme deflection on the 4" pipe. Member is required to contact the local Engineering office prior to approval of rack's location.
5/8" x 8' copper ground rod
date:approveddrawn:
REB MJB
Page 6
2" Maximum extension
Unistrut support 3/4" x 1 1/2"
of required length
3" Threaded, galvanized
and rigid cap
Watertight connector
13' Minimum
200A
Main
Panel
200A
Meter
Socket
3" Galvanized pipe 2' - 4'
in ground and cemented,
depending on soil type
200A Single Phase Loop
(Rack Type) with Side Mount
2" Schedule 40 rigid pipe, IMC,
or EMT with weather tight
connectors or electrical grade PVC
PEC shall provide and install a service wire drop to the member's meter loop. The member shall own the meter rack, and
shall be solely responsible for the construction, installation and maintenance of all electrical and structural components.
PEC retains full discretion to refuse or disconnect service to any member owned meter rack that PEC deems to be
structurally unsound or hazardous. The member shall be in compliance with the National Electric Code (NEC).
Member to supply and install eyebolt
for service attachment. It should be
installed 4" to 6" from top of pipe.
Wire size is based on the
guidelines provided on page 3 with
30" of tails out of the weatherhead.
Neutral conductor must be
electrically continuous through the
meter socket to the main panel
and must be attached to the meter
socket.
4" Threaded, galvanized
and rigid cap
Member shall purchase and install
4" Galvanized pipe 4' in ground and
cemented with 16' of pipe exposed.
5' Minimum
6' Maximum
Weatherhead to be within
12" from top of pipe.
Member shall purchase
meter socket. Member will be
responsible for replacement
and repair of meter loop,
including meter socket.
Height of the wire between PEC's
pole and 4" pipe must meet
pedestrian ground clearance per
Table 232.1 of the NESC of 12 feet.
Note: Installation of 4" pipe should not be more than 40' from PEC pole. Beyond that could violate NESC clearance and create an
extreme deflection on the 4" pipe. Member is required to contact the local Engineering office prior to approval of rack's location.
5/8" x 8' copper ground rod
#6 Copper minimum
date:approveddrawn:
REB MJB
Page 7