ATTACHMENT 3 .
TROJAN NTCLEAR PU37
REPORT ON TESTING OFCCMPOSITE MASONRY WALLS
Novenber 1979
Portland General Electric Co.
Northwest Testing Laboratories
Wiss, Janney, Elstner & Assoc., Inc.
1528 157
_. __ _ _ . _ . _ . _ _79 /2 //03Y4
f,.
.
s
.
TABLE OF CONTENTS
Section Page
1 Test Objectives 1
2 Methodology 3
3 Results 10
4 Evaluation of Test Results 12
.
a
6
1528 :53
* ..,
Section 1 Test Objectives
1.1 The testing was performed in order to confirm the accuracy of
our judgment with respect to the tension capacity at the interface between masonry
block and concrete core of composite walls located in the Trojan Nuclear Plant. -
The testing was performed "in-situ" on walls repr.3sentative of the various
types of composite walls at the plant.
Figure 1.1 shows a cross-section of the type of composite wall utili:ed
in the facility.
.
1528 159--
._.
. ...
CONCRETE MASONRY
,
REINFORCING STEEL
CELL GROUT
1
CONCRETE CORE
.-!
'e NNNNN'N' s' A ' " ' S NN N N '<1 .A N. ' . s n ' '
s)X"'p'k.,.'N}'.2.'.,s'i'.ra'isTd'' *x .s
$ x ') .., r a ^'
j. *x!57,N
.
x -\s . i e :i .
'
c.E N -| * *Yi= i- f -| . y. _ ."
*'< .
-,- .. q .'3 .. , . e - s .s .< x .<.N*..' ,c3 . .e .e. .
'
^
.
, __ . . .+. ' O i N L 6,0,6 , i .# A i e , .a ' . c' ; , . ,, 4*w
T 's ' \ N ' s N 's N \ \ \ N s N'N \NN N s s. 's N N N \ \ N\ ' \ \ '''
'
. y ~ ~. , c I , . :: , %.'.f *:'.A.~ , :.' ' 1 j*,i. :' '
C,
, J. . , p- t ,I.g .^,# , . '- = * <
f. . .-:.. ; a. ., .s. ; . p;x..
~.. . ..*M <.
I~
4B"gsg =4E= ,,
p ., . s. .. , . . c .8 . 'a...h / '*?.t>.:) 2 ,,'.' / :.'|'e-#
a
sy N N N N 'xNNNN NNN N sN,N N N N N o . .'\\NN
. ,z'ss\NNN'sy . ,. , , ,.s , .w c' y4 m.j., t ,j...s. \; . .
. 4- N ,d"
*.e N'N-
N--
,,,gf Ns-,. ,,N -
N' . * <* c... N,f " ' N d j# .4 d T' 4 ,' a - \ .'- D i* I*- \s
, ,,4s. ' ''~ - # -
.,
hNNNNxx 'x x s u NN' N N N N x ' \ x x x x xN\\\NY' x
PL AN SECTION.
REPRESENTATIVE COMPOSITE WALL
.
F16 l . |
-2-
1528 160. ._ - . . . - . _ __-
*.,
: .
Section 2 Methodology
2.1 Location of test sites.
By inspection of Plant drawings, test sites which are representative -
of the cenposite walls at the Plant and which are readily accessible in the
present plant operating mode were chosen. Those chosen were located at the
25' and 5' elevations in the Auxiliary Building and are shown in Figure 2.1.
Preliminary ava-4 nation was conducted to assure that no wall attach =ents were
present on either side of the test region and to atte=pt to identify rebar that
might interfere with the test.
2.2 Test preparation.
The testing program was conducted in two stages. In the first stage
the bond strength between the front facing block and the central core concrete
was tested and the second stage the bond strength between the central core
concrete and the remaining bicek at the same sites tested in the first stage.
This procedure was followed with the exception of test No. 3A where the second
stage test could not be performed validly due to wall geometry.,
.
2.2.1 First stage preparation.
A 12" dia, diamond drill type core borer was utilized to core through
the front facing block and into the concrete core, providing an "in-situ" sample
1528 161-'-
.. -.. _. .-.
''
' ~
; If I .
SITE 4 & 4A r | 9 i223 s-
,
| -.
: g' s W,
|
sa v .M _ . _ .@ . I._. =
551 i
r#'4 ;' '
SITE 2 & 2A- SITE 5 & SA*
|'DI
SITE 3 \,
I. i
SITE 8 & 8A- k#' ''
s5 E; : ',7'
.M I: >2?^hOg F,- - -
.- u.
E s. .
-
:
I
--. - ga<. i
es! *
f* bOH
# "'-
s!l t'-,, ,,
SITE 7 & 7A g ,
9t'fI
|, +
' 5' PAP,TI AL FLOOR PLAN 6 25',,
p) ,
j_., ),ySITE9&9A~
r,
' ,u! -. - ,
i (' hgyn. gw mn.- s
V f g=2-.
|t
-
D - - FIG. 2.1,
PARTIAL FLOOR PLAN 8 5' 1528 162_4_
m - e .
s a,
of 11-1/2" dia, with a 1/4" annulus between it and toe surrounding material.3-
Block dimensions are 7-5/8" thick. To assure adequate penetration of the
block the core bore was extendad beyond that depth by about 1".
Initial placing of vedge anchors utilized one of two recommended.
patterns as depicted in Figure 2.2. Anchor bolts utilized were 3/4" phillips
wedge anchors set to the =anufacturers recoc=endations and torqued prior to
the coring operation. The 11-1/2" dia. core was drilled concentric round the
6" dia. anchor tolt pitch circle. This method (utilizing three wedge anchors)
was discontinued following the first three tests due to the concern of possible
bolt interaction and was replaced by a method utilizing one central 1" phillips
wedge anchor.
2.2.2 First stage testing.
The testing equipment utilized consisted of the following:
1. Fabricated compression beam and bearing plate, hydraulic jack
support bracket with 4 "C" clamps. Figure 2.3
2. Threaded 1" dia. rod with nuts and coupling.
3. Calibrate; hydraulic jacking system * consisting of:
a. Enerpac Eand Pump (SN 11754)
b. Enerpac 30 Ton Ram (SN 11752)
Ashcrof t 3000 PSIG Hydraulic Gauge (SN 11755)c.
*This equipment provided and operated by Northwest Testing 'aboratories. SeeAppendix 1.
-5-
__
, ..
..
|
3TYPE 5.2 CENTER OF 6" BOLT CIRCLEI
I
y-| BLOCK JOINT (TYP.)
!_ h _ _ .2 _
~
3/4" HOLE (TYP.)O'
12" 0.0._ -
M 5.3 11 " I.D. _ ,
.
I| '= BLOCK JOINT (TYP.)
I
i CENTER OF BLOCK
: \ ))|O 3/4" HOLE (TYP.)_ g _ - _ _ 7 _= _ _ , _ _
'
CENTRAL ANCHOR -
1" HOLE (TYP.)l
n
I != BLOCK JOINT (TYP.)i I
'$ |*
|y : i = CENTER OF BLOCK.
!*/ |
N C | |__L_ ______._s__
Uo
FIG. 2.2-6-
1528 164ma w.m , , . .
* O
s' e
i |
| !,. .
!| | !!; i i
'
|
PLAN VIEW _
i
_ _ _ _ _ .J______ __ _
j.
_c--
ELEVATION VIEW
FI G, 2.3
-7-
1528 165
.-. . . . - -. . . _
- .
'
.- .
d. Ashcrof t 6000 PSIG Hydraulic Gauge (SN 11757)
Multi-port Hydraulic Couplings and Hydraulic Hose.e.
4. Two dial micrometer.
.
The assembled test rig is shown in Figure 2.4
The testing was perforned in accordance with SPT-51 (Special
Plant Test - 51) Rev. O included here as Appendix 2. Results were recorded in
accordance with SPT-51 and also independently by the Northwest Testing Laboratory
Representative. These results are reproduced in Section 3 of this report.
2.2.3 Second stage preparation
Following completion of the first stage test for each rest site and
subsequent napping and photography of the broken section a 1" dia, phillips
wedge anchor was set into the central core concrete, concentric with the exist-
ing geometry, and further coring utilizing the 11-1/2" dia. core borer proceeded.
The depth of the coring was determined such that the inside surface of the re-
=aining block was just penetrated (no more than 1/8") .
.
2.2.4 Second stage testing
*The testing was performed as described in Section 2.2.2. Subsequent
to the testing the broken sections were mapped and photographed.
.
-8-
1SJ28 166
- -._
. ..
'tI Il
||il !
////kH//EV//n .
E ?' I
,
,
y . .
t i i !
l ! ! I
7 4\ ., - _=
I| -s,,
'! |i -
!! M.1,,p
.5i
PLAN VIEW
"C" CLAMP LOCATION TYP. ALL CORNERS
I I, .
f_ _ __ _ i _I i_.. s,
-
,i'
; --7 , - ".(-- ",
' i ! j
ELEVATION
FIG. 2 A.
g
1528 167 '
.- . ._ ...
.
, ,
#
Section 3 Results
The test results were recorded by PGE personnel utilizing the dr.ta
sheet from $PT-51, Rev. O and were also recorded by Northwest Testing Laboratory
Representative using standard laboratory workaheets. Appendix 1 provides.
a su==ary from Northwest Testing Laboratories of tha failure loads and cali-
bration data for the test equipment. Appendix 2 provides a copy of SPT-51
(Special Plant Test Procedure). (The deflection data from the microne 2rs was
disregarded due to the difficulty of obtaining representative readings).
In addition, all test sites were mapped and the broken spec 1=ents photographed.
.
The results are presented 's tabular form Table 3.1.
.
3
}h-10-
_ _ . _ _ __ _
j-
~
TABl.E 3.1.
TAllUI.ATIOt10F TEST RESUI.TS.
-
|
1'
110. OF CYCLESTE.ST D1 A Al i I.I I.0AD.
LOCATIOli APPLIED| SITE PATTER!l 0F COHE
AT FAILURE5,000# 7,500# 10,000# 15,000# 20,000f: 4
. 2 Elev. 25' 5.3 8 1/16" 5 0 1 0 0 9,820ff
i! 2A Eic e. 25' Central Anctior 20 1/2" 5 3 3 0 0 17,670f
3 Elev. 25' 5.2 9 1/4" 1 0 0 0 0 4,5007
4 Elev. 25' 5.3 9" 5 2 0 0 0 7,120f
; 4A Elev. 25' Central Anctior 19 1/2" 5 3 3 0 0 24,5007
), 5 Elev. 25' 5.3 9" 5 0 0 0 0 4,730f
r.
i SA Elev. 25' Central Anctior 19 7/16" 5 3 3 0 0 14,460#!
7 Elev. 25' Central Anctior 9 1/8" 5 3 3 3 0 15,G90f
I 7A Elev. 25' Central Anciaor 19 3/4" 5 5 5 5 3 21,790#
8 Elev. 25' Central Anctior 9" 1 0 0 0 0 3,7907
8A ! Elev. 25' Central Anctior 22" 5 5 5 5 0 14,8507
9 Elev. S' Central Anctior 9" 5 5 5 3 0 l 'i,000f
9A Elev. 5' central Anctior 12 1/8" 5 5 5 5 1 21,7907s
NCO .
-
@
i.
. .
Section 4 Evaluation of Test Results,
The testing results were evaluated by a representative of Wiss, Janney,
Eistner & Associates Incorporated of Chicago. The report is attached as Appendix
3.
_
e
9
-12-
1528 170
. . .. _ .. _ .. -
*13V1111177 M 1 11.A.J 1 A.L 1 % JI .2 a AJ / %# Au n. a. v s swv*.
f, 's . 4115 N. MISSISSIPPtAVENuEP. O. 5OX 17126 mon.ossinuenya vasnno
constavenom insesenose wasoswo cannricanon" Avan ass insesano" P Q R T t. A N D. OREGCN 97217 so66 vasnnoenameca6 ana6vs s .ss n.o
vs.cai vasn o
November 19, 1979
Portland General Electric Company -
121 S.W. SalmonPortland, Oregon 07204
Re: Trojon Nuclear Power Plant
Report Of: Composit Wall Masonry Block - Concrete Core interface Bond Testing
Load App!ication EquipmentTest Loads were applied by e calibrated hydraulic jacking system consistingof the following: Enerpac hand pump (SN11754), Enerpac 30 Ton Ram(SN11752), Ashcraft 3000 Psig hydraulic gage (SN 11755), Ashcraft 6000psig hydraulic gage (SN11757), Multi-Port hydraulic coupling and 25 feetof hydraulic hose.
Test Site No. Ulimate Failure Loads (Pounds)* Cage Used .{ PSI 6)
1 Not Applicable / Hit Rebar in Block2 9820 60002A 17670 60JO
3 4500 60004 7120 60004A 24500 60005 4730 3000SA 14460 60006 Not Applicable /Not Composit Wall7 15890 60007A 21790 60008 3790 30008A 14850 30009 15000 30009A 21790 6000
* Note: Failure Loads determined by Mathmatical Interpolation betweenadjacent calibration points.
.
e
.
1528 171
. -- .
-
. .o...... . .. . . ... ... ....,. .., ._,. _.
', Re: Trojan Nucelar Power Planti ,
The test loading system, including hydraulic ram, couplings and pressuregages were calibrated on a Tinius Olson Testing Machine. Certifiedaccuracy of this machine was established December 7,197f by Cal-Cert Co.
8 f u nluihBy hand pumping, a wide range of loads were applied to the test machine.These loads along with the associated gage pressures were recorded. This ,
was done for both the 3000 Psig PCE gage and the 6000 Psig NorthwestTesting laboratory gage. Results of this calibaration follows:
Actual Load (pounds)from Tinius Olson 3000 PSIC Gage 6000 PSIG Cage
320 100 200950 . 200 30 0
1,690 300 3752,390 400 4752,500 430 5005,000 800 8757,500 1150 1225
10,000 1500 157512,500 1860 192515,000 2200 227517,500 2540 262522,000 2900 300022,500 beyond range 335025,000 beyond range 372527,500 beyond range 407530,000 beyond range 4425
.
Respectfully,NORTHWEST TESTING LABORATORIES, INC.
9
_
Charles R. Lane, P.E.
CRL/lz
Report No. 211094
:
1523 172
-- .