Reflective Products: An Energy- Reflective Products: An Energy- Savings Solution for Post-Frame Savings Solution for Post-Frame Buildings Buildings David W. Yarbrough, PhD, PE David W. Yarbrough, PhD, PE R&D Services, Inc. R&D Services, Inc. Cookeville, TN Cookeville, TN Sponsored by The Reflective Sponsored by The Reflective Insulation Insulation Manufacturers Association Manufacturers Association International International

Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

  • Upload
    wayne

  • View
    21

  • Download
    0

Embed Size (px)

DESCRIPTION

Reflective Products: An Energy-Savings Solution for Post-Frame Buildings. David W. Yarbrough, PhD, PE R&D Services, Inc. Cookeville, TN Sponsored by The Reflective Insulation Manufacturers Association International. - PowerPoint PPT Presentation

Citation preview

Page 1: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Reflective Products: An Energy-Savings Reflective Products: An Energy-Savings Solution for Post-Frame BuildingsSolution for Post-Frame Buildings

David W. Yarbrough, PhD, PEDavid W. Yarbrough, PhD, PE

R&D Services, Inc.R&D Services, Inc.

Cookeville, TNCookeville, TN

Sponsored by The Reflective InsulationSponsored by The Reflective Insulation

Manufacturers Association InternationalManufacturers Association International

Page 2: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Components of this PresentationComponents of this Presentation

Physical Basis: Design of InsulationsPhysical Basis: Design of Insulations Expected PerformanceExpected Performance

Installation - Reflective AssembliesInstallation - Reflective Assemblies

Savings – Reduce Heating/CoolingSavings – Reduce Heating/Cooling

Hybrid SystemsHybrid Systems

Page 3: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

A Time LineA Time Line

1650-1850 The physics is established1650-1850 The physics is established 1850-1920 Air space resistance recognized1850-1920 Air space resistance recognized 1920-1950 Reflective systems appear1920-1950 Reflective systems appear 1950-1985 Reflective data base is developed1950-1985 Reflective data base is developed 1985-20001985-2000 Product development Product development 2000- Advanced systems2000- Advanced systems

Page 4: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

ProductProduct Categories Categories

Reflective InsulationsReflective Insulationsenclosed air space (0-10 in.)enclosed air space (0-10 in.)R-valueR-valueASTM C 1224, ASTM C 1363ASTM C 1224, ASTM C 1363

Radiant BarriersRadiant Barriers large (ventilated) air space (2-20 ft)large (ventilated) air space (2-20 ft) reduction in heat flowreduction in heat flow ASTM C 1313, ASTM C 1340ASTM C 1313, ASTM C 1340 Interior Radiation Control CoatingsInterior Radiation Control Coatings Increases air film resistance (at surface)Increases air film resistance (at surface) ASTM C 1321ASTM C 1321

A property in common to all of these products: low thermal A property in common to all of these products: low thermal emittance (low emissivity)emittance (low emissivity)

Page 5: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Reflective Insulations and Radiant Reflective Insulations and Radiant Barriers have Low-Emittance SurfacesBarriers have Low-Emittance Surfaces

Reflective InsulationsReflective Insulations

Enclosed air spaceEnclosed air space

Small air gap ( 0-6 in. )Small air gap ( 0-6 in. )

Thermal Resistance ( up to 14 )Thermal Resistance ( up to 14 )

Radiant Barriers (attic)Radiant Barriers (attic)

Open air space (or ventilated Open air space (or ventilated space)space)

Large air gap ( up to 10-15 ft. )Large air gap ( up to 10-15 ft. )

Thermal ResistanceThermal Resistance

Page 6: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Large Scale Test FacilityLarge Scale Test Facility12 by 12 ft. specimen12 by 12 ft. specimen

8 by 8 ft. metering area8 by 8 ft. metering area

Page 7: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings
Page 8: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Design of InsulationsDesign of Insulations

Insulations Based on AirInsulations Based on Air

Mechanism Mechanism Mass-TypeMass-Type Reflective-TypeReflective-TypeConduction Increases Increases-slightConduction Increases Increases-slight

Convection None DecreasesConvection None Decreases (some exceptions)(some exceptions)

Radiation Decreases Almost ZeroRadiation Decreases Almost Zero

Increase in conduction because solids like glass, wood, Increase in conduction because solids like glass, wood,

concrete, or paper have much higher thermal conductivityconcrete, or paper have much higher thermal conductivity

than air. Air is an excellent thermal insulation.than air. Air is an excellent thermal insulation.

Page 9: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Thermal Conductivity of AirThermal Conductivity of Air

T (°F)T (°F) k (Btuk (Btu∙∙in./ftin./ft22∙∙hh∙∙°F) °F) R/inchR/inch

00 0.1550.155 6.456.45

7575 0.1780.178 5.625.62

100100 0.2010.201 4.784.78

No Convection and No RadiationNo Convection and No Radiation

Page 10: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Thermal Emittance (Thermal Emittance (εε) – A Property) – A Property

A fraction 0 < A fraction 0 < εε < 1 that is measured. < 1 that is measured. εε = 0 no radiation = 0 no radiation εε = 1 maximum radiation (black body) = 1 maximum radiation (black body)

Page 11: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

^̂ ↓ ↓(radiation in, Q(radiation in, Qradrad) |) | ↓ ↓ (radiation reflected, r)(radiation reflected, r)______________________________________//______________________________|_ →→(radiation absorbed, a) |_|_ →→(radiation absorbed, a) |_|__________________________________|_|__________________________________|_ ↓ ↓ ↓ ↓(radiation transmitted, t)(radiation transmitted, t)

Page 12: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Radiation TerminolgyRadiation Terminolgy

QQrad rad = Reflected + Absorbed + Transmitted= Reflected + Absorbed + Transmitted If opaque ,then transmitted is zero (t=0)If opaque ,then transmitted is zero (t=0) Expressed as fractionsExpressed as fractions

1 = r + a but 1 = r + a but a = ea = e so we have so we have

1 = r + e1 = r + e

If e is small, then r is largeIf e is small, then r is large

e= 0.03, r= 0.97 systems perform in both directionse= 0.03, r= 0.97 systems perform in both directions

Page 13: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Total Hemispherical Emittance Total Hemispherical Emittance (all directions)(all directions)

PaintsPaints 0.8 < e < 1.00.8 < e < 1.0

WoodWood 0.8 < e < 0.90.8 < e < 0.9

MasonryMasonry 0.9 < e < 1.00.9 < e < 1.0

MetalsMetals 0.02 < e < 0.100.02 < e < 0.10

IRCCIRCC 0.15 < e < 0.250.15 < e < 0.25

aluminum foil aluminum foil 0.03<e<0.040.03<e<0.04

Al metallized film Al metallized film 0.04<e<0.060.04<e<0.06

Page 14: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

What to choose ? What to choose ? ε→ε→00

At 75 °F (room temperature)At 75 °F (room temperature)

AluminumAluminum 0.030.03

Polished brassPolished brass 0.030.03

CadmiumCadmium 0.020.02

Polished copperPolished copper 0.030.03

GoldGold 0.02-0.030.02-0.03

NickelNickel 0.040.04

PlatinumPlatinum 0.030.03

TinTin 0.050.05

ZincZinc 0.050.05

American Institute of Physics (early edition)American Institute of Physics (early edition)

Page 15: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Why Emittance is Key PropertyWhy Emittance is Key Property(Boltzmann Equation)(Boltzmann Equation)

Q/A = E * [ Q/A = E * [ σσ * (T * (T4422

– T– T4411)])]

↑ ↑

1/E=1/e1/E=1/e1 1 + 1/e+ 1/e2 2 – 1– 1

ee1 1 ee2 2 E % reductionE % reduction

no foil/film no foil/film 1 1 1 1 1 1 00Foil one side Foil one side 1 0.03 0.03 1 0.03 0.03 9797Foil one side Foil one side 0.03 1 0.03 0.03 1 0.03 9797Foil both sides Foil both sides 0.03 0.03 0.015 0.03 0.03 0.015 98.598.5

Page 16: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Boltzmann 1844-1906 AustriaBoltzmann 1844-1906 AustriaStefan published in 1879 Boltzmann published in 1884Stefan published in 1879 Boltzmann published in 1884Stefan-Boltzmann Law and Stefan-Boltzmann ConstantStefan-Boltzmann Law and Stefan-Boltzmann Constant

5.6704 x 105.6704 x 10-8 -8 W/m W/m22·K·K44

Page 17: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Transfer Mechanisms

0102030405060708090

100

0 0.2 0.4 0.6 0.8 1

Effective Emittance (E)

% o

f T

OT

AL RADIATION

CONVECTION

CONDUCTION

Page 18: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Insulation Assembly DesignInsulation Assembly Design Identify the space to be insulated.Identify the space to be insulated. ChoicesChoices Attach RI to one side or the otherAttach RI to one side or the other to create a single reflective air to create a single reflective air

space. space.

Attach RI in center to form twoAttach RI in center to form two reflective air spaces.reflective air spaces.

Install RI that forms more than twoInstall RI that forms more than two reflective air spaces.reflective air spaces.

Page 19: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings
Page 20: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings
Page 21: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings
Page 22: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Heat Flow Down

4

6

8

10

12

14

16

0 0.05 0.1 0.15 0.2

Emittance

R

1D

2D

Page 23: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Horizontal Heat Flow

4

4.5

5

5.5

6

6.5

7

0 0.05 0.1 0.15 0.2

Emittance

R

1D

2D

Page 24: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Heat Flow Up

33.2

3.43.63.8

44.24.4

4.64.8

0 0.05 0.1 0.15 0.2

Emittance

R 1D

Page 25: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Quick Estimate of SavingsQuick Estimate of Savings Use HDD/CDD dataUse HDD/CDD data CLIMATOGRAPHY OF THE UNITED STATES No. 81 CLIMATOGRAPHY OF THE UNITED STATES No. 81

SUPPLEMENT NO. 2SUPPLEMENT NO. 2 Title: “Annual Degree Days to Selected Bases”Title: “Annual Degree Days to Selected Bases” Heating: 40 to 65 °F Cooling: 45 to 70 °FHeating: 40 to 65 °F Cooling: 45 to 70 °F Louisville HDDLouisville HDD65 65 4352 CDD 4352 CDD70 70 797797 Heat flow out Heat flow out HDD*24*Area/RHDD*24*Area/R Utility Use Utility Use HDD*24*Area/(R*E)HDD*24*Area/(R*E) Heat flow in Heat flow in CDD*24*Area/RCDD*24*Area/R Utility Use Utility Use CDD*24*Area/(R*COP)CDD*24*Area/(R*COP) Convert from BTU/yr to KWH/yr multiply by 0.000293Convert from BTU/yr to KWH/yr multiply by 0.000293 Kwh at 0.1 as exampleKwh at 0.1 as example

Page 26: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Calculation of SavingsCalculation of SavingsLouisville – 1000 square feetLouisville – 1000 square feet

Savings for 1000 square feet

0

500

1000

1500

2000

0 5 10 15 20

Added R (Base R 2)

Sav

ing

s ($

/yr)

Cooling

Heating

Total

Page 27: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Hybrid SystemsHybrid Systems

Combine TechnologiesCombine Technologies

Examples: fiberglass + foamExamples: fiberglass + foam

fiberglass + reflectivefiberglass + reflective

foam + reflectivefoam + reflective

Utilize air spaces to increase R-valueUtilize air spaces to increase R-value

Page 28: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings
Page 29: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

Wall Cavity R vs. R* of Foam

5

7.5

10

12.5

15

17.5

20

3 4 5 6 7

R-per-inch of Foam

Wal

l Cav

ity R

0.5 in.

1.0 in.

1.5 in.

2.0 in.

Page 30: Reflective Products: An Energy-Savings Solution for Post-Frame Buildings

SummarySummary

Reflective technology is a mature areaReflective technology is a mature area Products: Insulation, radiant barriers, IRCCsProducts: Insulation, radiant barriers, IRCCs Evaluation: laboratory measurementsEvaluation: laboratory measurements

and/or engineering calculationsand/or engineering calculations Quick estimates of savings are possibleQuick estimates of savings are possible Combine technologies: HybridsCombine technologies: Hybrids