September 2010 • Supersedes 1/2009 Reference Data Reclosers Form 4A, Form 4C, Form 4D, Form 5, Form 5/TS, Form 6, Form 6-TS, FX, FXA, and FXB Recloser Controls Time-Current Curves R280-91-34 1 CURRENT (percent of minimum trip) TIME (sec) .06 .08 .2 .3 .1 2 4 5 6 8 10 20 30 40 50 60 3 .4 .5 .6 .8 .01 .02 .03 .04 .05 1 6000 5000 4000 3000 2000 1000 400 300 200 800 600 500 50000 40000 30000 20000 10000 8000 80 60 50 100 3.6 4.8 12 18 6.0 120 240 300 360 480 600 1200 1800 2400 3000 3600 180 24 30 36 48 0.6 1.2 1.8 2.4 3.0 60 TIME [cycles (60 hertz basis)] Time-Current Curve Cross Reference Form 3A to Form 4A, Form 4C, Form 4D, Form 5, Form 5/TS, Form 6, Form 6-TS, Types FX, FXA, and FXB F4 - All F4 - All F5 - All F5 - All F6 - All F6 - All F3A FX - All F3A FX - All TCC TCC TCC TCC 1 102 A 101 2 135 B 117 3 140 C 133 4 106 D 116 5 114 E 132 6 136 F 163 7 152 G 121 8 113 H 122 8* 111 J 164 8+ 111 K-Phase 162 9 131 L 107 11 141 M 118 13 142 N 104 14 119 P 115 15 112 R 105 16 139 T 161 17 103 V 137 18 151 W 138 K-Ground 165 Y 120 Z 134 TCC-634R_ Contents 101. . . . . . . 2 133 ....... 2 102. . . . . . . 5 134 ....... 8 103. . . . . . . 9 135 ....... 3 104. . . . . . . 2 136 ....... 6 105. . . . . . . 3 137 ....... 6 106. . . . . . . 10 138 ....... 2 107. . . . . . . 11 139 ....... 4 111. . . . . . . 4 140 ....... 3 112. . . . . . . 11 141 ...... 10 113. . . . . . . 11 142 ....... 6 114. . . . . . . 8 151 ....... 7 115. . . . . . . 7 152 ...... 11 116. . . . . . . 4 161 ....... 9 117. . . . . . . 3 162 ....... 9 118. . . . . . . 9 163 ....... 5 119. . . . . . . 10 164 ....... 5 120. . . . . . . 8 165 ....... 8 121. . . . . . . 6 200 ...... 12 122. . . . . . . 5 201 ...... 12 131. . . . . . . 10 202 ...... 12 132. . . . . . . 7 Curve No. Page Curve No. Page Maximum Short Time Recloser Limits When modifying F4A, F4C, F4D, F5, F5/TS, F6, F6-TS, FX, FXA, and FXB time-current curves, refer to Maxi- mum Short Time Recloser Limits on page 13. Recloser Clearing Time Add the following recloser interrupting time in seconds to the control response time to obtain average recloser clearing time; variations ±0.01 second: Recloser Interrupting Type Time NOVA (ACT II) 0.025 VSA12, VSA16, VSA20, VSA20A, VSA20B, VSAT, VSO12, VSO16, NOVA (ACT I), NOVA-TS, NOVA STS 0.042 VWE, VWVE27, VWVE38, PWE, PWVE, VWVE38X 0.034 RXE, RVE, WE, WVE, WVE38X 0.045 Form 4A, Form 4C Timing Group Time-Current Curves 101 101 101 101 102 102 102 102 104 104 103 104 105 105 104 105 106 106 105 106 111 107 106 111 114 111 111 114 116 112 115 116 117 113 116 117 119 116 117 119 131 117 120 131 132 118 121 132 133 132 122 133 135 133 132 135 136 135 133 136 138 138 134 138 140 140 135 140 141 152 137 141 142 161 139 200 162 163 140 201 165 164 151 202 Group 1 Group 2 Group 3 Group 4

Reference Data Recloser Controls Time-Current … 2010 • Supersedes 1/2009 Reference Data Reclosers Form 4A, Form 4C, Form 4D, Form 5, Form 5/TS, Form 6, Form 6-TS, FX, FXA, and

Embed Size (px)

Citation preview

September 2010 • Supersedes 1/2009

Reference Data

ReclosersForm 4A, Form 4C, Form 4D, Form 5, Form 5/TS,Form 6, Form 6-TS, FX, FXA, and FXBRecloser Controls Time-Current Curves R280-91-34

1

CURRENT (percent of minimum trip)

TIM

E (s

ec)

.06

.08

.2

.3

.1

2

4

5

6

8

10

20

30

40

50

60

3

.4

.5

.6

.8

.01

.02

.03

.04

.05

160

00

5000

4000

3000

2000

100040

0

300

200

800

600

500

5000

0

4000

0

3000

0

2000

0

1000

0

8000806050 10

0

3.6

4.8

12

18

6.0

120

240

300

360

480

600

1200

1800

2400

3000

3600

180

24

30

36

48

0.6

1.2

1.8

2.4

3.0

60

TIM

E [c

ycle

s (6

0 he

rtz

basi

s)]

Time-Current Curve Cross Reference Form 3A to Form 4A, Form 4C, Form 4D, Form 5, Form 5/TS, Form 6, Form 6-TS, Types FX, FXA, and FXB

F4 - All F4 - All F5 - All F5 - All F6 - All F6 - All F3A FX - All F3A FX - All TCC TCC TCC TCC

1 102 A 101 2 135 B 117 3 140 C 133 4 106 D 116 5 114 E 132 6 136 F 163 7 152 G 121 8 113 H 122 8* 111 J 164 8+ 111 K-Phase 162 9 131 L 107 11 141 M 118 13 142 N 104 14 119 P 115 15 112 R 105 16 139 T 161 17 103 V 137 18 151 W 138 K-Ground 165 Y 120 Z 134

TCC-634R_

Contents

101. . . . . . . 2 133 . . . . . . .2102. . . . . . . 5 134 . . . . . . .8103. . . . . . . 9 135 . . . . . . .3104. . . . . . . 2 136 . . . . . . .6105. . . . . . . 3 137 . . . . . . .6106. . . . . . .10 138 . . . . . . .2107. . . . . . .11 139 . . . . . . .4111. . . . . . . 4 140 . . . . . . .3112. . . . . . .11 141 . . . . . . 10113. . . . . . .11 142 . . . . . . .6114. . . . . . . 8 151 . . . . . . .7115. . . . . . . 7 152 . . . . . . 11116. . . . . . . 4 161 . . . . . . .9117. . . . . . . 3 162 . . . . . . .9118. . . . . . . 9 163 . . . . . . .5119. . . . . . .10 164 . . . . . . .5120. . . . . . . 8 165 . . . . . . .8121. . . . . . . 6 200 . . . . . . 12122. . . . . . . 5 201 . . . . . . 12131. . . . . . .10 202 . . . . . . 12132. . . . . . . 7

Curve No. Page Curve No. Page

Maximum Short TimeRecloser LimitsWhen modifying F4A, F4C, F4D, F5, F5/TS, F6, F6-TS, FX, FXA, and FXB time-current curves, refer to Maxi-mum Short Time Recloser Limits on page 13.

Recloser Clearing TimeAdd the following recloser interrupting time in seconds to the control response time to obtain average recloser clearing time; variations ±0.01 second:Recloser InterruptingType Time

NOVA (ACT II) 0.025VSA12, VSA16, VSA20, VSA20A, VSA20B, VSAT, VSO12, VSO16, NOVA (ACT I), NOVA-TS, NOVA STS 0.042VWE, VWVE27, VWVE38, PWE, PWVE, VWVE38X 0.034RXE, RVE, WE, WVE, WVE38X 0.045

Form 4A, Form 4CTiming Group Time-Current Curves

101 101 101 101 102 102 102 102 104 104 103 104

105 105 104 105 106 106 105 106 111 107 106 111

114 111 111 114 116 112 115 116 117 113 116 117

119 116 117 119 131 117 120 131 132 118 121 132

133 132 122 133 135 133 132 135 136 135 133 136

138 138 134 138 140 140 135 140 141 152 137 141

142 161 139 200 162 163 140 201 165 164 151 202

Group 1 Group 2 Group 3 Group 4

September 2010 • Supersedes 1/2009

Reference Data

ReclosersForm 4A, Form 4C, Form 4D, Form 5, Form 5/TS,Form 6, Form 6-TS, FX, FXA, and FXBRecloser Controls Time-Current Curves R280-91-34

6050

40

30

20

10

8

65

4

3

2

1

.8

.6

.5

.4

.3

.2

0.1

.08

.06

.02

.03

.04

.05

50 60 80 100

200

300

400

500

600

800

1000

2000

3000

4000

5000

6000

8000

1000

0

2000

0

3000

0

4000

0

5000

0

CURRENT (percent of minimum trip)

TIM

E (s

ec)

TIM

E [c

ycle

s (6

0 he

rtz

basi

s)]

0.6

1.2

1.8

2.4

3.03.6

4.8

6.0

12

18

24

3036

48

60

120

180

240

300360

480

600

1200

1800

2400

30003600

138

133

101

104

.01

2

TCC-634R_

Phase Trip or Ground TripControl Response Time

Curve 101: Maximum response time for one operation, variations negative

Curve 138: Average response time for one operation; variations ±10%

Curves 133 & 104: Average response time for one operation; variations ±10% or ±.008 second, whichever is greater

Tests conducted at 25 C

September 2010 • Supersedes 1/2009

Reference Data

ReclosersForm 4A, Form 4C, Form 4D, Form 5, Form 5/TS,Form 6, Form 6-TS, FX, FXA, and FXBRecloser Controls Time-Current Curves R280-91-34

60

50

40

30

20

10

8

65

4

3

2

1

.8

.6

.5

.4

.3

.2

0.1

.08

.06

.01

.02

.03

.04

.05

50 60 80 100

200

300

400

500

600

800

1000

2000

3000

4000

5000

6000

8000

1000

0

2000

0

3000

0

4000

0

5000

0

CURRENT (percent of minimum trip)

TIM

E (s

ec)

TIM

E [c

ycle

s (6

0 he

rtz

basi

s)]

0.6

1.2

1.8

2.4

3.03.6

4.8

6.0

12

18

24

3036

48

60

120

180

240

300360

480

600

1200

1800

2400

30003600

140

135

105

117

3

TCC-634R_

Phase Trip or Ground TripControl Response Time

Curves 135 & 140: Average response time or one operation; variations ±10%

Curves 105 & 117: Average response time for one operation; variations ±10% or ±.008 second, whichever is greater

Tests conducted at 25 C

September 2010 • Supersedes 1/2009

Reference Data

ReclosersForm 4A, Form 4C, Form 4D, Form 5, Form 5/TS,Form 6, Form 6-TS, FX, FXA, and FXBRecloser Controls Time-Current Curves R280-91-34

6050

40

30

20

10

8

65

4

3

2

1

.8

.6

.5

.4

.3

.2

0.1

.08

.06

.01

.02

.03

.04

.05

50 60 80 100

200

300

400

500

600

800

1000

2000

3000

4000

5000

6000

8000

1000

0

2000

0

3000

0

4000

0

5000

0

CURRENT (percent of minimum trip)

TIM

E (s

ec)

TIM

E [c

ycle

s (6

0 he

rtz

basi

s)]

0.6

1.2

1.8

2.4

3.03.6

4.8

6.0

12

18

24

3036

48

60

120

180

240

300360

480

600

1200

1800

2400

30003600

139

111

116

4

TCC-634R_

Phase Trip or Ground TripControl Response Time

Curves 111, 116, & 139: Average response time for one operation; variations ±10% or ±.008 second, whichever is greater

Tests conducted at 25 C

September 2010 • Supersedes 1/2009

Reference Data

ReclosersForm 4A, Form 4C, Form 4D, Form 5, Form 5/TS,Form 6, Form 6-TS, FX, FXA, and FXBRecloser Controls Time-Current Curves R280-91-34

6050

40

30

20

10

8

65

4

3

2

1

.8

.6

.5

.4

.3

.2

0.1

.08

.06

.01

.02

.03

.04

.05

50 60 80 100

200

300

400

500

600

800

1000

2000

3000

4000

5000

6000

8000

1000

0

2000

0

3000

0

4000

0

5000

0

CURRENT (percent of minimum trip)

TIM

E (s

ec)

TIM

E [c

ycle

s (6

0 he

rtz

basi

s)]

0.6

1.2

1.8

2.4

3.03.6

4.8

6.0

12

18

24

3036

48

60

120

180

240

300360

480

600

1200

1800

2400

3000

3600

102

122

164163

5

TCC-634R_

Phase Trip or Ground TripControl Response Time

Curve 102: Maximum response time for one operation, variations negative

Curves 163, 164, & 122: Average response time for one operation, variations ±10% or ±.008 second, whichever is greater

Tests conducted at 25 C

September 2010 • Supersedes 1/2009

Reference Data

ReclosersForm 4A, Form 4C, Form 4D, Form 5, Form 5/TS,Form 6, Form 6-TS, FX, FXA, and FXBRecloser Controls Time-Current Curves R280-91-34

6050

40

30

20

10

8

65

4

3

2

1

.8

.6

.5

.4

.3

.2

0.1

.08

.06

.01

.02

.03

.04

.05

50 60 80 100

200

300

400

500

600

800

1000

2000

3000

4000

5000

6000

8000

1000

0

2000

0

3000

0

4000

0

5000

0

CURRENT (percent of minimum trip)

TIM

E (s

ec)

TIM

E [c

ycle

s (6

0 he

rtz

basi

s)]

0.6

1.2

1.8

2.4

3.03.6

4.8

6.0

12

18

24

3036

48

60

120

180

240

300360

480

600

1200

1800

2400

30003600

137

142

121

136

6

TCC-634R_

Phase Trip or Ground TripControl Response Time

Curve 137: Average response time for one operation; variations ±10%

Curves 121, 136, & 142: Average response time for one operation, variations ±10% or ±.008 second, whichever is greater

Tests conducted at 25 C

September 2010 • Supersedes 1/2009

Reference Data

ReclosersForm 4A, Form 4C, Form 4D, Form 5, Form 5/TS,Form 6, Form 6-TS, FX, FXA, and FXBRecloser Controls Time-Current Curves R280-91-34

60

50

40

30

20

10

8

65

4

3

2

1

.8

.6

.5

.4

.3

.2

0.1

.08

.06

.01

.02

.03

.04

.05

50 60 80 100

200

300

400

500

600

800

1000

2000

3000

4000

5000

6000

8000

1000

0

2000

0

3000

0

4000

0

5000

0

CURRENT (percent of minimum trip)

TIM

E (s

ec)

TIM

E [c

ycle

s (6

0 he

rtz

basi

s)]

0.6

1.2

1.8

2.4

3.03.6

4.8

6.0

12

18

24

3036

48

60

120

180

240

300360

480

600

1200

1800

2400

30003600

151

132

115

7

TCC-634R_

Phase Trip or Ground TripControl Response Time

Curve 151: Average response time for one operation; variations ±10%

Curves 115 & 132: Average response time for one operation, variations ±10% or ±.008 second, whichever is greater

Tests conducted at 25 C

September 2010 • Supersedes 1/2009

Reference Data

ReclosersForm 4A, Form 4C, Form 4D, Form 5, Form 5/TS,Form 6, Form 6-TS, FX, FXA, and FXBRecloser Controls Time-Current Curves R280-91-34

60

50

40

30

20

10

8

65

4

3

2

1

.8

.6

.5

.4

.3

.2

0.1

.08

.06

.01

.02

.03

.04

.05

50 60 80 100

200

300

400

500

600

800

1000

2000

3000

4000

5000

6000

8000

1000

0

2000

0

3000

0

4000

0

5000

0

CURRENT (percent of minimum trip)

TIM

E (s

ec)

TIM

E [c

ycle

s (6

0 he

rtz

basi

s)]

0.6

1.2

1.8

2.4

3.03.6

4.8

6.0

12

18

24

3036

48

60

120

180

240

300360

480

600

1200

1800

2400

30003600

165

134

114

120

8

TCC-634R_

Phase Trip or Ground TripControl Response Time

Curves 120 & 134: Average response time for one operation; variations ±10%

Curve 114 & 165: Average response time for one operation, variations ±10% or ±.008 second, whichever is greater

Tests conducted at 25 C

Curve 165 starts at 100% minimum trip at 90 seconds.

September 2010 • Supersedes 1/2009

Reference Data

ReclosersForm 4A, Form 4C, Form 4D, Form 5, Form 5/TS,Form 6, Form 6-TS, FX, FXA, and FXBRecloser Controls Time-Current Curves R280-91-34

6050

40

30

20

10

8

65

4

3

2

1

.8

.6

.5

.4

.3

.2

0.1

.08

.06

.01

.02

.03

.04

.05

50 60 80 100

200

300

400

500

600

800

1000

2000

3000

4000

5000

6000

8000

1000

0

2000

0

3000

0

4000

0

5000

0

CURRENT (percent of minimum trip)

TIM

E (s

ec)

TIM

E [c

ycle

s (6

0 he

rtz

basi

s)]

0.6

1.2

1.8

2.4

3.03.6

4.8

6.0

12

18

24

3036

48

60

120

180

240

300360

480

600

1200

1800

2400

30003600

162

118

103

161

9

TCC-634R_

Phase Trip or Ground TripControl Response Time

Curves 103, 118, 161, & 162: Average response time for one operation, variations ±10% or ±.008 second, whichever is greater

Tests conducted at 25 C

September 2010 • Supersedes 1/2009

Reference Data

ReclosersForm 4A, Form 4C, Form 4D, Form 5, Form 5/TS,Form 6, Form 6-TS, FX, FXA, and FXBRecloser Controls Time-Current Curves R280-91-34

60

50

40

30

20

10

8

65

4

3

2

1

.8

.6

.5

.4

.3

.2

0.1

.08

.06

.01

.02

.03

.04

.05

50 60 80 100

200

300

400

500

600

800

1000

2000

3000

4000

5000

6000

8000

1000

0

2000

0

3000

0

4000

0

5000

0

CURRENT (percent of minimum trip)

TIM

E (s

ec)

TIM

E [c

ycle

s (6

0 he

rtz

basi

s)]

0.6

1.2

1.8

2.4

3.03.6

4.8

6.0

12

18

24

3036

48

60

120

180

240

300360

480

600

1200

1800

2400

30003600

131

119

106

141

10

TCC-634R_

Phase Trip or Ground TripControl Response Time

Curves 119, 131, & 141: Average response time for one operation; variations ±10%

Curve 106: Average response time for one operation, variations ±10% or ±.008 sec-ond, whichever is greater

Tests conducted at 25 C

September 2010 • Supersedes 1/2009

Reference Data

ReclosersForm 4A, Form 4C, Form 4D, Form 5, Form 5/TS,Form 6, Form 6-TS, FX, FXA, and FXBRecloser Controls Time-Current Curves R280-91-34

60

50

40

30

20

10

8

65

4

3

2

1

.8

.6

.5

.4

.3

.2

0.1

.08

.06

.01

.02

.03

.04

.05

50 60 80 100

200

300

400

500

600

800

1000

2000

3000

4000

5000

6000

8000

1000

0

2000

0

3000

0

4000

0

5000

0

TIM

E (s

ec)

TIM

E [c

ycle

s (6

0 he

rtz

basi

s)]

0.6

1.2

1.8

2.4

3.03.6

4.8

6.0

12

18

24

3036

48

60

120

180

240

300360

480

600

1200

1800

2400

30003600

113

112

107

152

CURRENT (percent of minimum trip)

11

TCC-634R_

Phase Trip or Ground TripControl Response Time

Curves 113 & 152: Average response time for one operation; variations ±10%

Curves 107 & 112: Average response time for one operation, variations ±10% or ±.008 second, whichever is greater

Tests conducted at 25 C

Curve 152 starts at 100% mini-mum trip at 74 seconds.

September 2010 • Supersedes 1/2009

Reference Data

ReclosersForm 4A, Form 4C, Form 4D, Form 5, Form 5/TS,Form 6, Form 6-TS, FX, FXA, and FXBRecloser Controls Time-Current Curves R280-91-34

6050

40

30

20

10

8

65

4

3

2

1

.8

.6

.5

.4

.3

.2

0.1

.08

.06

.01

.02

.03

.04

.05

50 100

200

300

400

500

600

800

1000

2000

3000

4000

5000

6000

8000

1000

0

2000

0

3000

0

4000

0

5000

0

CURRENT (percent of minimum trip)

TIM

E (s

ec)

TIM

E [c

ycle

s (6

0 he

rtz

basi

s)]

0.6

1.2

1.8

2.4

3.03.6

4.8

6.0

12

18

24

3036

48

60

120

180

240

300360

480

600

1200

1800

2400

30003600

200

80

202

201

60

12

TCC-634R_

Phase Trip or Ground TripControl Response Time

Curves 200, 201, & 202: Average response time for one operation; variations ±10% or ±.008 second, whichever is greater

Tests conducted at 25 C

Curves 200, 201, & 202 start at 100% minimum trip. Timing is indeterminate at currents less than 110%.

September 2010 • Supersedes 1/2009

Reference Data

ReclosersForm 4A, Form 4C, Form 4D, Form 5, Form 5/TS,Form 6, Form 6-TS, FX, FXA, and FXBRecloser Controls Time-Current Curves R280-91-34

60

50

40

30

20

10

8

65

4

3

2

1

.8

.6

.5

.4

.3

.2

0.1

.08

.06

.01

.02

.03

.04

.05

50 60 80 100

200

300

400

500

600

800

1000

2000

3000

4000

5000

6000

8000

1000

0

2000

0

3000

0

4000

0

5000

0

CURRENT (amps)

TIM

E (s

ec)

TIM

E [c

ycle

s (6

0 he

rtz

basi

s)]

0.6

1.2

1.8

2.4

3.03.6

4.8

6.0

12

18

24

3036

48

60

120

180

240

300

360

480

600

1200

1800

2400

30003600

1 652 3 4 7

13

TCC-634R_

NOTE: When modifying Form 4A, Form 4C, Form 4D, Form 5, Form 5/TS, Form 6, Form 6-TS, Type FX, FXA, and FXB time-current curves, timing of modified phase trip curve must not exceed recloser short time limit for a single timing operation.

Maximum Short T ime Rec loser L imi ts

*Curves are recloser short time currents for a single trip operation.

MaximumRecloser InterruptingType Rating (sym A) Curve*

RXE, RVE 6000 1

WVE, WV38X, WVE38X 8000 2

WE 10000 3

VWE, VSA12, VWVE27 12000 4VWVE38, VWV38X, VWVE38XVSAT, VSO12, PWE, PWVE

VSA16, VSO16 16000 5

VSA20, VSA20A 20000 6

NOVA, NOVA-TS, NOVA STS 12,500 6

NOVA 16,000 7