RC & M Remote Control and Management System System of remote control and monitoring of telecommunication network sites. Purpose of RC&M. Remote control, management and monitoring of network and base stations equipment RBS, MSC and other network sites of mobile network operators. - PowerPoint PPT Presentation
Citation preview
RC & MRemote Control and Management SystemSystem of remote control and monitoring of telecommunication network sites
Purpose of RC&M
Remote control, management and monitoring of network equipment of RBS (radio base station), BSC (base station controller), MSC (mobile switch center) and other network sites of mobile network operators.
Purpose of RC&M
Complex provides data collection from different sources, that are used on a site (temperature/humidity sensors, electricity meters, alarm, fire and security sensors, power supplies system, diesel generators, network equipment etc.) and transfer this data to EMS.
Purpose of RC&M
Complex gives possibility of remote control from operator workplace to network equipment, power supply systems, diesel generator, climate systems, telecom equipment etc.
Complex provides organization of video security, alarm on entry to the territory of base station and access control to sites.
Main functi ons of the system
Control and monitoring of climate parameters: temperature and humidity
Control and monitoring of environment parameters: gas and dust pollution
Security and fire alarm, room flooding alarm
Creating ad-hoc report
Support different protocols of connection
Main functi ons of the system
Control, management and monitoring of power supply systems
Control, management and monitoring of diesel generators
Remote data collection of energy consumption on network sites
Automation of data processing for the calculation of consumed electricity
Main functi ons of the system
Remote troubleshooting of telecommunication site equipment for instance - BTS, DXX, XDM, MiniLink
Remote access from site to a corporate computer network
Outdoor and indoor video monitoring
Access control to the remote site and to individual rack units
Main functi ons of the system
System operability monitoring
Fault management (FM) and process tracking
SMS and E-mail messages
Administration and audit of users
Inventory management
Components of RC&M
PVS-LX
Controller PVS LX
EMS
Client software
Protocol software
System architecture of complex
Sensors and system equipment
PVS LX control ler
Computer: CPU ARM9 544 MHz; DRAM 128 MB; Flash 32 MB
Interfaces: 1x LAN, 1x WAN Ethernet 10/100 BaseT (RJ45);
5 Serial RS-232/RS485/С2; 2x USB 2.0; 1x 1-Wire;
16 x 3-level digital inputs; 2x outputs relay contacts
Temperature: -20℃~+55℃
Supply: 48V or 24V DC or 220V AC
Form factor: 1U rack
Hardware specifications:
READY / POWER
48V DC CLIMATE
COOLER / HEATER
LANPVS LX15
1 2 3 4 5WAN USB DIGITAl INPUTRS – 232/485
Control ler PVS-LX
OS: Linux Kernel Version: 2.6.27
Network protocols: TCP, UDP, IPv4, SNMP(v1,v2), ICMP, ARP,
SSH, DHCP, Telnet, FTP, PPP, DNS, HTTP, HTTPS, SMS, SMTP, SSL
Transfer protocols: RS232/RS485/С1, Modbus over TCP/ІР
Telecontrol protocol: IEC 60870-5-104
Electrical meter protocol: IEC 61107, IEC 1142,
IEC 61334 (DLMS/COSEM)
Security data: Secure Real COM, Secure TCP Server,
Secure TCP Client and Secure Pair Connection
Software specifications and protocols:
Components of RC&M
Alarm system
Electricity accounting system
Climate control system
Video security system
Access control system
Fault Management System
Components of RC&M
Control and management of network equipment
Administration of access permissions
Creating and editing forms of reports
Inventory management of resources
Control of power supply and diesel generator
RC&M Cl ient soft ware
User interface
Cl imate control system
• Measurement and monitoring of temperature and humidity• Charts and diagrams • Coolers/heaters autonomous/remote on/off• Formation of alarm messages in case of limits exceeding
Alarm system
• Signal discrete inputs monitoring of a fire and security alarm systems, backup power, etc.
• Alarm messages about event • Alarm audit system administration
CCTV system
• Twenty-four-hour simultaneous CCTV of many different points or areas on a single monitor with the ability to track movement in a frame
• Distributed video monitoring with the ability to view recordings at any time for analysis
• Video by motion detectors• Synchronic tracking of alarm signals
Electr ic ity accounti ng system
• Automatic data collection of technological and commercial electricity consumption accounting for each accounting point (group) equipment for defined commercial intervals
• Accumulation, processing and storage of accounting parameters • Comparative analysis of electricity consumption of similar sites• Control of electric power parameters (current, voltage, cos φ, frequency)
at a given polling interval
Consumed electr ic ity calculati on system
• Calculation of average consumption, taking into account losses• Providing multi-tariff zone accounting of electricity consumption (rates
are registered separately for each accounting point) • Maintenance of accounting contracts with electricity suppliers• Ad-hoc reports (daily, monthly, annual)• Control of electricity consumption limits• Electricity balance in the estimated group• Export data base on Oracle tool
Fault management system (FMS)
• Monitoring of connection to equipment • Creating of alarm messages • SMS and email notification • Easy adaptation to FMS based on SNMP protocols
Administrati on
• User profile • Access permissions• Audit
Ad-hoc reports
• Create and save of different type of reports• Automatic generation of reports based on system data• Print and export reports
Inventory management
• System equipment and connected devices • Oracle database • Audit of replacement equipment
Diagnosti cs of network equipment operati on
• Remote diagnostics of network equipment condition (switches, controllers, base radio stations, etc.)
• Adjustment parameter change
Management of power supply systems
• Remote control of parameters• Adjustment parameter change• Periodic remote testing of rechargeable batteries• Diagnostics of power supply system
Management of diesel generators
• Remote start/stop of generator• Remote load on/off• Control of voltage, current, frequency, battery voltage• Control of oil temperature, level and pressure • Control of fuel level, condition and running time
Air conditi oner remote control
• Control of environmental parameters • Remote control and diagnostic• Parameters setting• Analysis and diagnostic of cooling efficiency
Free cooling systems
• Setting parameters of operation• FreeCooler on/off• Control of temperature and engine speed• Own development