CITATION STARTERS
Range of Starters.... for Every Need
BCH manufactures a wide range of motor starters to suit every application in the field. The capacity starts from fractional horse power to 250 hp completely assembled ready to use units with built in overload and single phasing protection.
Direct-On-Line, manually operated, Mini Starter is designed for non-reversing control of all types of squirrel cage motors with an intermittent duty of 15 starts per hour (utilisation category AC3) complying with performance requirements of IS 8544 Part I. It is capable of switching motors upto 10HP, 415V, 3Phase or 3 HP single phase.The starter unit comprises of a double break, on load switch operated by means of a toggle link mechanism. Adjustable bimetable thermal overload trips are included which can be set to follow closely the heating characteristics of the motor.
Mini Manual Starter (Upto 10 Hp)
A Range of Starters
Utilisation category AC 3 as per IEC 292-1 and IS 8544 Part IInsulation voltage 600VThermal rating 20AOperational current Ie 16A at 415VFrequency of operation 15 operation per hourAC3 rating 16A at 415V, 50HzMechanical life 1x105 operationsEnclosure category Sheet steel enclosure to IP 51 as per IS 2147Terminal capacity One cable of 6 mm2 or two cables of 4 mm2
Characteristics
Selection Chart
** Substitute E by C for flush mounting.
2
2
6
10
20
25
50
0.23-0.47
0.46-0.8
0.85-1.55
1.60-3.20
3.50-6.50
6.80-11.70
11.00-20.00
AMLE 10
AMLE 20
AMLE 30
AMLE 40
AMLE 50
AMLE 60
AMLE 70
CATALOGUE** CODERECOMMENDED
FUSE(AMPS)
RELAY RANGEAMPS
0.5
0.75
1.0
1.5
3.0
5.0
10
0.37
0.52
0.75
1.10
2.20
3.70
7.5
1/6
1/6
0.5
0.75
1.0
2.0
3.0
HP KW
SINGLE PHASE 230V1 PHASE3 PHASE
0.095
0.13
0.37
0.52
0.75
1.50
2.20
KW
RECOMMENDED HP (KW)
AMLE 10-SP
AMLE 20-SP
AMLE 30-SP
AMLE 40-SP
AMLE 50-SP
AMLE 60-SP
AMLE 70-SP
3PHASE 415V
HP
The Time Delay Relay used in Automatic Star Delta Starter has superb repeat accuracy, gives satisfactory performance in frequent starting applications. It resets fast and the timing is not affected by variation in ambient temperature and voltage.
Excellent temperature compensation between -100 C and +800 C (+550 C max. ambient).Facility for selection of either manual or automatic resetting of the trip switch.Snap-on cover to prevent inadvertent alteration to the setting of current adjustment or to the hand/auto lever.Test facility for tripping relay manually for checking of the circuit and wiring.
Overload Protection : The relay fitted in the starter protects the motor from operational overload as per relevant standards established for the protection of motors. The range of current setting on any relay is between 100% to 160% of its minimum setting.Single Phasing Protection : The relay offers protection against single phasing through its sensitive differential mechanism in excess of the requirements of IS specification 13947-4-1 and trips when it carries in healthy phases 0.9 times the minimum current setting, regardless of the value to which the current adjustment lever is set. Full protection is provided on single phasing under varying operational up to 50% of the full load rating of the motor. No protection is required below this value.Protection against unbalanced voltage : The relay allows minor imbalance in voltage conditions in the three phases within the limits motors are designed to withstand. Beyond these limits, the relay trips and protects the motor.
Citation M Starters
REVERSING DOL UPTO 20 HP
DOL UPTO 30 HP
STAR DELTA UPTO 250 HP
The contactors used in starters are NHD and Citation. They are built to IS 13947 and have many distinctive features such as :
High grade moulding which reduces tracking and prolong
operational life.
Precision ground magnet frame and armature surfaces
ensure consistent quiet operation.
Exposed metals are treated for corrosion resistance.
Low bounce and weld resistant contacts of silver cadmium
oxide.
Contactors can be inspected and maintained without disturbing
adjacent wiring or altering contractor mounting positions.
Coil is totally encapsulated in resin resisting moisture,
corrosive atmosphere and damage while handling.
Mechanical interlocking is provided between Star and Delta
Contactors in case of Starter ratings 40HP and above.
Contactor
Overload Relay
Automatic Time Delay Relay
Starters with '00', 0 & 1 contactors have 380/415V coil and D,E & M5 have 415V coil.
* Also available starters for reversing function. For details consult us.
MOTOR OUTPUT 415V
(3 PHASE 50 HZ.) CONTACTOR SIZE
BACKUP PROTECTION
HRC FUSETYPE GII/GL
(AMP)
OVERLOAD RELAY RANGE
AMPERES(PHASE
CONNECTED)
CATALOGUE CODE
KW
2.23.75.57.59.311.015.018.522.026.030.037.055.067.575.093.0110.0150.0187.0
HP
3.05.07.510.012.515.020.025.030.035.040.050.075.090.0100.0125.0150.0200.0250.0
2.4 - 3.83.8 - 6.06.0 - 9.36.0 - 9.38.9 - 13.58.9 - 13.513.2 - 20.017.4 - 24.017.4 - 24.022.0 - 30.024.4 - 39.037.6 - 60.037.6 - 60.056.4 - 90.056.4 - 90.084.6 - 135.084.6 - 135.0131.6 - 210.0131.6 - 210.0
0000000000000001DDEE
M5M5M5RR
NASAGLENNASAHLENNASAJLENNASAJLENNASAKLENNASAKLENNASALLENNASAMLENNASAMLENNASANLEN
NASACT1LEDMNASACT2LEDMNASACT2LEEMNASACT3LEEM
NASACT3LEC5MNASACT4LEC5MNASACT4LEC5MNASACT5LEC6MNASACT5LEC6M
NASSGLENNASSHLENNASSJLENNASSJLENNASSKLENNASSKLENNASSLLENNASSMLEN
-----------
101620202532355050638080100125160200200300300
AUTOMATICSTAR DELTA
STARTER
SEMI- AUTOMATIC STAR DELTA
STARTER
Selection Chart - Star Delta
MOTOR OUTPUT415V 3 PHASE 50 HZ. CONTACTOR
SIZE
BACKUP PROTECTION
HRC FUSETYPE GII/GL
(AMP)
OVERLOAD RELAYRANGE
AMPERES
STARTER CATALOGUE
CODEKW
0.37
0.55
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15.0
18.5
22.0
HP
0.5
0.75
1.0
2.0
3.0
5.0
7.5
10.0
15.0
20.0
25.00
30.0
0.72-1.14
1.07-1.7
1.58-2.5
2.4-3.8
3.8-6.0
6.0-9.3
8.9-13.5
13.2-20.0
17.4-24.0
22.0-30.0
24.4-39.0
37.6-60.0
00
00
00
00
00
00
00
00
0
1/D
1/D
D
NADLEN
NAELEN
NAFLEN
NAGLEN
NAHLEN
NAJLEN
NAKLEN
NALLEN
NAMLEN
NANLEN
NACT1LEN
NACT2LEDM**
4
6
10
16
20
25
35
50
63
63
100
100
Selection Chart - DOL
Tripping Characteristics
Dimensions (mm)
.5 .100 101
104
103
102
101
100
TRIP
PIN
G T
IME
IN S
EC
ON
DS
(ts)
MULTIPLE OF FULL LOAD CURRENT X I
Mini Manual Starter
360.
0
215.0280.0
7.0 DIA. 4MTG. HOLES
11.036.0
162.0
315.
0
DOL STARTER 30 HP.
39.0 DIA. 4 HOLESFOR CONDUIT
16
95
5.5 DIA. 4 MTG. HOLES64
105
110
155
20 DIA. 4 HOLESFOR CONDUIT ENTRY42
104
29
1
10
100
1,000
10,000
TRIP
PIN
G T
IME
(SE
CO
ND
S)
MULTIPLE OF FULL LOAD/TRIP CURRENT
MAX.NOM.MIN.
TWO POLE
TRIP
PIN
G T
IME
(SE
CO
ND
S)
10
1
100
1,000
10,000
MAX.
MIN.
NOM.
THREE PHASE
MULTIPLE OF FULL LOAD/TRIP CURRENT
10.5 1 10.5 1 10.5 1
DOL & Star Delta Starter
Direct Operated CT Operated
MAX.
MIN.
1
10
100
1,000
10,000
TRIP
PIN
G T
IME
(SE
CO
ND
S)
MULTIPLE OF FULL LOAD/TRIP CURRENT
NOMINAL
MINI MANUAL STARTER
89
Flush Type
127
111
8X5 2 SLOTS.
DIRECT-ON-LINE STARTER
5 5DIA. 4MTG. HOLES
146.
0
180.
0
96.0130.0
11.0
160.
030
.0
60.0
4 HOLES DIA. 26.5
FOR CONDUITS
7.0 DIA. 4MTG. HOLES
280.
0
129.0180.0
11.0'A'
36 4 HOLES DIA 33.0 FORCONDUITS
217.
0
DOL STARTER 20 & 25 HP
25 HP DOL. 162.020 HP DOL. 120.0DESCRIPTION DIMN. 'A'
ALL
RA
NG
E/S
TAR
TER
S/3
000/
JAN
. '06
40 & 50 HP AUTO STAR DELTA STARTER (WITH SIZE-D)
400.0
75X38X6M.S.CHANNEL 2NOS.
365.0
CABLE ENTRY200X70
13.5 DIA. 4POLES FOR WALL MOUNTING
706.
0
750.
075
.0
14.0 DIA. 4HOLESFOR FLOOR MTG. 11
.017
2.0
212.
0
82.0
45.0
200.0
11.0 .40.0
556.
0
AUTO STAR DELTA STARTER 90/70 HP (WITH SIZE-E) AND 100/150HP(WITH SIZE-M5)
510.0
600.0
CABLE ENTRY250X100
600.
075
.0
240.
0
155.
022
.5
14.0 DIA. 4HOLESFOR MOUNTING
13.5 DIA. 4 HOLESFOR WALL MOUNTING
STAR DELTA STARTER
315.080.0
39.0 DIA. HOLEFOR CONDUIT
26.5 DIA.3 HOLESFORCONDUIT
215.
0
280.
016
2.0
36360.0
11.0
STAR DELTA STARTER 40HP (WITH NHD1)
215.
028
0.0
120.
036
360.0
7.0 DIA. 4 MTG. HOLES
26.5 DIA. 3HOLESFOR CONDUIT
39.0 DIA. HOLESFOR CONDUIT
80.0
315.0
SEMI AUTO & AUTO STAR DELTA STARTER UPTO 35HP
11.0
7.0 DIA. 4 MTG. HOLES
Dimensions (mm)
RP /
5,00
0 / J
an '0
8