Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
Professor Bjarne W. Olesen, PhDProfessor Bjarne W. Olesen, PhDDirector Director
International Centre for Indoor Environment and International Centre for Indoor Environment and EnergyEnergy
Department of Civil EngineeringDepartment of Civil EngineeringTechnical University of DenmarkTechnical University of Denmark
Radiant Heating and Cooling Systems Radiant Heating and Cooling Systems for for
Better Comfort and Energy EfficiencyBetter Comfort and Energy Efficiency
International Centre for Indoor Environment And Energy
INDOOR - OUTDOOR
• Highest exposure to the indoor environment
• People spend ~90 % of the time indoors during work, during transportation and athome
No cooling – decreased performanceLow energy costsLow operation costs
Full Air-ConditioningConstant temperatureDraught, Noise, SBSHigh energy costsHigh operation costs
Thermo-Active-Building-SystemsTemperature rampsReasonable energy costsLow operation costs
COMFORT-PERFORMANCE
People 100Maintenance 10Financing 10Energy 1
COMFORT-PRODUCTIVITYBuilding costs
CONCEPTS OF RADIANT HEATING AND COOLING SYSTEMS
• Heating - cooling panels• Surface systems• Embedded systems
Suspended cooled ceilings
RadiantRadiant surfacesurface heatingheatingand and coolingcooling systemssystems
FloorFloor WallWall
Thermo Active Building SystemsThermo Active Building Systems
CeilingCeiling
ReinforcementReinforcement
FloorFloor
ConcreteConcrete PipesPipes
RoomRoom
RoomRoom
WindowWindow
Embedded piping systems
• Free use of space• No cleaning• Safety• Comfort• Energy
OPERATIVE TEMPERATURE
– to = (hcta + hrtr)/(hc + hr)– to = 0.5ta + 0.5tr ( low air velocity)
» ta = Air temperature» tr = Mean radiant temperature» hc = Convective heat exchange coefficient» hr = Radiative heat exchange coefficient
SURFACE HEATING AND COOLINGHeat transfer coefficient
8,08,0
6,0
11,011,0
7,0
5,5
6,5
7,5
8,5
9,5
10,5
11,5
Floor
Ceiling
Wall
W/m2K
HeatingCooling
Types of systems, heating cooling capacity
Heat exchange coefficient between surface and space
99 42 17 ~27 9-11 6 Ceiling 72 160 17 ~40 8 8 Wall
42 99 20 29 7 9-11 Occupied Zone
42 165 20 35 7 9-11 Perimeter Floor
Cooling Heating Min. Cooling
Max. Heating
Cooling Heating
Maximum capacity
W/m²
Acceptable surface
temperature °C
Total heat exchange coefficient W/m².K
1. Screed 2. Pipes3. Plastic foil 4. Insulation5. Levelling 6. Concrete
Thermal resistance method
System modules
ALUMINUM HC device: Floor Heating & Cooling (type B), R=0.01~0.1, T=150 & 300
0
20
40
60
80
100
120
140
160
-15 -10 -5 0 5 10 15 20 25 30Heating/cooling medium differential temperature ΔθH=θH-θi [°C]
Hea
t exc
hang
e [W
/m2]
T=150, R=0.01T=150, R=0.1T=300, R=0.01T=300, R=0.1
Figure 4.17 Heat exchange between the surface (with ceramic tiles, wooden
parquets or carpet R?B=0.1 and no covering R?B=0) and the space when aluminium heat conductive device used
Heating/ cooling capacity, EN1264 and EN 15377
Floor Heating (& Cooling) (type G), R=0.01 ~0.1, T=150, 300
0
10
20
30
40
50
60
70
-15 -5 5 15 25Heating/cooling medium differential temperature ΔθH=θH-θi [°C]
Hea
t exc
hang
e [W
/m2]
qi (T=150, R=0)qe (T=150, R=0)qi (T=300, R=0)qe (T=300, R=0)qi (T=150, R=0.1)qe (T=150, R=0.1)qi (T=300, R=0.1)qe (T=300, R=0.1)
Figure 4.21 Heat exchange between the surface (with ceramic tiles, wooden parquets or carpet and no covering) and the space when steel heat conductive device used. Thermal insulation of 3cm from back side.
BoilerChiller
Temperature-Humidity
Outsidetemperature
Floor temp.
Supply Limiter
ReturnMixing valve
Shut off valves
Control
Room sensor Control unit
ValveManifold
Pump
Control of a combined floor heating-cooling systemwith individual room control
Radiant Floor Cooling Radiant Floor Cooling Airport BangkokAirport Bangkok
Airport BangkokAirport Bangkok Airport Bangkok
Airport BangkokAirport Bangkok
Lisboa Dolce Vita Tejo
Lisboa Dolce Vita Tejo FLOOR COOLING IN SOUTHERN EUROPE
• Computer Simulation (IDA Indoor Climate and Energy 3.0)
• Simulation period from April 20th to November 15th
• Variation of one parameter at a time• Variation of the location
Parameter Study
• Dwelling Types• Room Orientation• Control Strategy• Air Handling Unit• Internal Loads• Shading Levels• Floor Covering• Floor System
• Reference conditions• Rome• Ts ≥ Tpd limits cooling• 0.8 h-1 8 to 23h
else 0.3 h-1
• Int. Loads from 8 to 23h• No Dehumidification• 50% Shading
Location Study
Palermo
Rome
VeniceTorino
Braganca
Faro
PortoMadrid Barcelona
Sevilla
Santander
Location StudyRepresentative Cities – No dehum.
TABSTABSThermo Active Building SystemsThermo Active Building Systems
InsulationInsulationFloorFloor
ConcreteConcrete
ReinforcementReinforcement
PipePipe
RoomRoom
RoomRoom
WindowWindow
ConceptConcept of of Thermo Active Building SystemsThermo Active Building Systems
The analysed building
West room
Width of the room: 3.6 m
Window portion of the outside wall: 50%
Office building
CONTROL OF WATERTEMPERATURE• Supply water temperature is a function of outside
temperature according to the equation:
• Average water temperature is a function of outside temperature according to:
• Average water temperature is constant and equal to: 22°C in summer and 25°C in winter.
• Supply water temperature is a function of outside temperature according to the equation:
)22(*6,12020*52,0sup oexternalply ttt °C (case 801)
)22(*6,12020*52,0 oexternalaverage ttt °C (case 901)
1818*35,0sup externalply tt °C summer (case 1401)
1818*45,0sup externalply tt °C winter (case 1401)
PERFORMANCE EVALUATION
• Range of operative temperature • Pump running time • Energy consumption
Operative temperature range, May to September Different control concepts for water temperature, Time of operation 18:00 - 6:00 Uhr
33
14
54 54 52
38
0
10
20
30
40
50
60
70
80
90
100
Tsup =Tdp
Pump Tsup =F(ext)
Pump Tavg =F(ext)
Pump Tavg =22 °C
Pump Tavg =20 °C
Pump Tavg =18 °C
Pump
Control of water temperature
Ope
rativ
e te
mpe
ratu
re ra
nge
[%]
>27
26-27
25-26
22-25
20-22
<20
Pump %
CONTROL OF WATER TEMPERATURESUMMER
Operative temperature May to September
Water temperature control. Time of operation 6 pm to 6 am
2636
26303339
3234
0
10
20
30
40
50
60
70
80
90
100
Tsup= f(Ti,Te) Tave= f(Ti,Te) Tave= 22 °C Tsup= f(Te) Tsup= f(Ti,Te) Tave= f(Ti,Te) Tave= 22 °C Tsup= f(Te)
Control methods
Ran
ge o
f ope
rativ
e te
mpe
ratu
re %
>2726-2725-2622-2520-22<20
Venezia Würzburg
ART MUSEUM BREGENZ
ART MUSEUM IN BREGENZ
• Design requirements– Air temperature variations during a day within 4 K– Relative humidity variations less than 6 % during a day. – Seasonal variations between 48 and 58 %– Room temperature in winter 18 oC to 22 oC– Room temperature in summer 22 oC to 26 oC, occasional up to 28 oC
• Design load 250 persons pr. day, 2 hours• Displacement ventilation < 0,2 h-1
• Floor area 2.800 m² , 4 floors• 28.000 m plastic pipes embedded in walls and floor slabs
ART MUSEUMBREGENZ
• 3.750 m² floor area• 4.725 m² embedded pipes
• Condensing boiler
• Ventilation 750 m3/h per floor (first design was 25.000 m3/h
ART MUSEUM IN BREGENZ ART MUSEUM BREGENZ
ART MUSEUM BREGENZ
OfficesM+W ZanderStuttgart, Germany- TABS –
- in 6.500 m2
MW-Zander Measurementsduring normal operation
Operative temperature sensor
Air temperature sensor
Transmitters
Stuttgart
Stuttgart 24.07. - 28.07, 2000
20
21
22
23
24
25
26
24. J
ul
24. J
ul
25. J
ul
25. J
ul
26. J
ul
26. J
ul
27. J
ul
27. J
ul
28. J
ul
28. J
ul
29. J
ul
Zeit
Tem
pera
tur [
°C]
O1-Operative Büro 4. Stock Fenster-Ost F1-Fläche 4. Stock RucklaufO-Operative Büro 5. Stock Fenster-West O6-Operative Büro 5. Stock Fenster-Ost
Energy concept in BOB.1 Temperatures for one year in BOB.1
cooling period in BOB.1 Heating period in BOB.1
0
5000
10000
15000
20000
25000
30000
35000
Heizung Kühlung Lüftung Beleuchtung Pumpen Warmwasser Summe
Year
ly e
nerg
ie c
osts
[€/m
²a]
BestandBOB.1
Energy efficiency of BOB.1
94 % energy saving compared with conventionalcooling
60 % energy saving for lighting by daylight steering
The need of energy for heating, cooling, air-ventilation lighting and warm water is 27,8 kWh/m²per yearEnergy costs per m², per year: 2,7 EUR,
per month 22,5 Cent
6. Energy sources
Developing Low Exergy Systemsin the Tropics
(Malaysia, Singapore, Thailand, Indonesia)
Climates where :• Evaporative cooling is not possible• Earth coupling is not useful• Dehumidification is necessary• Ambient temperatures are above internal comfort temperature• Cooling is 100% and heating is zero
ENERGY-10 Optimisation
0
25
50
75
100
125
Cooling Lights Other
MECM LEO Super Low E. Building
64
37
116
25
8
100
51
kWh/m2year
Total
Trickling PV roof :
PV Powerplant and “Cooling Tower”
Self-shading facadeSet-back façade shades against direct solar radiation
100% daylightingLight guiding façade and max. 8 meters deep offices
Concrete slab coolingThermal comfort with air @27°C and ceiling/ floor @ 23°C
High temp. coolingSupply temp. for concrete slab cooling is 18°C resulting in high COP of Chiller
ZEO Building(Zero Energy Office)
Section, Office B, version 3Outdoor Atrium
Highly reflective ceiling
Lightshelf Blind reflecting light upwardsAir ducts
No direct sky view
Transm. 0.8
Transm. 0.520°C
15°CEvaporator AHU
15°C
20°C
20°C
22°C
23°C
23°C
Embeddedwater pipes
Off coil temperature of chiller in increased from 7 oC to 18 oCincreased COP of Chiller
Sky Radiant Temperature10 – 20 oC at night
Trickling Cool Roof
~ 25 oC~ 95% RH
15 o
RadiationConvection
EvaporationPV Roof
Chiller Condenser ( heat rejection )
~ 30 oC
~ 25 oC
ChillerPump
Microsoft Excel Worksheet
PRE-FABRICATION
PRE-FABRICATIONLow Exergy Low Exergy HydronicHydronic RadiantRadiant HeatingHeating and and
CoolingCoolingWhyWhy??
•• Water Water basedbased systemssystems•• Low Low temperaturetemperature heatingheating -- High High temperaturetemperature coolingcooling•• MoreMore economicaleconomical to to movemove heatheat byby waterwater::
–– GreaterGreater heatheat capacitycapacity thanthan airair–– MuchMuch smallersmaller diameterdiameter pipespipes thanthan airair--ductsducts–– ElectricalElectrical consumptionconsumption forfor circulationcirculation pump pump isis lowerlower thanthan forfor fansfans
•• LowerLower noisenoise levellevel•• LessLess riskrisk forfor draughtdraught•• LowerLower building building heightheight•• HigherHigher efficiencyefficiency of of energyenergy plantplant•• ButBut
– Reduced capacity?– Acoustic?– Latent load?