LV Power Distribution Product Catalogue Quicklag Circuit Protection Products

Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

LV Power Distribution Product Catalogue

Quicklag Circuit Protection Products

Page 2: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

Corporate Overview .............................................................................. 1

Quicklag Circuit Protection........................................................ .......... 2

Quicklag Introduction ........................................................................... 3

Quicklag Miniature Circuit Breaker.................................................... 4

ELQ Earth Leakage Breaker ................................................................ 6

ELDO/QELDO Residual Current Device ........................................... 8

Quickmov Surge Protection........................ ...................................... 10

Quicklag Accessories............................................................... ...........12

Quicklag Panelboards .........................................................................14

LCQ Metal Load Centres .................................................................... 16

Echidna QCE IP44 Panelboards .......................................................18

EWQ IP66 Panelboards ....................................................................20

EWQ+ IP66 Panelboards...................................................................21

Quicklag Chassis ...................................................................................22

Quicklag Panelboard Accessories ....................................................24

Quicklag Technical Data .....................................................................26

Dimensional Drawings ........................................................................27

Quicklag/ELQ Time Current Curves ................................................32

Fuse Backup Table ..............................................................................34

Motor Starting Application Tables ...................................................34

Earth Fault Loop Impedance ............................................................36

Cascading and Discrimination Tables .............................................37

Contents

2

14

3

26

Page 3: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

Founded in 1911, Eaton® Corporation is a diversified industrial manufacturer and a global leader in various industrial markets, including:

• Electricalsystemsandcomponentsforpowerquality,distributionandcontrol • Hydraulicscomponents,systemsandservicesforindustrialandmobileequipment •Hydraulics,fuelandpneumaticsystemsforcommercialandmilitaryaircraft •Intelligenttruckdrivetrainsystemsforsafetyandfueleconomy •Automotiveengineairmanagementsystems,powertrainsolutionsandspecialtycontrolsfor performance,fueleconomyandsafety

Corporate overview

Powering Business Worldwide

With 2008 sales of $15.4 billion USD, Eaton employs 75,000 people all over the world and sells products to customers in more than 150 countries.

1

Page 4: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

2

QuicklagMiniatureCircuitBreakerandResidualCurrentDevices

Quicklag CircuitProtection

Page 5: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

3www.eatonelectric.com.au

Quicklag CircuitProtection

TheQuicklagrangeofminiaturecircuitbreakerswasoriginallyreleasedinAustraliabyEmail-Westinghousein1957beforethecompanychangeditsnametoCutler-HammerandthentoEaton.

Throughtheyears,theQuicklaghasbeenwidelyrecognisedassettingtheelectricalindustrybenchmarkforMiniatureCircuitBreakers.Someofthereasonsinclude:

• Togglecentrepositiontripindication Clearlyshowswhenthebreakerhas tripped

• Ratingsupto100Aintheone framesize Commonframepolewidthto avoidtheneedforhybrid/mixed widthchassis

• Abilitytobemountedside-by-side withoutde-rating Utilisesthemaximumratingofthe breaker

• Fullyintegratedsurgeprotection solutionwiththeuseofQuickmov™ SurgeDiverters Connectstothechassisbusbarfor thelowestsourceimpedanceand

Quicklagisthelargestandmostcompletefamilyofindustrialthermalmagneticminiaturecircuitbreakers.Theyprovidethefeatureofsteelframecalibrationandarcchutesineverypole.Quicklagcircuitbreakersareprovidedinrangesfrom8to100amperescontinuousinone,two,threeandfour-poleconfigurations.

TheQuicklagfamilyincludesarangeofelectricalsafetydevices:theELQsingleandtwopolesRCBOandtheELDOsingleandmulti-poleearthleakagecircuitbreakers.

AccompaniedbyEchidnapanelboards,busbarchassisandmanyaccessories,includingtheQuickmov™integratedsurgeprotectiondevice.Quicklagistheidealchoiceforindustrialandcommercialapplications.

With over 50 years of service to the Australian Electrical Industry, Quicklag Circuit Breakers have a proven track record of reliability and safety.

MiniatureCircuitBreaker

Over 50 Years of Service to the Australian Electrical Industry

maximumsurgeperformance

Page 6: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

4

QuicklagMiniatureCircuitBreakersareusedinavarietyofcircuitprotectionapplicationsthatrangefromprotectionforsubmaincircuitsandlightandpowercircuitsthroughtovariousmotorstartingapplications.

TheQuicklagMiniatureCircuitBreakerisavailablein1,2,3and4poleconstructioninthermalcurrentratingsfrom8Ato100A,allofwhicharephysicallyinterchangeable.

TheQuicklagNon-Automatic80Aand100Amodelwhichhasnoovercurrentprotection,isavailableinsingletofourpolewidthconfigurationsandcanbeusedforcircuitdisconnection.

KeyFeatures• Breakingcapacity6kAat415VAC/2,3,4poleand 6kAat240VAC/1pole• Extensiverangeofaccessories• Non-Autobreakersavailable• Centretripindication• Approvalsandtests:ComplieswithAS3111and AS2184,Lloyd’sapproved

Applications• Protectionforsub-maincircuits• Lightandpower• Motorstartingapplications

Product: MiniatureCircuitBreakerBreakingCapacity: 6kA Voltage: 240/415VAC50/60HzAmperage: 8-100APoles: 1,2,3,and4Poles

MiniatureCircuitBreaker

Quicklag Miniature Circuit Breaker

Quicklag Miniature Circuit Breakers are designed to protect electrical circuits from damage caused by overload or short circuit.

Page 7: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

5www.eatonelectric.com.au

QuicklagMCBRating 1Pole 2Pole 3Pole 4Pole

(A) Cat.No. Cat.No. Cat.No. Cat.No.

8 Q108 Q208 Q308 Q408

10 Q110 Q210 Q310 Q410

16 Q116 Q216 Q316 Q416

20 Q120 Q220 Q320 Q420

25 Q125 Q225 Q325 Q425

32 Q132 Q232 Q332 Q432

40 Q140 Q240 Q340 Q440

50 Q150 Q250 Q350 Q450

63 Q163 Q263 Q363 Q463

80 Q180 Q280 Q380 Q480

100 Q1100 Q2100 Q3100 Q4100

80* Q180N Q280N Q380N Q480N

100* Q1100N Q2100N Q3100N Q4100N

QuicklagMCBfittedwithshunttripRating 1Pole 2Pole 3Pole 4Pole

(A) Cat.No. Cat.No. Cat.No. Cat.No.

8 Q108-ST2 Q208-ST2 Q308-ST2 Q408-ST2

10 Q110-ST2 Q210-ST2 Q310-ST2 Q410-ST2

16 Q116-ST2 Q216-ST2 Q316-ST2 Q416-ST2

20 Q120-ST2 Q220-ST2 Q320-ST2 Q420-ST2

25 Q125-ST2 Q225-ST2 Q325-ST2 Q425-ST2

32 Q132-ST2 Q232-ST2 Q332-ST2 Q432-ST2

40 Q140-ST2 Q240-ST2 Q340-ST2 Q440-ST2

50 Q150-ST2 Q250-ST2 Q350-ST2 Q450-ST2

63 Q163-ST2 Q263-ST2 Q363-ST2 Q463-ST2

80 Q180-ST2 Q280-ST2 Q380-ST2 Q480-ST2

100 Q1100-ST2 Q2100-ST2 Q3100-ST2 Q4100-ST2

80* Q180N-ST2 Q280N-ST2 Q380N-ST2 Q480N-ST2

100* Q1100N-ST2 Q2100N-ST2 Q3100N-ST2 Q4100N-ST2

*Non-AutoBreaker

*Non-AutoBreaker

Quicklagwithshunttrip

QuicklagMCB1pole

QuicklagMCB2pole

QuicklagMCB3pole

QuicklagMCB4pole

Page 8: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

6

ResidualCurrentDevice

ELQ Earth Leakage Breaker

TheELQEarthLeakagebreakercombinesoverload,shortcircuitandresidualcurrent(earthleakage)protectioninonecompactunitineitheroneortwopoleconfigurations.ThetwopoleELQincorporatesaswitchedneutralontheleftsidepole.

Thisstyleofcircuitbreaker,whichhasbecomemandatoryinnewinstallations,safeguardspeoplefromthedangerofelectricshockbyinstantlyinterruptingtheelectricalcircuittotheloadwhenafaultcurrenttoearthexceedstheratedsensitivity.

Protectionapplicationsincludesuchareasaselectricalofficeequipment,industrialplants,electricalhandtools,GPOsandsocketoutlets.Specialhighsensitivity(10mA)ELQbreakersareavailableforhospitalapplicationsandmedicalequipment.

TheELQ’sabilitytorespondtothesefaultcurrentsisremarkablyfast–infact,theresponsetimeislessthan40millisecondsinallELQ’slevelsofratedsensitivity.Athoughthebreakercombinesthreefunctions,themountingwidthspaceisthesameasastandardsingle-poleQuicklagcircuitbreaker.

FeaturesandBenefits• Overload,shortcircuitandresidualcurrent protectioninonecompactunit• 6kAat240VAC/Sym(AS214)• Sensitivityavailablein10,30and100mAmodels.• ApprovalNo.N20187• Tripindicationwindow• Testbuttonwithpreventativeaccidentalpushdesign

Applications• Electricalofficeequipment• Industrialplants• Electricalhandtools• GPOs• Socketoutlets• Miningsites

Product: EarthLeakageCircuitBreakerBreakingCapacity: 6kA Voltage: 240VAC50HzAmperage: 10-32APoles: 1and2Poles

Page 9: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

The ELQ Earth Leakage breaker is a safety device used in residential, industrial and commercial installations to prevent electric shock.

*Forindustrialuseonly

ELQEarthLeakageBreakerSensitivity Rating 1Pole 2Pole

(mA) (A) Cat.No. Cat.No.

30mA 10 ELQ110C3TW ELQ210C3TW*

16 ELQ116C3TW ELQ216C3TW*

20 ELQ120C3TW ELQ220C3TW*

25 ELQ125C3TW ELQ225C3TW*

32 ELQ132C3TW ELQ232C3TW*

10mA 10 ELQ110C1TW -

16 ELQ116C1TW -

20 ELQ120C1TW -

25 ELQ125C1TW -

32 ELQ132C1TW -

100mA 10 ELQ110C10TW -

16 ELQ116C10TW -

20 ELQ120C10TW -

25 ELQ125C10TW -

32 ELQ132C10TW -

7www.eatonelectric.com.au

Page 10: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

8

ResidualCurrentDevice

ELDO/QELDO Residual Current Device

TheELDOresidualcurrentrelaywillinstantaneouslydetectacurrentimbalanceduetoearthleakagethatmayoccurwithintheelectricaldistributionsystem.TheELDOwilltriptheassociatedcircuitbreaker,bymeansofaseparateshunttripfittedtothebreakerandisolatethesupplytocreateasafecondition.

TheELDOresidualcurrentdevicecanbemountedonitsownbracketorcanbedirectlyclippedintoanyQuicklagchassis,eitherseparatelyornexttotheQuicklagcircuitbreakers.Ineitherformation,thetwounitsarefittedasseparatecomponents.EachELDOcomescompletewithacomprehensiveinstructionsheetdetailinginstallationandconnectioninformation.ThesecompactresidualcurrentrelaysfitintothesamespaceasasinglepoleQuicklagbreaker.TheELDO

relayusesanelectricalsignaltotripthebreakerviaanintegralshunttripandcanbemountedseparatelyfromtheQuicklagbreakerwhichmustbeorderedwithashunttripdevicefitted(e.g.ELDO32+Q320-ST2).

TheQELDOisacombinationofaresidualcurrentrelayassembledwithanyQuicklagcircuitbreakerprovidingoverload,short-circuitandearthleakageprotection.TheQELDOhasaninbuiltshunttripdevicefortrippingthebreaker.TheQELDOismechanicallylinkedinternallytherebyoptimisingthetrippingoperationofthedevice.AQELDOcanincorporateanyofthecharacteristicsandratingsassociatedwithboththeQuicklagminiaturecircuitbreakerandtheELDOdevices.QELDOisamadetoorderitem.

TheQELDOrelayusesamechanicallinktotripthebreakerandcannotbeseparatedfromthebreaker.TheQELDOandQuicklagbreakermustbeorderedassembledatthefactory,alsoindicatingwhichsidetheQELDOwillbeon(e.g.QELDO34+Q320RHS).

FeaturesandBenefits• Instantaneouslydetectsacurrentimbalancedueto earthleakage• FitsinthesamespaceasasinglepoleQuicklag breaker• Sensitivityrangeavailablefrom10mAto1000mA• AS3190approvalandCS399993Ncertification

Applications• Electricalofficeequipment• Industrialplants• Electricalhandtools• GPOs• Socketoutlets• Heavyindustrialmachinery

Product: ResidualCurrentDeviceSensitivity: 10mA-1000mA ControlVoltage: 240/440/550VACApprovals: AS3190&CS39993N

Page 11: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

*Theserelayshaveaseperatechange-overrelayforusewithcontactorsandundervoltagereleasedevices.

ELDOResidualCurrentDeviceSensitivity ControlVoltage Approval Cat.No.

(mA) (VAC)

10 240V A ELDO12

30 240V A ELDO32

30 440V A ELDO34

30 550V - ELDO35

100 240V A ELDO102

100 440V A ELDO104

300 240V A ELDO302

300 440V A ELDO304

500 240V C ELDO502

500 440V C ELDO504

1000 240V C ELDO1002

30 240V A ELDO32X3*

30 440V A ELDO34X3*

100 240V A ELDO102X3*

300 240V A ELDO302X3*

500 440V C ELDO504X3*

1000 240V C ELDO1002X3*

*A=AS3190approvalandC=CS399993Ncertification

QELDOResidualCurrentDeviceSensitivity ControlVoltage Approval Cat.No.

(mA) (VAC)

10 240V A QELDO12

30 240V A QELDO32

30 440V A QELDO34

100 240V A QELDO102

100 440V A QELDO104

300 240V A QELDO302

300 440V A QELDO304

500 240V C QELDO502

500 440V C QELDO504

1000 240V C QELDO1002

QELDOPartNumberConfiguration

9www.eatonelectric.com.au

Page 12: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

10

IntegratedSurgeDiverter

Quickmov™ Surge Protection Device

Quickmov™isanintegratedSurgeProtectionDevice(SPD),designedtoprotectsingleandmultiphaseelectricaldistributionsystemsagainstthedamagingeffectsofvoltagespikesandsurges.Eaton’sQuickmov™plugsstraightintoaQuicklagloadcentre,connectingtothechassisbusbarforthelowestsourceimpedance.ItsintegratedHRCfuseenablestheQuickmov™tobeconnecteddirectlytotheneutralbar,providingtheshortestpossiblecablelengthforsuperiorprotectionoftheentireloadcentre.Itsavesspaceandinstallationtimebyeliminatingtheneedtoinstallaseparateover-currentprotectiondevice.AwiderangeofaccessoriesenablestheQuickmov™to

beeasilyadaptedtomanyotherapplicationsandmostDINloadcentresandpanelboards.Quickmov™employsadvancedMOVtechnologywithembeddedthermalprotectionhousedinadualbarrierflameretardantcasetoprovideoptimumsurgeprotectionperformancewithoutcompromisingsafetyandreliability.AfailsafemechanicalflagprovidesindicationofMOVstatusviaaduallayerviewingwindow.

KeyFeatures• Surgerating30kAInom&60kAImax• Integratedsurgeprotectionsolution• In-builtHRCfusing• Safethermaldisconnect• Dualbarrierflameretardanthousing• Failsafestatusindicator• ProtectionforM.E.Nandnon-M.E.Napplications• DesignedinAustralia

Applications• Multi-storeyComplexes• CommercialBuildings• Hospitals&MedicalCentres• Hotels&Clubs• Schools&Universities• Process&ControlSystems• UPS&ComputerSystems• TrafficControlSystems• EmergencyServicesSystems

Product: ShuntSurgeDiverterSurgeRating: 60kA Voltage: 240/415VAC50HzPole: Single

Page 13: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

QuickmovSurgeProtectionDeviceDescription Surgerating Cat.No.

1Pole60kAQuickmovSurgeDiverter 60kA SPDQM1

50kANetraltoEarthSurgeProtector/EquipotentialCoupler 50kA SPD50NGi

Quickmov™ combines surge suppression with fail-safe protection to deliver unsurpassed levels of safety and performance.

InstallationFormainswitchboardinstallationstypicallywithanadjacentM.E.Npoint,theQuickmov™shouldbemounteddirectlyonthechassisbusbarandcloseaspossibletotheneutralbaronQuicklagstyleboardotherwisemountingaccessorieswillallowforinstallationinothertypesofswitchboardorenclosuresystems.ForinstallationindistributionboardsremotefromtheM.E.Npoint,theQuickmov™shouldbeusedinconjunctionwithaSPD50NGineutral-earthsurgearrestor.

OperationTheQuickmov™usesamechanicalflagtoindicateitsoperatingandprotectionstatus.Theflagisvisiblethroughthewindowonthefrontfaceoftheunit.Ifthewindowisshowinga“GREEN”colouredflagthentheQuickmov™isfunctioningnormallyandthereisstillprotectionavailable.Whenthewindowchangestoshowa“RED”colouredflag,thismeanstheunitisdamagedandneedstobereplaced.FormoreinformationonoperationrefertotheQuickmov™InstallationGuide.

1 Mode (L-N) 1 Stage Diverter

Quickmov Block Diagram

MOV Protection

PowerInput

PowerOutput

Normal Mode

HRC Fuse

MOV

ThermalFuse

Element

11www.eatonelectric.com.au

Page 14: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

12

AccessoriesQuicklag’sextensiverangeofaccessoriesextendsitsfeaturesandbenefitstomanyapplications.Mouldedcoversandpolycentresallowforretrofitinstallationswherespaceislimited.Awiderangeoflockingdevicescaneasilyprovideextrasecurityandsafetyinsituationswhereitisrequired.

1.S1Q 2.S3Q 3.QPC 4.SC3Q,SC6Q,SC12Q,SC24Q

5.T50Q 6.T100Q 7.QLUGKIT

8.PLKQ1 9.PLKQ24 10.PLKQ3

MiniatureCircuitBreakerAccessories

Quicklag Accessories

Page 15: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

13www.eatonelectric.com.au

AccessoryIdentification1. SIQ-1PoleMouldedCover2. S3Q-3PoleMouldedCover3. QPC-QuicklagPolycentre6Pole4. SC3Q,SC6Q,SC12Q,SC24Q-Sliding ClipTray3,6,12and24Pole5. T50Q-50ATerminal25mm2

6. T100Q-100ATerminal50mm2

7. QLUGKIT-TunnellTerminalKit35mm2

8. PLKQ1-HandleLock1Pole+Padlock9. PLKQ24-HandleLock2or4Pole+Padlock10. PLKQ3-HandleLock3Pole+Padlock11. 1517-1281/1-SingleLockOff/OnDevice12. 1517-1290/1-LockOff/OnDevice(opposing breaker)13. 1517-1277/1-LockOffDevice(opposing breaker)14. QLDINADAPT-QuicklagDINAdaptor(6pack)

15. ELQ-E-KIT-ELQtoEFrameAdaptorKit (S1Qalsorequired)16. C36Q-StandardClipTray36Pole17. 1517-0525/1-AlarmSwitchRightHandMount (FactoryFittedOnly)18. LKDQ-LockdogQuicklag(10pack)19. 1517-1299/1-LockOffBracketKit(10pack)20. LKDELQTW-LockdogKitELQ(NoPadlock,1P)

17.1517-0525/115.ELQ-E-KIT 16.C36Q

18.LKDQ 19.1517-1299/1

12.1517-1290/1 13.1517-1277/1 14.QLDINADAPT

20.LKDELQTW

Quicklag Accessories

11.1517-1281/1

Page 16: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

14

QuicklagLoadcentres,DistributionBoards,Switchboards,EquipmentBoxes,Chassis

Quicklag Panelboards

Page 17: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

15www.eatonelectric.com.au

Quicklag PanelboardsThe Quicklag Panelboard is manufactured in Eaton’s facility using Australian materials and comes in two versions, the Echidna QCE, which has an IP44 rating and the EWQ, which has an IP66 rating. The EWQ is also available in a “+” format with extra width and depth for those times when more space is needed.

As well as the Quicklag Breakers and Panelboards, Eaton manufacture a series of metal loadcentres called LCQ which are also suited to rigorous industrial environments.

Page 18: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

16

LCQ Metal Loadcentres

FlushMountLCQLoadcentres

SurfaceMountLCQLoadcentres

SurfaceMountLCQLoadcentreswithDoor

KeyFeatures• Availablein4to18poles• Completewithactivebusbar,earthbar&neutrallink• MetalconstructionandRippleGreyfinishasstandard• Coinfacekeylockoptional(referLCQCLK)• DesignedtomeetIP40requirementsasstandard• IP50andIP54requirementsavailableonrequest• Specialcoloursavailableonrequest

Applications:• Industrialswitchboards• Commercialswitchboards• Equipmentbox• Damp,ruggedandharshenvironments

QuicklagLoadcentres

Page 19: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

17www.eatonelectric.com.au

TheLCQloadcentrerangeismostsuitableforsmallandcompactindustrialinstallationsandisavailableincapacitiesrangingfrom4poleto18poleinasinglerow.TheLCQrangeisconstructedfromrobuststeelandisdimensionedsothatamplespaceforwiringisavailable.ThestandardLCQissuppliedwith100Aactivelinkandearthbarandaneutrallinkthatcanaccommodate35mm2incomingcable.For3phaserequirements,12poleand18pole100Abusbarsareavailableforlinesidetermination.

Withknockoutsonthetop,bottomandrear,theLCQcaneasilyfacilitatetheconnectionofconduitsandcableglands.

TheLCQmetalloadcentresareavailableforsurfaceorflushmountingandcanbesuppliedeitherwithorwithoutatophingeddoor.

ForRippleOrangefinishadd“–RO”totheendoftheCat.No.Door=+26mmextrafordepthFlushcover=+50mmextraforheightanddepth

LCQMetalLoadcentresPole WidthxDepthxHeight FlushMount SurfaceMount

Capacity (mm) Cat.No. Cat.No.

4 233x70x234 LCQ4F LCQ4S

6 284x70x234 LCQ6F LCQ6S

9 360x70x234 LCQ9F LCQ9S

12 436x70x234 LCQ12F LCQ12S

15 512x70x234 LCQ15F LCQ15S

18 589x70x234 LCQ18F LCQ18S

LCQMetalLoadcentreswithDropDownDoorPole WidthxDepthxHeight FlushMount SurfaceMount

Capacity (mm) Cat.No. Cat.No.

6 284x70x234 LCQ6FD LCQ6SD

9 360x70x234 LCQ9FD LCQ9SD

12 436x70x234 LCQ12FD LCQ12SD

15 512x70x234 LCQ15FD LCQ15SD

18 589x70x234 LCQ18FD LCQ18SD

ForRippleOrangefinishadd“–RO”totheendoftheCat.No.Flushcover=+50mmextraforheightanddepth

The LCQ range is constructed from robust steel and is dimensioned so that ample space for wiring is available.

Page 20: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

18

Echidna QCE IP44 Panelboards

QuicklagIP44Panelboards

TheEchidnaQCEPanelboardsprovideaversatileandeconomicalwaytohouseandprotectcircuitbreakersforcommercialandindustrialapplications.

TheQCEisIP44ratedandissuppliedcompletewithatypetested3phasecolourcodedinsulatedbusbarsystemratedfor250Aand20kAfor0.1second.TheQCE,likeallQuicklagpanelboards,isfittedwithaneutralandearthbar,alockabledoorhingedontherightaswellasacircuitschedulecardandcardholder.TheQCEcomeswithconduitknockoutsinthetopandbottomoftheenclosure,flushlockandisfinishedinapowdercoatgreyrippleasstandard.Orangeisalsoavailableonindent.

Features&Benefits• IP44asstandard–bettersuitedtodamp environments• Ahorizontalcut-outfor24x18mmmodulewidth DINrailaccessoriesisstandardonallpanelboards, allowingbasiccontroltobeeasilyadded• Largeremovableglandplates,topandbottomfor easycableaccess• Pintlehingedallowsquickremovalformaximum access• Easy“lift-off”escutcheonpermittingtotallyopen workarea• Cabletroughsarepartofthedesignelementand provideaneatareaforcables• Doublescrew,fullyratedEarthandNeutralbars

BusbarRating: 250A/20kAfor0.1secIPRating: IP44 PoleCapacity: 12-84Poles

Like its namesake, the Echidna has a number of unique qualities that make it perfectly suited to its normal operating environment.

Page 21: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

19www.eatonelectric.com.au

Note:Left-handhingeddooravailableonrequest.ForRippleOrangefinishadd-ROtotheendoftheCatNo.Otherboardcoloursareavailableuponrequest.400Amainswitchavailableonrequest.

EchidnaQCEPanelboardsColour PoleCapacity HeightxWidthxDepth(mm) QCECat.No. QCEw/250AM/SCat.No.

RippleGrey

12 750x550x204.5 QCE12SDR QCE12SDRMT

24 750x550x204.5 QCE24SDR QCE24SDRMT

36 1000x550x204.5 QCE36SDR QCE36SDRMT

48 1200x550x204.5 QCE48SDR QCE48SDRMT

60 1200x550x204.5 QCE60SDR QCE60SDRMT

72 1500x550x204.5 QCE72SDR QCE72SDRMT

84 1500x550x204.5 QCE84SDR QCE84SDRMT

PuggleEnclosuresEquipmentBoxType HeightxWidthxDepth(mm) Cat.No.

BlankMountingTray 250x550x204.5 ECPUG2NNN

400x550x204.5 ECPUG4NNN

750x550x204.5 ECPUGANNN

1000x550x204.5 ECPUGBNNN

1200x550x204.5 ECPUGCNNN

1500x550x204.5 ECPUGDNNN

DINRailandBlankEscutcheon 250x550x204.5 ECPUG2D1B

400x550x204.5 ECPUG4D2B

750x550x204.5 ECPUGAD3B

1000x550x204.5 ECPUGBD4B

1200x550x204.5 ECPUGCD6B

1500x550x204.5 ECPUGDD8B

RaisedDINRailandSlottedEscutcheon 250x550x204.5 ECPUG2D1T

400x550x204.5 ECPUG4D2T

750x550x204.5 ECPUGAD3T

1000x550x204.5 ECPUGBD4T

1200x550x204.5 ECPUGCD6T

1500x550x204.5 ECPUGDD8T

250AFaultCurrentLimiter 400x550x204.5 ECPUG4FCL

250AIsolatorFitted 400x550x204.5 ECPUG4PB250MS3PD

400AIsolatorFitted 400x550x204.5 ECPUG4PB400MS3PD

PuggleequipmentboxescompletewithmountingtrayandarangeofoptionsincludingFCLfusebaseorDINmountingrailseitherbehindorthroughtheescutcheon.EachDINRailandslotis20x18mmmoduleswide.

Page 22: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

20

EWQ IP66 Panelboards

Note:Left-handhingeddooravailableonrequest.ForRippleOrangefinishadd-ROtotheendoftheCatNo.Otherboardcoloursareavailableuponrequest.For100AmainswitchaddQTtoendofCatNo(onlyon24and36Pole),400Amainswitchavailableonrequest.

EWQIP66PanelboardsColour PoleCapacity HeightxWidthxDepth(mm) EWQCat.No. EWQw/250AM/SCat.No.

RippleGrey 24 860x550x175 EWQ24SDR EWQ24SDRMT

30 860x550x175 EWQ30SDR -

36 1035x550x175 EWQ36SDR EWQ36SDRMT

42 1230x550x175 EWQ42SDR EWQ42SDRMT

48 1230x550x175 EWQ48SDR EWQ48SDRMT

60 1600x550x175 EWQ60SDR EWQ60SDRMT

72 1800x550x175 EWQ72SDR EWQ72SDRMT

84 2000x550x175 EWQ84SDR EWQ84SDRMT

96 2000x550x175 EWQ96SDR EWQ96SDRMT

108 2000x550x175 EWQ108SDR -

THEEWQPanelboardisIP66ratedandissuppliedcompletewithremovableglandplatesontopandbottom.Designedfortheharshestofindustrialenvironmentsandbuiltwiththemostarduousconditionsinmind,theEWQPanelboardexcelswithitsfullyweldedconstruction.TheEWQisfittedwithatypetested3phasecolourcodedinsulatedbusbarsystemratedfor250Aand20kAfor0.1second.

ThestandardEWQPanelboardisalsoequippedwitharemovablehingedescutcheon,afullyratedneutralbarandfullyratedearthbar,alockabledoorhingedontheright,aswellasacircuitidentificationlabel,acircuitschedulecardandcardholder.TheEWQ’sboxanddoorarefinishedinapowdercoatgreyripplepolyesterasstandardwhilethehingedescutcheonispaintedwhiteasstandard.Ahorizontalcutoutfor24x18mmmodulewidthDINrailaccessoriesisstandardonallpanelboards,allowingbasiccontroltobeeasilyadded.Orangefinishisavailableonindent.

BusbarRating: 250A/20kAfor0.1secIPRating: IP66 PoleCapacity: 24-108Poles

QuicklagIP66Panelboards

Page 23: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

21www.eatonelectric.com.au

EWQ+ IP66 Panelboards

TheEWQ+rangeofpanelboardshaveallthesameinclusionsandfeaturesastheEWQrangebutwiththeaddedbenefitofmorespaceinside,idealformountinglargeancillaryequipment.TheEWQ+alsoincludesahingedescutcheonwhichcanberemovedfromtheenclosureprovidinggoodaccessforeaseofworkwithinthepanelboard.

Thepanelboardisfittedwithtypetested3-phase,colourcoded,insulatedbusbarsystem,ratedat250A/20kAfor0.1second.Theenclosurefeaturesfullyweldedconstruction,witharighthingeddoorwith3-pointlockingandalockableL-handle.Thestandardfinishisgreyripplepolyester.

BusbarRating: 250A/20kAfor0.1secIPRating: IP66 PoleCapacity: 24-108Poles

Note:Left-handhingeddooravailableonrequest.ForRippleOrangefinishadd-ROtotheendoftheCatNo.Otherboardcoloursareavailableuponrequest.For100AmainswitchaddQTtoendofCatNo(onlyon24and36Pole),400Amainswitchavailableonrequest.

EWQ+IP66PanelboardsColour PoleCapacity HeightxWidthxDepth(mm) EWQ+Cat.No. EWQ+w/250AM/SCat.No.

RippleGrey 24 1000x650x257 EWQP24SDR EWQP24SDRMT

30 1200x650x257 EWQP30SDR EWQP30SDRMT

36 1200x650x257 EWQP36SDR EWQP36SDRMT

42 1200x650x257 EWQP42SDR EWQP42SDRMT

48 1400x650x257 EWQP48SDR EWQP48SDRMT

60 1400x650x257 EWQP60SDR EWQP60SDRMT

72 1600x650x257 EWQP72SDR EWQP72SDRMT

84 1800x650x257 EWQP84SDR EWQP84SDRMT

96 2000x650x257 EWQP96SDR EWQP96SDRMT

108 2000x650x257 EWQP108SDR EWQP108SDRMT

Page 24: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

22

ManfacturedbyEaton,designedandtestedtotherequirementsofAS1136.1,AS3439.1and3,Quicklagchassisassembliesareavailableinanumberofconfigurations,TheyareusedbyEatoninQuicklagpanelboardsandbyOriginalEquipmentManufacturer’sintheirownpanelboardandswitchboardassembliesthroughouttheelectricalindustry.

TheQuicklagchassisisavailableinastandard3phaseconstructionforeitherverticalorhorizontalapplicationsandisuniversalinthatitcanbefedfromeitherendofthebusbarchassis.TheQuicklagchassisisalsomadetosuitnarrowerapplicationsandcanbesuppliedinahalfwidthformat.Aneutralpolebusbarcanbeaddedtothe3phasebusbarsystembyEaton.

ChassiswithoutMainSwitchTheQuicklagchassisconsistsofagalvanisedsteelbaseplate,3phaseinsulatedbusbarsandinsulatedbusbarsupports.ThebaseplatehastworowsofclipinbracketsforthemountingofQuicklagbreakerswhilethebusbarismountedtothebaseplatebytheinsulatedsupports.

ThestandardQuicklagchassisassemblyhasbeentestedinaccordancewithAS1136.1,AS3439.1and3andisratedfor

250Acontinuouscurrentandhasawithstandcapacityof20kAfor0.1seconds.Non-standardvariationsareavailableandcanbeselectedfromunitswith250A,16kAfor0.5secondor300,16kAfor1.0secondand400A,20kAfor1.0second.Toorderthenon-standardvariationchassispleasecontactyourlocalEatonrepresentative.

ChassiswithMainSwitchTheQuicklagchassiscanbeeasilyfittedwithaMainSwitchforisolatingthesupplytothechassis.

QTSeriesThe100AMainSwitch,aQuicklagNon-AutoQ3100N,canbemountedeitherinthetopcentrefeedingintothechassisorcanbepositionedonthechassispanwhereitwilloccupy3polespacesofthechassis.

MTSeriesA250Aor400AMainSwitchcanbefittedreadilytothestandardQuicklagChassisandprovidesmanyexcellentcharacteristicssuchasvisibleindicationofthepositiveloadbreakandfaultmakecontactoperation.Theoperatinghandleispad-lockableintheOFFpositionforaddedsafetyandsecurity.

Quicklag Chassis

ChassisSystems

HorizontalChassisVerticalChassis HalfWidthChassis Chassiswith100AM/S

Page 25: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

23www.eatonelectric.com.au

ChassisVerticalandHorizontalTypePolesCapacity Height*(mm) Width(mm) VerticalCat.No. HorizontalCat.No.

12 229 332 Q12PV Q12PH

18 305 332 Q18PV Q18PH

24 381 332 Q24PV Q24PH

30 457 332 Q30PV Q30PH

36 534 332 Q36PV Q36PH

42 610 332 Q42PV Q42PH

48 686 332 Q48PV Q48PH

60 838 332 Q60PV Q60PH

72 991 332 Q72PV Q72PH

78 1067 332 Q78PV -

84 1143 332 Q84PV -

96 1291 332 Q96PV -

108 1444 332 Q108PV -

ChassisHalf-WidthTypeVertical: Height(mm) Width*(mm) Cat.No.

12 381* 230 1521-1560/1

18 534* 230 1521-1560/2

24 686* 230 1521-1560/3

30 838* 230 1521-1560/4

Horizontal:

12 230 381* 1521-1561/1

18 230 534* 1521-1561/2

24 230 686* 1521-1561/3

30 230 838* 1521-1561/4

*Busbarsextend42mmoverbothsidesofmountingpan*Half-WidthChassisaremadetoorder

*Busbarsextend42mmovertopandbottomofmountingpanonVerticaltypeandleftandrightonhorizontal.

Chassiswith100AMainSwitchPolesCapacity Height(mm) Width(mm) Cat.No.

12 305 332 Q12PVQT

24 457 332 Q24PVQT

36 610 332 Q36PVQT

Nonstandardvariationsareavailableonrequest

Page 26: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

24

4.PB250MS3PD,PB400MS3PD3.LCQ12BP,LCQ18BP

1.QSEALKIT 2.LCQCLK

5.1521-1236/1

Quicklag Panelboard Accessories

IndustrialPanelboardAccessories

6.1521-0070/15

AccessoriesThewiderangeofQuicklagpanelboardaccessoriesextendsthefeaturesandbenefitstomeetdifferentrequirements.Lockingsystemsprovideaddedsecuritytotheboards,flushsurroundsallowforin-wallinstallationsandthechoiceofan80,100,250or400Amainswitchtosuitthepanelboards.

Page 27: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

25www.eatonelectric.com.au

10.ECFLSRA

8.ECPLTH__7.ECELOCK 9.1521-1287/1

15.ANEWEMLTM2,ANEWEMLTM4

Quicklag Panelboard Accessories

12.15171281/1 13.1517-1290/1 14.1517-1277/1

11.QPF

AccessoryIdentification1. QSEALKIT-SealingScrewsforQuicklag Covers(10Pack)2. LCQCLK-LoadCentreCoinLockKit3. LCQ12BP,LCQ18BP-3PhaseInsulated BusbarKit,12Pole&18Pole4. PB250MS3PD,PB400MS3PD-MainSwitch3 PoleDINCutout250Aand400A5. 1521-1236/1-BusbarSplittingKit

6. 1521-0070/15-24PoleQuicklagBuscomb7. ECELOCK-FieldFitE-LockKit8. ECPLTH__:(#:1=1Tier,2=2Tier,3=3Tier (*:G=StainlessSteel,P=PaintedBlack, -RG=RippleGrey,-RO=RippleOrange)9. 1521-1287/1-Tee-offInsulationCap10. ECFLSRA-FlushSurround750mmEnclosure11. QPF-QuiclagPoleFiller

12. 15171281/1-SingleLockOff/OnDevice13. 1517-1290/1-LockOff/OnDevice(oppbreaker)14. 1517-1277/1-LockOffDevice(oppbreaker)15. ANEWEMLTM2-EmergencyLightingTestCCT 20A2N/C ANEWEMLTM4-EmergencyLightingTestCCT 24A4N/C

Page 28: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

26

QuicklagDimensionalDrawings,Specifications,TimeCurrentCurves,ApplicationTables.

Quicklag Technical Data

Page 29: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

27www.eatonelectric.com.au

Quicklag Technical Data

Quicklag Dimensions

C

M

Y

CM

MY

CY

CMY

K

ELQTW DIAGRAM.pdf 1/28/2009 5:33:14 PM

ELQ Dimensions

QuicklagTechnicalData

Page 30: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

28

ELDO / QELDO Dimensions

LCQ Load Centre Dimensions

4- OFF8mm DIA.MTG. HOLESALL SIZES

4- OFF 8mm DIA. MTG. HOLES 12, 15, & 18 LCQ ONLY

4 KNOCKOUTS 26mmIN BACK OF BOX

2 ALL ROUND (SURFACE)ALL ROUND (FLUSH)

21MM DIA. KNOCKOUTS2-OFF FOR 6 & 9 LCQ12, 15 & 18 LCQ

26mm DIA. KNOCKOUTS3-OFF FOR 6 & 9 LCQ12, 15 & 18 LCQ

DOOR

283

233

186

330

27

175

96

70

Ls

Lf

C

M

Y

CM

MY

CY

CMY

K

LCQ.pdf 1/29/2009 11:23:30 AM

QuicklagTechnicalData

LCQLoadcentresPole

CapacityCoverLength

FlushLf SurfaceLs

4PoleLCQ 233 283

6PoleLCQ 284 334

9PoleLCQ 360 410

12PoleLCQ 436 486

15PoleLCQ 512 562

18PoleLCQ 589 639

Page 31: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

29www.eatonelectric.com.au

QCE Panelboard Dimensions

C

M

Y

CM

MY

CY

CMY

K

PUGGLE_400.pdf 1/29/2009 11:46:43 AM

Puggle Enclosure Dimensions

PuggleEnclosuresBoxHeight H(mm) A(mm) B(mm)

250HPUGGLE 250 206.8 150

400HPUGGLE 400 356.8 300

750HPUGGLE 750 706.8 650

1000HPUGGLE 1000 956.8 900

1200HPUGGLE 1200 1156.8 1100

1500HPUGGLE 1500 1456.8 1400

EchidnaQCEPanelboardsPoles A(mm) B(mm) C(mm)

12 750 300.8 650

18 750 300.8 650

24 750 300.8 650

30 1000 605.6 900

36 1000 605.6 900

42 1000 605.6 900

48 1200 910.4 1100

60 1200 910.4 1100

72 1500 1062.8 1400

84 1500 1062.8 1400

Page 32: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

30

EWQ Panelboard Dimensions

EWQ+ Panelboard Dimensions

QuicklagTechnicalData

Page 33: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

31www.eatonelectric.com.au

Chassis Dimensions

Chassis with Main Switch Dimensions

QuicklagChassisPoles ChassisVertical

HeightDimA(mm)ChassisHorizontalWidthDimA(mm)

12 313 313

18 389 389

24 465 465

30 541 541

36 618 618

42 694 694

48 770 770

60 922 922

72 1075 1075

78 1151 -

84 1127 -

96 1375 -

108 1528 -

ChassiswithMainSwitchPoles DimensionA(mm)

24 579

36 731

42 807

48 883

60 1112

78 1341

84 1462

96 1569

Page 34: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

32

Eaton Quicklag Time Current CurveQQQQuuuuiiiicccckkkkllllaaaagggg CCCCiiiirrrrccccuuuuiiiitttt BBBBrrrreeeeaaaakkkkeeeerrrrssss8888 ttttoooo 111100000000AAAA,,,, 1111,,,, 2222,,,, 3333 aaaannnndddd 4444 ppppoooolllleeee

0.005 001

002

003

004

005

0060070080090001

0002

0003

0004

0005

0006

00070008000900001

00051

00002

0.01

0.02

0.030.040.05

0.1

0.2

0.30.40.5

1.0

2

345

10

20

304050

100

200

300400500

1000

2000

300040005000

10000

sdnocesni

emiT

1minute

1hour

2hours

Percent Rated Current

Maximum63-100A

Maximum8-50A

Minimum63-100A

Minimum8-50A

Maximum interrupting time

5040

32

2520

16

108

63

80

100Range of magnetictrip setting forrating indicated

Time/Curent Curves

TD.19.01.T.E

November, 2000

Time-current curves show response times in seconds forapplied overcurrent expressed in percentages of ratedcurrent. The values are for breakers operating in openair in an ambient of 40oC, or inside an enclosure in anambient of 25oC, with no current through the breakerbefore application of overcurrent.

The characteristics are presented not as a single curvebut as a band defined by maximum and minimumcurves. The characteristic curve for any particularbreaker will lie within this band. However, this does notimply that its tolerance band is as wide as the plottedband, which allows for manufacturing and calibratingvariations for the range overall.

Specifications - The specifications in thispublication were correct at the time the

publication went to press. Eaton Corporationreserves the right to change the specifications

of its products without notice.Installation and Use - The products describedin this publication should only be installed and

used in accordance with any accompanyinginstruction sheets. To the full extent permitted bylaw, Eaton Corporation expressly excludes all andany liability arising from installation or use of the

products which is not in accordance with therelevant instruction manual.

C

M

Y

CM

MY

CY

CMY

K

Quicklag Time-Current Curve.pdf 1/29/2009 6:22:10 PMQuicklagTechnicalData

Page 35: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

33www.eatonelectric.com.au

Eaton ELQ Time Current CurveEEEELLLLQQQQ CCCCiiiirrrrccccuuuuiiiitttt BBBBrrrreeeeaaaakkkkeeeerrrrssss,,,,11110000 ttttoooo 33332222AAAA

0.005

001

002

003

004

005

0060070080090001

0002

0003

0004

0005

0006

00070008000900001

00051

00002

0.01

0.02

0.030.040.05

0.1

0.2

0.30.40.5

1.0

2

345

10

20

304050

100

200

300400500

1000

2000

300040005000

10000

sdnocesni

emiT

1minute

1hour

2hours

Percent Rated Current

Maximum

Minimum

Maximum interrupting time

3225

2016

10

Range of magnetictrip setting forrating indicated

Time/Curent Curves

TD.19.02.T.E

November, 2000

Time-current curves show response times in seconds forapplied overcurrent expressed in percentages of ratedcurrent. The values are for breakers operating in openair in an ambient of 40oC, or inside an enclosure in anambient of 25oC, with no current through the breakerbefore application of overcurrent.

The characteristics are presented not as a single curvebut as a band defined by maximum and minimumcurves. The characteristic curve for any particularbreaker will lie within this band. However, this does notimply that its tolerance band is as wide as the plottedband, which allows for manufacturing and calibratingvariations for the range overall.

Specifications - The specifications in thispublication were correct at the time the

publication went to press. Eaton Corporationreserves the right to change the specifications

of its products without notice.Installation and Use - The products describedin this publication should only be installed and

used in accordance with any accompanyinginstruction sheets. To the full extent permitted bylaw, Eaton Corporation expressly excludes all andany liability arising from installation or use of the

products which is not in accordance with therelevant instruction manual.

Specifications - The specifications in thispublication were correct at the time the

reserves the right to change the specificationsof its products without notice.

Installation and Use - The products describedin this publication should only be installed and

used in accordance with any accompanyinginstruction sheets. To the full extent permitted by

any liability arising from installation or use of theproducts which is not in accordance with the

relevant instruction manual.

Page 36: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

34

Fuse Backup

FaultCurrentLimitingFusesforSeriesConnectedProtectionofEatonQuicklagandELQCircuitBreakersRatings BS88Fuse DINFuse

Amps Quicklag ELQ-TW Quicklag ELQ-TW

8 160 160 -

10 160 160 160 160

16 160 160 200 200

20 200 200 200 200

25 200 200 200 200

32 200 200 250 200

40 200 - 250 -

50 200 - 250 -

63 200 - 250 -

80 200 - 250 -

100 200 - 250 -

QuicklagTechnicalData

RecommendCircuitBreakerTypeandContinousCurrentRatingformotorswithstarttimesFLC ApproximateMotor Quicklag

Amps kW HP 5secstart 10secstart

1.8 0.75 1 8* 8*

3 1.1 1.5 10 16*

4 1.5 2 16* 16*

5 2.2 3 16* 20*

6-7 3 4 20* 25*

8 4 5.5 20 25*

9 4.5 6 25 32*

11 5.5 7.5 40* 50*

12-16 7.5 10 50* 63*

17-20 9 12.5 63* 63*

21-24 11 15 63 63

25-30 15 20 63 80*

31-40 18.5 25 80 100

41-44 22 30 100 -

45-52 25 35 100 -

53-56 30 40 100 -

FusebrandsrecommendedarebasedonexhaustivetypetestingconductedattheAustraliaElectricalTestCentre,UniversityofSouthAustralia,inaccordancewiththerelevantsubclausesunderclause8.2.3ofAustralianStandardAS3439.1-1993.Peaklet-throughcurrentandenergy,asstatedbytherespectivefusesuppliers,havebeendetailedinthetechnicaldatagridbelowtoassistinchoosingareplacementfuse.Therecommendedback-upfuseratingsarevalidforprospectivesystemfaultlevelsupto50kArms,415VAC,3-phase.Theminimumfusesizewhichcanbeusedforsuchapplicationsisbasedongradingunderoverload,onebreakerwithonefuse.MinimumBS88/DINfusesizesrecommendedforusewithEatoncircuitbreakersisasfollows:Quicklag

8-16A:63A;Quicklag20-40A:80A;Quicklag50-63A:100A;Quicklag80-100A:160A;ELQ-TW10-32A:63A.

Thistableisbasedonaverage3-phase,415VACmotorsonly,holding125%FLCcontinouslyand600%motorFLCforatleast5andatleast10secondsasshown.Thebreakerslistedinthistable,haveeithersolidstateorthermal/magnetictripreleases.Thebreakerhavingadjustablethermaland/ormagneticsettingsmustbesetattheirminimumvalues.

AS3000-1991 *ThesebreakersdonotprovideprotectionagainstshorttimeoverloadcurrentsinaccordancewithAS3000-1991,section2.4.3.4(b). *Aseparateoverloadprotectiondeviceshouldbeusedinconjuctionwiththisbreaker(referAS3000-1991,section2.4). AS/NZS3000-2000 AttentionisdrawntoAS/NZS3000-2000,section2.4.3.2whichrequirescoordinationbetweentheconductorsandtheprotectivedevice.Notethatthismayinvolve provisionofadditionaloverloadprotectionorappropriatecablesizeselection.

AS3000-1991-Attentionisdrawntoclause2.19.4.4ofAS3000-1991requiringthatfaultcurrentlimitersprotectingfireandlifeequipmentshalnotbeaffectedbyafaultonthegeneralinstallationAS/NZS3000-2000-Attentionisdrawntoclause7.10.4.4ofAS/NZS3000-2000requiringthatfaultcurrentlimitersprotectingfireandlifeshallnotbeaffectedbyafaultonthegeneralinstallation.

D.O.L Starting

Page 37: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

RecommendCircuitBreakerTypeandContinousCurrentRatingformotorswithstarttimesFLC ApproximateMotor Quicklag

Amps kW HP 20secstart

3 1.1 1.5 8*

4 1.5 2 8

5 2.2 3 10

6-7 3 4 16*

8 4 5.5 16

9 4.5 6 20*

11 5.5 7.5 25*

12-16 7.5 10 32*

17-20 9 12.5 40

21-24 11 15 50*

25-30 15 20 50

31-40 18.5 25 63*

41-44 22 30 63

45-52 25 35 80

53-56 30 40 80

57-60 34 45 100

61-70 37 50 100

Thistableisbasedonaverage3-phase,415VACmotorsonly,holding115%FLCcontinouslyand350%motorFLCforatleast20secondsasshown.Thebreakerslistedinthistable,haveeithersolidstateorthermal/magnetictripreleases.Thebreakerhavingadjustablethermaland/ormagneticsettingsmustbesetattheirminimumvalues.AS3000-1991 *ThesebreakersdonotprovideprotectionagainstshorttimeoverloadcurrentsinaccordancewithAS3000-1991,section2.4.3.4(b). *Aseparateoverloadprotectiondeviceshouldbeusedinconjuctionwiththisbreaker(referAS3000-1991,section2.4).AS/NZS3000-2000-AttentionisdrawntoAS/NZS3000-2000,section2.4.3.2whichrequirescoordinationbetweentheconductorsandtheprotectivedevice.Notethatthismayinvolveprovisionofadditionaloverload protectionorappropriatecablesizeselection.

RecommendCircuitBreakerTypeandContinousCurrentRatingformotorswithstarttimesFLC ApproximateMotor Quicklag

Amps kW HP 20secstart

1.5 0.55 0.75 10*

1.8 0.75 1 10*

3 1.1 1.5 10*

4 1.5 2 16*

5 2.2 3 20*

6-7 3 4 25*

8 4 5.5 32*

9 4.5 6 32*

11 5.5 7.5 40*

12-16 7.5 10 63*

17-20 9 12.5 63*

21-24 11 15 63*

25-30 15 20 80*

Thistableisbasedonaverage3-phase,415VACmotorsonly,holding125%FLCcontinouslyand600%motorFLCforatleast20secondsasshown.Thebreakerslistedinthistable,haveeithersolidstateorthermal/magnetictripreleases.Thebreakerhavingadjustablethermaland/ormagneticsettingsmustbesetattheirminimumvalues.

AS3000-1991 TherecommendedbreakerratingsarebasedonAS3000-1991,section2.19.9.2andthatonlyonefire-pumpmotorisprotectedbyeachrecommendedcircuit-breakerrating. *ThesebreakersdonotprovideprotectionagainstshorttimeoverloadcurrentsinaccordancewithAS3000-1991,section2.4.3.4(b). *Aseparateoverloadprotectiondeviceshouldbeusedinconjunctionwiththisbreaker(referAS3000-1991,section2.4).

AS3000-2000 TherecommendedbreakerratingsarebasedonAS/NZS3000-2000,section7.10.9.2andthatonlyonfire-pumpmotorisprotectedbyeachrecommendedcircuitbreakerrating.Attention isdrawntoAS/NZS3000-2000,section2.4.3.2whichrequirescoordinationbetweentheconductorsandtheprotectivedevice.Notethatthismayinvolveprovisionofadditionaloverload protectionorappropriatecablesizeselection.

Star Delta, Auto-transformer, Resistor orReactance Motor Starting

Fire Pump Motor Starting

35www.eatonelectric.com.au

Page 38: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

36

Earth Fault Loop Impedance

QuicklagEquivalenttoTable8.1fromAS/NZS3000:2007Quicklagrating MeanAutomaticOperation

CurrentMaximumCircuitImpedance

In(A) Ia(A) Zs(Ohms)

8 135 1.70

10 170 1.35

16 270 0.85

20 335 0.69

25 355 0.65

32 440 0.52

40 425 0.54

50 390 0.59

63 520 0.44

80 590 0.39

QuicklagTechnicalData

QuicklagEquivalenttoTableB1fromAS/NZS3000:2007ConductorSize QuicklagRating MeanAutomatic

OperationCurrentMaximumCircuitLength(Copper)

MaximumCircuitLength(Aluminium)

Active Earth

Sph(mm2) Spe(mm2) In(A) Ia(A) Lmax(m) Lmax(m)

1 1 8 135 30 18

1 1 10 170 24 15

1.5 1.5 10 170 36 22

1.5 1.5 16 270 22 14

2.5 2.5 16 270 37 23

2.5 2.5 20 335 30 19

4 2.5 25 355 35 22

4 2.5 32 440 28 17

6 2.5 40 425 33 21

10 4 50 390 59 37

16 6 63 520 68 42

16 6 80 590 60 37

25 6 80 590 67 41

25 6 100 700 56 35

35 10 100 700 90 56

ThistablewascalculatedusingtheformuladefinedinclauseB4.5

ThistablewascalculatedusingtheformuladefinedinclauseB4.5

where:Uo=230VIa=KnownValue(derivedfrompublishedQuicklagtripcurves)

ThistablewascalculatedusingtheformuladefinedinclauseB5.2.2

where:Uo=230VIa=KnownValue(derivedfrompublishedQuicklagtripcurves)=ResistivityvaluesshowninthestandardSph&Spe=CrosssectionalAreasofConductors

This table was calculated using the formula defined in clause B4.5

a

Os I

UZ =

where:Uo = 230V Ia = Known Value (derived from published Quicklag trip curves)

This table was calculated using the formula defined in clause B5.2.2

)(8.0

maxpepha

pephO

SSISSU

L+

where:Uo = 230V Ia = Known Value (derived from published Quicklag trip curves)ρ = Resistivity values shown in the standardSph & Spe = Cross sectional Areas of Conductors

Quicklag Equivalent to Table B4.1 from AS/NZS3000:2000

Quicklag Mean Automatic Maximum Circuitrating Operation Current Impedance

In (A) Ia (A) Zs (Ω)8 135 1.70

10 170 1.3516 270 0.8520 335 0.6925 355 0.6532 440 0.5240 425 0.5450 390 0.5963 520 0.4480 590 0.39

100 700 0.33

Quicklag Equivalent to Table B5.1 from AS/NZS3000:2000

Quicklag Mean Automatic Maximum Circuit Maximum Circuitrating Operation Current Length (Copper) Length (Aluminium)

Sph (mm2) Spe (mm2) In (A) Ia (A) Lmax (m) Lmax (m)1 1 8 135 30 181 1 10 170 24 15

1.5 1.5 10 170 36 221.5 1.5 16 270 22 142.5 2.5 16 270 37 232.5 2.5 20 335 30 194 2.5 25 355 35 224 2.5 32 440 28 176 2.5 40 425 33 2110 4 50 390 59 3716 6 63 520 68 4216 6 80 590 60 3725 6 80 590 67 4125 6 100 700 56 3535 10 100 700 90 56

Active Earth

Conductor size

This table was calculated using the formula defined in clause B4.5

a

Os I

UZ =

where:Uo = 230V Ia = Known Value (derived from published Quicklag trip curves)

This table was calculated using the formula defined in clause B5.2.2

)(8.0

maxpepha

pephO

SSISSU

L+

where:Uo = 230V Ia = Known Value (derived from published Quicklag trip curves)ρ = Resistivity values shown in the standardSph & Spe = Cross sectional Areas of Conductors

Quicklag Equivalent to Table B4.1 from AS/NZS3000:2000

Quicklag Mean Automatic Maximum Circuitrating Operation Current Impedance

In (A) Ia (A) Zs (Ω)8 135 1.70

10 170 1.3516 270 0.8520 335 0.6925 355 0.6532 440 0.5240 425 0.5450 390 0.5963 520 0.4480 590 0.39

100 700 0.33

Quicklag Equivalent to Table B5.1 from AS/NZS3000:2000

Quicklag Mean Automatic Maximum Circuit Maximum Circuitrating Operation Current Length (Copper) Length (Aluminium)

Sph (mm2) Spe (mm2) In (A) Ia (A) Lmax (m) Lmax (m)1 1 8 135 30 181 1 10 170 24 15

1.5 1.5 10 170 36 221.5 1.5 16 270 22 142.5 2.5 16 270 37 232.5 2.5 20 335 30 194 2.5 25 355 35 224 2.5 32 440 28 176 2.5 40 425 33 2110 4 50 390 59 3716 6 63 520 68 4216 6 80 590 60 3725 6 80 590 67 4125 6 100 700 56 3535 10 100 700 90 56

Active Earth

Conductor size

This table was calculated using the formula defined in clause B4.5

a

Os I

UZ =

where:Uo = 230V Ia = Known Value (derived from published Quicklag trip curves)

This table was calculated using the formula defined in clause B5.2.2

)(8.0

maxpepha

pephO

SSISSU

L+

where:Uo = 230V Ia = Known Value (derived from published Quicklag trip curves)ρ = Resistivity values shown in the standardSph & Spe = Cross sectional Areas of Conductors

Quicklag Equivalent to Table B4.1 from AS/NZS3000:2000

Quicklag Mean Automatic Maximum Circuitrating Operation Current Impedance

In (A) Ia (A) Zs (Ω)8 135 1.70

10 170 1.3516 270 0.8520 335 0.6925 355 0.6532 440 0.5240 425 0.5450 390 0.5963 520 0.4480 590 0.39

100 700 0.33

Quicklag Equivalent to Table B5.1 from AS/NZS3000:2000

Quicklag Mean Automatic Maximum Circuit Maximum Circuitrating Operation Current Length (Copper) Length (Aluminium)

Sph (mm2) Spe (mm2) In (A) Ia (A) Lmax (m) Lmax (m)1 1 8 135 30 181 1 10 170 24 15

1.5 1.5 10 170 36 221.5 1.5 16 270 22 142.5 2.5 16 270 37 232.5 2.5 20 335 30 194 2.5 25 355 35 224 2.5 32 440 28 176 2.5 40 425 33 2110 4 50 390 59 3716 6 63 520 68 4216 6 80 590 60 3725 6 80 590 67 4125 6 100 700 56 3535 10 100 700 90 56

Active Earth

Conductor size

MaximumValuesofEarthFault-LoopImedance(Zsat230V)

Maximumcircuitlengths,inmetres,fordifferentsizeofconductorsandprotectivedevicesusingapproximatemeantrippingcurrents(Ia)*

Page 39: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

Cascading and Discrimination Tables

Frequently Asked Questions

TechnicalDataonHRCFusesTypeTestedforBack-upProtectionofEatonQuicklagandELQ-TWCircuitBreakersFuse

ManufacturerFuseType FuseCat.

No.Fuse

Rating(A)i2-tValuePre-Arcing(AMP2-sec)

i2-tValueTotal@415VAC(AMP2-sec)

i2-tValueTotal@550VAC(AMP2-sec)

i2-tValueTotal@600VAC(AMP2-sec)

PeakCut-OffCurrent@50kA(kA)

WattsLoss(W)

Bovara-Crady DIN AC-1 160 0.52x105 N/A 1.00x105 N/A 15.00 13.12

DIN AC-1 200 1.00x105 N/A 2.00x105 N/A 17.00 17.00

DIN AC-1/2 250 1.50x105 N/A 3.50x105 N/A 20.00 20.00

SiemensLtd BS88 3NWTF 160 0.52x105 1.42x105 1.96x105 N/A 17.50 13.00

BS88 200 1.16x105 3.30x105 4.56x105 N/A 21.00 15.20

CascadingandDiscriminationofSeriesConnectedEatonQuicklagMCBandMouldedCaseCircuitBreakersBreakerUpstream

FWF40kA FW40kA HFWF70kA HFW70kA

BreakerDownstream

160A 200A 225A 160A 200A 225A 160A 200A 225A

QuicklagMCB X/Y 1.2/18 1.6/18 1.8/18 1.6/18 2/18 2.2/18 1.2/18 1.6/18 1.8/18 1.2/18 1.6/18 1.8/18

X=Discriminationupto4kA Y=Cascadingupto40kAThistableisbasedoncircuitbreakersinstalledonasystemwithavoltageof415Vac,50Hz,3-PhaseUpstreamcircuitbreakersmusthavetheirthermalandmagneticcharacteristicssetattheirmaximumvaluestoobtainthestateddiscriminationlevel.4/40meansthatupto4kA,onlythedownstreamcircuitbreakerwilltrip.Abovethislevel,eitherorbothcircuitbreakerwilltrip.Thiscombinationhasbeentestedinseriesforcascadingat40kA

Fuse Backup Let-through Energies

CurrentRatingsatthefollowingambient(A)CurrentRating(A)

25˚C 40˚C 50˚C 60˚C

8 9 8 7 6

10 11 10 9 8

16 18 16 15 13

20 23 20 19 16

25 28 25 23 21

32 35 32 30 28

40 45 40 36 31

50 56 50 45 41

63 69 63 57 50

80 88 80 72 64

100 110 100 90 80

FigureA:QuicklagDe-ratingTable

1. IsthereaDCurveQuicklagMiniatureCircuitBreaker? No,becauseDCurveisdefinedinAS/NZS60898.1andthe QuicklagbreakersaretestedtodifferentstandardsAS3111 andAS2184.

2. WhatisthemechanicalandelectricallifeoftheQuicklag? TheQuicklagistestedtocomplywithAS2184-1980,this standard’sendurancetestrequires6,000operationswith theratedcurrentand4,000without,10,000operationin total.

3. WhatarethecontactratingsoftheQuicklagalarmswitch? TheBurgresstypeV4Quicklagalarmswitchhasthefollowing contactratings: @125/250VAC=5Aresistiveand5Ainductive @30VDC=5Aresistiveand3Ainductive4. Whatde-ratingshouldbeappliedforapplicationofthe quicklagatelevatedambients RefertoFigureA

37www.eatonelectric.com.au

Page 40: Quicklag Circuit Protection Products · 2020. 7. 4. · 100* Q1100N Q2100N Q3100N Q4100N Quicklag MCB fitted with shunt trip Rating 1 Pole 2 Pole 3 Pole 4 Pole (A) Cat. No. Cat. No

Eaton Corporation is a diversified power management company rankedamong the largest Fortune 500 companies. The electrical group is Eaton’slargest division and is a global leader in electrical control, powerdistribution, power quality, automation, and monitoring products andservices. Eaton’s global electrical brands, including Cutler-Hammer®,MGE Office Protection Systems™, Powerware®, Holec®, MEM®, Santakand Moeller, provide customer-driven PowerChain Management®solutions to serve the power system needs of the industrial, institutional,government, utility, commercial, residential, IT, mission critical and OEMmarkets worldwide.

PowerChain Management solutions help enterprises achieve sustainableand competitive advantages through proactive management of thepower system as a strategic, integrated asset throughout its life cycle.With Eaton’s distribution, generation and power quality equipment;full-scale engineering services; and information management systems,the power system is positioned to deliver powerful results: greaterreliability, operating cost efficiencies, effective use of capital, enhancedsafety, and risk mitigation.

PowerChainManagementisatrademarkofEatonCorporation.Allothertrademarksarepropertyoftheirrespectiveowners.

©2009EatonCorporationAllRightsReservedPrintedinAUSCAT2009AUS08