1
Surge Protect Discharge For
Flexi Power Rectifier
Quick Start Guide
Emerson Network Power Co., Ltd. http://www. emersonnetworkpower.com.cn Manual Version: 01
Surge Protect Discharge for FPRA Quick Start Guide
2
Manual Number: 03370500100 Manual Issue: 1.0 Manual Status: Standard Release Date: Sep 2008
Copyright © 2008 Emerson Network Power Co., Ltd. All rights reserved Published in China This document, and the information it contains, are the property of Emerson Network Power Co., Ltd, and are protected by law. Both must be held in strictest confidence at all times. Emerson Network Power grants no license or right to copy, use or disclose either, expressly or by implication.
Disclaimer
This document and the information contained herein are provided on an "AS IS" basis. Emerson Network Power may make improvements or changes in this documentation, at any time and without notice and as it sees fit. The information in this documentation was prepared by Emerson Network Power with reasonable care and is believed to be accurate. However, Emerson Network Power shall not assume responsibility for losses or damages resulting from any omissions, inaccuracies, or errors contained herein.
Surge Protect Discharge for FPRA Quick Start Guide
History 3
History
Date Version Author Change Note No./Notes 02/09/2008 01 David Cao First release
Surge Protect Discharge for FPRA Installation Manual
Table of contents 4
Table of contents
History...................................................................................................................3 Table of contents ..................................................................................................4 List of figures ........................................................................................................4 List of tables..........................................................................................................4 List of terms ..........................................................................................................5 Preface .................................................................................................................7 SPD installation.....................................................................................................9 SPD replacement................................................................................................17 Appendix – Tools and Torques ...........................................................................19
List of figures
Figure 1 – PDA rear internal chassis layout ................................................................ 9 Figure 2 – Connecting the SPD – 3Y.......................................................................... 13 Figure 3 – Connecting the AC terminal block – 3Y................................................... 14 Figure 4 – AC connection with the SPD - 3Y............................................................. 15 Figure 5 – Removing the damaged OVP module from the SPD ............................ 17 Figure 6 – Fitting a new OVP module to the SPD .................................................... 18
List of tables
Table 1 – Reference documents.................................................................................... 7 Table 2 – Configurations of AC connection with the SPD ....................................... 10 Table 3 – Schematic diagram of AC connection with the SPD............................... 12 Table 4 – Tools and torques required for installation ............................................... 19
Surge Protect Discharge for FPRA Installation Manual
List of terms 5
List of terms
A Ampere
AC Alternative current
AWG American Wire Gauge
BAT Battery
BR Battery Return
BTS Base Transceiver Station
CB Circuit Breaker
CSA Cross Section Area
CU Control unit
DC Direct current
EMC Electromagnetic Compatibility
ESD Electrostatic Discharge
FPRA Flexi Power Rectifier
GND Ground
GUI Graphical User Interface
IE Internet Explorer
IP Ingress Protection
IP Internet Protocol
L Live cable from the AC mains
LAN Local Area Network
LED Light Emitting Diode
LVD Low Voltage Detection
MAC Media Access Control
MCB Micro Circuit Breaker
N Neutral cable from the AC mains
Surge Protect Discharge for FPRA Installation Manual
List of terms 6
PC Personal Computer
PCB Printed Circuit Board
PDA Power Distribution Assembly
PE Protective earth
PSU Power Supply Unit
SPD Surge Protect Discharge
V Volt
VPN Virtual Private Network
1Φ Single-phase AC type
3Y 3-phase star AC type
3∆ 3-phase delta AC type
Surge Protect Discharge for FPRA Installation Manual
Preface 7
Preface
About this guide This quick start guide is for quick installation or an overview of the SPD. Thus only the three-phase star AC connection with SPD is described in this guide. User shall refer to the main SPD user manual (Emerson file No. 03370500080) for more details about the other AC connections.
SPD Introduction The Flexi Power Rectifier (FPRA, Emerson part number AA25020L) is an up to 6kW output power AC rectifier package. The Surge Protect Discharge (SPD, Emerson part number AA25130L) is used to prevent the damages to the FPRA that caused by input over voltage or surge. The SPD consists of three same OVP modules that used between live cables and neutral cable from the AC mains; one OVP module that used between the neutral cable from the AC mains and the earth; and one remote signaling contact.
Reference documents The reference documents of the SPD contains:
Table 1 – Reference documents
Document Emerson Network Power File No.
Internal product specification – System / PDA 41970005110
Internal product specification – Rectifier 41970004980
Surge Protect Discharge for Flexi Power Rectifier – User Manual (main SPD user manual)
03370500080
- To be continued -
Surge Protect Discharge for FPRA Installation Manual
Preface 8
Table 1 – Reference documents
Flexi Power Rectifier - User Manual 03370500090
Flexi Power Rectifier- Installation Manual 03370500070
Surge Protect Discharge for Flexi Power Rectifier– Quick Start Guide (this manual) 03370500100
Flexi Power Rectifier– Quick Start Guide 03370500110
Surge Protect Discharge for FPRA Installation Manual
SPD installation 9
SPD installation Warning: The AC power supply must be switched off prior to any access of the AC cable. Note: The 3-phase star AC connection with SPD is for illustration herein. Refer to Appendix – Tools and Torques for each installation step.
Figure 1 shows the PDA rear internal chassis layout.
PDA rear cover
A
AC terminal block SPD DIN Rail
SPD ground clamp
AC ground clampPDA earth cable C
B
DE
SPD sensor connection
Strain-relief Rear cover retention cable
F
Figure 1 – PDA rear internal chassis layout
Surge Protect Discharge for FPRA Installation Manual
S
PD
inst
alla
tion
10
Tabl
e 2
– C
onfig
urat
ions
of A
C c
onne
ctio
n w
ith th
e SP
D
Term
inal
s co
nnec
tion
AC
type
AC
m
ains
SP
D
AC
ter
min
al
bloc
k C
hass
is (3
)
Sho
rt lin
k av
aila
ble
(1)
AC
term
inal
blo
ck
Con
figur
atio
n (2
)
SPD
co
nfig
urat
ion
N/A
L1
6
N/A
L1
for t
hree
-pha
se
L L2
5
N/A
L2
for t
hree
-pha
se
N/A
L3
4
N/A
L3
for t
hree
-pha
se
N
N
2 N
/A
N fo
r thr
ee-p
hase
sta
r
PE
N
/A
N/A
A
C g
roun
d cl
amp
N/A
1Φ
N/A
N/A
S
PD
gro
und
clam
pS
PD
gro
und
link
Sho
rt te
rmin
als
1,2,
3 an
d 4,
5,6
resp
ectiv
ely
Sho
rt te
rmin
als
L1, L
2, L
3
L1
L1
5 N
/A
L1 fo
r thr
ee-p
hase
L2
L2
3 N
/A
L2 fo
r thr
ee-p
hase
L3
L3
1 N
/A
L3 fo
r thr
ee-p
hase
N/A
N
N
/A
SP
D g
roun
d cl
amp
SP
D g
roun
d lin
k
3∆
PE
N
/A
N/A
A
C g
roun
d cl
amp
N/A
Sho
rt te
rmin
als
1,2
and
3,4
and
4,5
resp
ectiv
ely
N/A
S
urge
Pro
tect
Dis
char
ge fo
r FP
RA
Inst
alla
tion
Man
ual
S
PD
inst
alla
tion
11
Tabl
e 2
– C
onfig
urat
ions
of A
C c
onne
ctio
n w
ith th
e SP
D
Term
inal
s co
nnec
tion
AC
type
AC
m
ains
SP
D
AC
ter
min
al
bloc
k C
hass
is (3
)
Sho
rt lin
k av
aila
ble (1
) A
C te
rmin
al b
lock
C
onfig
urat
ion
(2)
SPD
co
nfig
urat
ion
L1
L1
6 N
/A
L1 fo
r thr
ee-p
hase
L2
L2
5 N
/A
L2 fo
r thr
ee-p
hase
L3
L3
4 N
/A
L3 fo
r thr
ee-p
hase
N
N
2 N
/A
N fo
r thr
ee-p
hase
sta
r
PE
N
/A
N/A
A
C g
roun
d cl
amp
N/A
3Y
N/A
N/A
S
PD
gro
und
clam
pS
PD
gro
und
link
Sho
rt te
rmin
als
1,2,
3 N
/A
Not
e: (1
) The
sho
rt lin
k na
mes
list
ed h
erei
n ar
e in
acc
orda
nce
with
the
actu
al la
bels
on
the
shor
t lin
ks.
(2
) The
AC
term
inal
blo
ck s
houl
d be
con
figur
ed b
efor
e th
e A
C c
onne
ctio
n. U
ser s
hall
refe
r to
sect
ion
3.4
in F
lexi
Pow
er R
ectif
ier–
In
stal
latio
n M
anua
l (Em
erso
n fil
e N
o.03
3705
0007
0) fo
r mor
e de
tails
.
(3
) Ref
er to
Fig
ure
1 fo
r the
cor
resp
ondi
ng c
lam
ps.
S
urge
Pro
tect
Dis
char
ge fo
r FP
RA
Inst
alla
tion
Man
ual
SPD installation 12
Table 3 – Schematic diagram of AC connection with the SPD
AC Type
Schematic diagram Configuration of AC terminal block
3Y
L1 L2 L3 N
1 2 3 4 5 6SPD
AC Terminal Block
L1 L2PE
AC Mains
L3 N
Short terminals 1,2,3
1Φ
L1 L2 L3 N 1 2 3 4 5 6
SPDAC Terminal Block
L NPE
AC mains
Short terminals 1,2,3; 4,5,6 respectively
3∆
L1 L2 L3 N
1 2 3 4 5 6SPD
AC Terminal Block
L1 L2PE
AC mains
L3
Short terminals 1,2; 3,4; 5,6 respectively
Surge Protect Discharge for FPRA Installation Manual
SPD installation 13
1.1 Detach the cable strain-relief from the chassis by loosening the screw ‘A’ in Figure 1.
1.2 Detach the AC ground clamp and SPD ground clamp from the chassis by loosening the screws ‘B’ and C‘ in Figure 1.
1.3 Fit the PE cable from the AC mains into the AC ground clamp. 1.4 Fit the live cables from the AC mains and the bare end of L line short
links into the terminals ‘L1’, ‘L2’ and ‘L3’ on the SPD respectively referring to the diagram of 3Y AC connection in Table 2 and Table 3 (see Figure 2).
1.5 Fit the neutral cable from the AC mains and the flat end of N short link into terminal ‘N’ on the SPD referring to the diagram of 3Y AC connection in Table 2 and Table 3 (see Figure 2).
N short link
N
L3
L2
L3 short link
L2 short link L1
L1 short link
Figure 2 – Connecting the SPD – 3Y
1.6 Fit the ground cable link into the SPD ground clamp, and the other end
into the SPD ground terminal on the SPD referring to the diagram of 3Y AC connection in Table 2 and Table 3.
Surge Protect Discharge for FPRA Installation Manual
SPD installation 14
1.7 Secure the AC ground clamp back into its position on the chassis,
tightening the screw ‘B’ (refer to Figure 1). 1.8 Secure the SPD ground clamp back into its position on the chassis,
tightening the screw ‘C’ in Figure 1. 1.9 If required, detach the AC terminal block from the chassis by loosening
screws ‘D’ and ‘E’ in Figure 1. This will provide a better view of the AC terminal block connections.
1.10 Connect the L1, L2 and L3 line short links to terminals ‘6’, ‘5’, ‘4’ on the AC terminal block respectively referring to the diagram of 3Y AC connection in Table 2 and Table 3 (see Figure 3).
1.11 Connect the N line short link to terminal ‘2’ on the AC terminal block referring to the diagram of 3Y AC connection in Table 2 and Table 3 (see Figure 3).
N short link
L3 short link
L2 short link
L1 short link
Figure 3 – Connecting the AC terminal block – 3Y
Surge Protect Discharge for FPRA Installation Manual
SPD installation 15
1.12 Connect the SPD sense cable to the SPD remote signaling contact. 1.13 Secure the SPD to the DIN Rail by locating the grounding side bottom
slot of the SPD onto the DIN Rail and pressing down on the SPD until it locks in position.
1.14 Refit AC terminal block if removed from chassis, tightening the screws ‘D’ and ‘E’ in Figure 1.
1.15 Connect the SPD sense cable to the PDA sense connection, and restrain the cable to position ‘F’ on the chassis in Figure 1.
1.16 Restrain the AC cable on the socket by fitting the Strain-relief, tightening the screw ‘A’ in Figure 1.
Figure 4 shows the PDA rear layout after completing the 3-phase star AC connection with the SPD.
SPD ground cable
PE of AC mains
L1
L3
L2
SPD sense cable
N short link
L3 short link
L2 short link
L1 short link
N
Figure 4 – AC connection with the SPD - 3Y
1.17 Replace the PDA rear cover referring to section 3.4 in ‘Flexi Power Rectifier– Installation Manual’ (Emerson File No. 03370500070).
Surge Protect Discharge for FPRA Installation Manual
SPD installation 16
CAUTION: After installation of the SPD kit has been completed, the installer should check the installation against the steps outlined within this document, supported by a multi-meter to check for wiring continuity. It’s strongly suggested that the insulation test (2.5kV Hi-pot) is carried out.
Surge Protect Discharge for FPRA Installation Manual
SPD replacement 17
SPD replacement
Warning: The AC power supply must be switched off prior to any access of the SPD.
2.1 Hold the two sides of the damaged OVP module and pull it out from the SPD base (see Figure 5).
Figure 5 – Removing the damaged OVP module from the SPD
Surge Protect Discharge for FPRA Installation Manual
SPD replacement 18
2.2 Fit the new module into its position on the SPD base (see Figure 6).
Figure 6 – Fitting a new OVP module to the SPD
Surge Protect Discharge for FPRA Installation Manual
Appendix 19
Appendix – Tools and Torques ******************************************************************** Refer to the table below for the tools and torques required for each installation step:
********************************************************************
Table 4 – Tools and torques required for installation
Step Tool Usage Torque (N.m)
1.1 TORX screwdriver (T25) Loosen screw --
1.2 TORX screwdriver (T25) Loosen screw --
1.3 Flat screwdriver Tighten screw 1.5
1.4 Cross screwdriver Tighten screw 4.5
1.5 Cross screwdriver Tighten screw 4.5
1.6 TORX screwdriver (T25) Tighten screw 4.5
1.7 TORX screwdriver (T25) Tighten screw 2.0
1.8 TORX screwdriver (T25) Tighten screw 2.0
1.9 TORX screwdriver (T25) Loosen screw --
1.10 Flat screwdriver Tighten screw 1.5
1.11 Flat screwdriver Tighten screw 1.5
1.12 Manual Connection Fit
1.13 Manual Install the SPD Fit
1.14 TORX screwdriver (T25) Tighten screw 2.0
1.15 Manual Connection Fit
1.16 TORX screwdriver (T25) Tighten screw 2.0
1.17 TORX screwdriver (T10) Tighten screw 0.8
2.1 Manual Remove the OVP --
2.2 Manual Install the OVP Fit
Surge Protect Discharge for FPRA Installation Manual