Features Proportional Torque Control for optimised torque performance. Unique snaplock™ drive interface ensures user friendly connection of Control Mode to Damper. Tested and approved to BS ISO 10294-1:1996, BS EN 1366-2:1999 and BS476 pt. 20:1987 Fire Test Standards. SmokeShield PTC is an LPCB approved product and conforms to the requirements of LPS1162 iss 2. Easy connection to square, rectangular, circular and flat oval ductwork. Unique and patented Electrical Thermal Release for ultimate safety. Halogen Free Low Smoke and Fume cabling supplied as a standard safety feature. Actionpac Damper Control System compatibility. VentShield PTC™ reverse action dampers for smoke release or exhaust applications. Pneumatic Option. Proportional Torque Control Automatic Smoke and Fire Dampers SmokeShield PTC TM December 2009 SmokeShield PTC™ Dampers Controls Fancoils Ruskin Air Management Limited www.ruskinuk.co.uk Dampers Designed and Built in Britain

Proportional Torque Control Automatic Smoke and Fire …

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Proportional Torque Control Automatic Smoke and Fire …

Features

● Proportional Torque Control foroptimised torque performance.

● Unique snaplock™ driveinterface ensures user friendlyconnection of Control Mode toDamper.

● Tested and approved to BS ISO 10294-1:1996, BS EN 1366-2:1999 and BS476 pt. 20:1987 Fire TestStandards.

● SmokeShield PTC is an LPCBapproved product and conformsto the requirements of LPS1162iss 2.

● Easy connection to square,rectangular, circular and flat ovalductwork.

● Unique and patented ElectricalThermal Release for ultimatesafety.

● Halogen Free Low Smoke andFume cabling supplied as astandard safety feature.

● Actionpac Damper ControlSystem compatibility.

● VentShield PTC™ reverse actiondampers for smoke release orexhaust applications.

● Pneumatic Option.

Proportional Torque ControlAutomatic Smoke and Fire Dampers

SmokeShield PTCTM

December 2009 SmokeShield PTC™

Dampers Controls Fancoils

Ruskin Air Management Limitedwww.ruskinuk.co.uk

Dampers Designed and Built in Britain

Page 2: Proportional Torque Control Automatic Smoke and Fire …

Introduction Specification

Actionair has always been at the forefrontin the innovative development, design andmanufacture of life safety dampers andassociated controls. Now with the uniqueSmokeShield PTC™ range of AutomaticSmoke and Fire Dampers Actionaircontinues this tradition.

The SmokeShield PTC™ range of QualityEngineered Dampers are suitable for airconditioning and ventilation systemsrequiring up to 2 hours (vertical) and 4hours (horizontal) smoke and fireprotection.Refer to Installation and MaintenanceGuide on our website for precise details.

These aerodynamic stainless steelinterlocking opposed blade dampers arefail-safe spring close with manual orelectrical reset control modes.

The control mode and snaplock™ driveinterface provides the optimummechanical advantage to the damper bydelivering:

the right torque, in the right place, atthe right time.

The Range

ProportionalTorque Control

SmokeShield PTCTM

2 www.actionair.co.uk

SmokeShield PTC™A.Fire Rated Damper in accordancewith British Standard 5588: Part9999: 1999 should be held in theOpen Position by means of aThermally Actuated Device set tooperate at approximately 74 °C.

SmokeShield PTC™ AutomaticSmoke and Fire Control Dampers areFire Rated Dampers as they are heldin the Reset (Open) Position by aThermally Actuated Device (ControlMode 1 – Mechanical Fusible Link,Control Modes 5 and 6 – ElectricalThermal Release, Control Mode 9 –Pneumatic Thermal Release) operatingat a temperature of approximately 72 °C ± 4 °C.

VentShield PTC™Proportional Torque Control AutomaticSmoke Release Dampers with75mm x 0.5mm thick stainless steelaerodynamic blades incorporatingsynthetic seal, with steel blade endbearings and peripheral gasketting.Housed in a galvanised steel fullywelded spigotted casing suitable forsquare, rectangular, circular or flatoval duct connections.

The totally enclosed precisemovement opposed blade drive shallbe positioned out of airstream forprotection against damage, be hardwearing and free running.

The Control Mode/Damperconnection shall be by means of thesnaplock™ drive interfacemechanism, which is totallyindependent of the ductwork.

VentShield PTC™ Automatic SmokeRelease Dampers with theirappropriate control modes shall havespring Fail-Safe Open operation.

VentShield PTC™ Damper andselected Control Modes as suppliedby Actionair.

Note: Thermally activated devices arenot supplied with VentShield ControlModes as standard.

SmokeShield PTC™ Proportional Torque Control AutomaticSmoke and Fire Dampers with 75mm x0.5mm thick stainless steel aerodynamicinterlocking blades incorporating syntheticseal, with steel blade end bearings andperipheral gasketting. Housed in agalvanised steel fully welded 1.2mmspigotted casing suitable for square,rectangular, circular or flat ovalconnections. All PTC™ Dampers are supplied with theblades in the closed position to preventthe ingress of dirt an dust.The totally enclosed precise movement

ApplicationParametersSmokeShield PTC™ and VentShieldPTC™ Dampers to maximum width andheight dimensions (see pages 16 and 17)can be used where the operating totalsystem pressure is up to 1500 Pascalsand duct velocities to 15m/second.The SmokeShield PTC™ Damper bladesare normally open and fail-safe to theclosed position.This product is fire rated. The VentShield PTC™ Damper blades arenormally closed and fail-safe to the open

position for smoke release or exhaust.Dampers may be installed both verticallyand horizontally. In addition, for verticalinstallations, the damper may be installedwith the blades running vertically. Airflowcan be from either direction.Actionair SmokeShield PTC™ andVentShield PTC™ Dampers are designedfor applications in normal dry filtered airsystems. If exposed to fresh air intakesand/or inclement conditions, the dampersshould be subject to a planned inspectionprogramme.For specialist and/or aggressive applications,please refer to Actionair Sales Office.

opposed blade drive shall bepositioned out of airstream forprotection against damage, be hardwearing and free running.The Control Mode/Damper connectionshall be by means of the snaplock™drive interface mechanism, which istotally independent of the ductwork.SmokeShield PTC™ Automatic Smokeand Fire Dampers with theirappropriate control modes shall havespring Fail-Safe Closed operation.SmokeShield PTC™ Damper andselected Control Mode (M1, M5, M6and M9) as supplied by Actionair.

The VentShield PTC™ Damper rangeare reverse acting for smoke releaseor exhaust. (Manual system notavailable).

Page 3: Proportional Torque Control Automatic Smoke and Fire …

SmokeShield PTCTM

3www.actionair.co.uk

Casing Features

With double skin spigotted galvanisedsteel (to BS EN 10327) 1.2mm thickcasing the SmokeShield PTC™ damperscomply to Class A and B of EuroventDocument 2/2 and Test Procedures forClasses A, B and C of HVCA DuctworkSpecification DW144.

Damper casings are manufactured withfully welded spigotted connectionssuitable for Square, Rectangular, Circularand Flat Oval duct connections.

As an extra cost option, casings can bemanufactured in 430 grade (Type 1.4016)Ferritic or 316 grade (Type 1.4401)Austenitic stainless steel, 1.2mm thick. Type SPG Square / Rectangular

Type SPG Circular

Type SPG Flat Oval

SmokeShield damper blades areaerodynamic double skin, Type 1.4016(430) Ferritic stainless steel, which are75mm x 0.5mm thick and interlock toform a positive smoke and fire resistingshield.

Incorporated within the blade profile is asynthetic seal to ensure low closed bladesmoke leakage.

Blade Features

SmokeShield PTC™ fail-safe closed

SmokeShield PTC™ blade dimensions

VentShield PTC™ fail-safe open

75 41.5

12.7

Stainless steel blade end bearing andperipheral gasketting maintain the lowclosed blade smoke leakage whilstallowing for expansion under full fireconditions.

Optional Blade construction Type 1.4401(316) Austenitic stainless steel.

Square and rectangular casings areavailable in multiple module arrangementssupplied complete with joining channelsfor site fixing by others.

STDRHD

LHD

LHDPLAN VIEW

LHD

LHD

STDRHD

S

STDRHD

STDRHD

Multiple Assemblies

Page 4: Proportional Torque Control Automatic Smoke and Fire …

SmokeShield PTCTM

4 www.actionair.co.uk

A choice of Control Modes are locatedoutside of the ductwork for easy accessand installation. All SmokeShield Control Modes must be inthe released position prior to connection.

Control Mode 1 Mechanical Manual reset – with volt free contact forprovision of external indication of damperstatus.

Control Options

Note: VentShield PTC™ Dampers andassociated control modes are reverseaction with spring opening (Mode 1 notavailable).

Not available on VentShield.

Damper – Control Mode Interface (Right Hand Damper shown)

SmokeShield PTC™ Damper withunique snaplock™ Damper/ControlMode Interface

Automatic Smoke and Fire Damper andControl Mode assembly with a uniqueand dedicated Proportional TorqueControl for optimised Damper/ControlMode torque performance.

The unique snaplock™ drive interfaceensures user friendly, easy and secureconnection of the Control Mode to theDamper.

The drive interface which is totallyindependent of the ductwork, eliminatesthe need for costly dedicated ductsections, and provides ease ofconnection to square, rectangular, circularand flat oval ductwork.

This drive interface guarantees that onlythe correct and certified Actionairproducts can be used.

snaplock™ Drive InterfaceDesigned to developProportional Torque Control

Damper Drive Shroud andTransit Plate

SmokeShield PTC™501 Damper

3 PositionLocation Plate

Control Mode5/6 shown

Mode 9, PneumaticActuator

Pneumatic Bracket

Control Modes 5 and 6 ElectricalOptimised motor/spring return controlmodes with remote reset-release facilities,with volt free contacts for provision ofexternal indication, monitoring and controlby means of an Actionpac dampercontrol system, or by a suitablealternative proprietary control format.The motorised Control Modes 5 and 6can be fitted in 3 positions through 180°(see page 10 ) allowing maximum on-siteinstallation flexibility. (Position 2 issupplied as standard).

Control Mode 9 Pneumatic

Page 5: Proportional Torque Control Automatic Smoke and Fire …

Thermal Links and Release Types (SmokeShield Only)

Electrical Thermal Release (ETR) - Control Modes 5 and 6

Pneumatic Thermal Release (PTR) - Control Mode 9

SmokeShield PTCTM

Fail-safe is by means of a Pneumatic Thermal Release (PTR) whichoperates at 74°C, or if air supply is interrupted.

Fail-safe by means of a unique and patented electrical thermalrelease which operates at approx 72 °C or if power supply isinterrupted, complying with BS 9999 : 2008 (Ref 33.4.5.3).

The ETR incorporates triple safety features, including an ingeniousdevice that ensures the fail-safe status of the damper if the ETR isnot fitted on to the ductwork.

A manual test switch allows periodic operation of the damper fortesting purposes simulating actual fail-safe release undersmoke/fire conditions.

For safety reasons the ETR/PTR is designed to operate once onlywhen the activation temperature is reached.

ETR Indication lightAs standard, a green LED lamp is built into the ETRhousing. This gives the user a simple and clear visualcheck that the Actuator is receiving power, the ETR iscorrectly fitted, and the thermal fuse is intact.

5www.actionair.co.uk

Fail-safe by means of a unique and patented Mechanical FusibleLink which operates at approx. 72 °C, complying with BS 9999 :2008 (Ref 33.4.5.3).

The link assembly incorporates a safety feature that ensures thefail safe status of the damper if the link is not fitted on to theductwork.

A manual test may be performed by simple unscrewing the wingnut situated on the fusible link.

Mechanical Fusible Link - Control Mode 1

FUSIBLE LINK

Page 6: Proportional Torque Control Automatic Smoke and Fire …

SmokeShield PTCTM

6 www.actionair.co.uk

SmokeShield and VentShield

M5 PTC 10/2W (12.5VAMAX) 24V end switches SPDT 250V 6(3)A SmokeShield Thermal Release / Power Off – Fail-safe Close*

M6 PTC 12/4W (14VAMAX) 230V end switches SPDT 250V 6(3)A SmokeShield Thermal Release / Power Off – Fail-safe Close*

M5 PTC Vent 10/2W (12.5VAMAX) 24V end switches SPDT 250V 6(3)A VentShield Thermal Release / Power Off – Fail-safe Open*

M6 PTC Vent 12/4W (14VAMAX) 230V end switches SPDT 250V 6(3)A VentShield Thermal Release / Power Off – Fail-safe Open*

M5 PTC NON ETR 10/2W (12.5VAMAX) 24V end switches SPDT 250V 6(3)A SmokeShield Power Off – Fail-safe Close

M6 PTC NON ETR 12/4W (14VAMAX) 230V end switches SPDT 250V 6(3)A SmokeShield Power Off – Fail-safe Close

M5 PTC Vent NON ETR 10/2W (12.5VAMAX) 24V end switches SPDT 250V 6(3)A VentShield Power Off – Fail-safe Open

M6 PTC Vent NON ETR 12/4W (14VAMAX) 230V end switches SPDT 250V 6(3)A VentShield Power Off – Fail-safe Open

Control Mode Details

Control Mode 5 PTC and ControlMode 6 PTC 60 seconds MAX Reset/22 seconds Release Operation.

These series of control modes achieve 60seconds to drive to the end position, witha 22 second spring return time. Thisbrings Actionair dampers in line withimminent European standardisation for fireand smoke control.

As with all PTC modes, this series usesthe snap lock™ interface. Fire rateddampers are primarily designed to befitted into a wall or floor, and the interfacedisplaces the mode from the line of thewall. Dampers may be installed and finallythe mode removed from storage for easyfitting, thus preventing damage to themode before it is required. End switchesand LSF cable are provided as standardon all modes.

*SmokeShield Control Modes M5 PTC and M6 PTC are supplied as standard with the Electrical Thermal Release (ETR) (Not fittedto VentShield). The units Fail-safe by means of the unique and patented ETR device which operates at 72 °C, or if the powersupply is off/interrupted. Complying with BS 9999 : 2008 (Ref 33.4.5.3). Part 9 1999. Non ETR versions Fail-safe when the poweris off/interrupted.

Versions are available to allow fail-safeclose for fire safety (SmokeShield) or fail-safe open for smoke extract (VentShield).

The Electro Thermal Release (ETR)supplied for fire damper use has anintegral fail-safe device to ensure that it isinstalled into the ductwork correctly. ETRunits are not supplied with VentShield,because these are designed to fail-safeopen.

End switches are provided with eachmode, so that damper Reset and Releasepositions may be monitored. The mode ispermanently attached to the mechanismdriving the damper blades.

Control Mode 9 PTC

This mode has been developed to providepneumatic operation of the damper and isavailable in spring return versions for fail-safe operation. A Pneumatic ThermalRelease assembly (PTR) is available(SmokeShield only) to react to fireconditions. As with all PTC actuators, thisseries uses the snaplock™ interface. Switchbox and solenoid accessories available.

M9 PTC Pneumatic Thermal Release / Air Off – Fail-safe Close

M9 PTC Vent Pneumatic Air Off – Fail-safe Open

Control Mode 5 PTC and Control Mode 6 PTC Control Mode 9PTC

Page 7: Proportional Torque Control Automatic Smoke and Fire …

SmokeShield PTCTM

7www.actionair.co.uk

SmokeShield and VentShield

M5-3P PTC 24V 7/2W (10VA) end switches SPDT 250V 6(3)A SmokeShield Thermal Release / Power Off – Fail-safe Close 2-10V Set Position

M5-3P PTC NON ETR 24V 7/2W (10VA) end switches SPDT 250V 6(3)A SmokeShield Power Off – Fail-safe Close 2-10V Set Position

M5-3P PTC Vent 24V 7/2W (10VA) end switches SPDT 250V 6(3)A VentShield Thermal Release / Power Off – Fail-safe Open 2-10V Set Position

M5-3P PTC Vent NON ETR 24V 7/2W (10VA) end switches SPDT 250V 6(3)A VentShield Power Off – Fail-safe Open 2-10V Set Position

Control Mode Details Continued

Control Mode 5 – 3P PTC Control Monitoring Station

Control Mode 5 – 2P PTC and Control Mode 6 – 2P PTC

As with all PTC modes, this series usesthe snap lock™ interface. Fire rateddampers are primarily designed to befitted into a wall or floor, and the interfacedisplaces the mode from the line of thewall. Dampers may be installed and thenthe mode removed from storage for easyfitting, thus preventing damage to themode before it is required. End switches,LSF cable, and Electro Thermal Release(ETR) are provided as standard (not fittedon VentShield).Versions are available to allow fail-safeclose for fire safety or fail-safe open forsmoke venting.

SmokeShield and VentShield

M5-2P PTC 24V 12W (18VA), end switches SPDT 250V 6(3)A

M6-2P PTC 230V 8W (15VA), end switches SPDT 250V 6(3)A

Control Mode 5 – 3P PTC with additionalfacility for third (Control) Position.150 seconds Reset, 20 secondsRelease.This 3 position control mode allows adamper to be moved to both the resetand release position, with the additionalfacility to move the damper to a thirdcontrol position. The mode is given a 2-10V DC signal, defining the position thatthe damper needs to be set at. A return signal of 2-10V DC is provided toallow monitoring of position.To support this actuator and allowpositioning to be set local to the damper,Actionair have the M5-3P 24V and M5-3P 230V control units.

Drive Open / Drive Closed. 60 secondsoperation

This 2 position control mode has beendeveloped to provide drive open/drive closeddamper operation and it brings Actionairdampers in line with imminent EuropeanStandardisation for fire and smoke control,where for a given smoke control philosophy,or smoke source, a damper may be requiredto open or close to vent or contain thesmoke. This is a radical alternative to thetraditional spring return actuator, where uponpower failure, instead of moving to fail-safeposition, it remains in its desired emergencyposition. For any smoke control emergencysituation, this is an absolute necessity. Thesemodes do not have ETRs.As with all PTC actuators, this series usesthe snap lock™ interface. All modes haveLSF cables.

SmokeShield Control Modes M5 –3P PTC are supplied with the Electrical Thermal Release (ETR) (Not fitted to VentShield). The units Fail-safe by means of the unique and patented ETR device which operates at 72 °C, or if the power supply isoff/interrupted. Complying with BS 5588 Part 9 1999. Non ETR versions Fail-safe when the power is off/interrupted.

The M5-3P CMS (Control MonitoringStation) this control unit gives the user theopportunity to set a control position usingan integral potentiometer, or use anexternally supplied control voltage. Itprovides visual (lamp) and volt free (relay)indication of damper position (Released, atControl Position, Reset). A terminal isprovided to allow feedback of the 2-10V DC monitoring voltage. In addition, afire alarm input may be made (NC) whichwill cause the damper to Release if thecontact is broken. A second input isavailable to cause the damper to fully Resetto allow full air flow for smoke venting as anexample. The fire alarm Release input takesprecedence. Switches are provided thatallow the unit to be driven to Release orReset positions for testing purposes.

M5-3P 24V and M5-3P 230V CMS Control Stations

M5 – 3P – CMS M5 – 3P – CMS (230V)

Page 8: Proportional Torque Control Automatic Smoke and Fire …

SmokeShield PTCTM

8 www.actionair.co.uk

BLUE N

L1BROWNAC 230V

50 / 60 Hz

14 VA12 / 4 W

–30...+50 CCONTINUOUS

�–

+

1

2

1

2

3

5

6

4

VOLT FREECONTACT MADE BETWEEN 1 AND 2 WHEN DAMPER FULLY RELEASED

)

AC/DC 24V50 / 60 Hz

12.5 VA10 / 2 W

Imax8.3A @ 5ms

–30...+50 CCONTINUOUS

AC 250V6(3)A

SUPPLY24V AC or DCTYPICALLY 10W (MOTORING)2W (RESET)

DIAGRAM SHOWS ACTUATOR IN FULLY RELEASED STATE

DIAGRAM SHOWS ACTUATOR IN FULLY RELEASED STATE

DIAGRAM SHOWS ACTUATOR IN FULLY RELEASED STATE

M

ELECTRICAL THERMAL RELEASE (MUST BE FITTED TO DUCTING FOR DAMPER OPERATION). NON ETR VERSION AVAILABLE ON REQUEST(SPRING BIASED TEST SWITCH)

TF 72 C

AC 250V6(3)A

VOLT FREE CONTACT CLOSED WHEN DAMPER RESET (at 85 ) RATED 250V 5A

COMMON

NORMALLY CLOSED

NORMALLY OPEN

)

D

GREEN/YELLOW

BROWN

BLUE

BLACK

VOLT FREECONTACT MADE BETWEEN 4 AND 6 WHEN DAMPER FULLY RESET

1

2

3

5

6

4

VOLT FREECONTACT MADE BETWEEN 1 AND 2 WHEN DAMPER FULLY RELEASED

SUPPLY230V AC 50/60 HzTYPICALLY12W (MOTORING)4W (RESET

M

ELECTRICAL THERMAL RELEASE (MUST BE FITTED FITTED TO DUCTING FOR DAMPER OPERATION). NON ETR VERSION AVAILABLE ON REQUEST(SPRING BIASED TEST SWITCH)

TF 72 C

VOLT FREECONTACT MADE BETWEEN 4 AND 6 WHEN DAMPER FULLY RESET

BLACK

WHITE

Application and Wiring - Smoke (with ETR)

SmokeShieldMode 1 PTC (Manual System)

Manual opening.Spring instant closure via mechanicalfusible link.

(SmokeShield version only, VentShield not available.)

SmokeShieldMode 5 PTC (24V System)

The following applies for ETR version.(ETR not supplied on VentShield.)

Supply On – Damper motors reset.Supply Off – Spring release.Electrical Thermal Release.External mechanical position indicator withpointer.Release Time ≈ 22 secs.Reset Time ≈ 60 secs.

(Connect 24V via a safety isolatingtransformer.)

IP54 Rated.

SmokeShieldMode 6 PTC (230V System)

The following applies for ETR version.(ETR not supplied on VentShield.)

Supply On – Damper motors reset.Supply Off – Spring release.Electrical Thermal Release.External mechanical position indicatorwith pointer.Release Time ≈ 22 secs.Reset Time ≈ 60 secs.

(To isolate from main power supply, the systemmust incorporate a device which disconnectsthe phase conductors, with a least 3mmcontact gap.)

Note: 120V A.C. version also available.

IP54 Rated.

Page 9: Proportional Torque Control Automatic Smoke and Fire …

SmokeShield PTCTM

9www.actionair.co.uk

BLUE

BLACK

WHITE

N

L1BROWN

1

2

3

4

AC 230V50 / 60 Hz

–30...+50 CCONTINUOUS

M

�–

+

1

2

1

2

3

4

AC/DC 24V50 / 60 Hz

–30...+50 CCONTINUOUS

M

VOLT FREE CONTACTCLOSED WHENDAMPER RELEASED

SUPPLY230V AC 50/60 Hz

AC 250V6(3)A

VOLT FREE CONTACTCLOSED WHENDAMPER RELEASED

AC 250V6(3)A

SUPPLY24V AC or DC

VOLT FREE CONTACTCLOSED WHENDAMPER RESET

VOLT FREE CONTACTCLOSED WHENDAMPER RESET

12.5 VA10/2 W

14 VA12 / 4 W

(Connect via a safety isolating transformer)

Imax8.3A @ 5ms

General (Electrical)

One metre of halogen free low smoke andfume electric cable is also included withControl Modes 1, 5 and 6 forconvenience of on site wiring. This alsoprovides the distinct safety advantage ofall electrics terminating outside the duct,eliminating potential in-duct fire hazardsfrom wiring faults.

The Electrical Thermal Release is pre-wired with 0.5m halogen free low smokeand fume cabling to Control Modes 5 and6. (Not supplied on VentShield).

A Manual test switch fitted on the ETRallows periodic operation of dampersimulating actual fail-safe release undersmoke/fire conditions.

(Prewired Connection boxes available asfactory fitted option.)

Application and Wiring - Vent (or Smoke Non-ETR)

VentShield PTC™ Dampers andassociated Control Modes M5 and M6are reverse action with spring opening.

Air On – Damper resets.Air Off – Spring release.Release time ≈ 2 – 4 secs.Reset time ≈ 2 – 4 secs.Air inlet – 6mm dia. quick fit coupling.74 °C Pneumatic Thermal Link (PTR).(PTR not supplied on VentShield.)Air pressure ≈ 5.5 – 8.0 bar.Air consumption to reset @ 5.5 bar –535CC. External mechanical position indicator.Test operation by removing fusible linkelement.

VentShield Mode 5 (24V System)

Supply On – Damper motors reset.Supply Off – Spring release.

Cable specification:Si HF Low Smoke and Fume, HalogenFree, to IEC 754-1. Conforming to73/23/EEC directive.

Release Time ≈ 22 secs.Reset Time ≈ 60 secs.

(Connect 24V via a safety isolatingtransformer.)

IP54 Rated

VentShield Mode 6 (230V System)

Supply On – Damper motors reset.Supply Off – Spring release.

Cable specification:Si HF Low Smoke and Fume, HalogenFree, to IEC 754-1. Conforming to73/23/EEC directive.

Release Time ≈ 22 secs.Reset Time ≈ 60 secs.(To isolate from main power supply, the system mustincorporate a device which disconnects the phaseconductors, with a least 3mm contact gap.)

Note: 120V A.C. version also available.

IP54 Rated

Smoke Shield or Vent Shield Mode 9PTC (Pneumatic Operation)Control Modes 5 and 6 are available

without the ETR where thermal operationis not required. (This would not complywith BS 9999 : 2008 or SmokeShield (Ref33.4.5.3).

Page 10: Proportional Torque Control Automatic Smoke and Fire …

Transit Plate

STD RHDActuatorPosition

Control Mode 5/6 shown

Damper Installation and Control Mode Fitting

Step 3 (Control Modes 5 and 6) and M5 - 3P

Identify location for the Thermal Release (not requiredon VentShield). Ideally, this should be fitted to the tophalf of the duct, adjacent to the control mode. Fit theself adhesive drilling template (supplied) in this position.Drill holes as detailed on the template. Using the 2fixing screws provided, secure the Electrical ThermalRelease to the duct. Connect electrically, and testoperation.

As a safety feature the actuator will only operate ifthe ETR is correctly fitted to the duct.

Note: Non ETR version available.

10 www.actionair.co.uk

SmokeShield PTCTM

Step 1

Install the SmokeShield PTC™ Automatic Smoke and FireDamper (complete with transit plate) into the structure. Refer toInstallation Systems on page 12 and 13 and Installation andOperating Instructions. Connect and fit ductwork to damperspigots. Remove transit plate and discard (recycle).

(Care must be taken when back filling to ensure that thesnaplock™ retaining pin location hole and the entry slot of thedamper drive shroud is clear of builders work debris).

Step 2

Slide the snaplock™ Drive Interface into the damper driveshroud, ‘snaplock™’ into position.

The ‘snaplock™’ feature provides a user friendly, easy andsecure direct connection. It comes pre-set to enable direct fit toSmoke/VentShield damper.

Page 11: Proportional Torque Control Automatic Smoke and Fire …

315 ± 20mm

SMOKE/SHIELDDAMPER

MECHANICALFUSIBLE LINK

F

P

BOWDEN CABLE

40 ± *75mm

5mm

130mm

135mm Open

Closed

108

130m

m

TOP

Mark the Fusible Link position on the duct as dimensioned in thediagram above.

Fit the self adhesive drilling template (supplied) in this position.Drill holes as detailed on template. Using the 2 fixing screwsprovided, secure the Fusible Link to the duct. Reset Damperusing a 14mm A/F spanner, clockwise 1/4 turn. Test unit bysimply unscrewing wing nut – Damper releases. For ductlessinstallations a suitable sized plate or bracket must be fitted to theinstallation to allow the fitting of the Fusible Link.

As a safety feature the Control Mode will only operate if theFusible Link is correctly fitted to the duct.

*This dimension will vary on CircularDamper. Select dimension to givesmoothest radius on bowden cable.

Step 3 (Control Mode 1) SmokeShield only Step 3 (Control Mode 9)

1. Select position for PTR. (SmokeShield only). Ideally thisshould be in the top half of the duct and sufficiently close tothe actuator to allow easy connection of the 4mm diameternylon tube supplied.

2. Drill hole in selected position using a 30mm diameter holecutter, removing any sharp edges.

3. Position PTR and drill the 4 o f f 3mm diameter fixing holes.

4. Remove PTR and apply approved fire retardant sealant onthe duct around the hole.

5. Refit PTR and secure with the 4off Pozi head screwsprovided.

6. Connect 4mm diameter tube to actuator and PTR.

7. Connect 6mm diameter tube to input side of PTR.

8. Connect air supply. Damper opens fully.

9. Test operation.

SMOKE/SHIELDDAMPER

FLOW RESTRICTOR

AIR SUPPLYINLET

PNEUMATIC THERMAL RELEASE

4mm NYLONTUBING 500mm LENGTH

Damper Installation and Control Mode Fitting Continued

11www.actionair.co.uk

SmokeShield PTCTM

Page 12: Proportional Torque Control Automatic Smoke and Fire …

Installation Systems

Popular types of Installation Frame thatare available.

DWFXTM (DRY WALL FIX) InstallationSystemTypically for installation into Dry Wall, StudPartitions.

HEVAC / HVCA Galvanised SteelInstallation FramesTypically for installation into Blockwork,Concrete walls and floors.

DWFX-CDWFX-F

SpecificationThe Actionair DWFX-C installation methodis BRE Tested to EN1366-2, BRE TestReport 231741.

Classification E120/ES120 BS EN 13501.

The Actionair DWFX-C consists of 50mmx 50mm x 3mm steel angle cleats with 14x 24mm oval slots.

Fully welded to damper casing for droprod support prior to wall construction.

SpecificationThe Actionair DWFX-F installation methodis BRE Tested to EN1366-2 for 90minutes. (BRE test report 220895).

Classification E90/ES60 BS EN 13501.

The Actionair DWFX-F consists of a 1.2mm galvanised steel peripheral flangewith 50mm x 50mm x 3mm steel anglecleats with 14 x 24mm oval slots, weldedto damper flange for drop rod support.

Comprehensive literature, outlininginstallation and features, is available forour DWFX systems. Go to our website:-

www.actionair.co.uk

to view or download these as PDF files.

50 50 50

DWFX-FDimensional DataSee page 16 and 17.

DWFX-C Dimensional Data

24

14

SmokeShield PTCTM

12 www.actionair.co.uk

Page 13: Proportional Torque Control Automatic Smoke and Fire …

A binder containing approved installationillustrations is now available.

(Refer to Actionair Sales Office or visitour website, www.actionair.co.uk The illustrations are under the headingPRODUCTS DRAWINGS.)

Although the included methods have beentested and assessed, it is recommend,that these, as with all installation methodsmust be confirmed with Building Control /

Local Authority prior to manufacture.Actionair can also provide applications ofother proposed methods of installation,please contact our Sales Office to discussyour specific requirements.

These again are the responsibility of theclient to ensure that these are acceptable toBuilding Control / Local Authority beforeconstruction commences.

Approved Installations

Galvanised steel buildingties permit stablehandling, ease oftransport andconvenience of building into the surroundingstructure.

HEVAC / HVCA Galvanised Steel Installation Frames

Galvanised Steel Installation Frames(as required by HVC 6/5/83 Rev.1 July1999.)

Installation frames are delivered to site as acomplete assembly with the appropriateDamper fitted therein. The frame shall beinstalled centrally in the thickness of abrick, blockwork or concrete surroundingwall or floor, or in the case of thick walls orfloors, so that the centre line of the frame

is at least 50mm away from the nearestface of the wall or floor in which theassembly is mounted. The four tabs(building tie) forming each fixing pointshall provide a positive fixing into thestructure. Multiple assembly dampers upto 1500 x 1500 or 2000 x 1000 can befitted into fully assembled installationframes and delivered as one piece.Dampers in excess of these sizes will be

supplied in sections with the installationframe supplied in kit-form, Drg AA/F/8057.This drawing and method statement will besupplied for assembly to on site.

The maximum size of kit-form installationframes is 2500mm wide x 2000mm high.

a. In brick or blockwork walls the tabs shallbe bent out and solidly built into the mortarjoints between the brick or blockwork.

b. In the case of reinforced concrete wallsand floors, the tabs shall be bent out andtied with wire to the reinforcing bars whichwill be deliberately left protruding into theopening.

The gap between the installation frameand builders work shall be backfilledwith mortar or concrete on both sidesof the flange.

Adjacent frame assemblies must beseparated by builders work of a minimumthickness of 225mm (between installationframe upstand flanges) unless approvalhas been previously obtained from theappropriate Authority. For installationsbelow this dimension please refer toActionair Sales office.

In no case shall the HEVAC/HVCA frameand damper assembly be held in positionmerely by the adjacent ductwork, and itshould be noted that in reinforced concretestructures (especially floors), it will not besufficient to only backfill between thedamper installation frame and thesurrounding opening with mortar or fineaggregate concrete mix without provisionfor tying in the frame to the surroundingreinforced concrete structure.

SmokeShield PTCTM

13www.actionair.co.uk

Page 14: Proportional Torque Control Automatic Smoke and Fire …

DTU24 24V AC/DC

DTU120 120V AC

DTU230 230V AC

DSI24 24V AC/DC

DSI120 120V AC

DSI230 230V AC

DCU24 24V AC/DC

DCU120 120V AC

DCU230 230V AC

SmokeShield PTCTM

M52PDCU 24V AC/DC

M62PDCU 230V AC

DCB 24V – 230V AC/DC

M53PCMS 24V AC/DC

230V M53PCMS 230V AC

Accessories

Solenoid, (24V, 120V, or 230V). EEXD Solenoid, (24V,120V, or 230V). Damper Status Beacon. Switchbox andStatus Beacon. Zone 2 Switchbox and Status Beacon.

24 – 230V AC/DC

M5 and M6 – 2P Damper Control UnitSwitch power open/power close. Openand closed indication.

Damper Connection Box(All Voltages).

M5 – 3P – CMS Control Unit

230V M5 – 3P – CMS Control Unit

Pneumatic

A range of indicator panels, push button switches anddamper test units are also available. The housing forthese units are manufactured in rigid ABS plastic. The Damper Connection Box is in galvanised steel.

Damper Release and IndicationModule (DRIM)This is designed for control andmonitoring of the electrically operated Smoke Shield PTC™ Fire and Smokedampers.It will operate from 24V, 120V or 230Vsupplies, 50 or 60 Hz.Selection of the operating voltage isby use of internal links on the PCB,

prior to installation and connectionof actuator and supply.The DRIM may be used singly toprovide local damper control, orin pairs to provide control fromeither side of a damper. It canalso operate 2 actuators whendampers are provided in 2multiple sections.

Damper Test UnitReset and release indication. Spring bias (power OFF) test switch.Power normally ON.

Damper Status IndicatorReset and release indication.

Damper Control UnitSwitch ON/OFF function. Reset and release indication.

LED position and operationindication is provided.Operation is by push button toclose and twist to re-opendamper.Tested to BS EN 61010 -1: 2001and is CE compliant.IP44 rated.Operating range 5 - 40 °C.

DRIM 24V – 230V AC/DC

14 www.actionair.co.uk

Electrical

Page 15: Proportional Torque Control Automatic Smoke and Fire …

70 25

Snaplock RETAINING PIN LOCATION HOLE

1305

INPUTSHAFT

108

130

14

248

28

56

109

25

84

56260

100

112

12

108

Position 1

Position 2

Position 3

Control Mode Dimensions and Orientation

Mode 1 (SmokeShield only)

SmokeShield PTC™ Control Modes are locatedoutside of the ductwork for ease of access andinstallation.

Modes 5 and 6 Three position 180° (PivotableControl Mode)SmokeShield PTC™ Control Modes are locatedoutside of the ductwork for ease of access andinstallation.Control Modes 5 and 6 can be fitted in any one ofthree orientations i.e.Vertically down (Position 1)Horizontally (Position 2), or Vertically up (Position 3).This can be simply and easily carried out on site,by repositioning the Location Plate (see page 2)and Control Mode on to the snaplock™ DriveInterface.This flexibility ensures that the damper and controlmode require the minimal amount of room.(Supplied in position 2 as standard.)

Mode 9 Pneumatic Control

SmokeShield PTC™ Control Modes are locatedoutside of the ductwork for ease of access andinstallation.

115

255

95

55 59

160

CABLE ENTRY POINTS

SWITCHBOX / STATUS BEACONOptional Extra

SOLENOIDOptional Extra

102

222

143

155

108 22

2

SmokeShield PTCTM

15www.actionair.co.uk

Page 16: Proportional Torque Control Automatic Smoke and Fire …

90

90

90100 - 15025 = =

= =

25

50

25

83

57

DU

CT

H

EIG

HT

200 -

1000

OVERALL WIDTH OF INSTALLATION

FRAME IS 316mm

OVERALL HEIGHT OF INSTALLATION

FRAME IS 340mm

OVERALL FLANGE WIDTH = 370mm

OVERALL FLANGE HEIGHT = 395mm

OVERALL WIDTH OF INSTALLATION

FRAME IS 366mm

OVERALL HEIGHT OF INSTALLATION

FRAME IS 390MM

OVERALL FLANGE WIDTH = 420mm

OVERALL FLANGE HEIGHT = 445mm

OVERALL WIDTH OF INSTALLATION

FRAME IS DUCT WIDTH + 116mm

OVERALL HEIGHT OF INSTALLATION

FRAME IS DUCT HEIGHT + 140MM

OVERALL FLANGE WIDTH

= DUCT WIDTH + 170mm

OVERALL FLANGE HEIGHT

= DUCT HEIGHT + 195mm

20

0

151 - 19925 25

50

25

83

57

250

200 -1000

DUCT WIDTH

DUCT WIDTH

DUCT WIDTH

200

250

25 25

50

25

83

57

200 -

1000

Rectangular Dampers Series 501 and 1501

HEVAC / HVCA IFDampers with DWFX-F

Basic Dampers Dampers with Installation Systems

H

For Ducts with widths of 100- – 150mm*

For Ducts with widths and heights of 200- – 1000mm*

For Ducts with widths of 151- – 199mm*

38383838 78

38383838 78

DU

CT

HE

IGH

T

10

0 -

15

0

200 -

1000

20

0250

DU

CT

HE

IGH

T

151 -

199

3838 78

DU

CT

HE

IGH

T

200 -

1000

=

D

=

D

DUCT DIA + 190mm

7

= 370mm

O

=

D

=

D

= 420mm

O

11

08

52

00

110

250

85

50

110

200 -

1000

85

50

1

For Ducts with heights of 100- – 150mm*

For Ducts with heights of 151- – 199mm*

50

28

28

28

S

WA

Dimensional DataFor Rectangular Dampers spigots are 5mm under duct size. * Widths and heights available in 1mm increments.

(For further details pleaserefer to Actionair Sales Office.)

SmokeShield PTCTM

16 www.actionair.co.uk

Page 17: Proportional Torque Control Automatic Smoke and Fire …

HEVAC / HVCA IFDampers with DWFX-F

Basic Dampers Dampers with Installation Systems

F

F

=

==

==

=

DUCT DIA100 - 150*

DU

CT

DIA

ME

TE

R

90

10

88

2

50

25

10

0 -

15

0*

200 -

500*

300 – 950*

DUCT WIDTH *

DUCT WIDTH + 50mm*

50 50

25

28

25

75

25

25

50

DU

CT

HE

IGH

T

CIR

CU

LA

R *

*

FLA

T O

VA

L

108

82

50

25

DU

CT

HE

IGH

T

+50M

M

CIR

CU

LA

R

25

25

FLA

T O

VA

L *

*

65383865 78

65383865 78

OVERALL WIDTH OF INSTALLATION

FRAME IS DUCT WIDTH + 166mm

OVERALL HEIGHT OF INSTALLATION

FRAME IS DUCT HEIGHT +190mm

OVERALL FLANGE WIDTH =

DUCT WIIDTH + 220mm

OVERALL FLANGE HEIGHT =

DUCT HEIGHT + 245mm

OVERALL WIDTH OF INSTALLATION

FRAME IS 316mm

OVERALL HEIGHT OF INSTALLATION

FRAME IS 340mm

25 25

Circular Dampers Series 601 and 1601

Flat Oval Dampers Series 701 and 1701

200

20

0

50

25

250

50

25

Duct

DIA

+ 5

0m

m*

DUCT DIA151 - 199*

DUCT DIA200 - 950*

50 50

DU

CT

DIA

ME

TE

R

90

108

82

151 -

199*

25

25

CIR

CU

LA

R *

*

CIR

CU

LA

R

65383865 78

OVERALL WIDTH OF INSTALLATION

FRAME IS DUCT DIA + 166mm

OVERALL HEIGHT OF INSTALLATION

FRAME IS DUCT DIA + 190mm

75

50

DU

CT

DIA

ME

TE

R

90

108

82

200 -

950*

25

25

CIR

CU

LA

R *

*

CIR

CU

LA

R

65383865 78

OVERALL WIDTH OF INSTALLATION

FRAME IS 366mm

OVERALL HEIGHT OF INSTALLATION

FRAME IS 390mm

OVERALL FLANGE WIDTH = 370mm

OVERALL FLANGE HEIGHT = 395MM

1mm Increments **

1mm Increments **

1mm Increments **

1mm Increments **

OVERALL FLANGE WIDTH =

DUCT DIA. + 220mm

OVERALL FLANGE HEIGHT =

DUCT DIA. + 245mm

OVERALL FLANGE WIDTH = 420mm

OVERALL FLANGE HEIGHT = 445mm

2525 250

2525 Duct

90

= =

28

28

28

FOR 951 – 1000mm

DUCT DIM + 30mm

FOR 951 – 1000mm

DUCT DIM + 30mm

110

85

50

110

85

50

110

85

50

11

08

5

50

*

S

WA

For Circular and Flat Oval Dampers spigots are 3mm under duct size.*Diameters and flat oval diameters in 1mm increments.

(For further details please referto Actionair Sales Office.)

SmokeShield PTCTM

17www.actionair.co.uk

Page 18: Proportional Torque Control Automatic Smoke and Fire …

The data presented is from theLaboratory Determination of Acoustic andAerodynamic Performance ofSmokeShield PTC Automatic Smoke andFire Control Dampers.

A programme of extensive tests wascarried out in the Reverberation Chamberand North Transmission Chamber ofSound research Laboratories Limited,Holbrook Hall, Sudbury, Suffolk, generallyin accordance with BRITISH STANDARDSNos. 4196, 4773, 4856, 4857 and 4954.

This independent test facility is approvedunder the NAMAS Scheme.

From the selection of a duct velocitywithin the operational parameters of thedamper a resultant pressure drop fromGraph 1 can be determined and the sumof these two components applied to theVelocity x Pressure Drop Vs Sound PowerLevel Graph. (Graph 2)

The graph is the result of a full range of acoustic tests on SmokeShieldPTC™ Automatic Smoke and Fire ControlDampers with the blades set in their fullyopen position.

The Spectrum Correction Data is appliedto the number obtained from the graphand a complete Sound Spectrum of FlowGenerated Noise for both Outlet (in duct)and Breakout (casing radiated) can beobtained from Table 1.

Pressure Drop Vs Velocity

EXAMPLE LINE

1 2 3 4 5 6 7 8 9 10 15

100908070

60

50

40

30

20

10987

6

5

4

3

2

1

TYPE

501

TYPE

601

PRESSURE DROP (Pa)

VELOCITY (m/s)

Acoustic Data

Graph 1

Example:

Duct with a design velocity of 8 m/sec.SmokeShield PTC Damper Series 501fully open.

Pressure Drop = 21 Pa (Graph 1).Multiply Velocity x Pressure Drop 8 x 21 = 168.

From Sound Power Graph (Graph 2) plot168 on horizontal Velocity/Pressure axisagainst 501 outlet (induct) graph to obtain47 dBW on Vertical Sound Power Level

Axis. Add or subtract corrections to the47 dBW to provide full spectrum analysisusing appropriate Correction Table.

SmokeShield PTCTM

18 www.actionair.co.uk

Page 19: Proportional Torque Control Automatic Smoke and Fire …

SmokeShield PTC™ Breakout Spectrum Corrections

Octave Band Hz 63 125 250 500 1k 2k 4k 8k

Series 501 dB 8 11 9 6 -3 -6 -14 -17

Series 601 dB 6 10 8 4 -3 -3 -11 -14

1500

1200

1000

500

300

250

200

150

120

100

70

505 1005010 20 30 40

SmokeShield PTC™ Outlet (Induct) Spectrum Corrections

Octave Band Hz 63 125 250 500 1k 2k 4k 8k

Series 501 dB 5 4 5 5 3 1 -3 -5

Series 601 dB 9 4 4 5 3 1 -3 -6

Velocity (m/s) X Pressure Drop (Pa)Vs Sound Power Level (dBW)

90

70

80

60

50

40

30

20

10

0

10 20 30 40 50 60 70 80 90 100

200

300

400

500

600

700

800

900

1000

2000

3000

4000

5000

6000

7000

8000

9000

1000

0

EXAMPLE LINE

501

BREAKOUT

601

OUTLET

(INDUCT)

501 OUTLE

T (INDUCT)

601

BREAKOUTSOUND POWER LEVEL (dBW)

VELOCITY X PRESSURE DROP (m/s Pa)

Table 1

Correction Tables

Table 2

Graph 2

PRESSURE DIFFERENTIAL ACROSS CLOSED DAMPER (Pa)

SmokeShield PTC™ and VentShieldPTC™ closed blade leakage as tested ona damper 1000mm wide x 1000mm high.

LEAKAGE (I/s)

The SmokeShield PTC™ Damper hasbeen fire tested to BS ISO 10294-1 andBS EN 1366-2. It achieved ESclassification in accordance with BS ISO10294-2:1999. ES classification allows amaximum of 200m3/ Hr/m2 (corrected to20 °C) hot gas leakage throughout the testat 300 Pa pressure differential across thedamper.

Leakage data at Ambient temperature (Cold Smoke).

Graph 3

Damper Leakage

SmokeShield PTCTM

19www.actionair.co.uk

Page 20: Proportional Torque Control Automatic Smoke and Fire …

SmokeShield PTCTM

Fully comprehensive brochures are available on all Actionpac products. Visit theActionair website w.w.w.actionair.co.uk and download the relevant pdf.

Actionpac Damper Control Systems

• Optional automatic scheduled Dampertesting

• Multiple wiring configurations to includeRadial or Loop Topology

• Damper operational count provided

• Flexibility to accommodate any lastminute changes to strategy, zones,damper quantities, references anddescriptions etc.

• Powerful and flexible functionalityenables standardisation of software (nobespoke site specific versions required)

• Cause and effect scenarios easilyaccommodated

• Multiple options for monitoringdampers, individually or by group orzone - output contacts can betriggered when a predefinedpercentage within a group or zonechange position

• System designed to cater forenvironmental occupancy as well asthe building’s smoke/ fire strategy.RS232 BMS link provided enabling aBMS to link directly to the system toread damper positions etc.

• Optional remote access available

• Graphical User Interface displays livedamper status and details as well ascause and effect strategies

• Text fields facilitate clear description ofdevice references and locations

• System wide activity logged andviewable for diagnostics andmaintenance

• Allows for phased commissioning andfuture expansion

• CE marked, LVD and EMC compliant

Actionpac LNS3 Intelligent DamperControl and Monitoring System

The Actionpac LNS3 system represents anew generation of smoke/fire dampercontrol. The system has been designedwith the user in mind, providing anadvanced tool that simplifies installationand commissioning of smoke/firedampers and peripheral devices. ThePanel PC operates on a Windows™platform making it universally acceptedand utilises solid state technology foroptimum reliability.

It’s server architecture delivers newbenefits such as reduced commissioningtime, simplified operation and scope forfuture growth.

The Actionpac LNS3 system is designedto protect life and property from damagecaused by smoke and fire, by providingthe means to:–

• Compartmentalise fire zones.

• Reduce the spread of smoke and fire.

• Keep escape routes and fire-fightingaccess open.

• Allow pressurisation and smoke extractby combined operation of dampersand fans.

Benefits

• Completely flexible to meet practicallyany building’s damper requirements

• Three levels of alarm priority

• Panel PC driven system with real-timegraphic displays

• Panel PC utilises solid state technologyfor optimum reliability

• Full configuration and diagnostics fromPanel PC

Electro Mechanical SystemsActionpac EMS - Standard Controland Monitoring System

Control and monitoring of Mode 5 orMode 6 damper actuators in groups of12, 24 or 36.

Actionpac EMB - Bespoke Controland Monitoring System Control Panel

The EMB Control Panels typically consistsof the appropriate number of switches toprovide individual or group control, LEDindication for status monitoring and allnecessary relays and timers to complywith the customer needs for fully or semiautomatic damper operation. The EMBpanels are purposely manufactured forany particular project to suit specific clientrequirements.

Actionpac LNS3 Intelligent DamperControl and Monitoring System

Addressable SystemsActionpac 60/120 ( LNS Standard)Intelligent Damper Control andMonitoring System

Actionpac 60 for the control /monitoringof up to 60 off SmokeShield dampers.Actionpac 120 for the control /monitoringof up to 120 off SmokeShield dampers.

20 www.actionair.co.uk

Page 21: Proportional Torque Control Automatic Smoke and Fire …

General Schematic of Actionpac LNS3 Damper Control System

SmokeShield PTCTM

SFDI

SFDI

SFDI

SFDI NDI404

SFDI

SFDI

Panel PC

Fire Alarm Inputs

BMS Inputs

Fireman’s Switch InputsB.M.S.

Vent Panel

OU

TPU

TS

INP

UTS

SFDI

NDI404

Smoke Fire Damper Interface One per Control Mode

Damper Control Mode*

Network Digital Input / Output Device - provides four inputs and four outputs

To additional devices as required

To additional devices as required

Data Network

24/230 volt (local power by others)

24/230 volt (local power by others)

24/230 volt (local power by others)

24/230 volt (local power by others)

24/230 volt (local power by others)

24/230 volt (local power by others)

24/230 volt (local power by others)

24/230 volt (local power by others)

SFDI

* Only one Damper to be controlled by an SFDI, SDI or FDI.Supply to each Damper Interface from nearest local distribution board.

21www.actionair.co.uk

Page 22: Proportional Torque Control Automatic Smoke and Fire …

Square or Circular 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000Duct Size (mm)

Series 501 Square 3.4 3.4 3.4 4.2 4.8 5.6 6.5 7.4 8.6 9.6 10.8 12.4 13.6 14.9 16.2 17.7 19.2 20.8 23.5

Series 501 Square + I/F 6.2 6.2 6.2 7.4 8.7 10.3 11.9 13.2 14.6 16.3 18.5 20.5 22.1 24.0 25.9 28.1 30.3 32.4 34.5

Series 601 Circular 5.3 5.3 5.3 6.1 7.2 8.4 9.6 11.2 12.6 14.0 15.9 17.5 19.1 20.7 22.5 24.3 26.2 29.3 32.1

Series 601 Circular + I/F 8.5 8.5 8.5 10.0 11.9 13.7 15.4 17.1 19.2 21.8 24.0 26.0 28.2 30.4 32.8 35.3 37.8 40.3 43.1

Approximate Weights (Kg)

Control Mode 1 (SmokeShield only) (including drive interface) 4.1KgControl Modes 5, 5 - 3P, 5 - 2P, 6, 6 - 2P and 9 (including drive interface) 4.4Kg

The information contained herein is subject to changewithout notice due to continuing research anddevelopment.

Approvals

Approved by The Loss Prevention Councilfor use in up to 4 hour constructions.

Refer to Installation and Maintenance Guideon our website for precise details.

The SmokeShield PTC™ Damper testedand assessed to BS ISO 10294-1, BS EN 1366-2 and BS 476 pt. 20. It achieved ESclassification in accordance with BS ISO 10294-2:1999.

Low gas/smoke and fire integrity toClassification ES in vertical and horizontaltest installations.

Customer Service

Actionair provides quality productsbacked by a dedicated team committedto providing the very best in customerservice.

Offering experienced technical backup,comprehensive sales and administrativecustomer support, productcommissioning and maintenance service.

MaintenanceThe SmokeShield PTC™ Dampersare designed for applications innormal dry filtered air systems andshould be subjected to a plannedinspection programme, with cleaningand light oil lubrication in accordancewith BS9999. When exposed to freshair intakes and/or inclementconditions this may need to beperformed more regularly based onexperience gained from previousinspections.

Quality Assurance

SmokeShield PTCTM

Certification No.17

Assessed to ISO 9001

22 www.actionair.co.uk

An LPCB approved product, compliant tothe new Loss Prevention Council DesignGuide for Fire Protection of Buildings.

Fire tested in vertical and horizontalapplications under dynamic conditions byThe Loss Prevention Council.

Corrosion tested to LPS 1162.

Complies with the latest DW 144 casingleakage specification.

The Electrical Control Modes satisfy therequirements of EN 50081-1 and EN 50082-1 electro magneticcompatibility.

Page 23: Proportional Torque Control Automatic Smoke and Fire …

Number ofunits required

SS501/PTCSmokeShield PTC™ Square or Rectangular(Fail-safe closed).

SS601/PTCSmokeShield PTC™Circular (Fail-safe closed).

SS701/PTCSmokeShield PTC™Flat Oval (Fail-safe closed).

VS1501/PTC VentShield PTC™Square or Rectangular(Fail-safe open).

VS1601/PTCVentShield PTC™Circular (Fail-safe open).

VS1701/PTCVentShield PTC™Flat Oval(Fail-safe open).

1. DWFX-FDry Wall Fixing SystemFlange plus Cleats

2. DWFX-CDry Wall Fixing SystemCleats

3. IF HEVAC / HVCAInstallation Frame

4. Other SpecialFixings

Quantity Series Fixing Options Duct Size Control Mode Accessories3 SS501/PTC IF 600(W) x 450(H) M5

Ordering Information

Example

M1 PTCManual System

M5 PTC24V 10W (12.5VA)

M6 PTC230V 12W (14VA)

M5 PTC Vent NON ETR24V 10W (12.5VA)

M6 PTC Vent NON ETR230V 12W (14VA)

M5 PTC NON ETR24V 10W (12.5VA)

M6 PTC NON ETR230V 12W (14VA)

M5 PTC Vent 24V 10W (12.5VA)

M6 PTC Vent 230V 12W (14VA)

M5-2P ON/OFF24V 7W (10VA)

M6-2P ON/OFF230V 8W (12.5VA)

M5-3P PTC24V 7W (10VA)

M5-3P PTC Vent NON ETR24V 7W (10VA)

M5-3P PTC NON ETR24V 7W (10VA)

M5-3P PTC Vent 24V 7W (10VA)

M9 PTCPneumatic Operation

M9 PTC Vent NON PTRPneumatic Operation

SmokeShield PTCTM

Electrical

1. DTUDamper Test Unit Damper Test Unit For ControlModes. Spring bias testswitch providing illuminatedreset and release status

2. DSI Damper Status IndicatorReset and Release Indication

3. DCUDamper Control Unit Damper Control Unit forControl Modes. SwitchON/OFF function, reset andrelease indication

4. DRIM Damper Release andIndication Module

5. M52PDCUM5 and M6 -2P DCU Switch Power Open/PowerClose. Open and ClosedIndication

6. DCBConnection Box For Control Modes 1, 5 and 6(see page 10 for above)7. M5 – 3P - CMS 8. 230V M5 – 3P - CMS

Pneumatic

24 Volt Solenoid, (24,120, or230 volt).Status Beacon, Switchboxand Status Beacon.PTR XNNN05017

Mechanical

snaplock™ Interface LockingPlate (See page 10)

Actionpac DamperControl Systems

(See page 20 and 21)

23www.actionair.co.uk

Page 24: Proportional Torque Control Automatic Smoke and Fire …

South Street, Whitstable, Kent CT5 3DU England.Tel: 01227 276100 Fax: 01227 264262 Email: [email protected] Website: www.actionair.co.uk

BROCHURE PRODUCTION www.geoffstrange.co.uk LNNN00112

Ruskin Air Management Limited

SmokeShield PTC™

Ruskin Air Management Limitedis a ISO 9001 and 14001 registeredcompany.

The statements made in this brochure or by ourrepresentatives in consequence of any enquiriesarising out of this document are given for informationpurposes only. They are not intended to have anylegal effect and the company is not to be regardedas bound thereby. The company will only acceptobligations which are expressly negotiated for andagreed and incorporated into a written agreementmade with its customers.

Due to a policy of continuous product developmentthe specification and details contained herein aresubject to alteration without prior notice.

Comprehensive and detailed informationis available for all Actionair products.Visit our website at www.actionair.co.uk