PRIEST & ASSOCIATES CONSULTING, LLC 4607 Verdi Road Solutions for the 1-877-505-7743 Office Pleasanton, TX 78064 Building Materials Industry 210-410-8217 Mobile www.priestassociates.com [email protected] P January 7, 2015 Prosoco, Inc. 3741 Greenway Circle Lawrence, KS 66046 Re: Project No. 10261K, Revision 3 NFPA 285 Tables of Allowed Constructions for Prosoco Products The code requirement for NFPA 285 testing of wall assemblies incorporating combustible components presents an enormous compliance endeavor. Considering the number of choices for each component (interior gypsum sheathing, cavity insulation, stud sizes, exterior gypsum sheathing, water resistant barrier (WRB), exterior insulations, WRB, air gap, claddings), one can calculate that the number of possible constructions can reach into the tens of thousands of assemblies. Given that each NFPA 285 assembly test costs approximately $20,000, a manufacturer can spend many millions of dollars achieving compliance with the code for a wide variety of combinations. Pursuant to the discretionary provisions of the building code, the building code officials community allows assemblies which have not been tested under NFPA 285, where NFPA 285 testing has been conducted on worst-case assemblies, and where Engineering Evaluations have been performed which show that a specified alternative assembly can be assumed to perform as well or better than the tested assemblies. Strict rules based on known fire science principles are used to determine allowances of alternate materials. In the case of WRB products, an alternate WRB can substitute for a WRB incorporated in an NFPA 285 tested assembly or approved in a previous Engineering Evaluation if the relative flaming characteristics of the alternate product is the same or better than the baseline product. This is accomplished via Engineering Evaluations such as those written for PROSOCO as discussed below. This document is a compilation of tables of allowed constructions based on NFPA 285 tests, cone calorimeter flaming and combustion studies, and Engineering Evaluations 10261A, -B, -C, -D, -E, -F, -G, - H & -I representing assemblies incorporating XPS and polyisocyanurate exterior insulation products from Atlas, Carlisle, DOW, Hunter, Johns Manville, Owens Corning, and Rmax. The Engineering Evaluations and the attached compilation also cover assemblies utilizing mineral wool insulation, and assemblies with no insulation. The Engineering Evaluations assume utilization of common steel stud, external gypsum sheathing, and cladding assemblies as well as assemblies with back-up walls constructed of CMU or concrete. In each case, NFPA 285 tests were successfully conducted on various configurations of exterior wall system designs incorporating various WRB products as well as Prosoco products. The purpose of these evaluations was to determine engineering extensions for the alternative assemblies that can be expected to meet the requirements of NFPA 285. An analysis was conducted on the components incorporated in assemblies tested under NFPA 285. This allowed the determination of a base wall system from which replacement components can be interchanged. Cone calorimeter data was submitted to evaluate substitutions of the NFPA tested WRB products with PROSOCO WRB products. The data indicated that the WRB products tested in NFPA 285 assemblies

PRIEST & ASSOCIATES CONSULTING, LLC

  • Upload
    buidan

  • View
    245

  • Download
    21

Embed Size (px)

Citation preview

Page 1: PRIEST & ASSOCIATES CONSULTING, LLC

PRIEST & ASSOCIATES CONSULTING, LLC

4607 Verdi Road Solutions for the 1-877-505-7743 Office Pleasanton, TX 78064 Building Materials Industry 210-410-8217 Mobile www.priestassociates.com [email protected]

P

January 7, 2015 Prosoco, Inc. 3741 Greenway Circle Lawrence, KS 66046 Re: Project No. 10261K, Revision 3

NFPA 285 Tables of Allowed Constructions for Prosoco Products The code requirement for NFPA 285 testing of wall assemblies incorporating combustible components presents an enormous compliance endeavor. Considering the number of choices for each component (interior gypsum sheathing, cavity insulation, stud sizes, exterior gypsum sheathing, water resistant barrier (WRB), exterior insulations, WRB, air gap, claddings), one can calculate that the number of possible constructions can reach into the tens of thousands of assemblies. Given that each NFPA 285 assembly test costs approximately $20,000, a manufacturer can spend many millions of dollars achieving compliance with the code for a wide variety of combinations. Pursuant to the discretionary provisions of the building code, the building code officials community allows assemblies which have not been tested under NFPA 285, where NFPA 285 testing has been conducted on worst-case assemblies, and where Engineering Evaluations have been performed which show that a specified alternative assembly can be assumed to perform as well or better than the tested assemblies. Strict rules based on known fire science principles are used to determine allowances of alternate materials. In the case of WRB products, an alternate WRB can substitute for a WRB incorporated in an NFPA 285 tested assembly or approved in a previous Engineering Evaluation if the relative flaming characteristics of the alternate product is the same or better than the baseline product. This is accomplished via Engineering Evaluations such as those written for PROSOCO as discussed below. This document is a compilation of tables of allowed constructions based on NFPA 285 tests, cone calorimeter flaming and combustion studies, and Engineering Evaluations 10261A, -B, -C, -D, -E, -F, -G, -H & -I representing assemblies incorporating XPS and polyisocyanurate exterior insulation products from Atlas, Carlisle, DOW, Hunter, Johns Manville, Owens Corning, and Rmax. The Engineering Evaluations and the attached compilation also cover assemblies utilizing mineral wool insulation, and assemblies with no insulation. The Engineering Evaluations assume utilization of common steel stud, external gypsum sheathing, and cladding assemblies as well as assemblies with back-up walls constructed of CMU or concrete. In each case, NFPA 285 tests were successfully conducted on various configurations of exterior wall system designs incorporating various WRB products as well as Prosoco products. The purpose of these evaluations was to determine engineering extensions for the alternative assemblies that can be expected to meet the requirements of NFPA 285. An analysis was conducted on the components incorporated in assemblies tested under NFPA 285. This allowed the determination of a base wall system from which replacement components can be interchanged. Cone calorimeter data was submitted to evaluate substitutions of the NFPA tested WRB products with PROSOCO WRB products. The data indicated that the WRB products tested in NFPA 285 assemblies

Page 2: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 2

P

can be replaced with the PROSOCO WRB products. The tables of substitutions below outlines the allowed constructions based on the analysis of these reports. Prepared by,

Javier O. Trevino Date: January 6, 2015 Associate Engineer 210-601-0655

Page 3: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 3

P

HUNTER TABLES For all constructions, the window header shall consist of minimum 25 GA. sheet steel flashing. Wall Component Base Wall – Use either 1, 2 or 3

1) Cast Concrete Walls 2) CMU Concrete Walls 3) 25 GA. min. 3⅝" (min.) steel studs spaced 24" OC (max.)

a. ⅝" type X Gypsum Wallboard Interior b. Lateral Bracing every 4 ft

Fire-Stopping at floor lines

Any approved mineral fiber based safing insulation in each stud cavity at floor line. Safing thickness must match stud cavity depth.

Cavity Insulation – Use either: 1, 2, 3, 4, 5, 6 or 7.

1) Any noncombustible insulation per ASTM E136 2) Any Mineral Fiber (Board type Class A ASTM E84 faced or unfaced) 3) Any Fiberglass (Batt Type Class A ASTM E84 faced or unfaced) 4) 1½" (min.) of Bayer EcoBay CC SPF (up to full cavity thickness) 5) 1½" (min.) of BASF Walltite SPF (up to full cavity thickness) 6) Any foam plastic insulation which has been tested per ASTM E1354 (at a

minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable than the ones listed above.

7) None Exterior Sheathing 1) ½" or thicker exterior gypsum sheathing WRB Over Base Wall Surface – Use either 1, 2, 3, 4 or 5 WRB Membranes are used over exterior sheathing or exterior insulation but not both.

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Insulation – Use either 1, 2, 3 or 4

1) None 2) 3½" thick Xci-286 3) Any Noncombustible or fiberglass insulation (faced or unfaced) 4) Any exterior insulation which has been tested per ASTM E1354 (at a

minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable (improved Tign, Pk. HRR) than those listed above.

WRB Over Exterior Insulation – Use either 1, 2, 3, 4 or 5 WRB Membranes are used over exterior sheathing or exterior insulation but not both.

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Cladding - Use either 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 or 12

1) Brick – Nominal 4" clay or concrete brick or veneer with maximum 2" air gap behind the brick. Brick Ties/Anchors 24" OC (max.).

2) Stucco – minimum ¾" thick exterior cement plaster and lath. 3) Limestone – minimum 2" thick using any standard non-open joint

installation technique such as shiplap. 4) Natural Stone Veneer – minimum 2" thick using any standard non-open

joint installation technique such as grouted/mortared stone. 5) Cast Artificial Stone – minimum 1½" thick complying with ICC-ES AC 51

using any standard non-open joint installation technique such as shiplap. 6) Terra Cotta Cladding – minimum 1¼" thick (solid or equivalent by

weight) using any standard non-open joint installation technique such as shiplap.

Page 4: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 4

P

7) Any MCM that has successfully passed NFPA 285. 8) Uninsulated sheet metal building panels including steel, copper,

aluminum. 9) Uninsulated Fiber-cement siding.

10) Stone/Aluminum honeycomb composite building panels that have successfully passed NFPA 285 criteria.

11) Autoclaved-aerated-concrete (AAC) panels that have successfully passed NFPA 285 criteria.

12) Terra Cotta Cladding – Any Rain-screen Terra Cotta (min. ½" thick) with ventilated shiplap.

Wall Component Base Wall – Use either 1, 2 or 3

1) Cast Concrete Walls 2) CMU Concrete Walls 3) 25 GA. min. 3⅝" (min.) steel studs spaced 24" OC (max.)

a. ⅝" type X Gypsum Wallboard Interior b. Lateral Bracing every 4 ft

Fire-Stopping at floor lines

Any approved mineral fiber based safing insulation in each stud cavity at floor line. Safing thickness must match stud cavity depth.

Cavity Insulation – Use either: 1, 2, 3, 4, 5, 6 or 7.

1) Any noncombustible insulation per ASTM E136 2) Any Mineral Fiber (Board type Class A ASTM E84 faced or unfaced) 3) Any Fiberglass (Batt Type Class A ASTM E84 faced or unfaced) 4) 1½" (min.) of Bayer EcoBay CC SPF (up to full cavity thickness) 5) 1½" (min.) of BASF Walltite SPF (up to full cavity thickness) 6) Any foam plastic insulation which has been tested per ASTM E1354 (at a

minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable than the ones listed above.

7) None Exterior Sheathing ½" or thicker exterior gypsum sheathing WRB Over Base Wall Surface – Use either 1, 2, 3, 4 or 5 WRB Membranes are used over exterior sheathing or exterior insulation but not both

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Insulation – Use either 1, 2, 3 or 4

1) None 2) 3½" thick Xci-Class A 3) Any Noncombustible or fiberglass insulation (faced or unfaced) 4) Any exterior insulation which has been tested per ASTM E1354 (at a

minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable (improved Tign, Pk. HRR) than those listed above.

WRB Over Exterior Insulation – Use either 1, 2, 3, 4 or 5 WRB Membranes are used over exterior sheathing or exterior insulation but not both.

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5. 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Cladding - Use either 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 or 12

1) Brick – Nominal 4" clay or concrete brick or veneer with maximum 2" air gap behind the brick. Brick Ties/Anchors 24" OC (max.).

2) Stucco – minimum ¾" thick exterior cement plaster and lath. 3) Limestone – minimum 2" thick using any standard non-open joint

Page 5: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 5

P

installation technique such as shiplap. 4) Natural Stone Veneer – minimum 2" thick using any standard non-open

joint installation technique such as grouted/mortared stone. 5) Cast Artificial Stone – minimum 1½" thick complying with ICC-ES AC 51

using any standard non-open joint installation technique such as shiplap. 6) Terra Cotta Cladding – minimum 1¼" thick (solid or equivalent by

weight) using any standard non-open joint installation technique such as shiplap.

7) Any MCM that has successfully passed NFPA 285. 8) Uninsulated sheet metal building panels including steel, copper,

aluminum. 9) Uninsulated Fiber-cement siding.

10) Stone/Aluminum honeycomb composite building panels that have successfully passed NFPA 285 criteria.

11) Autoclaved-aerated-concrete (AAC) panels that have successfully passed NFPA 285 criteria.

12) Terra Cotta Cladding – Any Rain-screen Terra Cotta (min. ½" thick) with ventilated shiplap.

Wall Component Base Wall – Use either 1, 2 or 3

1) Cast Concrete Walls 6) CMU Concrete Walls 7) 25 GA. min. 3⅝" (min.) steel studs spaced 24" OC (max.)

a. ⅝" type X Gypsum Wallboard Interior b. Lateral Bracing every 4 ft

Fire-Stopping at floor lines

Any approved mineral fiber based safing insulation in each stud cavity at floor line. Safing thickness must match stud cavity depth.

Cavity Insulation – Use either: 1, 2, 3, 4, 5, 6 or 7

1) Any noncombustible insulation per ASTM E136 2) Any Mineral Fiber (Board type Class A ASTM E84 faced or unfaced) 3) Any Fiberglass (Batt Type Class A ASTM E84 faced or unfaced) 4) 1½" (min.) of Bayer EcoBay CC SPF (up to full cavity thickness) 5) 1½" (min.) of BASF Walltite SPF (up to full cavity thickness) 6) Any foam plastic insulation which has been tested per ASTM E1354 (at

a minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable than the ones listed above.

7) None Exterior Sheathing ½" or thicker exterior gypsum sheathing WRB Over Base Wall Surface – Use either 1, 2, 3, 4, or 5 WRB Membranes are used over exterior sheathing or exterior insulation but not both.

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Insulation – Use either 1, 2, 3 or 4

1) None 2) 3½" thick (max.) Xci-CG 3) Any noncombustible insulation (faced or unfaced) when any of cladding

options 1-6 are used. Any unfaced noncombustible insulation may be used with claddings 1-12.

4) Any exterior insulation which has been tested per ASTM E1354 (at a minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable (improved Tign, Pk. HRR) than those listed above.

WRB Over Exterior None

Page 6: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 6

P

Insulation – Use either 1, 2, 3 or 4 WRB Membranes are used over exterior sheathing or exterior insulation but not both.

1) Prosoco R-Guard VB 2) Prosoco R-Guard Cat 5 3) Prosoco R-Guard Cat 5 Rain Screen 4) Prosoco SprayWrap MVP

Exterior Cladding - Use either 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 or 12

1) Brick – Nominal 4" clay or concrete brick or veneer with maximum 2" air gap behind the brick. Brick Ties/Anchors 24" OC (max.).

2) Stucco – minimum ¾" thick exterior cement plaster and lath. 3) Limestone – minimum 2" thick using any standard non-open joint

installation technique such as shiplap. 4) Natural Stone Veneer – minimum 2" thick using any standard non-open

joint installation technique such as grouted/mortared stone. 5) Cast Artificial Stone – minimum 1½" thick complying with ICC-ES AC 51

using any standard non-open joint installation technique such as shiplap.

6) Terra Cotta Cladding – minimum 1¼" thick (solid or equivalent by weight) using any standard non-open joint installation technique such as shiplap.

7) Any MCM that has successfully passed NFPA 285. 8) Uninsulated sheet metal building panels including steel, copper,

aluminum. 9) Uninsulated Fiber-cement siding.

10) Stone/Aluminum honeycomb composite building panels that have successfully passed NFPA 285 criteria.

11) Autoclaved-aerated-concrete (AAC) panels that have successfully passed NFPA 285 criteria.

12) Terra Cotta Cladding – Any Rain-screen Terra Cotta (min. ½" thick) with ventilated shiplap.

Wall Component Base Wall – Use either 1, 2 or 3

1) Cast Concrete Walls 2) CMU Concrete Walls 3) 25 GA. min. 3⅝" (min.) steel studs spaced 24" OC (max.)

a. ⅝" type X Gypsum Wallboard Interior b. Lateral Bracing every 4 ft

Fire-Stopping at floor lines

Any approved mineral fiber based safing insulation in each stud cavity at floor line. Safing thickness must match stud cavity depth.

Cavity Insulation – Use either: 1, 2, 3, 4, 5, 6 or 7

1) Any noncombustible insulation per ASTM E136 2) Any Mineral Fiber (Board type Class A ASTM E84 faced or unfaced) 3) Any Fiberglass (Batt Type Class A ASTM E84 faced or unfaced) 4) 1½" (min.) of Bayer EcoBay CC SPF (up to full cavity thickness) 5) 1½" (min.) of BASF Walltite SPF (up to full cavity thickness) 6) Any foam plastic insulation which has been tested per ASTM E1354 (at

a minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable than the ones listed above.

7) None Exterior Sheathing ½" or thicker exterior gypsum sheathing. WRB Over Base Wall Surface – Use either 1, 2, 3, 4 or 5 WRB Membranes are used over exterior

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Page 7: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 7

P

sheathing or exterior insulation but not both. Exterior Insulation – Use either 1, 2, 3 or 4

1) None 2) 3½" thick (max.) Xci-Foil 3) Any Noncombustible or fiberglass insulation (faced or unfaced) 4) Any exterior insulation which has been tested per ASTM E1354 (at a

minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable (improved Tign, Pk. HRR) than those listed above.

WRB Over Exterior Insulation – Use either 1, 2, 3, 4 or 5 WRB Membranes are used over exterior sheathing or exterior insulation but not both

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Cladding - Use either 1, 2, 3, 4, 5 or 6

1) Brick – Nominal 4" clay or concrete brick or veneer with maximum 2" air gap behind the brick. Brick Ties/Anchors 24" OC (max.).

2) Stucco – minimum ¾" thick exterior cement plaster and lath. 3) Limestone – minimum 2" thick using any standard non-open joint

installation technique such as shiplap. 4) Natural Stone Veneer – minimum 2" thick using any standard non-open

joint installation technique such as grouted/mortared stone. 5) Cast Artificial Stone – minimum 1½" thick complying with ICC-ES AC 51

using any standard non-open joint installation technique such as shiplap.

6) Terra Cotta Cladding – minimum 1¼" thick (solid or equivalent by weight) using any standard non-open joint installation technique such as shiplap.

Wall Component Base Wall – Use either 1, 2 or 3

1) Cast Concrete Walls 2) CMU Concrete Walls 3) 25 GA. min. 3⅝" (min.) steel studs spaced 24" OC (max.)

a. ⅝" type X Gypsum Wallboard Interior b. Lateral Bracing every 4 ft

Fire-Stopping at floor lines

Any approved mineral fiber based safing insulation in each stud cavity at floor line. Safing thickness must match stud cavity depth.

Cavity Insulation – Use either: 1, 2, 3, 4, 5, 6 or 7

1) Any noncombustible insulation per ASTM E136 2) Any Mineral Fiber (Board type Class A ASTM E84 faced or unfaced) 3) Any Fiberglass (Batt Type Class A ASTM E84 faced or unfaced) 4) 1½" (min.) of Bayer EcoBay CC SPF (up to full cavity thickness) 5) 1½" (min.) of BASF Walltite SPF (up to full cavity thickness) 6) Any foam plastic insulation which has been tested per ASTM E1354 (at

a minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable than the ones listed above.

7) None Exterior Sheathing ½" or thicker exterior gypsum sheathing WRB Over Base Wall Surface – Use either 1, 2, 3, 4 or 5 WRB Membranes are used over exterior sheathing or exterior

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5. 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Page 8: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 8

P

insulation but not both. Exterior Insulation – Use either 1, 2, 3 or 4

1) None – (for claddings 1-6, or 9-14) 2) 3.6" (max.) Xci-Ply 3) Any noncombustible or fiberglass insulation (faced or unfaced) 4) Any exterior insulation which has been tested per ASTM E1354 (at a

minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable (improved Tign, Pk. HRR) than those listed above.

WRB Over Exterior Insulation – Use either 1, 2, 3, 4, or 5 WRB Membranes are used over exterior sheathing or exterior insulation but not both.

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Cladding - Use either 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11,12, 13 or 14

1) Brick – Nominal 4" clay or concrete brick or veneer with maximum 2" air gap behind the brick. Brick Ties/Anchors 24" OC (max.).

2) Stucco – minimum ¾" thick exterior cement plaster and lath. 3) Limestone – minimum 2" thick using any standard non-open joint

installation technique such as shiplap. 4) Natural Stone Veneer – minimum 2" thick using any standard non-open

joint installation technique such as grouted/mortared stone. 5) Cast Artificial Stone – minimum 1½" thick complying with ICC-ES AC 51

using any standard non-open joint installation technique such as shiplap.

6) Terra Cotta Cladding – minimum 1¼" thick (solid or equivalent by weight) using any standard non-open joint installation technique such as shiplap.

7) Thin brick/cultured stone set in thin set adhesive and metal lath that has been tested to ASTM E119 (brick exposed to furnace) and remains in place for a minimum of 30 minutes, or has passed an NFPA 285 test. Minimum ¾".

8) TABS II Panel System with ½" thick bricks using TABS Wall Adhesive. 9) Any MCM that has successfully passed NFPA 285.

10) Uninsulated sheet metal building panels including steel, copper, aluminum.

11) Uninsulated Fiber-cement siding. 12) Stone/Aluminum honeycomb composite building panels that have

successfully passed NFPA 285 criteria. 13) Autoclaved-aerated-concrete (AAC) panels that have successfully

passed NFPA 285 criteria. 14) Terra Cotta Cladding – Any Rain-screen Terra Cotta (min. ½ " thick)

with ventilated shiplap.

Page 9: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 9

P

RMax Table Window Headers for all constructions shall incorporate 0.078 in. (min.) aluminum flashing. Flashing of window, door, and other wall penetrations may use asphalt, acrylic, or butyl based flashing tape, or R-SEAL 6000 35 mil thick woven polyethylene tape – max. 12 in. width. Wall Component Base Wall – Use either 1, 2 or 3

1) Cast Concrete Walls 2) CMU Concrete Walls 3) 20 GA. (min.) 3⅝ in. (min.) steel studs spaced 24 in. OC (max.)

a. ⅝ in. (min.) type X Special Fire Resistant Gypsum Wallboard Interior

Fire-Stopping in Stud Cavity at floor-lines

4 pcf mineral fiber insulation installed with z-clips

Cavity Insulation – Use either 1, 2, 3 or 4

1) None 2) Any non-combustible insulation per ASTM E136 3) Any Mineral Fiber (Board type Class A ASTM E84 faced or unfaced) 4) Any Fiberglass (Batt Type Class A ASTM E84 faced or unfaced)

Exterior Sheathing ½ in. or thicker exterior gypsum sheathing WRB Over Sheathing– Use either 1, 2, 3, 4 or 5 installed per mfr's application instructions.

1) None 2) Prosoco R-Guard SprayWrap MVP 3) Prosoco R-Guard VB 4) Prosoco R-Guard Cat 5 5) Prosoco Cat 5 Rain Screen

Exterior Insulation – Use either 1 or 2

1) 3 in. (max. consisting of a single panel or multiple thinner panels) Rmax TSX-8500

2) 3 in. (max. consisting of a single panel or multiple thinner panels) Rmax ECOMAXci.

Exterior Cladding - Use either 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 or 12

1) Brick – Nominal 4 in. clay brick or veneer with maximum 2 in. air gap behind the brick. Brick Ties/Anchors 24 in. OC (max)

2) Stucco – minimum ¾ in. thick exterior cement plaster and lath with an optional secondary water resistive barrier between the exterior insulation and lath. The secondary barrier shall not be full coverage asphalt or self-adhered butyl membrane.

3) Limestone – minimum 2 in. thick using any standard installation technique.

4) Natural Stone Veneer – minimum 2 in. thick using any standard installation technique.

5) Cast Artificial Stone – minimum 1½ in. thick complying with ICC-ES AC 51 using any standard installation technique.

6) Terra Cotta Cladding – minimum 1¼ in. thick using any standard installation technique.

7) Any MCM (aluminum, steel, copper) (w/ 1⅛ in. ± ½ in. air gap) that has successfully passed NFPA 285 using any standard installation technique.

8) Uninsulated sheet metal building panels including aluminum, steel or copper using any standard installation technique.

9) Uninsulated Fiber-cement siding using any standard installation technique.

10) Stone/Aluminum honeycomb composite building panels that have passed NFPA 285 or equivalent. a. Stone Panels Inc. Stone Lite Panel system has been analyzed using

mfr's standard installation technique. 11) Autoclaved-aerated-concrete (AAC) panels that have successfully

passed NFPA 285 using any standard installation technique. 12) Thin Set Brick - Glen Gery Thin Tech Elite has been analyzed using

mfr's standard installation technique.

Page 10: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 10

P

ATLAS Tables Wall Component Base Wall Use 1, 2 or 3

1) Cast Concrete Walls 2) CMU Concrete Walls 3) 25 GA. (min.) 3⅝" (min.) steel studs spaced 24" OC (max.)

a. Any ⅝" type X Gypsum Wallboard Interior b. Any ½" (min.) Exterior Gypsum Sheathing c. Lateral Bracing Every 4 ft vertically

Fire Stopping at floor lines

4 pcf mineral fiber insulation (safing) filling stud cavity

Cavity Insulation Use 1, 2 or 3

1) None 2) Any Class A, B or C Fiberglass batt insulation (faced or unfaced) 3) Any noncombustible insulation

Exterior Sheathing ½" or thicker exterior gypsum sheathing WRB or AB Over Base Wall Surface Use 1, 2, 3, 4 or 5 Use mfg. instructions for application

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Insulation Use 1, 2, 3, 4, 5 or 6

1) Atlas ThermalStar CVT 25 (25 psi product, 1.8 pcf) up to 5.4 inches thick.

2) Atlas ThermalStar CVT 15 (15 psi product, 1.35 pcf) up to 7.2 inches thick.

3) ThermalStar LCi 15 (15 psi product, 1.35 pcf) up to 7.2 inches thick 4) ThermalStar LCi 25 (25 psi product, 1.70 pcf) up to 5.4 inches thick 5) ThermalStar CHROME 15 (15 psi product, 1.35 pcf) up to 7.2 inches

thick 6) ThermalStar CHROME 25 (25 psi product, 1.70 pcf) up to 5.4 inches

thick Exterior Cladding Use either 1, 2, 3, 4, 5, 6, 7 or 8

1) Brick – Nominal 4" clay brick or veneer with maximum 2" air gap behind the cladding. Brick with ties/anchors 24" OC (max.)

2) Concrete – Minimum 2" thick with maximum 2" air gap behind the cladding.

3) Concrete Masonry Units – Minimum 4" thick with maximum 2" air gap behind the cladding.

4) Limestone – minimum 2" thick with non-open joints installation technique such as shiplap

5) Natural Stone Veneer – minimum 2" thick with non-open joints installation technique such as shiplap

6) Precast Artificial Stone – minimum 1½" thick complying with ICC-ES, AC 51 with non-open joint installation technique.

7) Terra Cotta Cladding – minimum 1¼" thick (solid) with non-open joint installation technique such as shiplap.

8) Stucco – minimum ¾" thick exterior cement plaster and lath. Window Header Use either 1 or 2

1) Flashing composed of 25 GA. (min.) sheet metal (steel) with 1" thick, 4 pcf mineral wool over interior of sheet steel.

2) Any header design deemed more robust than item 1 per analysis.

Page 11: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 11

P

For the table below, the window header shall consist of minimum 25 GA. sheet steel flashing. Wall Component Base Wall – Use either 1, 2 or 3

1) Cast Concrete Walls 2) CMU Concrete Walls 3) 20 GA (min.) 3⅝ in. (min.) steel studs spaced 24 in. OC (max.)

a. ⅝ in. type X Gypsum Wallboard Interior b. ⅝ in. Exterior Gypsum Sheathing

Fire-Stopping in Stud Cavity at floor lines

4 inch, 4 pcf mineral fiber installed with Z-Clips

Cavity Insulation – Use either 1, 2, 3 or 4

1) None 2) Any noncombustible insulation per ASTM E136 3) Any Mineral Fiber (Board type Class A ASTM E84 faced or unfaced) 4) Any Fiberglass (Batt Type Class A ASTM E84 faced or unfaced)

Exterior Sheathing – Use either 1 or 2

1) ⅝ in. or thicker exterior gypsum sheathing 2) 2 in. precast concrete panels attached to structural elements of

building. WRB Over Sheathing – Use either 1, 2, 3, 4, or 5

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Insulation – Use either 1 or 2

1) 2 in. or 3 in. Atlas Energy Shield Pro (or Pro2), and 4 in. EnergyShield Pro (or Pro2) may be substituted for each-other in reports which utilize either of these insulations.

2) 4 in. RBoard Pro WRB Over Exterior Insulation – Use either 1, or 2 Note: Tape only used at panel joints.

1) None 2) 3 in. IPG Cold Weather Foil Tape and 4 in. Atlas WRB System Tape

may be interchanged.

Exterior Cladding - Use either 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, or 11

1) Brick – Nominal 4 in. clay brick or veneer with maximum 2 in. air gap behind the brick. Brick Ties/Anchors 24 in. OC (max)

2) Stucco – minimum ¾ in. thick exterior cement plaster and lath. 3) Limestone – minimum 2 in. thick. 4) Natural Stone Veneer – minimum 2 in. thick. 5) Cast Artificial Stone – minimum 1½ in. thick complying with ICC-ES

AC 51. 6) Terra Cotta Cladding – minimum 1¼ in. thick 7) Any ACM that has successfully passed NFPA 285. 8) Uninsulated sheet metal building panels including steel or copper. 9) Uninsulated fiber-cement siding (min. ¼ in. thick).

10) Stone/Aluminum honeycomb composite building panels that have successfully passed NFPA 285 criteria.

11) Autoclaved-aerated-concrete (AAC) panels (min. 1½ in. thick).

Page 12: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 12

P

Carlisle Tables For all constructions below, the window header shall consist of minimum 25 GA. sheet steel flashing. WRB Membranes are used over exterior sheathing or exterior insulation but not both.

Table 1: R2+ SHEATHE Exterior Insulation Wall Component Base Wall – Use either 1, 2 or 3

1) Cast Concrete Walls 2) CMU Concrete Walls 3) 25 GA. min. 3⅝" (min.) steel studs spaced 24" OC (max.)

a. ⅝" type X Gypsum Wallboard Interior b. Lateral Bracing every 4 ft

Fire-Stopping at floor lines

Any approved mineral fiber based safing insulation in each stud cavity at floor line. Safing thickness must match stud cavity depth.

Cavity Insulation – Use either: 1, 2, 3, 4, 5, 6 or 7

1) None 2) 1½" (min.) of Bayer EcoBay CC SPF (up to full cavity thickness) 3) 1½" (min.) of BASF Walltite SPF (up to full cavity thickness) 4) Any noncombustible insulation per ASTM E136 5) Any Mineral Fiber (Board type Class A ASTM E84 faced or unfaced) 6) Any Fiberglass (Batt Type Class A ASTM E84 faced or unfaced) 7) Any foam plastic insulation (SPF or board type) which has been tested

per ASTM E1354 (at a minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable (improved Tign, Pk. HRR) than Bayer EcoBay CC or BASF Walltite.

Exterior Sheathing ½" or thicker exterior gypsum sheathing WRB Over Base Wall Surface – Use either 1, 2, 3, 4, or 5

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5. 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Insulation – Use either 1, 2, 3 or 4

1) 3½" thick R2+ SHEATHE 2) Any Noncombustible insulation (faced or unfaced) when any of cladding

options 1-6 are used. Any Unfaced noncombustible insulation may be used with claddings 1-12.

3) Any exterior insulation which has been tested per ASTM E1354 (at a minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable (improved Tign, Pk. HRR) than those listed above.

4) None WRB Over Exterior Insulation – Use either 1, 2, 3, 4 or 5

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5. 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Cladding - Use either 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 or 12

1) Brick – Nominal 4" clay or concrete brick or veneer with maximum 2" air gap behind the brick. Brick Ties/Anchors 24" OC (max.).

2) Stucco – minimum ¾" thick exterior cement plaster and lath. 3) Limestone – minimum 2" thick using any standard non-open joint

installation technique such as shiplap. 4) Natural Stone Veneer – minimum 2" thick using any standard non-open

joint installation technique such as grouted/mortared stone. 5) Cast Artificial Stone – minimum 1½" thick complying with ICC-ES AC 51

using any standard non-open joint installation technique such as shiplap. 6) Terra Cotta Cladding – minimum 1¼" thick (solid or equivalent by

weight) using any standard non-open joint installation technique such as shiplap.

Page 13: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 13

P

7) Any MCM that has successfully passed NFPA 285. 8) Uninsulated sheet metal building panels including steel, copper,

aluminum. 9) Uninsulated Fiber-Cement siding.

10) Stone/Aluminum honeycomb composite building panels that have successfully passed NFPA 285 criteria.

11) Autoclaved-aerated-concrete (AAC) panels that have successfully passed NFPA 285 criteria.

12) Terra Cotta Cladding – Any Rain-screen Terra Cotta (min. ½" thick) with ventilated shiplap.

Table 2: R2+ MATTE Exterior Insulation Wall Component Base Wall – Use either 1, 2, or 3

1) Cast Concrete Walls 2) CMU Concrete Walls 3) 25 GA. min. 3⅝" (min.) steel studs spaced 24" OC (max.)

a. ⅝" type X Gypsum Wallboard Interior b. Lateral Bracing every 4 ft

Fire-Stopping at floor lines

Any approved mineral fiber based safing insulation in each stud cavity at floor line. Safing thickness must match stud cavity depth.

Cavity Insulation – Use either: 1, 2, 3, 4, 5, 6 or 7

1) None 2) 1½" (min.) of Bayer EcoBay CC SPF (up to full cavity thickness) 3) 1½" (min.) of BASF Walltite SPF (up to full cavity thickness) 4) Any noncombustible insulation per ASTM E136 5) Any Mineral Fiber (Board type Class A ASTM E84 faced or unfaced) 6) Any Fiberglass (Batt Type Class A ASTM E84 faced or unfaced) 7) Any foam plastic insulation (SPF or board type) which has been tested

per ASTM E1354 (at a minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable (improved Tign, Pk. HRR) than Bayer EcoBay CC or BASF Walltite.

Exterior Sheathing ½" or thicker exterior gypsum sheathing WRB Over Base Wall Surface – Use either 1, 2, 3, 4 or 5

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Insulation – Use either 1, 2, 3 or 4

1) 3½" thick (max.) R2+ MATTE 2) Any noncombustible insulation (faced or unfaced) when any of cladding

options 1-6 are used. Any unfaced noncombustible insulation may be used with claddings 1-12.

3) Any exterior insulation which has been tested per ASTM E1354 (at a minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable (improved Tign, Pk. HRR) than those listed above.

4) None WRB Over Exterior Insulation – Use either 1, 2, 3, 4 or 5

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Cladding - Use either 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 or 12

1) Brick – Nominal 4" clay or concrete brick or veneer with maximum 2" air gap behind the brick. Brick Ties/Anchors 24" OC (max.).

2) Stucco – minimum ¾" thick exterior cement plaster and lath. 3) Limestone – minimum 2" thick using any standard non-open joint

installation technique such as shiplap. 4) Natural Stone Veneer – minimum 2" thick using any standard non-open

joint installation technique such as grouted/mortared stone.

Page 14: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 14

P

5) Cast Artificial Stone – minimum 1½" thick complying with ICC-ES AC 51 using any standard non-open joint installation technique such as shiplap.

6) Terra Cotta Cladding – minimum 1¼" thick (solid or equivalent by weight) using any standard non-open joint installation technique such as shiplap.

7) Any MCM that has successfully passed NFPA 285. 8) Uninsulated sheet metal building panels including steel, copper,

aluminum. 9) Uninsulated Fiber-cement siding.

10) Stone/Aluminum honeycomb composite building panels that have successfully passed NFPA 285 criteria.

11) Autoclaved-aerated-concrete (AAC) panels that have successfully passed NFPA 285 criteria.

12) Terra Cotta Cladding – Any Rain-screen Terra Cotta (min. ½" thick) with ventilated shiplap.

Table 3: R2+ SILVER Exterior Insulation Wall Component Base Wall – Use either 1, 2 or 3

1) Cast Concrete Walls 2) CMU Concrete Walls 3) 25 GA. min. 3⅝" (min.) steel studs spaced 24" OC (max.)

a. ⅝" type X Gypsum Wallboard Interior b. Lateral Bracing every 4 ft

Fire-Stopping at floor lines

Any approved mineral fiber based safing insulation in each stud cavity at floor line. Safing thickness must match stud cavity depth.

Cavity Insulation – Use either: 1, 2, 3, 4, 5, 6 or 7

1) None 2) 1½" (min.) of Bayer EcoBay CC SPF (up to full cavity thickness) 3) 1½" (min.) of BASF Walltite SPF (up to full cavity thickness) 4) Any noncombustible insulation per ASTM E136 5) Any Mineral Fiber (Board type Class A ASTM E84 faced or unfaced) 6) Any Fiberglass (Batt Type Class A ASTM E84 faced or unfaced) 7) Any foam plastic insulation (SPF or board type) which has been tested

per ASTM E1354 (at a minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable (improved Tign, Pk. HRR) than Bayer EcoBay CC or BASF Walltite.

Exterior Sheathing ½" or thicker exterior gypsum sheathing. WRB Over Base Wall Surface – Use either 1, 2, 3, 4 or 5

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Insulation – Use either 1, 2, 3 or 4

1) 3½" thick (max.) R2+ SILVER 2) Any Noncombustible insulation (faced or unfaced) 3) Any exterior insulation which has been tested per ASTM E1354 (at a

minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable (improved Tign, Pk. HRR) than those listed above.

4) None WRB Over Exterior Insulation – Use either 1, 2, 3, 4 or 5

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Cladding - Use either 1, 2, 3, 4, 5 or 6

1) Brick – Nominal 4" clay or concrete brick or veneer with maximum 2" air gap behind the brick. Brick Ties/Anchors 24" OC (max.)

2) Stucco – minimum ¾" thick exterior cement plaster and lath. 3) Limestone – minimum 2" thick using any standard non-open joint

installation technique such as shiplap.

Page 15: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 15

P

4) Natural Stone Veneer – minimum 2" thick using any standard non-open joint installation technique such as grouted/mortared stone.

5) Cast Artificial Stone – minimum 1½" thick complying with ICC-ES AC 51 using any standard non-open joint installation technique such as shiplap.

6) Terra Cotta Cladding – minimum 1¼" thick (solid or equivalent by weight) using any standard non-open joint installation technique such as shiplap.

Table 4: R2+ BASE Exterior Insulation Wall Component Base Wall – Use either 1, 2 or 3

1) Cast Concrete Walls 2) CMU Concrete Walls 3) 25 GA. min. 3⅝" (min.) steel studs spaced 24" OC (max.)

a. ⅝" type X Gypsum Wallboard Interior b. Lateral Bracing every 4 ft

Fire-Stopping at floor lines

Any approved mineral fiber based safing insulation in each stud cavity at floor line. Safing thickness must match stud cavity depth.

Cavity Insulation – Use either: 1, 2, 3, 4, 5, 6 or 7

1) None 2) 1½" (min.) of Bayer EcoBay CC SPF (up to full cavity thickness) 3) 1½" (min.) of BASF Walltite SPF (up to full cavity thickness) 4) Any noncombustible insulation per ASTM E136 5) Any Mineral Fiber (Board type Class A ASTM E84 faced or unfaced) 6) Any Fiberglass (Batt Type Class A ASTM E84 faced or unfaced) 7) Any foam plastic insulation (SPF or board type) which has been tested

per ASTM E1354 (at a minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable (improved Tign, Pk. HRR) than Bayer EcoBay CC or BASF Walltite.

Exterior Sheathing ½" or thicker exterior gypsum sheathing WRB Over Base Wall Surface – Use either 1, 2, 3, 4 or 5

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Insulation – Use either 1, 2, 3 or 4

1) 3.6" (max.) R2+ BASE 2) Any Noncombustible insulation (faced or unfaced) when any of cladding

options 1-8 are used. Any Unfaced noncombustible insulation may be used with claddings 1-14.

3) Any exterior insulation which has been tested per ASTM E1354 (at a minimum of 20 kW/m2 heat flux) and shown by analysis to be less flammable (improved Tign, Pk. HRR) than those listed above.

4) None – None except when Thin Brick/TABS II cladding is used since these require use with R2+ Base

WRB Over Exterior Insulation – Use either 1, 2, 3, 4 or 5

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5. 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Cladding - Use either 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11,12, 13 or 14

1) Brick – Nominal 4" clay or concrete brick or veneer with maximum 2" air gap behind the brick. Brick Ties/Anchors 24" OC (max.).

2) Stucco – minimum ¾" thick exterior cement plaster and lath. 3) Limestone – minimum 2" thick using any standard non-open joint

installation technique such as shiplap. 4) Natural Stone Veneer – minimum 2" thick using any standard non-open

joint installation technique such as grouted/mortared stone. 5) Cast Artificial Stone – minimum 1½" thick complying with ICC-ES AC 51

using any standard non-open joint installation technique such as shiplap.

Page 16: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 16

P

6) Terra Cotta Cladding – minimum 1¼" thick (solid or equivalent by weight) using any standard non-open joint installation technique such as shiplap.

7) Thin brick/cultured stone set in thin set adhesive and metal lath that has been tested to ASTM E119 (brick exposed to furnace) and remains in place for a minimum of 30 minutes, or has passed an NFPA 285 test. Minimum ¾" (for use with R2+ BASE).

8) TABS II Panel System with ½" thick bricks using TABS Wall Adhesive. For use with R2+ BASE.

9) Any MCM that has successfully passed NFPA 285. 10) Uninsulated sheet metal building panels including steel, copper,

aluminum. 11) Uninsulated Fiber-cement siding. 12) Stone/Aluminum honeycomb composite building panels that have

successfully passed NFPA 285 criteria. 13) Autoclaved-aerated-concrete (AAC) panels that have successfully

passed NFPA 285 criteria. 14) Terra Cotta Cladding – Any Rain-screen Terra Cotta (min. ½ " thick) with

ventilated shiplap. Note 1: CCW LM 800 XL adhesive applied discontinuously at a rate of ⅜" x 3" dabs, 16" OC may be used to adhere exterior insulation to WRB over sheathing, concrete or CMU for those applications requiring this adhesive to be used. Note 2: The following may be used as gap filler between insulation panels, FOMO HandiFoam FireBlock, and TVM FireBlock. Note 3: CAV-GRIP™ or Low VOC Travel-Tack may be used as an adhesive (application rate as per mfg. instructions) to attach exterior insulation panels to the WRB surface. Table 5: R2+ SHEATHE Interior Insulation (See Notes 1 & 2) Wall Component Base Wall – Use either 1 or 2

1) Cast concrete walls (min. 8" thick) 2) CMU concrete walls (min. 8" thick)

Exterior Coating - Use either 1, 2, 3 or 4

1) Portland cement or Lime Stucco. 2) Any ASTM E84 Class A Paint or Elastomeric Coating 3) Any ASTM E84 Class A Clear Sealer 4) None

Air/Vapor Barrier Membrane Position 1 Over Base Wall Interior - Use either 1, 2, 3, 4 or 5. See Note 1

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Continuous Insulation

1) R2+ SHEATHE, 3½" Thick (max.)

Air/Vapor Barrier Membrane Position 2 Over Insulation - Use either 1, 2, 3, 4, or 5. See Note 1

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Interior Cladding

⅝" type X Interior Gypsum Sheathing installed directly over R2+ SHEATHE insulation or installed over Metal Hat or Z Furring, 2" depth air gap (max.)

Note 1: Membrane used in Position 1 or Position 2, not both. Note 2: R2+ SHEATHE insulation can be tacked in place with Cav-Grip or Travel-Tack during installation. Follow Instructions on Product Data Sheet.

Page 17: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 17

P

Owens Corning Tables (with figures) Wall Component Base Wall – Use either 1, 2 or 3

1) Cast Concrete Walls 2) CMU Concrete Walls 3) 20 GA. (min.) 3⅝" (min.) steel studs spaced 16 in. OC (max.) with

lateral bracing every 4 ft vertically. ⅝" type X Gypsum Wallboard Interior

Fire-Stopping in Stud Cavity at floor lines

4 pcf mineral fiber insulation (mineral wool) installed with z-clips or equivalent. Typical brand is Thermafiber.

Cavity Insulation – Use either 1, 2, 3 or 4

1) None 2) Any noncombustible insulation (faced or unfaced) 3) Any Fiberglass Batt (faced or unfaced) 4) Demilec Sealection 500 (0.5 pcf) Spray Polyurethane foam (SPF) up to

full cavity depth Exterior Sheathing – Use either 1 or 2

1) ½” Exterior Gypsum Sheathing 2) ⅝" Exterior Gypsum Sheathing

WRB Over Sheathing – Use either 1, 2, 3, 4 or 5

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Insulation – Use either 1 or 2 4 inch wide (max.) asphalt or butyl type sealing tape to seal insulation panel joints and/or veneer tie penetrations is allowed

1) ½ inch (min.) to 3 inch (max.) Foamular XPS Type IV or Type X per ASTM C578 – must use special condition 1 (see special conditions and drawings below) window/door header details.

2) ½ inch (min.) to 5 inch (max.) Foamular XPS Type IV or Type X per ASTM C578 – must use special condition 2 (see special conditions and drawings below) window/door header details.

WRB Over Exterior Insulation – Use either 1 or 2

1) None 2) Prosoco SprayWrap MVP

Exterior Cladding - Use either 1, 2, 3, 4, 5, 6, 7 or 8

1) Brick – Nominal 4" clay brick with maximum 2" air gap between exterior insulation and brick. Standard brick ties/anchors installed 24" OC (max.) vertically on each stud.

2) Stucco – minimum 7/8" thick exterior cement plaster and lath 3) Concrete – minimum 2" thick with maximum 2” air gap between exterior

insulation and concrete. 4) Concrete Masonry Units (CMU) – minimum 4” thick with maximum 2”

air gap between exterior insulation and CMU. 5) Limestone Veneer – minimum 2” thick using any standard non-open

joint installation technique such as ship lap, etc. 6) Natural Stone Veneer – minimum 2" thick using any standard non-open

joint installation technique such as ship lap, etc. 7) Cast Artificial Stone – minimum 1½" thick complying with ICC-ES AC

51 using any standard non-open joint installation technique such as ship lap, etc.

8) Terra Cotta Cladding – minimum 1¼" thick (solid) using any standard non-open joint installation technique such as ship lap, etc.

Page 18: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 18

P

Special Conditions Use 1 or 2 depending on thickness of exterior insulation Note: As an option, flash all window, door and other openings with limited amounts of acrylic, asphalt or butyl based flashing tape – max. 12” wide.

1) Use header treatments in Figures 1, 2, 3 or 4 below for all window and door openings in wall.

2) Use header treatments in Figures 5, 6, 7 or 8 below for all window and door openings in wall.

Special Conditions Header Treatments See drawings below for Special Conditions referenced in the table above.

Page 19: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 19

P

Page 20: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 20

P

Page 21: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 21

P

Page 22: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 22

P

Page 23: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 23

P

Page 24: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 24

P

Page 25: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 25

P

Page 26: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 26

P

DOW Tables (with figures) Wall Component Base Wall – Use either 1, 2 or 3

1) Cast Concrete Walls 2) CMU Concrete Walls 3) 20 GA. (min.) 3⅝" (min.) steel studs spaced 16 in. OC (max.) with

lateral bracing every 4 ft vertically. ⅝" type X Gypsum Wallboard Interior

Fire-Stopping in Stud Cavity at floor lines

4 pcf mineral fiber insulation (mineral wool) installed with z-clips or equivalent.

Cavity Insulation – Use either 1, 2 or 3

1) None 2) Any noncombustible material 3) Any Fiberglass Batt (faced or unfaced)

Exterior Sheathing – Use either 1 or 2

1) ½” (min.) Exterior Gypsum Sheathing 2) ⅝" Exterior Type X Gypsum Sheathing

WRB Over Sheathing – Use either 1, 2, 3, 4 or 5

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Insulation – 4 inch wide (max.) asphalt or butyl type sealing tape to seal insulation panel joints is allowed

½ inch (min.) to 3 inch (max.) DOW Styrofoam Type IV ASTM C578 – must use special window/door header details below.

WRB Over Exterior Insulation – Use either 1 or 2

1) None 2) Prosoco SprayWrap MVP

Exterior Cladding - Use either 1, 2, 3, 4, 5, 6 or 7

1) Brick – Nominal 4" clay brick with maximum 2" air gap between exterior insulation and brick. Standard brick ties/anchors installed 24" OC (max.) vertically on each stud.

2) Concrete – minimum 2" thick with maximum 2” air gap between exterior insulation and concrete.

3) Concrete Masonry Units (CMU) – minimum 4” thick with maximum 2” air gap between exterior insulation and CMU.

4) Limestone– minimum 2” thick using any standard non-open joint installation technique such as ship lap.

5) Natural Stone Veneer – minimum 2" thick using any standard non-open joint installation technique such as ship lap.

6) Pre-Cast Artificial Stone – minimum 1½" thick complying with ICC-ES AC 51 using any standard non-open joint installation technique such as ship lap, etc.

7) Terra Cotta Cladding – minimum 1¼" thick (solid) using any standard non-open joint installation technique such as ship lap, etc.

Special Conditions

Use header treatments in Figures 5, 6 & 7 below for all window and door openings in the wall.

Page 27: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 27

P

Special Conditions Header Treatments See drawings below for Special Conditions referenced in the table above (Fig 5, 6 & 7 Ref. 1).

Page 28: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 28

P

Page 29: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 29

P

For all constructions below, the window header shall consist of minimum 25 GA. sheet steel flashing. Wall Component Base Wall – Use either 1, 2, 3 or 4

1) Cast Concrete Walls 2) CMU Concrete Walls 3) Standard Clay Brick Walls 4) 20 GA. (min.) 3⅝" (min.) steel studs spaced 24 in. OC (max.) with

lateral bracing every 4 ft. vertically. ⅝" type X Gypsum Wallboard Interior

Fire-Stopping in Stud Cavity at floor lines

4 pcf mineral fiber insulation (mineral wool) installed with z-clips or equivalent.

Cavity Insulation – Use either 1, 2 or 3

1) None 2) Full stud depth (max.) Dow Styrofoam Spray Polyurethane Foam

CM2030, 2045, or 2060 complying with ESR 2670. Apply to interior side of exterior sheathing.

3) Any Fiberglass Batt insulation (faced or unfaced) complying with the applicable code.

Exterior Sheathing – Use either 1 or 2

1) ½” Exterior Gypsum Sheathing 2) ⅝" Exterior Gypsum Sheathing

WRB Over Sheathing – Use either 1, 2, 3, 4 or 5

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Insulation – Use either a, b, c, or d for cladding options 1-6. Use either a or e, for cladding options 7-11 Flashing tape to cover insulation joints and/or cladding ties and connections consisting of 4 inch (max.) Dow Weathermate Flashing, or asphalt or Butyl based flashing tape (complying with AAMA 71 or ICC-ES AC 148) is allowed.

1) For Claddings 1-6 a. None (only with exterior WRB 1 or 2 below). b. ⅝ inch (min.) to 4¼ inch (max.) DOW Thermax Insulation c. 3½ inch (max) Dow Styrofoam Spray Polyurethane Foam

CM2030, 2045, or 2060 complying with ESR 2670. d. Combination of exterior insulation 2 and 3 in any order not to

exceed 4¼ inches. 2) For Claddings 7-11

e. ⅝ inch (min.) to 3 inch (max.) DOW Thermax Insulation

WRB Over Exterior Insulation – Use either 1 or 2

1) None 2) Prosoco SprayWrap MVP

Exterior Cladding – Use either 1, 2, 3, 4, 5 or 6 for exterior insulation 1 (a-d). Use 7, 8, 9, 10 or 11 for exterior insulation 1a or 2e.

1) Brick – Nominal 4" clay brick with maximum 2" air gap between exterior insulation and brick. Standard brick ties/anchors installed 24" OC (max.) vertically on each stud.

2) Stucco – ¾ inch (min.) exterior cement plaster and lath. An optional secondary WRB (not full coverage asphalt or butyl based self-adhered membrane) may be applied in between the exterior insulation and lath. Fasteners must attach to base wall framing and designed to withstand wind and cladding load per applicable code.

3) Limestone– minimum 2” thick using any standard non-open joint installation technique such as ship lap.

4) Natural Stone Veneer – minimum 2" thick using any standard non-

Page 30: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 30

P

open joint installation technique such as ship lap. 5) Cast Artificial Stone – minimum 1½" thick complying with ICC-ES

AC 51 using any standard non-open joint installation technique such as ship lap.

6) Terra Cotta Cladding – minimum 1¼" thick (solid) using any standard non-open joint installation technique such as ship lap. Fasteners must attach to base wall framing and designed to withstand wind and cladding load per applicable code.

7) Use any MCM system that has successfully passed NFPA 285 (must have test report or ESR report)

8) Terra Cotta Cladding – minimum 1¼" thick installed using standard installation technique.

9) Metal exterior panels (steel, aluminum, copper) installed using standard installation technique.

10) Cement Board Siding – Installed per manufacturer instructions or per ICC-ES ESR report for a specific product.

11) StoneLite wall panels manufactured by Stone Panels per ESR 1500 Johns Manville Table For all constructions, the window header shall consist of minimum 25 GA. sheet steel flashing. Wall Component Base Wall – Use either 1, 2, 3 or 4

1) Cast Concrete Walls 2) CMU Concrete Walls 3) Standard Clay Brick Walls 4) 25 GA. (min.) 3⅝" (min.) steel studs spaced 24 in. OC (max.).

⅝" type X Gypsum Wallboard Interior Fire-Stopping in Stud Cavity at floor lines

Friction fit 4 pcf mineral fiber insulation (mineral wool such as Thermafiber)

Cavity Insulation – Use either 1, 2, 3, 4 or 5

1) None 2) Fiberglass Batt insulation (faced or unfaced) complying with the

applicable code. 3) Spray-in Fiberglass Insulation. 4) Mineral Wool insulation (faced or unfaced) 5) Sprayed cellulose insulation complying with IBC section 702 and

ASTM C739. Exterior Sheathing – Use either 1 or 2

1) ½” Exterior Gypsum Sheathing 2) ⅝" Type X Exterior Gypsum Sheathing

WRB Over Sheathing – Use either 1, 2, 3, 4 or 5

1) None 2) Prosoco R-Guard VB 3) Prosoco R-Guard Cat 5 4) Prosoco R-Guard Cat 5 Rain Screen 5) Prosoco SprayWrap MVP

Exterior Insulation –

4½ inch (max.) Johns Manville AP Foil Faced Sheathing Board installed with offset joints or non-staggered. Note: Insulation joints may be covered with 6 inch (max.) acrylic, asphalt or Butyl based flashing tape.

WRB Over Exterior Insulation

See Note for Flashing Tape for exterior Insulation

Exterior Cladding – Use either 1, 2, 3, 4, 5, 6 or 7

1) Brick – Nominal 4" clay brick with maximum 1" air gap between exterior insulation and brick. Standard brick ties/anchors installed 24" OC (max.) vertically on each stud.

2) Stucco – ¾ inch (min.) exterior cement plaster and lath. An optional secondary WRB (not full coverage asphalt or butyl based, self-

Page 31: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 31

P

adhered membrane) may be applied in between the exterior insulation and lath. Fasteners must attach to base wall framing and designed to withstand wind and cladding load per applicable code.

3) Natural Stone Veneer (Limestone, granite, marble, sandstone) – minimum 2" thick using any standard non-open joint installation technique such as ship lap.

4) Cast Artificial Stone,– minimum 1½" thick complying with ICC-ES AC 51 using any standard non-open joint installation technique such as ship lap.

5) Terra Cotta Cladding – minimum 1¼" thick (solid) using any standard non-open joint installation technique such as ship lap. Fasteners must attach to base wall framing and designed to withstand wind and cladding load per applicable code.

6) Concrete – minimum 2 inches thick with maximum 1 inch air gap between exterior insulation and concrete.

7) Concrete Masonry Units (CMU) – minimum 4 inches thick with maximum 2 inch air gap between exterior insulation and CMU.

Page 32: PRIEST & ASSOCIATES CONSULTING, LLC

PRIEST & ASSOCIATES CONSULTING, LLC

4607 Verdi Road Solutions for the 1-877-505-7743 Office Pleasanton, TX 78064 Building Materials Industry 210-410-8217 Mobile www.priestassociates.com [email protected]

P

May 20, 2015 Prosoco, Inc. Sean Scott 3741 Greenway Circle Ankrom Moisan Architects, Inc. Lawrence, KS 66046 6720 SW Macadam Ave / Suite 100 / Portland, OR 97219 Re: Project No. 10313, Revision 2

NFPA 285 Compliance of a Specific Stucco Wall Assembly utilizing Prosoco WRB’s and FRT Elements

Note: Revision 2 of this letter adds a signature block at the end (which was omitted in prior revisions). No other changes from Revision 1 have been made. INTRODUCTION The purpose of this engineering letter is to determine if a specific wall design can meet NFPA 285. The following diagram was provided. After some discussions with parties involved, the wall design was finalized and is listed below the diagram.

From interior to exterior, the wall layers are as follows:

1) 2 layers of ⅝ type X gypsum wallboard 2) FRT wood studs (2x4 or 2x6) 3) FRT plywood (½ or ⅝ or ¾ inch) 4) 2 layers ⅝ type X gypsum wallboard 5) Prosoco WRB product applied to exterior layer of ⅝ type X board (one of the following)

a. Prosoco R-Guard Cat 5 b. Prosoco SprayWrap MVP c. Prosoco R-Guard VB d. Prosoco R-Guard Cat 5 Rain Screen

6) 3½ inch Mineral fiber insulation 7) 1x4 borate treated wood furring strips 8) Dow Weathermate Plus WRB 9) Metal Lath

10) 7/8 inch stucco

Page 33: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 2

P

REFERENCED DOCUMENTS

1) ICC-ES ESR 1659 – Dow Thermax Products Evaluation Report 2) NFPA 285-12 Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of

Exterior Non-loadbearing Wall Assemblies Containing Combustible Components 3) Cone Calorimeter Data Prosoco, vs Approved WRB products – Data Confidential between

Prosoco and Priest & Associates. 4) Priest & Associates Engineering Evaluation 10261F Prosoco WRB allowances with DOW

Thermax NFPA 285 wall Assemblies 5) White, R.H., and Dietenberger, M.A., Wood Handbook Chapter 18 “Fire Safety of Wood

Construction”. 6) Benichou, N., Sultan, M.A., Kodur, V.R., Fire resistance performance of light weight framed wall

assemblies: effects of various parameters, key design considerations and numerical modelling. NRCC-45688, Institute of Research in Construction, National Research Council, Ottawa, Canada.

7) Babrauskas et. al. 10 Years of Heat Release Research NIST Publication http://fire.nist.gov/bfrlpubs/fire93/PDF/f93048.pdf

8) Lindholm et. al., Cone Calorimeter – a Tool for Measuring Heat Release http://www.ffrc.fi/FlameDays_2009/4B/LindholmPaper.pdf

EVALUATION METHOD An existing DOW ESR report (Ref. 1) lists their approved NFPA 285 constructions which includes various WRB products. Based on this, Priest & Associates has written an Engineering Evaluation (EEV, Ref. 4) which allows various Prosoco WRB products to replace the approved WRB products in the Dow ESR based on cone calorimeter flammability comparison data (Ref. 3). The issue to examine is that the construction depicted above does not exactly match the allowed constructions in the ESR or EEV. The main combustibles (other than the FRT wood) are the Prosoco WRB and the Dow Weathermate Plus WRB. There is no foam insulation in this assembly so it is very conservative compared to what Dow is allowed in their ESR report. We list the following points to prove that the proposed wall design can pass the NFPA 285 test:

1) Dow Thermax ESR 1659 allows a wide range of combustible exterior wall designs based on actual 285 tests.

2) Stucco construction and various WRB products (including Dow Weathermate Plus over the insulation/under the stucco) are allowed in the ESR.

3) Priest & Assoc. EEV 10261F allows various Prosoco WRB products to replace the WRB products in the DOW ESR based on cone calorimeter relative flammability data.

4) Data and code allowances allow replacing the steel suds and gypsum wallboard with FRT wood framing and sheathing in Type III walls

5) In the proposed construction, the FRT wood products are behind 2 layers of ⅝ inch type X gypsum wallboard. Ignition of the FRT elements is nearly impossible during a 30 minute NFPA 285 test.

6) Use of noncombustible insulation provides more fire protection than use of Dow Thermax Polyisocyanurate insulation.

Point 1 and 2 This evaluation is based on the Dow ESR report for analysis (Ref. 1). The approval report lists NFPA 285 tests (Item 6.7, Ref. 1) as the basis for the approval. It is assumed that these tests utilized various wall designs incorporating DOW Thermax foam products and a worst case WRB product. In the DOW ESR report, stucco and Dow Weathermate Plus are both allowed in the approved assembly table. Based on

Page 34: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 3

P

the approved items, this covers four of the elements (Items 7, 8, 9 & 10) in the proposed wall design since they are all elements of typical stucco construction:

7) 1x4 borate treated wood furring strips 8) Dow Weathermate Plus WRB 9) Metal Lath

10) 7/8 inch stucco Point 3 and 4 Exterior wall tests which utilize a worst case WRB product allow use of other WRB products which tend to perform the same or better. The approval submitted (Ref. 1) lists various types/brands/models of WRB systems. Prosoco flammability data (Ref. 3) indicates that the four Prosoco WRB products listed below perform better than at least one of the approved WRB products listed in the approval (Carlisle Barritech VP). We use peak HRR and Time to Ignition as the comparative data. Ranking of Cone Calorimeter Data When conducting cone calorimeter data comparisons, smaller Peak Heat Release Rate (Pk. HRR) values and longer time to ignition (Tign) values are considered to be improvements (i.e., less flammable). However, data for a given comparison are often conflicting. To resolve these types of discrepancies, researchers (Ref. 6) have used a ranking system and measurement uncertainty (Ref. 7) to organize cone calorimeter data for flammability comparisons. The expression:

Rank = Pk. HRR / Tign Is used to resolve inconsistencies in relative flammability data obtained from the Cone Calorimeter (Ref. 7). Lower HRR and longer Tign make the rank smaller. So, smaller rank materials are considered less flammable than higher rank materials. With that understood, the ranks of the materials being evaluated in this report are show below. Also, the relative error of the HRR in cone calorimeters is approximately 20 - 30% for 1 kW fires, 10% for 3 kW fires and less than 10% for 5 kW fires (Ref. 8). The HRR is the raw HRR (kW) – not the normalized HRR expressed in cone data (kW/m2). For normalized data in the range of 200 kW/m2, the raw heat release rate is 1/100th since the specimen measures 0.01 m x 0.01 m. So the uncertainty in this range is approximately 20%. The HRR uncertainty range of Prosoco R-Guard VB (179 to 269), overlaps that of Barritech VP (144 to 216). So, not only does R-Guard VB data have a smaller rank than Barritech VP, it also falls within the range of uncertainty of Barritech VP.

Product Pk HRR (kW/m2) Tign Rank Carlisle Barritech VP 180 25 7.2 Prosoco R-Guard Cat 5 165 40 4.1 Prosoco SprayWrap MVP 15 – no ignition No Ign. <1 Prosoco R-Guard VB 224 90 2.5 Prosoco R-Guard Cat 5 Rain Screen

145 33 4.4

Based on this analysis, item 5a, b, c or d in the proposed construction are allowed:

9) Prosoco WRB product applied to exterior layer of 5/8 type X board a. Prosoco R-Guard Cat 5 b. Prosoco SprayWrap MVP c. Prosoco R-Guard VB d. Prosoco R-Guard Cat 5 Rain Screen

Page 35: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 4

P

Point 4 and 5 Exterior wall tests which utilize steel stud base wall systems allow use of the system in Type I, II, III and Type IV construction (see Ref 1, Section 4.3). TYPE IIIA is a construction type which allows fire-retardant-treated wood (FRTW) framing in place of noncombustible steel studs in exterior walls having a fire rating of 2 hours or less. Type IIIA buildings include 2 hour noncombustible loadbearing and nonbearing exterior walls, 1 hour bearing interior walls, 1 hour structural frame, and 1 hour floor and roof construction. The use of fire-retardant-treated wood (FRTW) framing and sheathing in accordance with IBC Section 2303.2 and complying with Section 604.2.1 is allowed in Types III and IV construction within bearing and nonbearing exterior walls with required fire ratings of two hours or less. Types I and II construction also allow for FRT wood (framing and sheathing) in nonbearing exterior walls where a fire rating is not required. The use of FRT framing and sheathing in the exterior walls is not expected to detract from the NFPA 285 performance of the proposed wall systems for the following reasons:

1) The code recognizes an equivalency, between steel studs and FRTW, with FRTW materials considered interchangeable with noncombustible materials in specific exterior wall applications.

2) In ASTM E1354 Cone calorimeter testing, the initial peak Heat Release Rate (Pk HRR) and 1 minute average HRR for FRT plywood are comparable to results for gypsum sheathing (Ref. 5).

3) From the literature (Ref. 6), it has been established that steel stud walls exhibit fire resistance behavior similar to wood stud walls.

4) The building code allowance for the use of FRT framing in lieu of noncombustible materials is predicated on its Class A flame spread rating and the fact that it does not support progressive combustion during the ASTM E84 30 minute fire test. In the E84 30 minute test, FRTW does not spread flame in the E84 test apparatus more than 10.5 feet during the 30 minute test period, and does not support combustion once the flame source is removed (ref. http://www.frtw.com/sites/default/files/specs/common/class_abc_123.pdf).

5) In the proposed construction, the FRT plywood is behind 2 layers of ⅝ inch type X gypsum wallboard, a layer of 3½ inch mineral fiber insulation, and 7/8 inch stucco. Ignition of the FRT plywood is nearly impossible during a 30 minute NFPA 285 test which produces a heat exposure less severe than the ASTM E119 test. The graph (black line) below depicts the ASTM E119 Curve. This curve is generated using large time delay thermocouples (5 to 7 minute delay). The actual temperatures using a fast response thermocouple (similar to NFPA 285 thermocouples) is higher by a few hundred degrees. During the first 5 minutes, the actual E119 temperatures are closer to 1400° F (Ref. actual experiment conducted by the author March 2015).

Page 36: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 5

P

The graph below depicts the temperature profile of the exterior fire in the NFPA 285 test (ignore TC1 since it is in direct contact with window plume from room burner).

Clearly, the E119 fire test curve is more severe – especially considering use of fast response thermocouples. In the proposed construction, it is expected that the FRT plywood will not ignite, since it is protected by at least 3 layers of thermally thick non-combustible products. Based on the discussion above, Items 1, 2, 3 & 4 in the proposed construction are therefore covered.

1) 2 layers of ⅝ type X gypsum wallboard 2) FRT wood studs (2x4 or 2x6) 3) FRT plywood (½ or ⅝ or ¾ inch) 4) 2 layers ⅝ type X gypsum wallboard

Point 6 Exterior wall tests which utilize combustible exterior insulation allow use of other insulations which tend to perform the same or better. In the Dow ESR report (Ref. 1), tests were conducted using Dow Thermax polyisocyanurate insulation – a combustible product. In the proposed construction, 3½ inches of mineral fiber insulation is being used. This is a noncombustible product and is clearly an improvement in the wall design. Based on the discussion above, item 6 in the proposed construction is covered.

6) 3½ inch mineral fiber insulation CONCLUSIONS The discussion above shows that the proposed wall design is more conservative than the allowed constructions in the Dow ESR report (Ref. 1), or the allowed constructions in the Priest & Assoc. EEV (Ref. 4). Therefore, the construction depicted below is expected to be able to pass NFPA 285 test criteria.

Page 37: PRIEST & ASSOCIATES CONSULTING, LLC

Priest & Associates Consulting Solutions for the Building Materials Industry Page 6

P

From interior to exterior, the wall layers are as follows:

1) 2 layers of ⅝ type X gypsum wallboard 2) FRT wood studs (2x4 or 2x6) 3) FRT plywood (½ or ⅝ or ¾ inch) 4) 2 layers ⅝ type X gypsum wallboard 5) Prosoco WRB product applied to exterior layer of ⅝ type X board (one of the following)

a. Prosoco R-Guard Cat 5 b. Prosoco SprayWrap MVP c. Prosoco R-Guard VB d. Prosoco R-Guard Cat 5 Rain Screen

6) 3½ inch Mineral fiber insulation 7) 1x4 borate treated wood furring strips 8) Dow Weathermate Plus WRB 9) Metal Lath

10) ⅞ inch stucco If you have any questions or comments, please let us know. The conclusions reached by this evaluation are true and correct, within the bounds of sound engineering practice. All reasoning for our decisions is contained within this document.

Javier Trevino Associate Engineer Date: May 20, 2015

Deggary N. Priest President Date: May 20, 2015