Hindawi Publishing Corporation Conference Papers in Engineering Volume 2013, Article ID 198021, 7 pages http://dx.doi.org/10.1155/2013/198021 Conference Paper Prevention of Cascaded Events of Distance Relay Zone Three Using Logic Controls Mohamed Younes E. Henna 1 and Sayed A. Nagy 2 1 Middle Delta Electricity Production Company, Ministry of Electricity and Energy, Cairo, Egypt 2 Department of Electrical Power Engineering, University of Al-Azhar, Cairo, Egypt Correspondence should be addressed to Mohamed Younes E. Henna; eng [email protected] Received 7 February 2013; Accepted 29 April 2013 Academic Editors: M. Elmusrati, A. Gaouda, and H. Koivo is Conference Paper is based on a presentation given by Mohamed Younes E. Henna at “International Conference on Electrical and Computer Engineering” held from 26 March 2013 to 28 March 2013 in Benghazi, Libya. Copyright © 2013 M. Y. E. Henna and S. A. Nagy. is is an open access article distributed under the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited. is paper presents a new method to prevent cascaded events caused by zone 3 elements of distance relays due to transmission line overload by using logic controls. A proposed adaptive distance relay algorithm provides a new concept to distinguish between actual faults and flow transfers and secures time to perform remedial controls by a defense system during cascaded events. Maloperation of distance relay is a very critical situation, leading to more operation of other distance relays and finally partial or total blackout. Logic controls are used to insure the operating decision through observing the system parameters and compare it with a setting already being input to the system. When distance relay is activated and the logic controls find that the system is healthy (unfaulted) and that the activation resulted from transmission line overload not real fault, the operation signal will be blocked to protect the system from maloperation. 1. Introduction Transmission lines are a vital part of the electrical distribution system , as they provide the path to transfer power between generation and load. Transmission lines operate at voltage levels from 66 kV to 765 kV and are ideally tightly intercon- nected for reliable operation. Factors like deregulated market environment, economics, right of way clearance, and environmental requirements have pushed utilities to operate transmission lines close to their operating limits. Any fault, if not detected and isolated quickly will cascade into a system-wide disturbance causing widespread outages for a tightly interconnected system oper- ating close to its limits. Transmission protection systems are designed to identify the location of faults and isolate only the faulted section. e key challenge to the transmission line protection lies in reliably detecting and isolating faults compromising the security of the system [1]. e effects of a major blackout have become more serious as a result of the wide area interconnections. Due to the lack of transmission enhancement during the last decades and the resulting low security margins, the risk of major outages for the power grid has also increased [1]. Distance protection is the most widely used method to protect transmission lines. e fundamental principle of distance relaying is based on the local measurement of voltages and currents, where the relay responds to the impedance between relay terminal and the fault location. As compared to differential protection, distance protection can operate properly without a communication device. is aspect is attractive from both a reliability and an economical point of view. However, in some applications, communication links are used as a supplement to speed up the fault clearing time [2, 3]. In usual practice, distance relays are constructed to give three zones protection in forward direction and one zone in reverse each zone has different time delaying. Faults occurring within those zones are cleared by circuit breakers [4].

Prevention of Cascaded Events of Distance Relay Zone Three ...Distance protection is the most widely used method to protect transmission lines. The fundamental principle of distance

  • Upload
    others

  • View
    2

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Prevention of Cascaded Events of Distance Relay Zone Three ...Distance protection is the most widely used method to protect transmission lines. The fundamental principle of distance

Hindawi Publishing CorporationConference Papers in EngineeringVolume 2013, Article ID 198021, 7 pageshttp://dx.doi.org/10.1155/2013/198021

Conference PaperPrevention of Cascaded Events of Distance Relay Zone ThreeUsing Logic Controls

Mohamed Younes E. Henna1 and Sayed A. Nagy2

1 Middle Delta Electricity Production Company, Ministry of Electricity and Energy, Cairo, Egypt2 Department of Electrical Power Engineering, University of Al-Azhar, Cairo, Egypt

Correspondence should be addressed to Mohamed Younes E. Henna; eng [email protected]

Received 7 February 2013; Accepted 29 April 2013

Academic Editors: M. Elmusrati, A. Gaouda, and H. Koivo

This Conference Paper is based on a presentation given by Mohamed Younes E. Henna at “International Conference on Electricaland Computer Engineering” held from 26 March 2013 to 28 March 2013 in Benghazi, Libya.

Copyright © 2013 M. Y. E. Henna and S. A. Nagy. This is an open access article distributed under the Creative CommonsAttribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work isproperly cited.

This paper presents a newmethod to prevent cascaded events caused by zone 3 elements of distance relays due to transmission lineoverload by using logic controls. A proposed adaptive distance relay algorithmprovides a new concept to distinguish between actualfaults and flow transfers and secures time to perform remedial controls by a defense system during cascaded events. Maloperationof distance relay is a very critical situation, leading to more operation of other distance relays and finally partial or total blackout.Logic controls are used to insure the operating decision through observing the system parameters and compare it with a settingalready being input to the system.When distance relay is activated and the logic controls find that the system is healthy (unfaulted)and that the activation resulted from transmission line overload not real fault, the operation signal will be blocked to protect thesystem from maloperation.

1. Introduction

Transmission lines are a vital part of the electrical distributionsystem , as they provide the path to transfer power betweengeneration and load. Transmission lines operate at voltagelevels from 66 kV to 765 kV and are ideally tightly intercon-nected for reliable operation.

Factors like deregulatedmarket environment, economics,right of way clearance, and environmental requirements havepushed utilities to operate transmission lines close to theiroperating limits. Any fault, if not detected and isolatedquickly will cascade into a system-wide disturbance causingwidespread outages for a tightly interconnected system oper-ating close to its limits. Transmission protection systems aredesigned to identify the location of faults and isolate onlythe faulted section. The key challenge to the transmissionline protection lies in reliably detecting and isolating faultscompromising the security of the system [1].

The effects of a major blackout have becomemore seriousas a result of the wide area interconnections. Due to the lack

of transmission enhancement during the last decades and theresulting low security margins, the risk of major outages forthe power grid has also increased [1].

Distance protection is the most widely used methodto protect transmission lines. The fundamental principleof distance relaying is based on the local measurementof voltages and currents, where the relay responds to theimpedance between relay terminal and the fault location.As compared to differential protection, distance protectioncan operate properly without a communication device. Thisaspect is attractive from both a reliability and an economicalpoint of view.However, in some applications, communicationlinks are used as a supplement to speed up the fault clearingtime [2, 3].

In usual practice, distance relays are constructed to givethree zones protection in forward direction and one zonein reverse each zone has different time delaying. Faultsoccurring within those zones are cleared by circuit breakers[4].

Page 2: Prevention of Cascaded Events of Distance Relay Zone Three ...Distance protection is the most widely used method to protect transmission lines. The fundamental principle of distance

2 Conference Papers in Engineering

A: normal load

G: PSB setting

D: power swing locus

B: heavy loadF: load angle

𝑅

𝑋

C: blinder E: dt

Figure 1: Characteristics of a distance relay.

Power swing, over load, transient periods, or current infeed may cause maloperation of distance relay for zone 3,because the value of the impedance may move and locate inzone 3 activation zone Figure 1. So, the distance relay will beactivated, although the network is healthy. As a result of thisoperation, the flow of the disconnected line will flow in therest lines causing more overloading on it, leading to moreoperation of other distance relays and finally partial or totalblackout. So, the tripping signal must be blocked in this caseto prevent undesirable operation [5–7].

Logic controls are used to insure the operating decisionthrough observing the system parameters and compare itwith a setting already being input to the system. So, whenthe distance relay is activated the logic controls can sendthe operation signal or block it depending on the observingsystem parameters and the input setting.When distance relayis activated and the logic controls find that the system ishealthy and the activation resulted from transmission lineoverload not real fault, the operation signal will be blockedto protect the system from maloperation. If the overloadincreases, the program will take another action like loadshedding.

2. Flow Chart of the Logic ControlCharacteristic

Distance protection can operate without communicationlinks (nonpilot distance relay) or with communication links(pilot distance relay).

2.1. Nonpilot Distance Relay. In nonpilot distance relays,program takes local measurements for currents and voltagesand calculates the impedance of the line; nonpilot means nocommunication system between distance relays in differentbuses.When the calculated impedance of the line reduces andlocates in zone 3 activation zone, the program will comparethe value of voltage with a setting value already being inputin the program and the same in the current. When theprogram finds that the values of voltage and current arewithin acceptable range, the programwill block the trip signalfor zone 3, or it will send load shedding signal to disconnectsome of the loads to recover the stability to the network.The following flow charts are for logic control characteristic

Table 1: Line impedances of the six-bus system.

Line 𝑍 (ohm) 𝑌 (mho)L1 26.6 + 𝐽105.8 𝐽3.8𝐸 − 5

L2 26.6 + 𝐽105.8 𝐽3.8𝐸 − 8

L3 42.3 + 𝐽158.7 𝐽5.7𝐸 − 5

L4 26.34 + 𝐽52.9 𝐽1.89𝐸 − 5

L5 52.9 + 𝐽158.7 𝐽3.8𝐸 − 5

L6 37 + 𝐽105.8 𝐽3.8𝐸 − 8

L7 26.5 + 𝐽52.9 𝐽5.7𝐸 − 5

L8 26.5 + 𝐽52.9 𝐽1.89𝐸 − 5

in distance protective relay in case of being without loadshedding and with load shedding Figures 2 and 3.

Figures 4 and 5 show the logic control of distanceprotective relay in case of being without load shedding andwith load shedding. In case of being without load shedding,when the three parameters of (Z, V, and I) were achieved,the logic control would delay the trip signal with setting ofzone 3 delayed time; after this time, if the parameters arestill in activation zones, the logic control will send trip signalto the line breaker. In case of with load shedding, when thethree parameters of (Z, V, and I) were achieved, the logiccontrol would delay load shedding signal with time delaythat is less enough for zone 3 delayed time; after this time, ifthe parameters are still in activation zones, the logic controlwill send load shedding signal. If the parameters are still inactivation zones, the logic control will send a trip signal tothe line breaker.

Setting of voltage depending on the acceptable dippinglevel allowable was according to North of American Relia-bility Corporation (NERC), automatic load shedding was setblow 0.9 P.U. with time delay from 3.5 sec to 8 sec, and thesetting of generation unit under voltage was set at 0.8 P.U.;so, the setting of voltage must be set higher enough forgeneration unit trip setting. Setting of voltage was put at0.85 P.U., and setting of current was put lower enough fromthe physical limit of the transmission line.

3. Case Study

In order to study the feasibility of the proposed algorithm,computer simulations have been performed for a simple six-bus system. Figure 6 shows a system that consists of six busesincluding three generators, three loads, and eight lines. Thegenerations, loads, and the corresponding MW power on thebuses in a normal operation state are given in Figure 6.

Table 1 gives the impedances and admittances of the eighttransmission lines. Table 2 provides the settings of blinderelements for the distance relays on each line of the six-bussystem. The settings are calculated by the authors accordingto the setting guideline of Korean Electric PowerCooperation(KEPCO) [1].

TheMATLAB Power System Tool Box is used to simulatethis case.

Page 3: Prevention of Cascaded Events of Distance Relay Zone Three ...Distance protection is the most widely used method to protect transmission lines. The fundamental principle of distance

Conference Papers in Engineering 3

Start

Delay time 0.9

𝑋 = 0

End

Dis trip = 1

𝑋 = 𝑋 + 1

No

No

No

No

Yes

Yes

Yes

Yes

Read 𝑉𝑛 , 𝐼𝑛

𝑍𝑛 = 𝑉𝑛/𝐼𝑛

Is

Is

Is

Is

𝑍3 > 𝑍𝑛 > 𝑍2

𝐾𝑉𝑛 > 𝑉𝑛

𝐼𝑛 > 𝐾𝐼𝑛

𝑋 = 1

Set 𝑉𝑛 = 0, 𝐼𝑛 = 0, 𝑍𝑛 = 0, dis trip = 0, L shed = 0, 𝑋 = 0

Figure 2: Flow chart of logic control characteristic of nonpilot distance relay in case without load shedding.

Start

Set 𝑉𝑛 = 0, 𝐼𝑛 = 0, 𝑍𝑛 = 0, dis trip = 0, L shed = 0, 𝑋 = 0

Read 𝑉𝑛 , 𝐼𝑛

𝑍𝑛 = 𝑉𝑛/𝐼𝑛𝑋 = 0

Is

Is

Is

Is

Is

𝑍3 > 𝑍𝑛 > 𝑍2

𝐾𝑉𝑛 > 𝑉𝑛

𝐼𝑛 > 𝐾𝐼𝑛

𝑋 > 0

𝑋 = 1

Dis trip = 1

End

𝑋 = 𝑋 + 1𝑋 = 𝑋 + 2

Delay time 0.9 Delay time 0.6

L shed = 1Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

Figure 3: Flow chart of logic control characteristic of nonpilot distance relay in case with load shedding.

4. Simulation and Results

The system under study was simulated to find out thefeasibility of the purposed system. The system under studywas tested in normal operation, overloaded operation, cas-caded events operation, using logic control operationwithoutload shedding, and using logic control operation with loadshedding.

Table 3 shows the impedances of all lines in the systemseen to the distance relays under normal operation, over-loaded operation, and in case of tripping of line 7 leading tocascaded events.

As shown in Table 3, when the system was overloadedwith excess 40MW which might be an acceptable level andline 7 was tripped for any reason, the distance relays weresupposed to be in healthy status, and all voltage ranges for

Page 4: Prevention of Cascaded Events of Distance Relay Zone Three ...Distance protection is the most widely used method to protect transmission lines. The fundamental principle of distance

4 Conference Papers in Engineering

Trip signalDelay time

𝑍

𝐼

𝑉

Figure 4: Logic control diagram of nonpilot distance relay in caseof without load shedding.

Load sheddingsignal

Trip signal

Delay time 1

Delay time 2

𝑍

𝐼

𝑉

Figure 5: Logic control diagram of nonpilot distance relay in caseof with load shedding.

Table 2: Blinder element setting in the six-bus system.

Bus Line Setting (ohm)B1 L1 576.6B1 L2 576.6B1 L3 433.7B2 L4 692.9B2 L5 692.9B2 L6 576.6B3 L7 491.9B3 L8 491.9B4 L1 576.6B4 L2 576.6B4 L4 692.9B5 L3 433.7B5 L5 692.9B5 L7 491.9B6 L6 576.6B6 L8 491.9

all buses were in acceptable levels. But the impedance ofsome lines moved and located in zone 3, activation zone, andconsequently, the second line was tripped. When the secondline was tripped, power flowed in the other rest lines thatmade another distance relay of another line activated andtripped. Another line was the same, which led the systemto cascaded events, and finally; the system was divided intotwo sections; in the first section, the voltage dropped to about0.30 P.U., and in the second section, the voltage rose to about2 P.U., and finally, the enter system collapsed.

By observing the system parameters the voltages and thecurrents shown in Figures 7, 8, 9, 10, 11, 12, 13, and 14, the

L1

L2

L5

L4

B4

B2B5

B6B3

G2

G3

G1

B1

L8

L6L7

L3

Load 1

Load 2

Load 3

150 MW

140 MW180 MW

190 MW

90 MW75 MW38 MVAR

36 MVAR

27.5 MVAR 22 MVAR

15 MVAR

40 MVAR

Figure 6: Six-bus system in normal operation condition.

10.90.80.70.60.50.40.30.20.1

00.1 0.150.05 0.2 0.25 0.3 0.35 0.4 0.45

0.98 0.94 0.93

0.38

Time (s)

Volta

ge (P

.U.)

𝑉1

Figure 7: Voltage at bus 1 during cascaded events.

voltages and the currents were in an acceptable ranges at allbuses before tripping the second line by distance relay.

From the previous observing parameters for voltages andcurrents, it is found that all voltages at all buseswere at normalranges or with acceptable ranges and currents also, until thesecond line tripped by maloperating of distance relay andthe cascaded system collapsed and finally total blackout.Thisblackout caused by maloperation of the distance relays.

After using logic controls, the system was secured andbecame more reliable. When the impedance moved andlocated in activation zone for zone 3, the program wouldhave checked on voltage and current levels for this line andcompared these values with input values set on the program.When the program found that the values were within ranges,it blocked the trip signal to protect the enter system fromcascaded events.

In the previous case, when line 7 was tripped for anyreason, the current of line 5 rose to about 2.2 times of theoperation value, and the value of voltage dropped to about0.87 P.U.; those values activated distance relay and tripped theline leading the enter system to total blackout, although thetransmission line was working far of its physical limits, andthe dropping of the voltage was not very high. Logic controlsobserved and analysed these parameters and blocked the tripsignal to protect the system from collapsing.

Page 5: Prevention of Cascaded Events of Distance Relay Zone Three ...Distance protection is the most widely used method to protect transmission lines. The fundamental principle of distance

Conference Papers in Engineering 5

Table 3: Cascaded events leading to a system collapse.

Line Normal Overloaded Trip line 7 2nd line trip 3rd line trip System is landing1 3405 3450 9060 2060 1550

System was divided into two sections, andthe voltage dropped to 0.3 P.U. in the 1stsection and rose to 2 P.U. in the 2nd section.

2 3405 3450 9060 2060 15503 2615 1421 890 452 4504 1455 1477 961 522 Trip5 2340 1252 657 Trip Open6 2614 1891 1835 2445 27187 1346 1020 Trip Open Open8 3812 9948 881 1118 3573

21.81.61.41.2

10.80.60.40.2

00.1 0.150.05 0.2 0.25 0.3 0.35 0.4 0.45

0.99 0.981.07

2.03

Time (s)

Volta

ge (P

.U.)

𝑉2

Figure 8: Voltage at bus 2 during cascaded events.

21.81.61.41.2

10.80.60.40.2

00.1 0.150.05 0.2 0.25 0.3 0.35 0.4 0.45

0.981.1 1.18

2.02

Volta

ge (P

.U.)

Time (s)

𝑉3

Figure 9: Voltage at bus 3 during cascaded events.

10.90.80.70.60.50.40.30.20.1

00.1 0.150.05 0.2 0.25 0.3 0.35 0.4 0.45

0.940.87

0.75

0.3Volta

ge (P

.U.)

1.1

Time (s)

𝑉5

Figure 10: Voltage at bus 5 during cascaded events.

140120100

80604020

00.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45

Time (s)

Curr

ent (

Am

p)

0.5 0.55

𝐼1 and 2

26.5 A

140 A

76 A87A

Figure 11: Current in line 1 and 2 during cascaded events.

250

150

100

50

00.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45

Time (s)

200

𝐼3

Curr

ent (

Am

p)

72 A

132 A

256 A

110 A

Figure 12: Current in line 3 during cascaded events.

160140

10080604020

00.1 0.15 0.2 0.25 0.3 0.35 0.4

𝐼5

Time (s)

Curr

ent (

Am

p) 120

80 A

162 A

Figure 13: Current in line 5 during cascaded events.

Page 6: Prevention of Cascaded Events of Distance Relay Zone Three ...Distance protection is the most widely used method to protect transmission lines. The fundamental principle of distance

6 Conference Papers in Engineering

120

100

80

60

40

20

00.1 0.2 0.3 0.4 0.5 0.6

𝐼6

Time (s)

Curr

ent (

Am

p)

51 A

98 A

119 A104 A

Figure 14: Current in line 6 during cascaded events.

1

0.8

0.6

0.4

0.2

00.1 0.150.05 0.2 0.25 0.3 0.35 0.4

0.97 0.941.02

Time (s)

Volta

ge (P

.U.)

𝑉1

Figure 15: Voltage at bus 1 using load shedding.

1

0.8

0.6

0.4

0.2

00.12 0.14 0.16 0.2 0.22 0.24 0.26

𝑉5

0.94 0.870.97

Time (s)

Volta

ge (P

.U.)

0.18

1.2

Figure 16: Voltage at bus 5 using load shedding.

10.90.80.70.60.50.40.30.20.1

00.12 0.140.1 0.16 0.18 0.2 0.22 0.24 0.28

𝑉6

0.97 0.951.03

Time (s)

Volta

ge (P

.U.)

1.1

0.26

Figure 17: Voltage at bus 6 using load shedding.

Table 4: Cascaded events prevented by using load shedding.

Line Normal Overloaded Trip line 7 After loadshedding

1 3405 3450 9060 85802 3405 3450 9060 85803 2615 1421 890 11654 1455 1477 961 9635 2340 1252 657 8486 2614 1891 1835 15937 1346 1020 Trip Open8 3812 9948 881 792Italic and bold font: abnormal values (faulted values).

Logic control could take remedial controls like loadshedding to help system to reach now equilibrium operationpoint [8]. Amount of load shedding predefined depending onload demand, generation capacity, and may be put in severalstages. Location of load to be shed also predefined dependingon load center and type of load. Table 4 shows impedancesof all lines in the system under normal operation, overloadedoperation, and tripping of line 7 in case of using logic controlto shed part of the load at bus 5 at about 40MW to returnthe system stability. As shown in Table 4, the impedances ofall lines after using load shedding moved and located out ofactivation zone of distance relay zone 3. So, the system wassecured against cascaded events that led to total blackout.Time delay of zone 3 is about 900ms, this is enough time todo the remedial control of load shedding.

Figures 15, 16, and 17 show the voltage at several buses inthe system and show the advantage of using logic control.

5. Conclusion

Many factors have pushed utilities to operate transmissionlines close to their operating limits, and the utilities mustbe able to work under such situations with high efficiency.Overloading on the transmission lines became often matters.Maloperation of distance relays is a very critical situation,leading to more operation of other distance relays and finallypartial or total blackout. As shown in this paper, the useof logic controls with distance protection relays secures theutilities and makes it more reliable in many critical cases.In addition to adding a great advantage to the system bydistinguishing between actual faults and flow transfers oroverloading and securing time to perform remedial controlslike load shedding during cascaded events, logic controls areused to insure the tripping decision through observing andanalyzing system parameters.

References

[1] S. I. Lim, C. C. Liu, S. J. Lee, M. S. Choi, and S. J. Rim, “Blockingof zone 3 relays to prevent cascaded events,” IEEE Transactionson Power Systems, vol. 23, no. 2, pp. 747–754, 2008.

[2] M. Jonsson, Line Protection and Power System Collapse, Depart-ment of Electric Power Engineering, Chalmers University ofTechnology, Gothenburg, Sweden, 2001.

Page 7: Prevention of Cascaded Events of Distance Relay Zone Three ...Distance protection is the most widely used method to protect transmission lines. The fundamental principle of distance

Conference Papers in Engineering 7

[3] T. Manokaran and V. Karpagam, “Performance of distancerelay estimation in transmission line with UPFC,” InternationalJournal of Computer and Electrical Engineering, vol. 2, no. 1, pp.158–161, 2010.

[4] C. J. Mozina, M. Reichard, Z. Bukhala et al., “Coordination ofgenerator protection with generator excitation control and gen-erator capability,” in Proceedings of the IEEE Power EngineeringSociety General Meeting (PES ’07), June 2007, paper no. 1-4244-1298-6/07.

[5] J. G. Andrichak and G. E. Alexander, “Distance Relays Fun-damentals,” GE Power Management, General Electric Co.Malvern, PA, GER-3966.

[6] N. Zhang and M. Kezunovic, Verifying the Protection SystemOperationUsing anAdvanced Fault Analysis Tool Combinedwiththe Event Tree Analysis, Department of Electrical Engineering,Texas A&M University, College Station, Tex, USA, 2004.

[7] M. Jonsson, J. Daalder, and K. Walve, “An emergency strategyscheme based on conventional distance protection to avoidcomplete system collapse,” in Proceedings of the IEEE PESTransmission and Distribution Conference and Exposition, pp.315–319, September 2003.

[8] Undervoltage Load Shedding Task Force (UVLSTF),Undervolt-age Load Shedding Guideline, Technical Studies Subcommittee,Western Systems Coordinating Council, 1999.

Page 8: Prevention of Cascaded Events of Distance Relay Zone Three ...Distance protection is the most widely used method to protect transmission lines. The fundamental principle of distance

Impact Factor 1.73028 Days Fast Track Peer ReviewAll Subject Areas of ScienceSubmit at http://www.tswj.com

Hindawi Publishing Corporation http://www.hindawi.com Volume 2013Hindawi Publishing Corporation http://www.hindawi.com Volume 2013

The Scientific World Journal

Page 9: Prevention of Cascaded Events of Distance Relay Zone Three ...Distance protection is the most widely used method to protect transmission lines. The fundamental principle of distance

Submit your manuscripts athttp://www.hindawi.com

VLSI Design

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

International Journal of

RotatingMachinery

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

Hindawi Publishing Corporation http://www.hindawi.com

Journal ofEngineeringVolume 2014

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

Shock and Vibration

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

Mechanical Engineering

Advances in

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

Civil EngineeringAdvances in

Acoustics and VibrationAdvances in

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

Electrical and Computer Engineering

Journal of

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

Distributed Sensor Networks

International Journal of

The Scientific World JournalHindawi Publishing Corporation http://www.hindawi.com Volume 2014

SensorsJournal of

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

Modelling & Simulation in EngineeringHindawi Publishing Corporation http://www.hindawi.com Volume 2014

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

Active and Passive Electronic Components

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

Chemical EngineeringInternational Journal of

Control Scienceand Engineering

Journal of

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

Antennas andPropagation

International Journal of

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014

Navigation and Observation

International Journal of

Advances inOptoElectronics

Hindawi Publishing Corporation http://www.hindawi.com

Volume 2014

RoboticsJournal of

Hindawi Publishing Corporationhttp://www.hindawi.com Volume 2014