ARABIA ELECTRIC LTD. Equipment Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.: Consultant : Substation : AL- BAWADI 110 / 13.8 K.V S/S 1. General Information about the Relay: Panel No. CT Ratio 1200 / 1 A Relay Type 7SA522 Secondary Rated Current ( I n ) 1 A Manufacturer SIEMENS PT Ratio 110 / 0.1 KV SERIAL NO Secondary Rated Voltage ( U n ) ( PH –PH ) 100 V MLFB - No. 7SA522-4DB00-4QN4 U 4 Voltage Transformer is Not Connected Software Version 4.61 DC. Auxiliary . Voltage 110- 125 DCV Test Equipment OMICRON – CMC 156 Frequency F n 60 Hz 2 . Mechanical Check and Visual Inspection Ite m Description Remarks 1 Check the name plate data according to the drawings and specifications 2 Check for transportation damage and correct positioning 3 Verify tightness of all connections siemens Client: SEC - CSD Consultant: Saudconsult Name: Name: Name: Signature: Signature: Signature: Date: Date: Date: CSD – DAR ENGINEERING – AL FANAR Page 1 of 85 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

How to Test Distance Relay 7SA522

Embed Size (px)

Citation preview

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

1. General Information about the Relay:

Panel No. CT Ratio 1200 / 1 A

Relay Type 7SA522 Secondary Rated Current ( In )

1 A

Manufacturer SIEMENS PT Ratio 110 / 0.1 KV

SERIAL NO Secondary Rated Voltage ( Un ) ( PH –PH )

100 V

MLFB - No. 7SA522-4DB00-4QN4 U4 Voltage Transformer is Not Connected

Software Version 4.61 DC. Auxiliary . Voltage 110- 125 DCV

Test Equipment OMICRON – CMC 156 Frequency Fn 60 Hz

2 . Mechanical Check and Visual Inspection

Item Description Remarks

1 Check the name plate data according to the drawings and specifications2 Check for transportation damage and correct positioning3 Verify tightness of all connections

3. Electrical Checks

Item Description Remarks

1 All connections checked according to the wiring diagram2 Auxiliary power supply checked for rating and polarity3 CT shorting checked4 Indications checked5 Casing earthing checked6 Contact earthing checked7 Contact resistance of tripping and alarm checked

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 1 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

4. General Functions in the Relay :

Function Selected

Phase Distance Protection Quadrilateral Earth Distance Protection QuadrilateralPower Swing Detection Enabled

Teleprotection For Distance Protection PUTT ( Z1B acceleration )/ POTT /

BLOCKING / Un BLOCKINGDTT Direct Transfer Trip Disabled Instantaneous High Speed SOTF Over Current EnabledWeek Infeed ( Trip & / Or Echo ) EnabledBack Up Over Current Protection Time Over Current Curve IECEarth Fault Over Current Protection Time Over Current Curve IECTeleprotection For Earth Fault Over Current DisabledAuto – Reclose Function Not Applicable in this typeSynchronism & Voltage Check Not Applicable in this typeFault Locator Enabled

5. Power System Data :

OHL / UG Cable Under Ground Cable Line

CT Star Point Towards Line

System Star point Solid Earthed

Line Length Km

Line Angle 85

X ∕ = Line Reactance( Ω / Km )

Zero Sequence Compensation Factors

RE / RLZ1 =Z2----- Z5 =

XE / XLZ1 =Z2----- Z5 =

6. Secondary Injection Measurements :

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 2 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/SSetting:* 1201=Distance Protection = OFF.* We should insure that: 1 – CT. & VT. Ratios are as setting in Power System Data 1 , Address ( 0203 ---0206 ) 2 –From Setting Group A : Power System Data 2 , insure the value of % in : Address (1103 ) Measurement : Full Scale Voltage ( 100 % ) (1104 ) Measurement : Full Scale Current ( 100 % )

3 –The Direction of the Earthing is as per approved Drawings & as setting in Power System Data 1

( i ) If the direction of the Earthing is Towards the line ( Cable ): The Current is Lagging the Voltage by 45° ( As shown below )

( ii ) If the direction of the Earthing is Towards the Bus Bar: The Current is Leading the Voltage by 135° ( As shown below )

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 3 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

V1 = 57.73 V ∟0° V2 = 57.73 V ∟-120° V3 = 57.73 V ∟+120°

I 1 = 1 A ∟- 45° I 2 = 1 A ∟-165° I 3 = 1 A ∟+75°

V1 = 57.73 V ∟0° V2 = 57.73 V ∟-120° V3 = 57.73 V ∟+120°I 1 = 1 A ∟+135° I 2 = 1 A ∟+15° I 3 = 1 A ∟-105°

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

90°

135°

I

0° V

180°

I

45°-

270°

Injected quantities:

* Inject 3 Phases Currents & Voltages.

( i ) The angle between I & V is ( 0° )

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 4 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Phase - L1 Phase -L2 Phase -L357.73 V ∟0° 57.73 V ∟-120° 57.73 V ∟+120° 1 A ∟0° 1 A ∟-120° 1 A ∟+120°

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

( ii ) The angle between I & V is (- 45° )

( iii ) The angle between I & V is ( +135° )

Note : Print out from the Relay is Attached ( Primary & Secondary & % values )

Parameters

Measured Values In The Relay

At angle ∟ 00 At angle ∟ - 45o At angle ∟+ 135primary secondary

% values

primary secondary%

valuesprimary secondary

% values

Current IL1

Current IL2

Current IL3

3I0

I1 - positive Sequence

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 5 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

L1 L2 L357.73 V ∟0° 57.73 V ∟-120° 57.73 V ∟+120°

1 A ∟-45° 1 A ∟-165° 1 A ∟+75°

L1 L2 L357.73 V ∟0° 57.73 V ∟-120° 57.73 V ∟+120°

1 A ∟+135° 1 A ∟ +15° 1 A ∟-105°

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/SI2 - Negative Sequence

Voltage UL1EVoltage UL2EVoltage UL3EVoltage UL12

Voltage UL21

Voltage UL31

3U0

U1 - positive Sequence

U2 - Negative Sequence

Apparent power(S)Active power(P)Reactive power(Q)FrequencyPower Factor

7. Impedance Secondary Measurements :

Note : Before starting this test , for easy calculation & to get correct readings

In the relay configuration , Setting Group A , power system data 2

Address (1116-1119) : setting for Zero Sequence Compensation Factors

RE / RL =0 & XE / XL = 0 ,

Also Zero Sequence Compensation Factors in the Tester setting should be Zero

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 6 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

( I ) Inject the impedance ( Z ) = 6 Ω with angle = 60 o ( in Forward Side )

Calculate : R= Z x COS Φ , X= Z x SIN Φ

Then measure the impedance ( Z ) ( Primary & Secondary )

( II ) Inject the impedance ( Z ) = 6 Ω with angle = 240 o ( in Reverse Side )

Calculate : R= Z x COS Φ , X= Z x SIN Φ

Then measure the impedance ( Z ) ( Primary & Secondary )

Note :

[ C.T ratio = 1200 / 1 ] & [ V.T ratio = 110 / 0.1 K.V ]

= 1200 = 1100

The Primary measured values = Secondary measured values X [ V.T ratio / C.T ratio ]

= 0.92

Phase Impedance

Φ = 60o Φ = 240o

Calculated

Z

Measured Z Calculated

Z

Measured Z

Primary Secondary Primary Secondary

L1 - N RL1 3 -3

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 7 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/SXL1 5.196 -5.196

L2 - NRL2 3 -3

XL2 5.196 -5.196

L3 - NRL3 3 -3

XL3 5.196 -5.196

L1 – L2RL12 3 -3

XL12 5.196 -5.196

L2 – L3RL23 3 -3

XL23 5.196 -5.196

L3 – L1RL31 3 -3

XL31 5.196 -5.196

8- Distance protection pick up threshold ( Fault Detection Test ):

8.1- Phase Fault Current Threshold Detection ( I ph ) Test Address : ( 1202 )

*1201 : Distance Protection is = ON*1202 : Phase Current Threshold ( I ph ) for Distance Measurement= 0.2A*1203 : 3Io Threshold for Neutral Current PickUp = 0.1ANote:-* 3Io Earth Fault setting should be < I ph Phase Fault setting.*You must inject voltage more than the setting voltage at Address ( 2913A ) : Maximum Voltage Threshold U < ( 3 Phase ) = 5VOr ( 2915 ) : Voltage Failure supervision = OFF

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 8 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S& ( 2910 ) : Fuse Failure Monitoring = OFF& ( 2901 ) : Measurement Supervision = OFF

Then*Inject Phase - Phase Current more than the setting at Address ( 1202 ) & Zero Voltage. ∟0° ∟180°

Also Note :- Address No. ( 1209 ) : Criterion of Earth Fault Recognition Not important if it is (3I0 OR 3U0) / (3I0 AND 3U0)

PhasePhase Fault I ph Setting

(Address:1202)Measurement (A)

Pick Up (A) Drop Off (A)L1∟0° – L2 ∟180°

0.2 A

L2∟0° – L3 ∟180°L3∟0° – L1 ∟180°

inject voltage the setting voltage at Address ( 2913A ) Or Fuse Failure=Off ( The

Volt =0 )

Inject Phase - Phase Current more than the setting at Address ( 1202 )

8.2-Earth fault detection Test:

8.2.1- Earth Fault Current Threshold ( 3Io ) Detection Address : ( 1202 )

*1201 : Distance Protection is = ON*1202 : Phase Current Threshold ( I ph ) for Distance Measurement= 0.1A

*1203 : 3Io Threshold for Neutral Current ( Earth Fault ) PickUp = 0.4A

*1209 : Criterion of Earth Fault Recognition should be selected as = ( 3I0 OR 3U0 )

*1204 : ( 3 VO )Threshold Zero Sequence Voltage pick up = 5 VNote:- 1 - ( 3Io ) Threshold for Neutral Current ( earth fault ) PickUp setting ( Address:1203A ) should be above the phase fault setting (Address: 1202) 2 –You must inject voltage more than the setting voltage at Address ( 2913A ): Maximum Voltage Threshold U < ( 3 Phase ) = 5V Or ( 2915 ) : Voltage Failure supervision = OFF

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 9 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

I ph

Trip&

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S & ( 2910 ) : Fuse Failure Monitoring = OFF & ( 2901 ) : Measurement Supervision = OFF

Then , Inject Phase – Earth Fault Current (single phase current ) more than the setting at Address ( 1202 ) & more than the setting at Address ( 1203 ) & Zero Voltage.

PhaseEarth Fault 3Io

(Neutral Current ) Setting(Address:1203)

Measurement (A)

Pick up (A) Drop off (A)

L1 - N

0.4A

L2 - N

L3 - N

Note : I ph will operate ( Pick Up ) first, because the setting is less , but the Trip will be with 3Io value.

inject voltage the setting voltage at Address ( 2913A ) Or Fuse Failure=Off ( The

Volt =0 )

Inject Phase - Earth Current more than the setting at Address ( 1203 )

8.1.2- Zero Sequence Voltage Threshold Check 3 VO Detection ( Address 1204 )

* 1204 : (3 VO )Threshold Zero Sequence Voltage pick up = 5 V*1209A : Criterion of Earth Fault Recognition should be selected as = ( 3I0 AND 3U0 )

*1202 : Phase Current Threshold ( I ph ) for Distance Measurement = 0.1A

*1203 : 3Io Threshold for Neutral Current ( Earth Fault ) PickUp = 0.4ANote : ( 2915 ) : Voltage Failure supervision = OFF & ( 2910 ) : Fuse Failure Monitoring = OFF & ( 2901 ) : Measurement Supervision = OFFThen

1 - Inject Phase – Earth Fault Current (Single Phase Current ) more than ( 3I0 ) Setting

(Address 1203 ) and also more than Phase Current ( I ph ) Setting (Address 1202 )

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 10 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

3Io

Trip&

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S Inject 3-Phase Current = Rated Current = 1 A

2 - Inject 3 VO Zero Sequence Voltage V L1–N = 6v, V L2–N =10V, V L3 –N =10V, Reduce slowly V L1–N voltage till relay E/F element operates, then:

take the pick up value of the relay by switching On & Off of fault & check the pick up

value of distance relay.

Setting value of 3Vo (V) Measured Pick Up value (V)

5

make Unbalance in 3 VO , Reduce slowly V L1–N

Inject 3-Phase Current = Rated Current = 1 A

9- Zones reach & Time Testing ( Manual Check )

To test the ZONE Reach & Time , we adjust the ZONES from the relay Settings as following: Settings Device configuration :

0112 Phase Distance Quadrilateral 0113 Earth Distance Quadrilateral

From Setting Group A : 0013 Distance zones (Quadrilateral )

Zone-Z1 1301 Operating Mode Zone-1 Forward 1302 R ( Z1 ) , Resistance for Ph- Ph Faults 1.0 Ω 1303 X ( Z1 ) , Reactance 2.5 Ω 1304 RE( Z1 ) , Resistance for Ph- E Faults 1.0 Ω 1305 T1-1 Phase , delay for single phase faults 0.0 Sec. 1306 T1-multi Ph , delay for single phase faults 0.0 Sec.

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 11 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

3 VO

Trip&

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/SZone-Z1B 1351 Operating Mode Z1B( OverReach Zone ) Forward 1352 R (Z1B ) , Resistance for Ph- Ph Faults 1.3 Ω 1353 X (Z1B) , Reactance 3.5 Ω 1354 RE(Z1B) , Resistance for Ph- E Faults 1.3 Ω 1355 T1B-1 Phase , delay for single phase faults 0.3 Sec. 1356 T1B-multi Ph , delay for single phase faults 0.3 Sec.

Zone-Z2 1311 Operating Mode Zone-2 Forward 1312 R ( Z2 ) , Resistance for Ph- Ph Faults 2.0 Ω 1313 X ( Z2 ) , Reactance 5.0 Ω 1314 RE( Z2 ) , Resistance for Ph- E Faults 2.0 Ω 1315 T2-1 Phase , delay for single phase faults 0.5 Sec. 1316 T2-multi Ph , delay for single phase faults 0.5 Sec.

Zone-Z3 1321 Operating Mode Zone-3 Reverse 1322 R ( Z3 ) , Resistance for Ph- Ph Faults 3.0 Ω 1323 X ( Z3 ) , Reactance 6.0 Ω 1324 RE( Z3 ) , Resistance for Ph- E Faults 3.0 Ω 1325 T3 delay 1.0 Sec.

Zone-Z4 1331 Operating Mode Zone-4 Forward 1332 R ( Z4 ) , Resistance for Ph- Ph Faults 5.0 Ω 1333 X ( Z4 ) , Reactance 10.0 Ω 1334 RE( Z4 ) , Resistance for Ph- E Faults 5.0 Ω 1335 T4 delay 1.5 Sec.

Zone-Z5 1341 Operating Mode Zone-5 Non-Directional 1342 R ( Z5 ) , Resistance for Ph- Ph Faults 7.0 Ω 1343 X ( Z5 ) +, Reactance for Forward direction 12.0 Ω 1344 RE( Z5 ), Resistance for Ph- E Faults 7.0 Ω 1345 T5 delay 2.5 Sec. 1346 X ( Z5 ) -, Reactance for Reverse direction 12.0 Ω

Note : In Reverse Zone , we can inject by the same angle of Forward , but Inverse the Earthing in the Relay Or Inverse the direction of injection.

Test Procedure with OMCRON :

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 12 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S1- Distance Advanced Distance2- Choose “Shot Test “.3- Put the Points4- Choose “Add To “ 5 –Choose “ ALL “ , Then OK.

We should insure from the Parameter that the Earthing is as the actual.

Zones

Settings

Ax

is

Fault Types

Time(m Sec. )Time

Imp

edan

ce

Z L1 - N L1 - N L1 - N L1 – L2 L1 – L2 L1 – L2 L1 L2 L3

Z1

Fo

rwar

d

01 R∟0°

2.5 X∟90°

Z1B

Fo

rwar

d

0.31.3 R∟0°

3.5 X∟90°

Z2

Fo

rwar

d

0.52 R∟0°

5 X∟90°

Z3

Rev

ers

e

13 R∟180°

6 X∟270°

Z4

Fo

rwar

d

1.55 R∟0°

10 X∟90°

Z5

No

n D

irec

tio

nal

2.5

7 R∟0°

12 X∟90°

-7 R∟180°

-12 X∟270°

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 13 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

Note : Zones reach & Time Testing ( Auto Check )

See the Attached Print out from the Relay

10- Distance directionality check :

Note :- 1- If any Zone is adjusted to be Non-Directional , you must reverse it ( or adjusted it

to be Inactive ) to be able to determine the Undefined Areas. 2 - You must Configure LEDs for Distance Pick Up Forward and Distance Pick Up Reverse.Settings Device configuration :

0112 Phase Distance Quadrilateral 0113 Earth Distance Quadrilateral

From Setting Group A : 0013 Distance zones (Quadrilateral ) Zone-Z5 1341 Operating Mode Zone-5 Inactive

From Masking I / O ( Configuration Matrix ) : LED13 = 3719 = Distance FORWARD LED14 = 3720 = Distance REVERSE

3 - The 3-Phase Fault Injection , 1- Phase Fault Injection & Ph-Ph Fault Injection Must Be same For All Types Of Faults.

Test Procedure with OMCRON : Apply a constant value of the Impedance Z , and change the angle, Select the zone operating time as sufficiently long ( e.g. 22 Sec. ) so that the relay should not trip while rotating / changing the angle.1- Distance Advanced Distance2- Choose “ Check Test “.3- Apply a constant value of the Impedance Z 4- Choose “Sequence “

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 14 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S5 –Determine the Range you want to test & Determine the increment in the Angle.

DirectionAngels

Expected Angels Measured AngelsFrom To From To

Forward338° ( - 22° ) 120°

Un-defined120° 150° 158°

Reverse150° 300° ( - 60° )

Un-defined300°( - 60° ) 338°

120°

Undefiened

150° FORWARD

REVERSE 338° Undefiened

300°

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 15 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

11- Distance Teleprotection Schemes :

11.1. P ermissive U nder R each ( PUTT ) (Z1B Acceleration)

( Local ) S / S Location of Fault Relay action ( Remote ) S / S

Location of Fault Relay actionZ1 Inst. Trip with Z1 Time + CS Z1 Inst. Trip with Z1 Time + CSZ1B + CR Inst. Trip with Z1B Time Z1 Inst. Trip with Z1 Time + CS

Z1 Inst. Trip with Z1 Time + CS Z1B + CR Inst. Trip with Z1B Time

Z1B W/O CR Trip with Z2 Time +No CS

Z3(reverse) W/O CR Trip with Z3(reverse) Time

Z2 , Z3, Z4, Z5 Trip with each Zone Time +No CS

Z3(reverse) W/O CR Trip with each Zone Time

Settings: Specify the followings Address No:3850 BO for Distance Trip Z1B With Teleprotection Scheme

4006 BI for Distance Teleprotection Carrier reception channel 1 ( Carrier Receive )

4054 LED 13 = Distance Teleprotection Carrier reception Signal ( Carrier Receive ) 4056 LED 14 = Distance Teleprotection Carrier Send Signal ( Carrier Send )

1 - From DIGSI Program :

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 16 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Trip Logic Z1B Fault + CR Instantaneous Trip with Z1B Time w/ o CS

Z1B Fault w/ o CR Trip with Z2 Time w/ o CS

Trip Logic Z1B Fault + CR Instantaneous Trip with Z1B Time w/ o CS

Z1B Fault w/ o CR Trip with Z2 Time w/ o CS

Send Logics ( CS ) Z1 Fault Instantaneous Trip with Z1 Time + CS Send Logics ( CS ) Z1 Fault Instantaneous Trip with Z1 Time + CS

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S Settings Device Configuration , Choose the Scheme “ PUTT “.

Address No: 0121 : Teleprotection for Distance protection PUTT (Z1B Acceleration)

2 - Setting Group A : Address No: 0021 : Teleprotection for Distance protection 3 – Choose “ Export “ , then OK 4 – Save the File by any Name ( Rio File )

Test Procedure with OMCRON : 1- Distance Advanced Distance2- Open “Setting “ , then Choose “ Extended Zones Active “ to show ( Active ) Z1B.3- Open the Saved File : From ( Parameters : Choose “ Test Object “ , then Inport )

11.2 P ermissive Ov er R each ( POTT )

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 17 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Send Logics ( CS ) Z1 Fault Instantaneous Trip with Z1 Time + CS Z1B Fault + CR Instantaneous Trip with Z1B Time + CS

Z1B Fault w/ o CR Trip with Z2 Time + CS

Send Logics ( CS ) Z1 Fault Instantaneous Trip with Z1 Time + CS Z1B Fault + CR Instantaneous Trip with Z1B Time + CS

Z1B Fault w/ o CR Trip with Z2 Time + CS

Send Logics ( CS ) Z1 Fault Instantaneous Trip with Z1 Time + CS Z1B Fault + CR Instantaneous Trip with Z1B Time + CS

Z1B Fault w/ o CR Trip with Z2 Time + CS

Send Logics ( CS ) Z1 Fault Instantaneous Trip with Z1 Time + CS Z1B Fault + CR Instantaneous Trip with Z1B Time + CS

Z1B Fault w/ o CR Trip with Z2 Time + CS

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

( Local ) S / S Location of Fault Relay action ( Remote ) S / S

Location of Fault Relay actionZ1 Inst. Trip with Z1 Time + CS Z1 Inst. Trip with Z1 Time + CS

Z1B + CR Inst. Trip with Z1B Time + CS Z1 Inst. Trip with Z1 Time + CS

Z1 Inst. Trip with Z1 Time + CS Z1B + CR Inst. Trip with Z1B Time + CS

Z1B W/O CR Trip with Z2 Time + CS Z3(reverse) + CR Trip with Z3(reverse) Time

Z3(reverse) + CR Trip with Z3(reverse) Time Z1B W/O CRTrip with Z2 Time + CS

Z2 , Z3, Z4, Z5 Trip with each Zone Time +No CS Z3(reverse) W/O CR Trip with each Zone Time

Note: If the Fault is in Z3 ( Reverse Zone ):

1- Z3 Fault ( Reverse ) + CR , & the Time is ‹ the Time at Address : 2109A: Transient Block: Duration external fault = 400 m Sec., The Trip will be Instantaneous . With Z1B Time

2- Z3 Fault ( Reverse ) W/O CR , & the Time is ‹ the Time at Address : 2109A: Transient Block: Duration external fault = 400 m Sec., The Trip will be with Z3( Reverse) Time.

3- Z3 Fault ( Reverse ) + CR , & the Time is ›the Time at Address : 2109A: Transient Block: Duration external fault = 400 m Sec., The Trip will be with the Time at Address : 2110A : Transient Block: Block Transient after external fault = 500 m Sec.

Settings Address No:3850 BO for Distance Trip Z1B With Tele Protection Scheme

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 18 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Trip Logic Z1B Fault + CR Instantaneous Trip with Z1B Time + CS Trip Logic Z1B Fault + CR Instantaneous Trip with Z1B Time + CS

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

4006 BI for Distance Teleprotection Carrier reception channel 1 ( Carrier Received )4054 LED 13 = Distance Teleprotection Carrier Signal Received ( Carrier Received )

4056 LED 14 = Distance Teleprotection Carrier Send Signal ( Carrier Send ) 4246 LED 14 = ECHO Send Signal

11.2.1. Weak Infeed Function ( with POTT Scheme ) ( ECHO only / ECHO And Trip ) Address No: 2501 11. 2.1.1. Echo only Settings : Configure Address No:

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 19 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S 00379 CB Auxiliary Contact 3 Pole Closed [CB. Close ] ( Binary Input ) 00380 CB Auxiliary Contact 3 Pole Open [CB. Open ] ( Binary Input )

Status Relay action should beRelay action

C.B off ( Open ) + Carrier Receive ( Z1B Fault )

Echo Signal Send Immediately ( CS )

C.B on ( Closed ) + Carrier Receive

( Z1B Fault )

Echo Signal Send (CS ) after time delay Address No: (2502A) : ( 40 m Sec.)Trip / Echo Delay After Carrier Receipt.

11. 2.1.2. ( Echo & Trip )

Status Relay action should beRelay action

C.B off ( Open ) + Carrier Receive ( Z1B Fault )

Echo Signal Send Immediately ( CS ) Without Local Trip

C.B on ( Closed ) + Carrier Receive

( Z1B Fault )

Local Trip & Echo Signal Send ( CS ) after time delay Address No: (2502A) : ( 40 m Sec.)Trip / Echo Delay After Carrier Receipt.

11. 2.1.3. Under Voltage Pick Up for Local Trip ( Weak Infeed Voltage )

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 20 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

Settings: Address No: ( 2502A ) : Trip / Echo Delay After Carrier Receipt. = 5 Sec. ( 2505 ) : Under Voltage ( Phase – Earth ) = 25.0 V ( 1130A ) : Pole Open Current Threshold = 0.1 A

If we apply one Phase Voltage ‹ Setting in Address No: (2505 ) : Under Voltage ( Phase – Earth ) and we apply the other two Phases Voltage by Normal value and

inject one phase current › Setting in Address No: ( 1130A ) : Pole Open Current Threshold = 0.1 A and the other two phases by Normal value.

All this with Carrier Receive then the relay will send an Echo and weak in feed Local Trip after the time of Address No: ( 2502A )

But if the one phase voltage is more than the Address No: ( 2505 ) the relay will send Echo Only after time of Address No: ( 2502A ) : Trip / Echo Delay After Carrier Receipt. = 5 Sec.

Under Voltage ( Ph–E) ( V )

Setting Value = 25 VAddress No: ( 2505)

Measured Voltage = V

Trip Time Delay for Local Trip ( Sec. )

Setting Value = 5 Sec.Address No: ( 2502A)

Measured Time = Sec.

Pole Open Current Threshold ( A )

Setting Value = 0.1 AAddress No: ( 1130A)

Measured Current = A

11.2.2. Current Reversal Logic ( with POTT Scheme ) 0021

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 21 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

11.3. Blocking Scheme :

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 22 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Send Logics ( CS ) Z3 Fault ( Reverse ) Instantaneous Trip with Z1B Time + CS Or ( Undefined Zones ) Z1B Fault + CR Block , Trip with Z2 Time

Send Logics ( CS ) Z3 Fault ( Reverse ) Instantaneous Trip with Z1B Time + CS Or ( Undefined Zones ) Z1B Fault + CR Block , Trip with Z2 Time

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

( Local ) S / S Location of Fault Relay action ( Remote ) S / S

Location of Fault Relay actionZ1 Inst. Trip with Z1 Time + CS Z1 Inst. Trip with Z1 Time + CS

Z1B + CR Inst. Trip with Z1B Time + CS Z1 Inst. Trip with Z1 Time + CS

Z1 Inst. Trip with Z1 Time + CS Z1B + CR Inst. Trip with Z1B Time + CS

Z1B W/O CR Trip with Z2 Time + CS Z3(reverse) w/o CR

Inst. Trip with Z1B Time

Z3(reverse) w/o CR

Inst. Trip with Z1B Time Z1B W/O CRTrip with Z2 Time + CS

Z2 , Z3, Z4, Z5 Trip with each Zone Time +No CS Z3(reverse) W/O CR Trip with each Zone Time

Note: If the Fault is in Z3 ( Reverse Zone ):

1- Z3 Fault ( Reverse ) W/O CR , & the Time is ‹ the Time at Address : 2109A: Transient Block: Duration external fault = 400 m Sec., The Trip will be Instantaneous . With Z1B Time

2- Z3 Fault ( Reverse ) + CR , & the Time is ‹ the Time at Address : 2109A: Transient Block: Duration external fault = 400 m Sec., The Trip will be with Z3( Reverse) Time.

3- Z3 Fault ( Reverse ) W/O CR , & the Time is ›the Time at Address : 2109A: Transient Block: Duration external fault = 400 m Sec.& ‹ Z3 time The Trip will be with the Time at Address : 2110A : Transient Block: Block Transient after external fault = 500 m Sec.

Settings Address No:3850 BO for Distance Trip Z1B With Tele Protection Scheme

4006 BI for Distance Teleprotection Carrier reception channel 1

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 23 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Trip Logic Z1B Fault W/O CR Instantaneous Trip with Z1B Time Trip Logic Z1B Fault W/O CR Instantaneous Trip with Z1B Time

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S ( Carrier Received )4054 LED 13 = Distance Teleprotection Carrier Signal Received ( Carrier Received )

4056 LED 14 = Distance Teleprotection Carrier Send Signal ( Carrier Send )

# 0021Current reversal logic WITH BLOCKING SCHEME: -

11.4. Unblocking Scheme :This Scheme is not related to any CR , Z1B is Active only with Binary Input ( From : Masking I / O ( Configuration Matrix )), use the Address No: 4030 Distance Teleprotection Unblocking :UNBLOCK Channel 1

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 24 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Send Logics ( CS ) Z1 Fault Instantaneous Trip with Z1 Time + CS Z1B Fault + CR Block , Trip with Z2 Time

Z2-----Z5 W/O CR Trip with each Zone Time W/O CS

Send Logics ( CS ) Z1 Fault Instantaneous Trip with Z1 Time + CS Z1B Fault + CR Block , Trip with Z2 Time

Z2-----Z5 W/O CR Trip with each Zone Time W/O CS

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

11.5. Direct Transfer Trip ( DDT )

From DIGSI Program : Settings Device Configuration , Choose the Scheme

Address No: 0121 : Teleprotection for Distance protection Disabled 0122 : DDT Direct Transfer Trip Enabled

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 25 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Send Logics ( CS ) Z1 Fault Instantaneous Trip with Z1 Time + CS Send Logics ( CS ) Z1 Fault Instantaneous Trip with Z1 Time + CS

Trip Logic Z1B Fault + CR Trip with Z1B Time Trip Logic Z1B Fault + CR Trip with Z1B Time

Trip Logic Z1B Fault W/O CR Instantaneous Trip with Z1B Time Trip Logic Z1B Fault W/O CR Instantaneous Trip with Z1B Time

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S Setting Group A : 0022 : DDT Direct Transfer Trip Address No: 2201 : Direct Transfer Trip ( DDT ) ON 2202 : Trip Time Delay 0.01 Sec. From : Masking I / O ( Configuration Matrix ) , Configure the following: Address No:

4417 : Direct Transfer Trip INPUT 3 Ph - L123 ( Binary Input Carrier Received) 4435 : DDT Trip Command L123 ( Binary Output Trip ) Also PUTT Scheme To Be Selected To SEND Signal In ZONE - 1.

12. Power Swing Detection Address No:0120 Enabled

Setting Group A : 0020 : Power Swing Address No:2007 :Trip Delay after Power Swing Blocking 5 Sec. ( Raise the Time Setting of Trip Delay after Power Swing Blocking Address No:2007 to more than the longest time of the Distance Zones )

Power Swing Operating ModeAddress No:2002

Relay Action

All zones Blocked

Z1 , Z1B , Z2 Blocked No trip withTrip with

Z1 , Z1B Blocked No trip withTrip with

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 26 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

Z2 to Z5 Blocked No trip withTrip with

** When the Fault comes to the line , the Voltage will decrease Or the Current increase , then the Impedance will decrease in very short time , then the relay will trip according to the setting of the fault case.

** In the Power Swing case , the Impedance will decrease but in very short time , it will be decrease related with proper time for that decreasing, so the Power Swing depend on changing the Impedance with Time ( dZ / dt ). However , the time has to be proper with this changing ( Not very short when the Impedance will decrease ) , then the relay will Block all the Zones ( in case of chosen “All zones Blocked “ in Address No:2002 )

Test Procedure with OMCRON Using ( State Sequencer ):

1 - Inject Normal Current & Normal Voltage. 2 – Then Decrease the Voltage by constant ( d / dt ),

[ (i.e.) Decrease the Impedance by ( dZ / dt ).]3 -The Power Swing depend on changing the Impedance with Time( dZ/dt )4 -The Power Swing Impedance starts before Z5 by 5Ω5 –When the Impedance enter the Polygon ,the Timer in Address No: 2007 : :Trip Delay after Power Swing Blocking 5 Sec. , Will Operate . ( i ) If the changing of the Impedance in the Polygon is slowly , then the relay will be Blocked by The Power Swing Function. ( ii ) If the changing of the Impedance in the Polygon is fastly and the Impedance is go out from the Polygon , then any Fault will make Trip.

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 27 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

13 . Switch On To Fault ( SOTF ) Function Check :

13.1. Instantaneous High Speed SOTF-O/C [ SOTF Separate Function ] From Device Configuration : Address No:0124 Enabled

Setting Group A : Address No:0024 Address No: 2401: Instantaneous High Speed SOTF-O/C is ON 2404: Iph››› Pick Up 2.5A

Also : Disable the Distance Protection Address No:1201 Disable Back Up Over Current Protection Address No:2601

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 28 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

Address No: 1201 : Distance Protection is OFF

1232 : Instantaneous Trip after SOTF for Distance Inactive

2601 : Operating Mode for BackUp O/C OFF

2615 : Instantaneous Trip after SOTF for O/C I›› NO 2625 : Instantaneous Trip after SOTF for O/C I› NO 2671 : Inst. Trip after SOTF for O/C Inverse Type NO

Also , From Setting Group A : Address No:0011 : Power System Data 2 ( Line Status ) Address No:1130 : Pole Open Current Threshold 0.1A

:1131A: Pole Open Voltage Threshold 30 V

1132A: Seal –in Time after All Closures 0.05 Sec.

:1133A: Minimal Time for Line Open before SOTF 0.25Sec.

1134 : Recognition of Line Closures with

(i) Manual Close Bi Only(ii) Current flow OR Manual Close Bi(iii) Current OR Voltage OR Manual Close Bi(iv) CB aux. OR Current OR Manual Close Bi

:1135: Reset of Trip Command(i) PickUP Reset

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 29 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

(ii) With CB aux. Open & I‹Pole Open Current

(iii) With Pole Open Current Threshold Only :1136: Open Pole Detector

(i)OFF (ii)With CB aux. Open & I‹Pole Open Current

(iii)With measurement ( U/I , Trip , PickUp, CB aux.) 1150A: Seal –in Time after Manual Closures 0.30Sec.

For C.B Closure Recognition Address No: (1134) : by Binary Input Manual Close OnlyRaise the Setting of Address No: ( 1150A ): Seal- in Time after Manual Closures

( This Time Controls the Time for Activation of BI:Manual Close ) Test Procedure :

From : Masking I / O ( Configuration Matrix ) , SOTF over current

Configure the following:

# Instantaneous High Speed SOTF O/C has a private Trip ,So you must Configure Binary Output and any LED for it.Address No: (4295) :SOTF- O/C Trip Command L123 ,

# Also you can Configure Binary Output for SOTF-O/C Picked Up Address No: (4281): SOTF- O/C Picked Up

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 30 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

for detecting Pick Up value ,but it is not important because the operation of SOTF is instantaneous.

# Configure Binary Input for Manual Close Address No:00356 :Manual Close Signal # Configure Binary Input for C.B off Address No:00380:CB. Aux. Contact 3 Pole Open

# Case No.( i ): Inject Current more than the Setting in Address No: 2404:

Iph››› Pick Up = 2.5A With activation of the Binary Inputs of C.B off & Manual Close . » The relay will Trip Case No.( ii ):Inject Current more than the Setting in Address No: 2404:

Iph››› Pick Up = 2.5A Without activation of the Binary Inputs of C.B off & Manual Close . » The relay will Not Trip Case No.( iii ):Inject Current Less than the Setting in Address No: 2404:

Iph››› Pick Up = 2.5A With activation of the Binary Inputs of C.B off & Manual Close . » The relay will Not Trip

Setting in Injected Measured

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 31 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

Address No: 2404 ( A )

Current ( A )

Trip Time (m Sec)

Case No.( i ) 2.5 2.7

Case No.( ii )2.5 2.7 No Trip

Case No.( iii ) 2.5 2.0 No Trip

Note : Address No: 1130 : Pole Open Current Threshold 0.1A 1133A: Minimal Time for Line Open before SOTF 0.25Sec. 1132A: Seal –in Time after All Closures 2 Sec.

Instead of using Binary Input : CB. Manual Close , we can Inject Current Less Than the Current in Address No: 1130 for a period of time =250 mSec ,So , the relay will know that the CB. of the Feeder as it is Opened ( OFF ), also the Time in Address No: 1132A , helping in Monitoring the Increase in Current after CB. is Closed ( ON ),If During that time 250 mSec , the Current Increased More than the Current in Address No: 1130 , Then the relay will be Tripe By SOTF Function.

Hence , we can make this Test as following :

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 32 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S1134 : Recognition of Line Closures with(Current flow OR Manual Close Bi)

Using State Sequencer in OMICRON as following :( 1 )1st State , Inject Normal Current (1 A ) & Voltage (57.73 V ) & Voltage Values for a period of time more than 250 mSec. ( 2 ) 2nd State , Inject Normal Current(1 A ) & Voltage (57.73 V ) Values for a period of time less than 2 Sec.

( 3 )3rd State , Inject a Current higher than the Current in Address No:

2404 : Iph››› Pick Up = 2.5A , & Normal Voltage Value( 57.73 V ) for a period of time less than 2 Sec.

Then » The relay will Trip by SOTF Function

ثم نحقن طبيعي زمن ms 250*نحقن طبيعي ثم نفصل االحقن زمن اعلي من سوف يفصل بلخاصيه A 2 ثم نحقن تيار اعلي من s 2اقل من

ثم نحقن طبيعي زمن ms 250*نحقن طبيعي ثم نفصل االحقن زمن اعلي من سوف ال يفصل بلخاصيه A 2 ثم نحقن تيار اعلي من s 2اعلي من

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 33 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S ثم نحقن طبيعي زمن ms 250*نحقن طبيعي ثم نفصل االحقن زمن اقل من

سوف ال يفصل بلخاصيه A 2 ثم نحقن تيار اعلي من s 2اقل من 9.1- SOTF associated with distance protection B) SOTF WITH DISTANCE PROTECTION: (1232 = ZONE PICK UP )ADDRESS NO1232 Dis. = ONADDRESS NO1201 SOTF WITH Dis. = ON

SOTF WITH Z1 T W/O SOTF = Sec (Manual close)T WITH SOTF = Sec

(Current flow )T WITH SOTF = Sec

SOTF WITH Z1B T W/O SOTF = Sec (Manual close)T WITH SOTF = Sec

(Current flow )T WITH SOTF= Sec

SOTF WITH Z2 T W/O SOTF = Sec (Manual close)T WITH SOTF = Sec

(Current flow )T WITH SOTF= Sec

SOTF WITH Z3 T W/O SOTF = Sec (Manual close)T WITH SOTF = Sec

(Current flow )T WITH SOTF = Sec

SOTF WITH Z4 T W/O SOTF = Sec (Manual close)T WITH SOTF = Sec

(Current flow )T WITH SOTF = Sec

Note:--LED: SOTF P/U.-BI: MANUAL CLOSED-BO: GENERAL TRIP OR SOTF.-MAKE FAULT WITH ALL -NO SOTF TRIP LED WILL GLOW . BUT ZONE TRIP TIME WILL BE BYPASSED)

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 34 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/SDisable the back up over current protection add ( 2601 )Disable the instantaneous high speed SOTF O/C add ( 2404 ) According to the specified zone that with instantaneous trip after SOTF is active add (1232 )For with zone Z1B Inject Z in this zone twice one with the activation of the binary inputs of C.B off and manual close and the other without them

Applied fault in zone

measured time (s)

with the activation of the binary inputs of C.B off and manual close

Z1B

without the activation of the binary inputs of C.B off and manual close

Z1B

with the activation of the binary inputs of C.B off and manual close

Z2

Z3

Z4

Z5

9.2- SOTF associated with back up over current2) SWITCH ON TO FAULT (SOTF)A) SOTF WITH BACKUP O/C: ADDRESS NO2615 O/C I> = ONADDRESS NO2625 O/C I>> = ONADDRESS NO2671 O/C Ip = ONADDRESS NO2601 SOTF WITH O/C = ON

AD 2625 SOTF WITH ( I ) T W/O SOTF = Sec

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 35 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/SI set = ………. (Manual close)T WITH SOTF = Sec

T set = ……… (Current flow )T WITH SOTF = Sec AD 2615 SOTF WITH ( I ) T W/O SOTF = Sec

I set = ………. (Manual close)T WITH SOTF = Sec

T set = ……… (Current flow )T WITH SOTF = Sec

AD 2617 SOTF WITH ( Ip) T W/O SOTF = Sec

I set = ……… (Manual close)T WITH SOTF = Sec

TMS = ……… (Current flow )T WITH SOTF = Sec

Note:--LED: SOTF P/U.-BI: MANUAL CLOSED.-MAKE FAULT WITH ALL TYPE OF O/C.

-CHECK THE SEAL-IN TIME SETTING FOR MANUAL CLOSE Disable the distance protection add ( 1201 )Disable the instantaneous high speed SOTF O/C add ( 2404 )Inject current more than the setting Iph >> pick up add ( 2610 ) twice one with the activation of the binary inputs of C.B off and manual close and the other without them. Repeat that withIph > pick up add ( 2620) and Iph > pick up add ( 2640)

Setting of all definite stages is 1A and 0.5 secSetting of inverse stage is 0.5 A and 0.1 sec long inverse

address Setting ( A )

Injected current (A)

measured time (msec)

Iph >> pickup add ( 2610)

with the activation of the binary inputs of C.B off and manual close

1 1.5

without the activation of the binary inputs of C.B off and manual close

1 1.5

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 36 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/SIph > pick up add ( 2620)

with the activation of the binary inputs of C.B off and manual close

1 1.5

without the activation of the binary inputs of C.B off and manual close

1 1.5

Ip > pick up add ( 2640)

with the activation of the binary inputs of C.B off and manual close

1 2

without the activation of the binary inputs of C.B off and manual close

1 2

Note : when you test any one of current stages you should raise the pick up setting of the others stages

10- Fuse failure monitoring 9. FUSE FAIL MONITOR:( 2910)

A)FUSE FAILURE MONITORING FUNCTION (3Io & 3Vo).……………

B)VOLTAGE ABSENT MONITORING FUNCTION (3 phase voltages).…….………

C)FUSE FAILURE MONITORING FUNCTION (3 phase voltages & Δ I )..……………

D)BROKEN CONDUCTOR………..……

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 37 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

Note:-- LED 14 = FUSE FAILURE=169, -LED: DISTANCE BLOCK. -INJECTION VOLTAGE LESS THAN(2913A)-MAX. VOLTAGE THRESHOLD V)>3-PHASES)-DISTANCE WILL BLOCK AFTER TIME (2916A) DELAY TIME VOLTAGE FAILURE SUPERVISION. -APPLY FAULT AT ANY ZONE (Z1….Z5)BEFORE TIME (2916A)THE RELAY SHOULD OPERATE.-2916A=0 SECS.-A) 1 PHASE SETTING = 30V, Vrn = 31v,Vyn=Vbn=60V, 3 PHASE CURRENT = 0.5A. SLOWLY DECREASE RN VOLTAGE & CHECK AT WHICH VOLTAGE FUSE FAIL LED APPEARS

406* موجود صفحه

3Vo>(AD2911A) و 3Io<(AD2912A)*شرطان البد من تحقيقها وهي اما . كما يلي الثاني نحقق واحد وننتظر

وبعد ذللك 3Io = 0 بقيمه صغيره ونحقن تيار متسوي نحقق 3Io- ضبط 1S 10 وبذلك سوف يعمل الريله بلوك بعد زمن الي اعلي من الضبط. 3Voنرفع

وبعد ذلك نحقناعلي من الضبط بقيمه صغيره ونحقق الفرق بالحقن 3Vo- ضبط 23Io 10. وبذلك سوف يعمل الريله بلوك زمن اكبر من الضبط وننزل بلحقن S

B) 3 PHASE SETTING = 5V, DISTANCE BLOCKED SPONTANEOUS INDICATION APPEARS ON FUSE FAILURE OPERATION. LED 14 = FUSE FAILURE=168, 2916A=0 SECS,

Vrn = Vyn=Vbn=6V, 3 PHASE CURRENT = 0.5A. SLOWLYDECREASE 3 PHASE VOLTAGE & CHECK AT WHICH VOLTAGE FUSE FAIL LED APPEARS

408* موجود صفحه في فيزه علي االقل اعلي*ويمكن في هذه الحاله معرفة ان الفيدر موصل اما بالتيار

. ونختبر هذه الحاله بضبط)AD1135( وذلك من CB او بوضعية ال ))AD1130Aمن وبعد ذلك نحقن تيار طبيعي لجميع الفيزات وجهد اعلي من))3V=5 )AD1130Aال

.الضبط وننزل بلجهد للفيزات الثالثه معا9. FUSE FAIL MONITOR:( 2910)

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 38 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/SC)FUSE FAILURE MONITORING FUNCTION (3 phase voltages & ΔI)

407* موجود صفحه ونحقن طبيعي وبعد ذلك نحقن جهد متساوي للفيزات)AD2915= OFF(*نعمل

ونحقن تيار للفيزات يحقق الفرق بينه وبين الحاله)AD2913A(اقل من الضبط)AD2914A (الطبيعيه .

ال* يكون ان تتحقق ان البد في Vشرطان التيارات بين الفرق و الضبط من اقل الثالثه الفيزات فيالضبط تحت والجهد طبيعي الجهد حالة

(AD2913A=5V) . (AD2914A=0.2A)

STAT1 STAT2

L1 I=1 V=30

L1 I=0.9 V=5

L2 I=1 V=30

L2 I=0.9 V=5

L3 I=1 V=30

L3 I=0.9 V=5

* اذا الفرق بين التيار في الحلتانن اقل من الضبط والجهد اقل من الضبط For voltage fail supervision add (2915) is with current supervisionNote: before starting the test you must specify Leds to failure voltage absent add (168)And V.T fuse failure alarm instantaneous add (170) and V.T fuse failure alarm> 10sec add (169) and distance is blocked add (3652) also you may specify a binary output for V.T fuse failure alarm> 10sec add (169) and distance is blocked add (3652) to be able measuring the time all of that can be done from the Masking in distance general and measurement supervision.10.1- For balanced loadIf the current is balanced in the 3 – phase and its amplitude is more than the setting maximum current threshold I< add (2912A) and the voltage difference in between any two phases is more than the setting minimum voltage threshold U> add (2911A), the fuse failure monitor FFM will appear instantaneously with distance blocking.

10.1- Fuse failure measurement add (2911A) Injected current in 3- phase = .2 A

minimum voltage threshold U> add (2911A) setting

Pick up voltage (V) FFM and distance block appear inst.R S T

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 39 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

30 V57.73 57.73

57.73 57.7357.73 57.73

10-2- For current less than the setting of Maximum current threshold I< add (2912A)

and zero voltage appear for more than the setting (add.2911) FFM will appear after

10 sec with distance blocking.

10.3- maximum voltage threshold U< ( 3 phase ) add (2913A)

-You can check that with applying the normal voltage 3 – phase and 3- phase current above the setting of open pole threshold add ( 1130A ) and the voltage is reduced in the 3- phase to less than the setting maximum voltage threshold U< ( 3 phase ) add (2913A) a voltage absent will appear after a time delay setting delay voltage failure supervision add (2916A). Injected current = .2 A

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 40 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

10.4 When VT mcb is off distance is blocked 8. VT MCB TRIP :(00361) power syst.Data2:-

ZONE 1: WITH OUT VT MCB TRIP : Distance trip ………….WITH VT MCB TRIP : Distance blocked (O/C trip) …..………

ZONE 1B WITH OUT VT MCB TRIP : Distance trip ………….WITH VT MCB TRIP : Distance blocked (O/C trip) …..………

ZONE 2: WITH OUT VT MCB TRIP : Distance trip ………….WITH VT MCB TRIP : Distance blocked (O/C trip) …..………

ZONE 3: WITH OUT VT MCB TRIP : Distance trip ………….WITH VT MCB TRIP : Distance blocked (O/C trip) …..………

ZONE 4: WITH OUT VT MCB TRIP : Distance trip ………….WITH VT MCB TRIP : Distance blocked (O/C trip) …..………

ZONE 5: WITH OUT VT MCB TRIP : Distance trip ………….WITH VT MCB TRIP : Distance blocked (O/C trip) …..………

Note:-

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 41 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S-LED: FAILURE FEEDER VT MCB TRIP.(AD3615)-BI: FAILURE FEEDER VT MCB TRIP.(AD3615) -LED: Distance Blook (AD3652)- MAKE FAULT WITH ALL ZONES WITH AND WITHOUT (BI)-DISTANCE PROTECTION WILL BLOCK.- MAKE O/C = ON

11- Fault locator

Line length = 6 Km x = 0.1526 Ω / km Q=900

R-N Y-N B-N R-Y Y-B B-RInjected impedance 1.526 1.526 1.526 1.526 1.526 1.526Relay reading (Km) km km km km km km

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 42 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

12- Memory test

12.1 Memory time measurement test

Sequence-1 Sequence-2 Sequence-3

Time =2sec Time was changed Time =0.5sec

Va Vb Vc Ia Ib Ic Va Vb Vc Ia Ib Ic Va Vb Vc Ia Ib Ic

57.73 57.73 57.73 0.2 0.2 0.2 0 0 0 0 0 0 0 0 0 1 1 1

180 60 300 0 -120 12 0 --- ---- -- -- -- --- --- --- --- 0 -120 120

Memory time measurement = sec

12.2 Memory voltage measurement test

Sequence-1 Sequence-2 Sequence-3

Voltage for this fault was changed Time =1sec Time =0.5sec

Va Vb Vc Ia Ib Ic Va Vb Vc Ia Ib Ic Va Vb Vc Ia Ib Ic

57.73 57.73 57.73 0.2 0.2 0.2 0 0 0 0 0 0 0 0 0 1 1 1

180 60 300 0 -120 12 0 --- ---- -- -- -- --- --- --- --- 0 -120 120

Memory voltage measurement = V

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 43 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

8- Back Up Over Current Protection: (Emergency)Note: while testing any stage of over current you have to raise the setting of the other stages.

8.1- Inverse over current 8.1.1- For IEC curve add (2660) is normal curve

Setting: Ip > pick up add (2640) = 0.5 A

Time R-Y Y-B B-R Calculated

time ( sec )Inj. Current = 2 Ip = 1A 1A 1A 1A 2.0 sec for

T= 0.2Measured time secInj. Current = 4 Ip = 2 A 2 A 2 A 2 A 0.5 sec for

T= 0.1Measured time secInj. Current = 6 Ip = 3 A 3 A 3 A 3 A 0.2 sec for

T= 0.05Measured time sec

T = 0.14TP / ( I/IP )0.02 – 1 (SEC), WHERE: T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 44 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

Setting: 3I0p pick up add (2650) = 0.5 A

R-N Y-N B-N Calculated time ( sec )

Inj. Current = 2 Ip = 1A 1A 1A 1A 2.0 sec for T= 0.2Measured time sec

Inj. Current = 4 Ip = 2 A 2 A 2 A 2 A 0.5 sec for T= 0.1Measured time sec

Inj. Current = 6 Ip = 3 A 3 A 3 A 3 A 0.2 sec for T= 0.05Measured time sec

T = 0.14TP / ( I/IP )0.02 – 1 (SEC), WHERE: T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT

8.1.2-For IEC curve add (2660) is very inverse curve

Setting: Ip > pick up add (2640) = 0.5 AR-Y Y-B B-R Calculated

time secInj. Current = 2 Ip = 1A 1A 1A 1A 2.7 sec for

T= 0.2Measured time secInj. Current = 4 Ip = 2 A 2 A 2 A 2 A 0.43 sec for

T= 0.1Measured time secInj. Current = 6 Ip = 3 A 3 A 3 A 3 A 0.135 sec for

T= 0.05Measured time sec

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 45 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

T = 13.5 TP / ( I/IP ) – 1 (SEC), WHERE: T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT

Setting: 3I0p pick up add (2650) = 0.5 AR-N Y-N B-N Calculated

time secInj. Current = 2 Ip = 1A 1A 1A 1A 2.7 sec for

T= 0.2Measured time secInj. Current = 4 Ip = 2 A 2 A 2 A 2 A 0.43 sec for

T= 0.1Measured time secInj. Current = 6 Ip = 3 A 3 A 3 A 3 A 0.135 sec for

T= 0.05Measured time sec

T = 13.5 TP / ( I/IP ) – 1 (SEC), WHERE: T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT

8.1.3- For IEC curve add (2660) is extremely curve

Setting: Ip > pick up add (2640) = 0.5 A Time

R-Y Y-B B-R Calculated time sec

Inj. Current = 2 Ip = 1A 1A 1A 1A 5.3 sec for T= 0.2Measured time sec

Inj. Current = 4 Ip = 2 A 2 A 2 A 2 A 0.53 sec for T= 0.1Measured time sec

Inj. Current = 6 Ip = 3 A 3 A 3 A 3 A 0.114 sec for T= 0.05Measured time sec

T = 80 TP / ( I/IP )2 – 1 (SEC), WHERE:

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 46 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT

Setting: 3I0p pick up add (2650) = 0.5 A Time

R-N Y-N B-N Calculated time sec

Inj. Current = 2 Ip = 1A 1A 1A 1A 5.3 sec for T= 0.2Measured time sec

Inj. Current = 4 Ip = 2 A 2 A 2 A 2 A 0.53 sec for T= 0.1Measured time sec

Inj. Current = 6 Ip = 3 A 3 A 3 A 3 A 0.114 sec for T= 0.05Measured time sec

T = 80 TP / ( I/IP )2 – 1 (SEC), WHERE: T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT

8.1.4- For IEC curve add (2660) is long inverse Setting: Ip > pick up add (2640) = 0.5 A Time

R-Y Y-B B-R Calculated time sec

Inj. Current = 2 Ip = 1A 1A 1A 1A 24sec for T= 0.2Measured time sec

Inj. Current = 4 Ip = 2 A 2 A 2 A 2 A 4 sec for T= 0.1Measured time sec

Inj. Current = 6 Ip = 3 A 3 A 3 A 3 A 1.2 sec for T= 0.05Measured time sec

T = 120TP / ( I/IP ) – 1 (SEC), WHERE: T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 47 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S IP : SETTING VALUE CURRENT I : FAULT CURRENT

Setting: 3I0p pick up add (2650) = 0.5 A Time

R-N Y-N B-N Calculated time sec

Inj. Current = 2 Ip = 1A 1A 1A 1A 24sec for T= 0.2Measured time sec

Inj. Current = 4 Ip = 2 A 2 A 2 A 2 A 4 sec for T= 0.1Measured time sec

Inj. Current = 6 Ip = 3 A 3 A 3 A 3 A 1.2 sec for T= 0.05Measured time sec

T = 120TP / ( I/IP ) – 1 (SEC), WHERE:T : TRIP TIMETP : SETTING VALUE TIME MULTPLIERIP : SETTING VALUE CURRENTI : FAULT CURRENT

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 48 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

8.2- low set stage I > Setting: Iph > pick up add (2620) = 1 A, T Iph > time delay add(2621) = 0.5 sec

Iph > Operating Time (s)for 1.5 A

PhasePick Up Drop Off

Setting Measured Calculated Measured Setting MeasuredR-Y 1

0.5Y-B 1B-R 1

Setting : 3I0 > pick up add (2622) = 1 A, T 3I0 > time delay add(2623) = 0.5 sec

8.3- high set stage I >>

Setting: Iph >> pick up add (2610) = 1 A, T Iph >> time delay add(2611) = 0.5 sec

Setting : 3I0 >> pick up add (2612) = 1 A, T 3I0 >> time delay add(2613) = 0.5 sec

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 49 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Injected current A Time secSetting Measured

R-N 1.50.5Y-N 1.5

B-N 1.5

Injected current A Time secSetting Measured

R-Y 1.50.5Y-B 1.5

B-R 1.5

Injected current A Time secSetting Measured

R-N 1.50.5Y-N 1.5

B-N 1.5

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

2.4- I- STUB

Note: you must specify a binary input active low for Enable I- STUB bus function add (7131) and binary output and led for O/C I- STUB TRIP add (7235).

Setting: Iph > STUB pick up add (2630) = 1 A, T Iph time delay add (2631) = 0.5 sec

Setting : 3I0 > STUB pick up add (2632) = 1 A, T 3I0 STUB time delay add(2633) = 0.5 sec

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 50 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Injected current A Time secSetting Measured

R-Y 1.50.5Y-B 1.5

B-R 1.5

Injected current A Time secSetting Measured

R-N 1.50.5Y-N 1.5

B-N 1.5

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

. Annunciation

.1. LEDsLEDS Description CheckedLED1 Pickup Distance Phase L1 ( Start ) LED2 Pickup Distance Phase L2 ( Start ) LED3 Pickup Distance Phase L3 ( Start ) LED4 Pickup Distance Neutral ( Start ) LED5 Zone 1 Trip ( Forward ) LED6 Zone 1B Trip ( Forward ) LED7 Zone 2 Trip ( Forward )

LED8 Zone 3 Trip ( Reverse ) LED9 Zone 4 Trip ( Forward ) LED10 Zone 5 Trip ( Forward ) LED11 LED12 LED13 LED14

5.2. Binary Out Puts

Annunciation Contact Description CheckedR1 Trip R2 Trip R3 Start R4 Start R5 Trip R6 Trip R7 Trip R8 Start R9 Watchdog

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 51 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report Customer : SEC – WRB Contract No.:

Consultant :

Substation : AL- BAWADI 110 / 13.8 K.V S/S

5.3. All Binary Inputs Checked.

siemens Client: SEC - CSD Consultant: Saudconsult

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

CSD – DAR ENGINEERING – AL FANAR Page 52 of 52 ENGR. / SAFWAT SAAD AHMED ( 0563683052 )