51
H V A C Heating Ventilating Air Conditioning

Presentation Cooling Load

Embed Size (px)

DESCRIPTION

A brief presentation on HVAC cooling load calculations

Citation preview

Page 1: Presentation Cooling Load

H V A CHeatingVentilatingAir Conditioning

Page 2: Presentation Cooling Load

Outline of Presentation Introduction Cooling Load Calculation

Step 1. Air Conditioning Design

Step 2. Basic Concept

Step 3. Outdoor Design Conditions

Step 4. Indoor Design Criteria

Step 5. Cooling Load Principles

Step 6. Computer Software's

Page 3: Presentation Cooling Load

Air Conditioning Design

Cooling load calculation for individual areas are required to

determine the peak air conditioning loads and the required supply air

for each area or zone of the building that is being designed.

Page 4: Presentation Cooling Load

Air Conditioning Design

Cooling load calculation should be made using data found in the ASHRAE Handbooks and by using format shown in the Design and Calculation topic.

The following information are which will make to generate the cooling load computations.

Orientation and location of the building, Types of operation. General construction of the space or building such as walls, roof, floor,

ceiling, etc. Door / Window types and quantities Machinery used or intended to be used within the space Lighting layouts Occupancy, that is the number of people and their degree of activity

within the given space Code and Standard requirements that deal with the cooling and heating

system for the building or space involved

Page 5: Presentation Cooling Load
Page 6: Presentation Cooling Load

Basic Concepts Thermal load

– The amount of heat that must be added or removed from the space to maintain the proper temperature in the space

When thermal loads push conditions outsider of the comfort range, HVAC systems are used to bring the thermal conditions back to comfort conditions

Page 7: Presentation Cooling Load

Basic Concepts Heat transfer mechanism

– Conduction– Convection– Radiation

Thermal properties of building materials– Overall thermal transmittance (U-value)– Thermal conductivity– Thermal capacity (specific heat)

Page 8: Presentation Cooling Load

Outdoor Design Conditions

They are used to calculate design space loads

Climatic design information– General info: e.g. latitude, longitude, altitude, atm. pressure– Outdoor design conditions

• Derived from statistical analysis of weather data• Typical data can be found in handbooks/databooks, such as

ASHRAE Fundamentals Handbooks

Page 9: Presentation Cooling Load

Outdoor Design Conditions

Climatic design conditions from ASHRAE– Previous data & method (before 1997)

• For Summer (Jun. to Sep.) & Winter (Dec, Jan, Feb)• Based on 1%, 2.5% & 5% nos. hours of occurrence

– New method (ASHRAE Fundamentals 2001):• Based on annual percentiles and cumulative frequency

of occurrence, e.g. 0.4%, 1%, 2%

Page 10: Presentation Cooling Load
Page 11: Presentation Cooling Load

Outdoor Design Conditions

Climatic design conditions (ASHRAE 2001):– Heating and wind design conditions

• Heating dry-bulb (DB) temp.• Extreme wind speed• Coldest month wind speed (WS) & mean coincident dry-

bulb temp. (MDB)• Mean wind speed (MWS) & prevailing wind direction

(PWD) to DB• Average of annual extreme max. & min. DB temp. &

standard deviations

Page 12: Presentation Cooling Load

Outdoor Design Conditions

Climatic design conditions (ASHRAE):– Cooling and dehumidification design conditions

• Cooling DB/MWB: Dry-bulb temp. (DB) + Mean coincident wet-bulb temp. (MWB)

• Evaporation WB/MDB: Web-bulb temp. (WB) + Mean coincident dry-bulb temp. (MDB)

• Dehumidification DP/MDB and HR: Dew-point temp. (DP) + MDB + Humidity ratio (HR)

• Mean daily (diurnal) range of dry-bulb temp.

Page 13: Presentation Cooling Load

Indoor Design CriteriaIndoor Design Criteria

Basic design parameters: (for thermal comfort)– Air temp. & air movement

• Typical: summer 24-26 oC; winter 21-23 oC• Air velocity: summer < 0.25 m/s; winter < 0.15 m/s

– Relative humidity• Summer: 40-50% (preferred), 30-65 (tolerable)• Winter: 25-30% (with humidifier); not specified (w/o

humidifier)– See also ASHRAE Standard 55-2004

• ASHRAE comfort zone

Page 14: Presentation Cooling Load

(*Source: ASHRAE Standard 55-2004)

Page 15: Presentation Cooling Load

Indoor Design CriteriaIndoor Design Criteria

Indoor air quality:– Air contaminants

• e.g. particulates, VOC, radon, bioeffluents– Outdoor ventilation rate provided

• ASHRAE Standard 62-2001– Air cleanliness (e.g. for processing)

Other design parameters:– Sound level– Pressure differential between the space & surroundings

(e.g. +ve to prevent infiltration)

Page 16: Presentation Cooling Load
Page 17: Presentation Cooling Load

Cooling Load PrinciplesCooling Load Principles

Page 18: Presentation Cooling Load

Cooling Load Principles

Terminology:– Space – a volume w/o a partition, or a partitioned room, or

group of rooms– Room – an enclosed space (a single load)– Zone – a space, or several rooms, or units of space having

some sort of coincident loads or similar operating characteristics

Page 19: Presentation Cooling Load

Cooling Load Principles

• Cooling load calculations• To determine volume flow rate of air system• To size the coil and HVAC&R equipment• To provide info for energy calculations/analysis

• Two categories:• External loads• Internal loads

Page 20: Presentation Cooling Load

Cooling Load Principles

• External loads• Heat gain through exterior walls and roofs• Solar heat gain through fenestrations (windows)• Conductive heat gain through fenestrations• Heat gain through partitions & interior doors• Infiltration of outdoor air

Page 21: Presentation Cooling Load

Convective and radiative heat in a conditioned space

Page 22: Presentation Cooling Load
Page 23: Presentation Cooling Load

Cooling Load Principles

• Internal loads• People• Electric lights• Equipment and appliances

• Sensible & latent cooling loads• Convert instantaneous heat gain into cooling load• Which components have only sensible loads?

Page 24: Presentation Cooling Load
Page 25: Presentation Cooling Load

[Source: ASHRAE Fundamentals Handbook 2001]

Page 26: Presentation Cooling Load

Cooling Load Principles

Instantaneous heat gain vs space cooling loads– They are NOT the same

Effect of heat storage– Night shutdown period

• HVAC is switched off. What happens to the space?

– Cool-down or warm-up period• When HVAC system begins to operate

– Conditioning period• Space air temperature within the limits

Page 27: Presentation Cooling Load

Thermal Storage Effect in Cooling Load from Lights

Page 28: Presentation Cooling Load
Page 29: Presentation Cooling Load

Cooling Load Principles

Load profile– Shows the variation of space load– Such as 24-hr cycle– What factors will affect load profile?– Useful for operation & energy analysis

Peak load and block load– Peak load = max. cooling load– Block load = sum of zone loads at a specific time

Page 30: Presentation Cooling Load

Block load and thermal zoning

Page 31: Presentation Cooling Load

Cooling Load Principles

Moisture transfer– Two paths:

• Moisture migrates in building envelope• Air leakage (infiltration or exfiltration)

– If slight RH variation is acceptable, then storage effect of moisture can be ignored• Latent heat gain = latent cooling load (instantaneously)

Page 32: Presentation Cooling Load

Cooling Load Components

• Cooling coil load consists of:• Space cooling load (sensible & latent)• Supply system heat gain (fan + air duct)• Return system heat gain (plenum + fan + air duct)• Load due to outdoor ventilation rates (or

ventilation load)

Page 33: Presentation Cooling Load

Cooling load

Cooling coil load

Page 34: Presentation Cooling Load
Page 35: Presentation Cooling Load
Page 36: Presentation Cooling Load

Cooling Load Components

• Space cooling load• To determine supply air flow rate & size of air

system, ducts, terminals, diffusers• It is a component of cooling coil load• Infiltration heat gain is an instant. cooling load

• Cooling coil load• To determine the size of cooling coil &

refrigeration system• Ventilation load is a coil load

Page 37: Presentation Cooling Load
Page 38: Presentation Cooling Load

“Carrier” E20-II Computer Program

Zone or Space

Input Sheet

System Input

Sheet

Page 39: Presentation Cooling Load

“Carrier” E20-II Computer Program

Zone Input Sheet :

Zone or Space Name General Zone Data Lighting Load Other Electrical Load People Miscellaneous Loads Infiltration Slab

Wall & Roof Data Wall & Roof Exposure Glass & External Shade Data Glass Exposure Partition Data

Page 40: Presentation Cooling Load
Page 41: Presentation Cooling Load
Page 42: Presentation Cooling Load

“Carrier” E20-II Computer Program

System Input Sheet : General System Data Sizing Specification Data Fan Data Thermostat Setpoint Factors Return Air Plenum Data System Arrangement Zone or Space Selection

Page 43: Presentation Cooling Load
Page 44: Presentation Cooling Load

Coefficient of Heat TransmissionU - value

I. Exterior Wall:

Resistance

“R” value

1. Outside Surface, @ 7.5 MPH wind - summer = 0.25

2. Cement Plaster, 3/4” thick = 0.15

3. Concrete block wall, 8” thick = 2.55

4. Cement Plaster, 3/4” thick = 0.15

5. Inside Surface, Still Air = 0.68

Total R-value = 3.78 Hr-Ft²-ºF/BTU

U-value = 1 / total R = 1 / 3.78 = 0.264 BTU / Hr - Ft² - ºF

Page 45: Presentation Cooling Load

Coefficient of Heat TransmissionU - value

II. Partition Wall (Type - 1):

Resistance

“R” value

1. Inside Surface, Still Air = 0.68

2. Cement Plaster, 3/4” thick = 0.15

3. Concrete block wall, 6” thick = 1.80

4. Cement Plaster, 3/4” thick = 0.15

5. Inside Surface, Still Air = 0.68

Total R-value = 3.46 Hr-Ft²-ºF/BTU

U-value = 1 / total R = 1 / 3.46 = 0.0289 BTU / Hr - Ft² - ºF

Page 46: Presentation Cooling Load

Coefficient of Heat TransmissionU - value

III. Partition Wall (Type - 2):

Resistance

“R” value

1. Inside Surface, Still Air = 0.68

2. Cement Plaster, 3/4” thick = 0.15

3. Concrete block wall, 6” thick = 1.80

4. Cement Mortar, 3/4” thick = 0.077

5. Ceramic Tile = 0.05

6. Inside Surface, Still Air = 0.68

Total R-value = 3.427 Hr-Ft²-ºF/BTU

U-value = 1 / total R = 1 / 3.427 = 0.29 BTU / Hr - Ft² - ºF

Page 47: Presentation Cooling Load

Coefficient of Heat TransmissionU - value

IV. Roof: Resistance

“R” value

1. Outside Surface, @ 7.5 MPH wind - summer = 0.25

2. Finish Floor Tile = 0.05

3. Cement Mortar, 1”thick, 120 ld./cu.ft. density = 0.10

4. Felt Water Proofing Membrane = 0.06

5. Glass Fiber organic bonded, 2” thick = 8.00

6. Roof Slab, 6” thick, 140 ld/Ft³ density = 0.51

7. Non-reflective air space = 1.00

8. Ceiling tile gypsum board, 5/8” thick = 0.56

9. Inside Surface, Still Air = 0.92

Total R-value = 11.45 Hr-Ft²-ºF/BTU

U-value = 1 / total R = 1 / 11.45 = 0.0873 BTU / Hr - Ft² - ºF

Page 48: Presentation Cooling Load

Coefficient of Heat TransmissionU - valueV. Glass:

Type: Clear Glass Single, 1/4” thick in aluminum framing

U = 1.04 BTU / Hr - Ft² - ºF

SC = 0.95 (Shading Coefficient factor)

VI. Wood Door:Type: Hollow flush door, 1-3/4” thick

U = 0.46 BTU / Hr - Ft² - ºF

VII. Steel Door:

Type: Solid fire rated with insulation, 1-3/4” thick

U = 0.29 BTU / Hr - Ft² - ºF

Page 49: Presentation Cooling Load

References

ASHRAE Handbook Fundamentals 2001– Chapter 26 – Ventilation and Infiltration– Chapter 27 – Climatic Design Information– Chapter 28 – Residential Cooling and

Heating Load Calculations– Chapter 29 – Nonresidential Cooling and

Heating Load Calculations– Chapter 31 – Energy Estimation and

Modeling Methods

Page 50: Presentation Cooling Load

References

Air Conditioning Principles and Systems by Edward G. Pita

Page 51: Presentation Cooling Load