15
1 ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. Cooling Load vs. Heat Gain Space Heat Gain The instantaneous rate at which heat enters into and/or is generated within a space at a given instant. Space Cooling Load The rate at which heat must be removed from the space to maintain a constant space air temperature. Heat Extraction The actual heat removed from the space taking account that space air temperature does not remain constant, but experiences minor, cyclic variations.

Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

Embed Size (px)

Citation preview

Page 1: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

1

ME 425 - Space Cooling Load1

ME 425

Space Cooling Load Calculations

Keith E. Elder, P.E.

Cooling Load vs. Heat Gain

Space Heat Gain� The instantaneous rate at which heat enters into and/or is

generated within a space at a given instant.

Space Cooling Load� The rate at which heat must be removed from the space to

maintain a constant space air temperature.

Heat Extraction� The actual heat removed from the space taking account

that space air temperature does not remain constant, but

experiences minor, cyclic variations.

Page 2: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

2

ME 425 - Space Cooling Load2

Solar Heat Gain (July)

0

50

100

150

200

250

300

1 2 3 4 5 6 7 8 9 10 11 1213 14 1516 17 18 1920 21 2223 24

Hour

Btu

/hr/

SF

West

East

North

Horzontal

South

Solar Cooling Load vs. Heat GainJuly oriented West – 48° N. Lat.

0

50

100

150

200

250

1 2 3 4 5 6 7 8 9 101112131415161718192021222324

Hour

Btu

/hr/

SF

Gain

Load

Page 3: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

3

ME 425 - Space Cooling Load3

Calculation Techniques

TETD/TA Method� Originally Developed by Willis Carrier

� Widely used but sources not well-documented

Transfer Function Method (TFM)� Rigorous & Complex

� Requires Computer

1989 CLTD/CLF Method� Hand Calculation Method

� Simplified Factors based on TFM (above)

Radiant Time Series (RTS) Method� Based on Heat Balance Method (exact solution)

� Requires Computer-Based Solution Techniques

CLTD/CLF Method Formulas

Glass cooling load is calculated:

q=A(SC)(SHGF)(CLF) for radiation

q=UA(CLTD) for conduction

Opaque surface cooling load is calculated:

q = UA(CLTD)

Internal loads are calculated:

qcooling load = qheat gain x CLF

Page 4: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

4

ME 425 - Space Cooling Load4

Opaque Surface Cooling Load

q = UA(CLTDcorrected )

� U = Assembly U-factor

� A = Opaque Surface Area

� CLTD = Cooling Load Temperature Difference

� Based on latitude

� Time-of-day

� Thermal storage in materials used

� R-value of component

� Presence of suspended ceiling (for roofs only)

Opaque Surface Calculation

Use Table 31 (89F26.36) for Wall Calculations

Use Table 29 (89F26.34) for Roof Calculations

� Select Wall/Roof Type

� Look up uncorrected CLTD

� Correct CLTD

CLTDcorrected = (CLTD + LM)k + (78 - troom) + (tm - 85)

LM = Latitude/Month Correction Factor (Table 32 - 89F26.37)

k = Color Correction (Dark = 1.0, Med = 0.83, Light = 0.65)

troom = design indoor space temperature

tm = average temperature on the design day

= max.outdoor temperature - (daily range) / 2

Page 5: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

5

ME 425 - Space Cooling Load5

Wall CLTD Tables

Roof CLTD Tables

Page 6: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

6

ME 425 - Space Cooling Load6

Opaque Adjustment Factors

ASHRAE Table 1B-Cooling

Daily Range

Page 7: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

7

ME 425 - Space Cooling Load7

Glass Cooling Load, Radiation

q=A(SC)(SHGF)(CLF)� A = glass area

� SC = Shading Coefficient

� SHGF = Solar Heat Gain Factor, tabulated by� Latitude

� Month

� Orientation

� CLF = Cooling Load Factor, tabulated by� Time-of-day

� Building Mass

� Floor Treatment (Optional)

Solar Heat Gain Factors(Table 34-89F26.40)

Page 8: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

8

ME 425 - Space Cooling Load8

Shading Coefficient

Shading Coefficients

(Table 11- ’97F29.25-26)

Page 9: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

9

ME 425 - Space Cooling Load9

Shading Coefficients (Table 19-05F31.48)(SC=1.15 x SHGC)

Cooling Load Factors (CLF) (Table 36-89F26.41)

Page 10: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

10

ME 425 - Space Cooling Load10

Cooling Load Factors (CLF) (Table 39-89F26.43)

Factors Affecting Reflectivity

All Solar radiation

values in all tables

and software have

a “surrounding

reflectivity”

assumption built in

to them.

Page 11: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

11

ME 425 - Space Cooling Load11

“Elliott Bay Phenomenon”

Infiltration Load

qsensible = 1.10 CFM ( tout - tin )

qlatent = 4840 CFM ( Wout - Win )

Requires

psychrometric

chart in most cases

Page 12: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

12

ME 425 - Space Cooling Load12

Internal Loads

qpeople-sensible = No. x Heat Gain x CLF

qpeople-latent = No. x Heat Gain

qlighting = Heat Gain x CLF

qequipment = Heat Gain x CLF

Use CLF = 1.0 unless HVAC runs 24 hours

Lighting Gain (Use Energy Code)

Police and fire stations8 1.20

� � Atria (atriums) 1.00

Assembly spaces9, auditoriums, gymnasia9, theaters 1.00

Group R-1 common areas 1.00

Process plants 1.00

Restaurants/bars5 1.00

� � Locker and/or shower facilities 0.80

� � Warehouses11, storage areas 0.50

� � Aircraft storage hangars 0.40

� � Parking garages See Section

1532

� � Plans Submitted for Common Areas Only

7

Main floor building lobbies3 (except mall concourses) 1.20

Common areas, corridors, toilet facilities and washrooms,

elevator lobbies 0.80

TABLE 15-1 Unit Lighting Power Allowance (LPA)

�Use1 LPA

2� (W/ft

2)

Painting, welding, carpentry, machine shops 2.30

� � Barber shops, beauty shops 2.00

Hotel banquet/conference/exhibition hall3 ,4

2.00

Laboratories 2.00

� � Aircraft repair hangars 1.50

Cafeterias, fast food establishments5 1.50

Factories, workshops, handling areas 1.50

Gas stations, auto repair shops6 1.50

Institutions 1.50

Libraries5 1.50

Nursing homes and hotel/motel guest rooms 1.50

Retail10

, retail banking 1.50

Wholesale stores (pallet rack shelving) 1.50

� � Mall concourses 1.40

� � School buildings (Group E occupancy only, school

classrooms, day care centers 1.35

� � Laundries 1.30

� � Office buildings, office/administrative areas in facilities of

other use types (including but not limited to schools, hospitals,

institutions, museums, banks, churches)5,7,11

1.20

Page 13: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

13

ME 425 - Space Cooling Load13

Gain vs. Load - Lighting Example

Lighting - Load Not in Space

Page 14: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

14

ME 425 - Space Cooling Load14

People Heat Gain

Office Equipment Heat Gain

Page 15: Space Cooling Load Calculations - Ductwork Installation Load-2009.pdf · ME 425 - Space Cooling Load 1 ME 425 Space Cooling Load Calculations Keith E. Elder, P.E. ... Use CLF = 1.0

15

ME 425 - Space Cooling Load15

Projected Office Equip. Wattage

In-Class Cooling Load Exercise

What is the July cooling load at 5:00 pm for the Seattle office space described in the heat loss example. Assume an indoor design condition of 78oF and 40% Relative Humidity.

50’

12’

10’

12’

N