Upload
rajeev-valunjkar
View
227
Download
0
Tags:
Embed Size (px)
DESCRIPTION
1
Citation preview
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 1/62
Practical Steps to Arc Flash Calculations Electrical engineers typically perform the calculations, since an understanding of the short
circuit behavior of power systems is necessary.
If the available short circuit values at various equipment and the associated fault clearing times
are known, then a trained person can also perform arc flash hazard assessment (A!" by using
the appropriate #$A %&E tables.
!owever, this approach has significant drawbacks due to gross oversimplification inherent in
this simplified approach.
or larger power systems with multiple sources and possible operating conditions, it is
preferable to do a detailed engineering analysis that can determine the worst'case arc flash
hazard conditions that can occur. As will be seen, this will not necessarily be the conditions with
the highest fault current.he following steps are involved in detailed arc flash study. $rior to beginning the data
collection, it should be determined and agreed upon which method of calculation will be used.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 2/62
). Identify all locations*equipment for A! assessment.
+. ata -ollection
a. Equipment data for short circuit analysis/ voltage, size (01A*k1A", impedance, 2*3 ratio,
etc.
b. Equipment data for protective device characteristics/ type of device, e4isting settings for
relays, breakers and trip units, rating amps, time'current curves, total clearing time.
c. Equipment data for arc flash study/ type of equipment, type of enclosure (open air, bo4,
etc.", gap between conductors, grounding type, number of phases, and appro4imate working
distance for the equipment.
d.All power system equipment, their e4isting connections and possible alternative
connections.
5. $repare a single'line diagram of the system.
6. 7hort circuit study
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 3/62
a. -alculate bolted (available" three'phase fault current for each equipment.
b. -alculate every contributing branch*load currents.
8. -alculate estimated arc current
a. -alculate arc current using empirical formula (#$A, IEEE, or other standards".
b. -alculate branch currents contributing to the arc current from every branch.
9.Estimate arcing time from the protective device characteristics and the contributing arccurrent passing through this device for every branch that significantly contributes to the arc
fault.
%. Estimate the incident energy for the equipment at the given working distances.
:. etermine the hazard*risk category (!3-" for the estimated incident energy level.
;. Estimate the flash protection boundary for the equipment.
)&. ocument the assessment in reports, one'line diagrams and with appropriate labels on the
equipment.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 4/62
Step 1 – Identification of Locations/Equipment for AFH
Arc flash hazard assessment is needed only for those locations where workers are e4posed to therisk. herefore, it may not be necessary to perform the assessment for each and every piece of
equipment in the power system.
$anels and switchboards rated +&: volts or less can generally be ignored if the service
transformer is less than )+8 k1A. he arc will not likely be sustainable at lower voltages and
smaller available fault currents.
All panels with breakers and fuses should be included in the assessment if there is potential for
significant arc flash in<ury. Incidents may occur when operating the breakers or fused
disconnects, even with the door closed.
=ou can consult the e4isting one'line diagrams for determining the equipment that require
assessment. If such a diagram does not e4ist, it should be constructed .
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 5/62
Step 2 – Data Collection
Equipment Data for Short Circuit Analysis
Although some equipment may not require arc flash hazard assessment, data about this
equipment may be required in a short circuit analysis.
ypical data required for the study is given in !andout.
7hort circuit analysis requires data on utility, generators, transformers, cables, transmission
lines, motors, etc.
he name'plate of the equipment can provide most of the necessary data. In the absence of
particular data, it may be possible to obtain the information from the manufacturers or their
representatives. Also, typical data can be assumed by referring to books and product literature.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 6/62
Chapter 4. Practical Steps to Arc-flash Calculations
Typical data needed for equipment for short circuit analysis
escription ata
Equipment ype
1oltage
01A*>1A
Impedance
2*3 3atio
$hases*connection
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 7/62
Equipment Data for Protective Device Characteristics
?btain data on the various protective devices that will determine the arcing time. able
shows what kind of information is required. his data may be obtained from e4istingdrawings, relay calibration data, coordination studies and from field inspection. ?btain
from the manufacturers the time'current characteristics (--" for these devices.
Determine whether the protective device is reliable enough . his can be done by
asking the operators, or by testing if necessary. 7ome companies have periodic relay
testing programs. If the protective device is deteriorating, the data provided by themanufacturer may not be applicable. If the fault interruption does not occur as e4pected
then the arc flash assessment cannot be accurate. It will be necessary to repair or replace
such equipment.
Table Protective device data to gather
$rotective ata to @ather evice
3elay
ype, - ratio, pickup (tap" setting, delay type (curve" and setting (time
dial".
use ype, amp rating, voltage, peak let'through current.
reaker ype, fault clearing time, pickup setting, delay curve, delay setting.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 8/62
Equipment Data For Arc Flash Study
epending on the method of calculation selected, the following equipment data is
required for an arc flash hazard study.
Table 4.3: Equipment data for A! stud"
escription ata
ype of enclosure (open air, bo4, etc."
@ap between e4posed conductorsB
@rounding typeB
$hases*-onnection
Corking istance
ata required for IEEE )8:6 method has been marked with D B D. he working distance is an appro4imate
measure that should be based on the type of work being performed and the type of equipment. It may vary
based on manufacturers design and work practices. Corking distances should be documented for various work
practices and equipment as part of a complete safety program.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 9/62
Determine All Possile !peratin" Conditions0ake note of all possible connections (system operating modes" using diagrams and tables. he
circuit breaker*switch*fuse status may change during abnormal operations. $arallel feeds can
greatly increase the available fault current and resulting arc flash hazard.
he contribution of connected motors to the fault will increase the hazard as well. Assessment
should include both the normal operating condition as well as the worst possible arc flash
scenario.
In general, the higher the available fault current, the greater the arc flash energy. !owever, since
arc flash energy is a function of the arc duration as well as the arc current, it cannot be
automatically assumed that the highest fault current will always be the worst'case A!.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 10/62
E#ample wor$sheet for connection scenarios
Equipment #ormal -o'generation 0aintenance 0aintenance
-onnected ?peration 7chedule A 7chedule
Ftility ?# ?# ? ?#
@enerator ? ?# ?# ?
0otor ?# ?# ?# ?
0'+ ?# ?# ?# ?#
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 11/62
Step 3 – repare sin!le"line dia!ram of t#e s$stem
7ingle'line (one'line" diagrams are powerful tools for documenting and communicatinginformation about power systems. hey are easy to read, show the connections and status of
equipment and contain data required for analysis.
he results of analysis such as short circuit studies and arc flash hazard assessment can easily be
placed on the diagrams. 0ost e4isting plants should already have one'line diagrams. heaccuracy of these should be verified before commencing the assessment. If a new diagram is
required, it can be prepared using the data collected.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 12/62
Step % – S#ort Circuit Stud$
?nly 5'phase faults are considered when performing A!. his may seem odd, but it isconsistent with the recommendations in IEEE')8:6 and #$A'%&E. here are several reasons
for this. ?ne is that 5'phase faults generally give the highest possible short circuit energy and
represent a worst'case.
Another important reason is that e4perience has shown that arcing faults in equipment or air that
begin as line'to'ground faults, can escalate very rapidly into 5'phase faults as the air ionizesacross phases.
his progression from single'phase to 5'phase happens generally within a few cycles. ecause
of this, most testing done on arc flash energy has been based on 5'phase faults. or singe'phase
systems, IEEE')8:6 recommends that calculations be done for an equivalent 5'phase system
and states that this will yield conservative results.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 13/62
ased on the data collected for various system operating modes, arc flash calculations should be
performed for each possible case. raditionally, when performing short circuit calculations todetermine ma4imum short circuit current, e4tremely conservative estimates and assumptions are
used. his makes sense if the goal is to determine ma4imum breaker or equipment duties.
!owever, for A!, using overly conservative short circuit data can yield non'conservative
results since a very high fault current may produce a very short arc duration due to the operation
of instantaneous trip elements.
he highest fault current does not necessarily imply the highest possible arc flash hazard
because the incident energy is a function of arcing time, which may be an inversely proportional
function of the arcing current.
or A! determinations, short circuit calculations should be conservative, but not overly
conservative.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 14/62
Calculate #olted Fault Current-alculate the 3%phase bolted fault current in s"mmetrical rms amperes for all buses or
equipment, and for each possible operating mode. -heck for the following while considering
various interconnections at the concerned bus or equipment
• 0ultiple utility sources that may be switched in or out of service.
• 0ultiple local generator sources that are operated in parallel or isolated depending on thesystem configuration.
• Emergency operating conditions. his may be with only small backup generators.
• 0aintenance conditions where short circuit currents are low but arc duration may be long.
•
$arallel feeds to 7witchgear or 0--s.• ie breakers which can be operated open or closed.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 15/62
• Garge motors or process sections not in operation.
A short circuit*arc flash case should be developed for each operating mode. his can be a
daunting task for most software or spreadsheet calculators. In commercial software 7cenario
0anager provides a simple and easy method to document and analyze each operating mode for
quick repeatable analysis.
!and calculations and spreadsheet calculators may typically neglect the transient short circuit
values that last for a few cycles. hese are higher than the sustained short circuit values. he
generator and motor transients during the fault contribute to the arc fault. o account for these
• Fse sub'transient and transient impedances of the generators to find the bolted fault current
if the arcing time is small. or long arcing times, use the sustained
short circuit values. his suggests an iterative process, since the arcing time depends upon
the fault current passing through the upstream protective device.
• Include contribution of connected motors in the calculations.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 16/62
4.4.$ Calculate Contriutin" #ranch Currents
-ontributing branch currents to faults are calculated to estimate the contributing arc currents by
various branches, which again, are used to determine the trip times of the protective devices on
the branches.
he protective device upstream to the fault sees only the current passing through it. he fault
current may be greater than the current passing through the upstream protective device.
herefore, the total fault current cannot be used to find the trip time unless other branch currents
are significantly smaller than the upstream current.
7imilarly, for parallel feeds, the contributing currents from each feed must be calculated to
determine the trip time.
Special care is needed when computing branch currents through transformers . his could be
one of the common source of errors since the branch current needs to be ad<usted by the
transformation ratio. Chen a fault occurs on the low voltage side of a transformer, the protective
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 17/62
device on the high voltage side of the transformer sees a smaller current due to the transformer
turns ratio.Step & – Determine E'pected Arc Current
Calculate Arc Current
-alculate arc current for every required equipment or bus using one of the empirical formulae
recognized by the #$A'%&E (#$A, IEEE, or other standards". he arc current may be a
function of the bolted fault current, the open circuit voltage, the type of enclosure and the gap between conductors depending on the calculation method selected.
Consider a ran"e of Arc Current
Tolerance due to %andom &ariation ased on 'EEE-()*4
o cover the variance that can occur in arcs, IEEE procedure suggests the following.). -alculate the ma4imum e4pected bolted fault condition.
+. -alculate the minimum e4pected bolted fault condition. he minimum bolted fault current
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 18/62
could be a light load condition with many motor loads or generators not running.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 19/62
5. -alculate the arcing current at )&&H of IEEE )8:6 estimate for the above two conditions.
6. -alculate the arcing current at :8H of IEEE )8:6 estimate for the two above conditions.
8. At these four arcing currents calculate the arc flash incident energy and use the highest of
the incident energies to select $$E.
he minimum fault current could take longer to clear and could result in a higher arc flash
incident energy level than the ma4imum'fault current condition.
he fault current in the main fault current source should be determined since the current in
this device may determine the fault clearing time for the ma<or portion of the arc flash
incident energy.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 20/62
Table 4.& 'ensitivit" of arc current to gap for (EEE )*+4 method
1oltage Enclosure 7ensitivity (H * mm"
G1 Ao4 ').&H
G1 ?pen '&.%H
01 ' #ot 3equired
E4ample
he e4act gap between conductors for various devices are not known. or low voltage
bo4, it was generally observed that the gap ranged from +8mm to 6&mm with an average
of 5+mm. here are two ways to deal with this. he first method is to obtain two estimates
for arc current, one for the least gap and the other for the highest gap. he second method
is to ad<ust the IEEE estimate for the average gap using the sensitivity shown in able 6.9.
Get us say that the arc current for 5+mm gap was found to be 6& kA.Arc current for min. gap Iarc B ()JsensitivityB(0in. gap K Average gap"*)&&"
6& B ()').&B(+8'5+"*)&&"
6+.: kA.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 21/62
Arc current for ma4. gap Iarc B ()JsensitivityB(0a4. gap K Average gap"*)&&"
6& B ()').&B(6&'5+"*)&&"
59.: kA.
If the variation in gap is small, then e4tensive analysis need not be carried out.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 22/62
+imits for Arc Currents
After calculating the range of possible arc current, it is necessary to check whether thecalculated values are within the practical range. -heck for the following
• Fpper limit It is not possible for the arc current to be greater than the bolted fault
current because of the additional impedance of the arc. herefore, after applying
ad<ustments for random variations and for gap variations, if the upper limit of the
range of arc current is greater than the bolted fault current, then discard that value andtake the bolted fault current as the upper limit.
• Gower Gimit Arcs do not sustain when the current is very low. or 6:&'volt systems,
the industry accepted minimum level for a sustaining arcing fault current is 5:H of the available three'phase fault current+). est data accompanying IEEE 7tandard )8:6shows arc sustaining for &.+ seconds at &.+&: k1 at a current of +)H of bolted fault
current. able 6.% shows the minimum arc current as a percentage of bolted faultcurrent obtained during tests. he lower limit of arc current is not yet clear. Fntilfurther information is obtained, it may be reasonable to use able 6.% as the cut'off minimum arc current as a percentage of the bolted fault current.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 23/62
Table 4.,: Ad-usted minimum arc current as a percentage of bolted fault currents.
0in 0easured Iarc H of 1oltage (k1" Ibf
&.+*&.+8 +)H
&.6*&.6: +)H
&.9 +:H
+.5 8)H
6.)9 96H
)5.: :6H
Bhe ad<ustment is based on ma4imum measured values taken normalized to the bolted fault current.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 24/62
Calculate #ranch Currents Contriutin" to the Arc Current
his is done using the branch current contributions to the bolted fault current obtained. o
calculate the contributing currents to the arc fault, use equation
I4,arc I4, B Iarc * I
Chere,
I4,arc -urrent through branch 4 for arc fault
I4, -urrent through branch 4 for bolted fault
I olted fault current.
Arc currents have been observed to be non'sinusoidal due to the non'linear nature of the
arc resistance.he harmonic contribution of different branches may vary, however, the fundamental
component can be appro4imated using the method describe above. It has been observed
that although the voltage waveform is highly distorted, the arc current however has low
harmonic content. herefore the linear relation is a reasonable appro4imation.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 25/62
Step ( – Determine Arcin! )ime
Estimate arcing time from the protective device characteristics and the contributing arc current
passing through this device for every branch that significantly contributes to the arc fault. 7incewe are considering a range of arc currents instead of a single value, we need to determine the
trip time for each arc current value K the upper bound, the lower bound and the value calculated
from #$A %&E or IEEE )8:6 equations.
he trip time of a protective device is obtained from its time 'current characteristics (--".
Information may be obtained from manufacturers in the form of -- plots or equations.
3elays and circuit breaker trip units usually have ad<ustable time delay for tripping operation.
he delay time may depend upon the magnitude of the current sensed by the device. ime
delays are provided to coordinate the tripping of the relays so that ma4imum reliability of supply
may be maintained.
7ince arc flash hazard can be minimized by reducing the duration of faults, it is beneficial tohave a good understanding of protective device coordination.
ypically, for lower fault currents, the trip time may be high due to the inverse time'current
relationship of the --.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 26/62
or higher currents, the arcing'fault current may be greater than the instantaneous pickup of the
protective device, and therefore the device may trip at the minimum response time.
or fault currents near the transition from the inverse'time curve to the instantaneous trip, a
small change in arcing current value can cause a very large difference in calculated arc energy.
etermining the trip time manually requires visual inspection of each time'current curve to
determine the operating time for a particular fault current. his also requires ad<ustment of the
fault currents to reflect the transformation ratio of any transformers involved. his must be done
before obtaining the trip times of the protective devices across the transformer.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 27/62
Evaluate Protective Device Performance
7pecial attention is required when the calculated branch currents seen by any protectivedevice is close to pickup current of the device.
If the branch current is lower than the pickup then the device will not trip. ypically,
protective devices are coordinated such that the downstream device trips before upstream
device for the same current (or the equivalent current converted to the same voltage base".
!owever in the absence of proper coordination, if the downstream device does not trip at
a given fault current, then the upstream device may trip.
herefore, it is necessary to identify which device will interrupt the arc fault. 7elective
coordination of devices should be ma4imized by ad<ustment of trip unit settings, if
possible.
his will not only improve the continuity of supply but will also provide the opportunity
to lower arc flash hazard by reducing the arcing time (although selectivity and arc flash
reduction are often conflicting goals".
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 28/62
he arcing fault currents close to pickup current of instantaneous trip function should be
e4amined closely. If the calculated fault current value is within the tolerance band of the
pickup, then there is a likelihood of the device not tripping at the e4pected instantaneous
value.
In such cases, if the time'overcurrent function e4ists in the device then the trip time for the
time'overcurrent function should be taken for arc flash calculations.
It is also important to realize that any changes to the protective device settings can have a
ma<or influence on the arc energy. If device or setting changes are made, the arc flash
calculations must be re'checked and appropriate changes made if necessary.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 29/62
Trip time for multiple feeds
Chen a bus is fed from multiple sources, as shown in igure 6.5, a fault at the bus may
cause a series of breaker operations. he actual fault current will change as the breakers
open, since the sources of power will be sequentially removed from the faulted bus. 7incethe current seen by the relays will change over time, further calculations are required to
determine the actual trip time for each breaker. Ce cannot simply obtain the trip time
corresponding to a single branch current by looking at the -- data. $rotective devices with
time'overcurrent functions typically operate like an integrating device. hat means, the
overcurrent or its function is integrated or LaddedL over time until the sum reaches a
predetermined trip value. his is when the relay trips. or details on how a relay or fuseintegrates the function of current, refer to literature on operation of protective devices.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 30/62
Step * – Determine Incident Ener!$
Estimate the incident energy for the equipment at the given working distances. he incidentenergy is a function of the arc current, arcing time, the enclosure type and the distance from the
arc. IEEE )8:6 also includes the gap between electrodes as a parameter. #$A %&E Anne4
method uses the bolted fault current rather than the arc currents.
In steps 8 and 9, various scenarios were considered. Fsing the selected method, calculate the
incident energy for each scenario. 0ake sure the following cases are evaluated
). Arc current based on IEEE')8:6 standard and its associated trip time.
+. Gower bound of arc current due to random variations, and its associated trip time.
5. Fpper bound of arc current due to random variations and its associated trip time.
6. 0ultiple feed scenarios
a. Evaluate incident energy for each type of possible connections as noted in 7tep 6.
b. Evaluate incident energy for arc current changing through series of breaker operations, as
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 31/62
described in step 9.
4.,.( Tolerance of Calculated 'ncident Ener"y
he selected method may have tolerance about the calculated value of incident energy because
of the random nature of arcs. ifferent calculation methods will generally yield different
results. or IEEE )8:6 equations use able 6.)& to find a more conservative estimate that
accounts for the randomness of arcs.
he ma4imum tolerance should be added to the calculated incident energy. his procedure issuggested to minimize risk to workers since test data has been found to have greater incident
energy than that yielded by IEEE )8:6 formula.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 32/62
Tolerances for (EEE )*+4 incident energ" estimates.
1oltage* ype of Enclosure0a4imum olerance (H of -alculated Incident Energy"
or ad<usted arc current a or IEEE )8:6 arc current b
Gow voltage arc in open air 99H :8H
Gow voltage arc in bo4 95H 96H
0edium voltage arc in open ;5H 86H
air
0edium voltage arc in bo4 8&H 8+H
able shows incident energy tolerances for two different kinds of arc currents. It can be seen
that there is not much difference in incident energy for arc in bo4 whether the e4act IEEE )8:6
arc current or the arc currents ad<usted for random variations is used. he choice of arcingcurrent significantly affects only the arcing time, which in turn affects the incident energy. rom
the table it can be observed that the calculated incident energy is higher than ma4imum
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 33/62
measured values for low voltage open air. !owever, for other cases, the estimate may be much
lower than the ma4imum measured values.Step + – Determine Ha,ard/-is. Cate!or$
!azard*risk category (!3-" is specified as a number representing the level of danger, which
depends upon the incident energy. -ategory & represents little or no risk, whereas category 6 is
the most dangerous.
!a/ard0ris$ classification as per 1PA ,2E
ategor" Energ" 4evel
& M + cal*cm+
) 8 cal*cm+
+ : cal*cm+
5 +8 cal*cm+
6 6& cal*cm+
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 34/62
Corkers should prepare according to the risk category before commencing work or inspection
near e4posed, live conductors. ocumentation and warning labels are also required. Althoughthe incident energy itself may provide a more accurate picture of the risk, the scale of & to 6 for
the risk category may convey more meaningful information to most workers. Employers are
required to perform a complete hazard assessment prior to commencing any work near e4posed
conductors.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 35/62
Step – Determine Flas# rotection 0oundar$
he flash protection boundary is the distance at which persons e4posed to arc flash,
without appropriate $$E, will obtain second degree burns that are curable. he flash
protection boundary is a function of the arc flash incident energy. he higher the arc flash
energy, the farther away the boundary will be. -alculate the flash protection boundary
using the equation prescribed by the standard being followed. Fse the highest incident
energy calculated in step %, after accounting for all the system connections and variations
due to randomness of arcs. Fse the equation (6.+" to determine the flash protection
boundary. his is applicable for both IEEE 7td )8:6 and proposed #$A %&E (+&&6".
1
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 36/62
E x
DB =
D
EB
where,
distance of the boundary from the arcing point (see note"
working distance (see note"
E ma4imum incident energy at working distance in cal*cm+
E incident energy at boundary, usually ).+ cal*cm+ for arcing time N &.)s. 4
distance e4ponent factor (see able 6.)+"
1ote istances and must both be in the same units. hey can be e4pressed in inches
or mm.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 37/62
Table 4.)5: Distance e#ponent 6#6
Enclosure ype IEEE )8:6 #$A %&E K #$A %&E K +&&5
+&&&?pen air (& K &.9 + ).;8;5
k1"
?pen air (N &.9 k1" + + +
7witchgear ).6%5
0-- and $anels ).96)
-able +o4 (& K &.9 k1" ).6%5:
o4 (M ) k1" ).9
o4 (N 8 k1" &.%%
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 38/62
Step 1 – Document )#e Arc Flas# Ha,ard Assessment
he arc flash hazard assessment should be documented in detailed reports, one'line diagramsand on the equipment. $rovide as much detail as possible. ocumentation has the following
advantages
). Easy for workers to access the necessary details and drawings. his is necessary for safety
planning.
+. -ompliance with ?7!A and #$A.5. Easy to implement changes in assessment when power system changes are made or when
the standards are revised.
6. In case of arc flash related in<uries, investigation is facilitated by documents. Gack of
assessment documents may result in penalty to the company.
Easy$ower software provides a detailed data repository and self documents the required shortcircuit, protective device coordination, and arc flash analyses for all system modes of operation.
A single source program to maintain compliance with the many aspects of #$A'%&E arc flash
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 39/62
requirements can greatly simplify a safety program.
4.(.( Documentation in %eports
he assessment report should include the following details
). #ame of person performing the assessment.
+. ate of assessment.
5. All data collected and used in the assessment, including protective device settings.
6. Assumptions used in the absence of data.
8. 0ethod of hazard assessment used K the standard and the revision year.
9. If software was used, the name of the software and the version.
%. he results K incident energy, hazard*risk category and flash protection boundary for everyequipment.
:. If various modes of operation are possible, document assessment for each mode.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 40/62
he assessment report should be available to all concerned persons. 7ome of these may be
). 7afety coordinator.
+. 7afety division*department.
5. oremen and electricians.
6. Electrical engineer.
8. Affiliated contractors.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 41/62
Documentation in !ne-+ine Dia"rams
he following steps are recommended for a practical documentation of arc flash data on one'
line diagrams
). $lace the arc flash hazard assessment results on every equipment that poses a risk.
+. 7pecify the flash protection boundary, also known as arc flash boundary (A".
5. 7pecify the incident energy at the estimated working distance in the standard unit, for e4amplein calories per cm+. 7pecify the estimated working distance as well. Corkers should check whether the working distance will be maintained while working on live equipment. If closer working distances are required, then it may be necessary to revise the assessment to reflecttrue working condition. he closer the distance the more the incident energy, and higher therisk.
6. 7pecify the hazard risk category at the estimated working distance.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 42/62
8. or breakers and fuses, specify the values for both the line side and the load side. 3emember
that a fault on the load side of the protective device would be interrupted by that device itself.
!owever, should a fault occur at the line side of the protective device, then the fault would be
interrupted by the upstream protective device. his would normally have higher incidentenergy because of longer tripping time. herefore it is important to evaluate and document arc
flash energies for the line side of protective device, and communicate this with workers.
9. Fse arrows to provide a clear indication of the load side and line side on the equipment if the
arc flash values are different.
%. In any equipment, if different parts have different incident energy values, the worst caseshould be highlighted or mentioned first in the list.
:.0ention the protective device that limits the incident energy. If that device is at some
distance, provide information on its location. It is also suggested that the settings be
documented.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 43/62
;. If there are various possible sources or interconnections, clearly mention in the one'line,
which source is connected and*or which breaker is open or closed. Corkers should first
determine if the assumed condition in the diagram reflects the condition of the power system
at the time of work. If the system conditions are different from those for which the assessmentwas performed, it is necessary to revise the evaluation
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 44/62
4.(. Documentation on Equipment
hree types of documentation are recommended for arc flash hazard assessment results
placed on the equipment
).Carning labels with arc flash values $ermanent stickers with a warning sign of
adequate size. he label should be located in a place that is easily visible and readable
from some distance. he flash protection boundary and its units, the incident energy at
the estimated working distance and its corresponding risk category number must be
clearly printed on the label. Additional information that is useful for future revisions arethe date of assessment, the method of calculation, and the software name and version.
Carning labels should also be placed <ust outside the flash protection boundary, so that
workers may see it and prepare accordingly before they enter the hazardous area.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 45/62
E#ample of arc flash warning label
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 46/62
+. Arc flash assessment results, in the form of a table and a small one'line diagram as
described in the previous section, should be placed on the equipment at a spot which
workers can easily access.
5. Garge multi'section equipment may be labeled at various sections of the equipment.
his facilitates hazard communications.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 47/62
Arc Flash /a0ard Pro"ram
Electrical Safet$ ro!ram
A safety program is an organized effort to reduce in<uries. Any electrical safety program should be a subset of an overall site safety program.O or these programs to be effective, it is necessaryfor safety professionals and technical professionals to collaborate.
)rainin!
raining must provide people the knowledge and understanding of the e4istence, nature, causes
and methods to prevent electrical hazards. he training should also include the selection and use
of appropriate $$E.
As part of regular electrical safety training it would be beneficial to include the following arc
flash related topics. 7pecial arc flash hazard sessions are recommended for introductory training
e4ercises.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 48/62
( A1areness
b. E4istence of the arc flash hazard Arc flash accidents are not as common as electrical shock.
herefore, many are not aware of the hazard. rainers and managers need to place adequateeffort in trying to convince the workers that arc flash hazard is indeed something to take
seriously.
c. -auses >nowing the causes helps immensely in avoiding the hazard.
d. #ature of arcs his can relate to the degree of potential damage and possible ways to reduce
hazard.
e. $ossible in<uries*damage indings and statistics from various studies and reported incidents
reveal the gravity of the hazard.
f. !istorical cases Giterature on arc flash incidents can be found in many documents. 3eview of
these cases is illuminating and convincing and is likely to influence workers to consider
taking measures to avoid arc flash in<uries. the hazard for the electrical worker, managers or
the responsible persons should be included in the training.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 49/62
Standards and Codes
7tandards and codes not only provide information on what employers and workers are required
to do, but also suggest solutions*methodology. In following the standards and codes,PcomplianceO should not be the only motive. he following provide the standards and codes.
a. #$A %&E
b. ?7!A
2nderstandin" of Arc Flash 3uantities
Corkers are e4pected to read signs*labels, drawings and tables to understand the degree of
hazard a worker may be e4posed to. 7ome of these pertain to the rating of the required $$E or
protection boundaries. It is important that workers understand the following quantities and their
units. An understanding of the physical significance of these quantities is helpful.
a. lash protection boundary
b. Corking distancec. Incident energy
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 50/62
d. !azard*risk category
e. A$1 of $$E.
PPE
-hapter 9 provides some information on $$E. 0ore detailed information can be obtained from
$$E vendors. Fse of $$E can restrict visibility and movement, cause discomfort, and slow down
the work. $ractice is recommended with $$E before working on energized equipment. he
following topics should be included in training on $$E.
a. 7election of $$E b. Information*Gabels on $$E
c. raining with new $$E
d. Inspection, care Q maintenance
e. Fseful life Q disposal
f. ocumentation of use and maintenance of $$Eg. Gimitations and potential risks using $$E
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 51/62
h. Gimitation of $$E Q degree of protection provided
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 52/62
%eadin" and Follo1in" arnin" Si"ns and +aelsCarning signs and labels are part of any safety program. Chen new labels or signs are placed,
workers need to be able to understand the meaning, and follow instructions precisely.
5ethods to %educe %is6 hile or6in" on +ive E7posed Parts
0any procedures can be developed in' house to suit the system and type of work the workers
may need to perform. $ractice on de'energized systems will greatly augment the knowledge, and
make the work safer. #ew procedures are introduced during the initial stages of the arc flash
program with the help of e4perienced workers and safety professionals. ormulation of new
procedures as an ongoing process is e4pected. -lear communication between different workers
who are part of procedure formulation e4pedites resolving safety issues.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 53/62
Arc Flash /a0ard Assessment
Arc flash hazard assessment should be carried out by skilled and e4perienced professionals. In'house engineers can be provided with the necessary training. It is necessary for the engineer to
apply short circuit analysis and protective device coordination, along with arc flash energy
calculations. Engineers should be aware of the limitations of the standards or methods they
employ and also have a good understanding of how these limitations can be overcome. It should
be noted that only some of the practical issues are discussed in this book because of time
limitations. A! programs, calculations, and procedures are new to the industry and changing ata rapid pace. $articipation in seminars and forums, reading of publications, and peer discussions
are recommended.
Documentation
ocumentation is described in greater detail later in this chapter. Corkers should be able to
document any changes performed in the power system, update the single'line diagrams, and alsomake note of any discrepancy between the actual equipment*system interconnection and the
single'line diagrams. Corkers should also understand the consequences of the drawings not
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 54/62
truly reflecting the actual system condition. Illustrations can be provided as to how such
circumstances may lead to selection of wrong $$E or wrong procedures.
Safet$ Audit
7afety audits are performed on a regular basis to evaluate various aspects of a safety program.Audit intervals should not e4ceed one year +%. he audit should be performed by e4periencedsafety professionals.
89
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 55/62
Purpose of Safety Audit
• Evaluate the effectiveness of safety program.
• Evaluate the performance of workers with regard to safety procedures.
• Evaluate the status of safety related activities such as documentation, training,
communications, etc.
• 3ecommend actions for improvement.
Arc Flash /a0ard and Safety Audit
As part of the regular safety audit, the following arc flash hazard related points should be
e4amined.
). 7ystem changes 7ince the last audit, were there any changes in the power systemR If LyesL
a. Cas the change properly documentedR Cere drawings updatedR
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 56/62
b. Cere any new arc flash calculations performedR
c. Cere new warning labels installed at the affected locationsR
+. $$E o the employees have the $$E needed for the highest level of arc flash e4posure in thefacilityR Chat is the condition of $$ER
5. o workers follow arc flash hazard warning labels, signs and instructions regarding flash
protection boundary and appropriate $$ER
6. Are arc flash hazard procedures followed correctly as they are documentedR
8. o the e4isting procedures provide protection adequatelyR
9. o workers have adequate knowledge and training in arc flash hazardR
%. !ave protective device settings been tampered with or modified from the intended settingsR
Are the fuse sizes the same as those specified by the engineerR
:. If any equipment requires special operation*maintenance procedures for safety reasons, is the
information readily available to workersR Chat is their understanding of the special
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 57/62
proceduresR
;. o workers have the tools and equipment for working safelyR (Insulated tools, shields, hot
sticks, etc."
)&. 3eview of accidents and near misses.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 58/62
5ethods of !tainin" 'nformation for Audit
). Interview with safety coordinators, responsible persons, trainers.
+. Inspection of records, documents, labels, signs, drawings pertaining to arc flash hazard.
5. Interview with electrical workers.
6. ?bservation of work procedures.
8. Inspection of $$E, safety tools and equipment.
Safet$ eetin!s
7afety meetings (or <ob briefings" are usually carried out before working on energized
equipment. his provides a review of the following
• Cork to be performed.
•$otential hazards.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 59/62
• Individual responsibilities.
• 7pecific procedures that require attention.
3egular safety meetings are also conducted in companies in which workers are continuallye4posed to hazards. 0onday morning meetings are held briefly to talk about safety. Accidents
and near misses are discussed. 7afety meetings are instrumental in disseminating information,
bringing new issues to attention, and discussing possible solutions. he 0onday morning
meetings also provide the workers an opportunity to focus on safety matters after returning to
work from their weekend. Corkers should be encouraged to discuss openly and share their
ideas. or e4ample, if a worker drops a tool on e4posed live equipment, it should be discussed,
since this event could have led to arc flash. his discussion could lead to reasoning why the tool
was dropped, and whether a better method or tool would have avoided the incident. rom these
insights, the procedures for arc flash hazards can be enhanced.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 60/62
Documentation
).ocument all data that was used for the arc flash hazard assessment. his is useful for
implementing changes and future assessment.+. $repare a report of the assessment identifying the type, name*I, incident energy at working
distances, flash protection boundary, hazard*risk category, and other pertinent information
such as voltage, available fault current, protective device description and its trip time, arc gap
and arc current.
5.$repare electrical drawings that contain the results of the arc flash analysis. Electrical
drawings a usually referred to for planning out maintenance <obs.
6. -irculate documents to all concerned people.
8. Install easily visible warning signs at the door, fence, etc. of the location where the hazard
e4ists, with information on the hazard, the arc flash boundary and the requirement of $$E
within the area.
9. Install warning labels on the equipment at some easily visible location near the e4posed live
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 61/62
part with information on hazard*risk category, estimated incident energy at working distances,
requirement of $$E, and the flash protection boundary.
%. If the equipment has a cover that needs to be removed before working on e4posed live
conductors, install similar warning labels inside so that the worker may see it after removing
the cover.
:. ocument and report the installation of all warning signs and labels.
;. ocument the safety audit and use it for continual improvement.
)&. ocument arc flash related accidents and near misses. ?7!A requires documentation and
reporting of all in<uries that result in loss of workday. ocumentation is suggested for near
misses as well, with the hope that prevention can be achieved more effectively.
*( ersonal rotecti4e Equipment
he following steps need to be taken regarding $$E.
). 7elect $$E based on arc flash hazard assessment.
7/17/2019 Practical Steps
http://slidepdf.com/reader/full/practical-steps 62/62
+. $rovide information*labels on $$E on thermal rating.
5. rain with new $$E.
6. $rovide regular inspection, care and maintenance of $$E.8. ocument use and maintenance of $$E.
9. ispose $$E after useful life has e4ceeded.