24
MINISTRY OF SCIENCE AND TECHNOLOGY DEPARTMENT OF TECHNICAL AND VOLCATIONAL EDUCATION DEPARTMENT OF ELECTRICAL POWER ENGINEERING FINAL EXAMINATION B.E (EP), 2006 EP 05022 POWER SYSTEM PROTECTION Date: 25.10.2006(Wednesday) Time:8:30am-11:30am ************************************************************** ********** Attempt any Six questions 1. Consider again the portion of a 138kV transmission system shown in figure. Lines1-2, 2-3 and 2-4 are respectively 64, 64 and 96 km long. The positive-sequence impedance of the transmission lines is 0.05 + j0.5 ohm per kilometer. The maximum load carried by line 1-2 is 50MVA. Design a three-zone step distance relaying system to the extent of determining for R 12 the zone settings which are the impedance values in terms of CT and CVT secondary quantities.

Power System1

Embed Size (px)

Citation preview

Page 1: Power System1

MINISTRY OF SCIENCE AND TECHNOLOGY

DEPARTMENT OF TECHNICAL AND VOLCATIONAL EDUCATION

DEPARTMENT OF ELECTRICAL POWER ENGINEERING

FINAL EXAMINATION

B.E (EP), 2006

EP 05022 POWER SYSTEM PROTECTION

Date: 25.10.2006(Wednesday) Time:8:30am-11:30am************************************************************************

Attempt any Six questions

1. Consider again the portion of a 138kV transmission system shown in figure. Lines1-2,

2-3 and 2-4 are respectively 64, 64 and 96 km long. The positive-sequence impedance

of the transmission lines is 0.05 + j0.5 ohm per kilometer. The maximum load carried

by line 1-2 is 50MVA. Design a three-zone step distance relaying system to the extent

of determining for R 12 the zone settings which are the impedance values in terms of

CT and CVT secondary quantities.

2. Discuss good practice in Transmission-line relay protection.

3. Derive and sketch in the complex impedance plane, the impedance seen by each of

the three phase distance relays for a phase b to phase c fault on the transmission line

by using the symmetrical components. Neglecting the mutual effects, charging

currents of the transmission lines and load current. Indicate on the same diagram, the

operating characteristics of an impedance relay, a mho relay and a reactance relay set

to protect the whole length of the line.

Zone 3

Zone 2

Zone 1

1 2 3

4B 12 P1 P2B 21

B 23

B 24

P3

P4

B 42

B 32

Page 2: Power System1

4. Derive the voltage and current equations at the relay location, and the impedance seen

by each of the three phase distance relays for a phase a to ground fault on the power

transmission line by the use of symmetrical components. Neglecting the mutual

effects, charging currents of the transmission lines and load current.

5. Explain the following protection-system.

(a) Stator-overheating protection

(b) Overvoltage protection

6. Discuss the protection of a three winding transformer with a two winding percentage

differential relay with necessary sketch.

7. Describe the following bus-protection.

(a) Current differential relaying with percentage differential relays.

(b) Current differential relaying with over voltage relays.

8. Name differential types of static relays. Discuss the use of electronic relays and

transistor relays.

Answers:

1.

Line 1-2 3.2 + j32

Line 2-3 3.2 + j 32

Line 2-4 4.8 + j 48

Max: Load crt, (ILoad) max =

(ILoad)max =

C.T Ratio = 200:5

Vp =

Page 3: Power System1

CVT Ratio =

Zp = ?

Line 1-2 0.11 + j 1.1 secondary

Line 2-3 0.11 + j 1.1 secondary

Line 2-4 0.16 + j 1.6 secondary

Assume p.f = cos = 0.8 sin = 0.6

Z Load =

= (10.2 + j 7.68)

Zone 1 of R12 = 0.8 (0.11 + j 1.1) = 0.088 + j0.88

Zone 2 of R12 = 1.2 (0.11 + j1.1) = 0.132 + j1.32

Zone 3 of R12 = (0.11 + j1.1) + 1.2 (0.16 + j1.6)

= 0.302 + j 3.02

2. Good practice in transmission line relay protection

On important high voltage lines, high speed fault clearing is generally necessary. For

reason of system stability and for other reasons. On many such lines high speed distance

relays are used which give high speed clearing of both ends of the line for fault in the middle

eight-tenth of the line length and sequencial clearing of faults in the two ends zone each one-

tenth of the line in length. The ground relays are usually of either the slow speed and the high

speed overcurrent types. Fortunately, from the standpoint of stability, high speed clearing is

not so necessary for one line to ground faults as for phase fault. If the stability situation is so

crital that high speed clearing of ground faults and end zone phase faults is required, then

carrier pilot relaying is generally employed.

On long or heavy load lines, the distance relay should be of a kind not too susceptible

to trip on swings for which the system will recover.

On short but important lines, pilot wire relaying is appropriated. It use has ground

greatly since relays were developed that give protection against all internal fault by means of

a pilot channel consisting of only two small wires.

Page 4: Power System1

On unimportant lines, slow speed overcurrent relays are ordinary used.

3.

Phase a phase network for a phase b to phase c fault

Z1 = (Z1×Zy1) / (Zx1 + ZY1)

Z2 = (Zx2× ZY2) / (Zx2 + ZY2)

I1 = E1/(Z1+Z2+Rf) = E1 / (2Z1+ Rf) (Z1=Z2)

I1= 1/K

K= (2Z1+Rf)/E1

V1= V2 + I1 Rf/2 – I2 Rf/2

= -I2 Z2 + I1 Rf/2 + I1 Rf/2

= I1 Z1 + I1 Rf

= I1 (Z1 + Rf)

Ia1 = I1 × (ZY1) / (Zx1+ ZY1)

Ia1 = I1 C1 ( C1= (ZY1) / (Zx1+ ZY1) )

Page 5: Power System1

Ia1 = (1/K) ×C1

K Ia1 = C1

Ia2 = I2 × (ZY2) / (Zx2+ ZY2)

= I2 × C2 ( C2 = (ZY2) / (Zx2+ ZY2) )

= - I1 C1 ( I1= - I2 , C1 = C2 )

= -(1/K) C1

K Ia2 = - C1

There is zero sequence component for phase to phase fault

K Ia0 = 0

The actual phase current in relay location are

K Ia = K Ia1 + K Ia2 + K Ia0 = C1 - C1 =0

K Ib = a2 K Ia1 + aK Ia2 + K Ia0 = ( a2 - a) C1

K Ic = a K Ia1 + a2K Ia2 + K Ia0 = ( a - a2 ) C1

If delta connected CT’s are involved

K(Ia - Ib) = KIa - KIb = - (a2 - a) C1

K(Ib - Ic) = KIb - KIc = (a2 - a - a + a2 ) C1

K(Ic - Ia) = KIc - KIa = (a - a2) C1

Va1 = V1 + Ia1 Z1 ́

= I1(Z1 + Rf) + I1C1 Z1 ́

= 1/K(C1 Z1 ́ + Z1 + Rf )

K Va1 = C1 Z1 ́ + Z1 + Rf

Va2 = V2 + Ia2 Z2́

= - I2 Z2 + I2 C2 Z2́

= I1Z1 – I1 C1 Z2́

= 1/K(-C1 Z1 ́ + Z1)

K Va2 = - C1 Z1 ́ + Z1

There is no zero sequence component for phase to phase fault

K Va0 = 0

The actual phase to neutral fault on relay location are

K Va = K Va1 + K Va2 + K Va0 = C1 Z1 ́ + Z1 + Rf - C1 Z1 ́ + Z1 = 2 Z1 +Rf

K Vb = a2K Va1 + aK Va2 + K Va0 = a2 (C1 Z1 ́ + Z1 + Rf ) + a (-C1 Z1 ́ + Z1)

= ( a2 – a) C1 Z1 ́+ ( a2

+ a) Z1 + a2 Rf

= ( a2 – a) C1 Z1 ́ - Z1 + a2 Rf

K Vc = aK Va1 + a2K Va2 + K Va0

Page 6: Power System1

= a (C1 Z1 ́ + Z1 + Rf ) + a2 (-C1 Z1 ́ + Z1)

= ( a – a2) C1 Z1 ́+ ( a2 + a) Z1 + a Rf

= ( a – a2) C1 Z1 ́ - Z1 + a Rf

The Phase to phase voltage are

K(Va - Vb ) = K Va - K Vb = (2Z1 + Rf ) – [ (a2-a) C1 Z1 ́- Z1 + a2 Rf]

= - (a2-a) C1 Z1 ́ + 3Z1 + (1- a2) Rf

K(Vb- Vc) = KVb- K Vc = [(a2-a) C1 Z1 ́- Z1+a2 Rf]-[(a2-a) C1 Z1 ́ - Z1+a2) Rf]

= 2(a2-a) C1 Z1 ́+ (a2-a) Rf

K(Vc - Va) = K Vc - K Va = [(a-a2) C1 Z1 ́- Z1+a Rf] –(2 Z1+ Rf)

= (a-a2) C1 Z1 ́- 3Z1 + (a-1) Rf

The impedance measured by the relays are

Zab = K(Va - Vb ) / K(Ia - Ib ) = [ - (a2-a) C1 Z1 ́ + 3Z1 + (1- a2) Rf] / [-(a2-a) C1]

= Z1 ́ + -

= Z1 ́ - j Zx1 -

Zbc = =

Page 7: Power System1

4.

Page 8: Power System1

( )

v1 = v2 + v0 + 3RFI1

= I2z2 + I0z0 + 3RFI1

= I1z1 + I1z0 + 3RFI1

= I1 (z1 + z0 +3RF)

Ia1 = I1 ,

kIa1 = c1

Iaz = I2 ,

kIa1 = c1

Page 9: Power System1

Ia0 = I0

kIa0 = c0

Actual phase to phase current for relay location are

kIa = kIa1 + kIa2 + kIa0 = 2c1 + c0

kIb = a2kIa1 + akIa2 + kIa0 = (a2 +a) c1 + c0 = -c1 + c0

kIc = akIa1 + a2kIa2 + kIa0 = (a2 + a2) c1 +c0 = -c1 + c0

If delta connected CT's are involved

k(Ia – Ib) = kIa – kIb = -c1 + c0 + c1 – c0 = 3c1

k (Ib - Ic) = kIb – kIc = -c1 + c0 + c1 – c0

k (Ic – Ia) = kIc – kIa = -c1 + c0 - 2c1 – c0 = -3c1

va1 = v1 + Ia1z1'

= I1 (z1 + z0 + 3RF ) + I1c1 z1'

= I1 (c1z1' + z1 + z0 + 3RF)

= (c1z1' + z1 + z0 + 3RF)

kva1 = c1z1' + z1 + z0 + 3RF

va2 = -v2 + Iazz2'

= -I1z2 + I2c2z2'

= -I1z1 + I1c1z1'

= I1 (c1z1'- z1)

= (c1z1'-z1)

kva2 = c1z1'-z1

va0 = -v0 + Ia0z0'

= -I0z0 + I0c0z0'

= -I1z0 + I1c0z0'

Page 10: Power System1

= I1 (c0z0 '- z0)

kva0 = c0z0'-z0

The actual phase to neutral phase voltage for relay location are

kva = kva1 + kva2 + kva0

= c1z1' + z1 + z0 + 3RF + c1z1' – z1 + c0z0' – z0

= 2c1z1' + c0z0 ' + 3RF

kvb = a2kva1 + akva2 + kva0

= a2(c1z1' + z1 + z0 + 3RF)+ a(c1z1' – z1) + c0z0' – z0

= (a2 + a) c1z1' + c0z0 ' + (a2 – a) z1 + (a2 – 1) z0 + a23RF

= -c1z1' + c0z0' + (a2 - a) z1 + (a2 – 1)z0 + 3a2RF

kvc = akva1 + akva2 + kva0

= a (c1z1' + z1 + z0 + 3RF) + a2 (c1z1' – z1) + c0z0' – z0

= (a + a2) c1z1' + c0z0 ' + (a2 – a) z1 + (a2 – 1) z0 + a23RF

= -c1z1' + c0z0' + (a - a2) z1 + (a – 1)z0 + 3aRF

The phase to phase voltage are

k(va – vb) = 2c1z1' + c0z0 ' + 3RF + c1z1' - c0z0' - (a2 - a) z1 - (a2 – 1)z0 - 3a2RF

= 3c1z1' – (a2 – a) z1 – (a2 – 1) z0 + (1- a2) 3RF

k (vb – vc) = -c1z1' + c0z0' + (a2 - a) z1 + (a2 – 1)z0 + 3a2RF + c1z1' - c0z0' - (a - a2) z1 –

(a - 1)z0 - 3aRF

= ( a2 – a – a + a2) z1 + ( a2 - 1 - a + 1) z0 + (a2 - a) RF

= 2 ( a2 – a) z1 + (a2 – a) z0 + (a2 – a) RF

k (vc – va) = -c1z1' + c0z0' + (a - a2) z1 + (a – 1)z0 + 3aRF - 2c1z1' - c0z0 ' - 3RF

= -c0z0' – 3RF

= -3c1z1' + (a – a2)z1 + (a – 1) z0 + (a – 1) 3RF

The impedance measured by the relays are

Zab =

Page 11: Power System1

Zbc =

zca =

=

=

5.(a) Stator overheating protection

Figure: Stator overheating relaying with resistance temperature detector

General stator overheating is caused by overloading or by failure of the cooling

system. It can be detected quite easily overheating because of short circuit lamination is very

localized it can be detected before serious damage is done.

Page 12: Power System1

The practice is to embed resistance temperature coil or thermocouple in the slot with

the stator winding of generator larger than about 500 to 1500 KVA. Enough of these dectors

are located at different places in the winding. Several of the detectors that give highest

temperature indication are selected for use with a temperature indicator or recorder usually

having alarm contacts.

One form of dector operated relaying equipment using a wheatstone bridge circuit and

a directional relay. In another form of equipment, the stator current is used to energize the

bridge.

The relay is arranged with heating and heat storage element so as to heat up an cool

down as soon as the same rating as the machine in response to the same variation in the

current. A thermostatic element closes contacts at a selected temperature and it will not

operate for failure of the cooling system.

The temperature detector operated devices are preferred because they response more

nearly to the actual temperature of stator.

In unattended station, temperature relays are arranged to reduce the load or shunt

down the unit if it overheats, but in an attended station the relay, if used merely sounds an

alarm.

5.(b) Overvoltage protection

The overvoltage protection is recommended for all hydroelectric or gas turbine

generator that are subject to overspeed and consequence overvoltage on loss of load. It is no

generally used with steam turbine generator.

This protection is often provided by the voltage regulating equipment if it is not

should be provided by an ac overcurrent relay. This relay should have a time delay unit with

pickup at about 130% to 150% of rated voltage. Both the relay units should be compensated

against the effect of variable frequency. The relay should be energized from a potential

transformer, other than the one used for the automatic voltage regulator. Its operation should

prefereably first cause additional resistance to be inserted in the generator or exciter field

circuit. Then, if overvoltage persists the main generator breaker and generator or exciter field

breaker should be tripped.

6. The protection of a three winding transformer with a two winding percentage differential

relay

Page 13: Power System1

Unless there is a source of generation bank of only one side of a power transformer a

two winding percentage differential relay should not be used to protect a three winding

transformer. As shown in fig(a) when a two winding relay is used the secondary on two sides

of generation bank of one of these sides the condition shown by the arrow of fig(a) may be

sufficient unbalance between CT currents, either because of mismatch or error or both to

cause the differential relay to operate undesirably. The relay should not have the benefit of

through current restraint which is the basis for using the percentage differential principle.

Instead only the unbalance current would flow all of the operating coil and half of the

restraining coil. In effect this consistitude a 200% unbalance and it is only necessary that

unbalance current be above the relays minimum pickup for the relay to operate.

Of course, if two sides where CT are paralleled in fig(a0 supply load and do not

connect to a source generation. A two winding relay may be used with impurity.

As shown in fig(b) if a three winding relay is used, there will always be through

current restraint to restrict the relay against undesired operation.

A further a advantage of a three winding relay with a three winding transformer is that

where relay types are involved having taps for matching the CT secondary current it is often

unnecessary to use any auxiliary contacts. Thus a three winding relay may even be used with

advantage whenever a two winding relay might suffice. There is no disadvantage other than a

slight increase in cost in using a three winding relay on a two winding transformer no harm is

done if on of the restraint circuit is left unconnected.

Page 14: Power System1

Figure: (a) A misapplication of two winding transformer differential relay

Figure: (b) illustrate advantage of a three winding relay with a three winding transformer

7.(a) Current differential relaying with percentage differential relays

As in differential relaying for generator and transformer the principle of percentage

differential relay is a great improvement over current relay in a differential CT circuit. The

Page 15: Power System1

problem of providing enough restraint circuit has been largely sloved by so called

multirestraint relay. By judicious grouping of circuit and by the use of two relays per phase

where necessary sufficient restraining circuit is generally provided. Further improvement in

sensitivity is also provided by the variable percentage characteristics like that decried in

connection with generator protection with this characteristics one should make sure that very

high internal fault current will not cause sufficient restraint to prevent tripping.

This type of relaying equipment is available with operating time of the order of 3 to 6

cycles. It is not suitable when high speed operation is required.

As in current differential relay with overcurrent relay the problem of calculating the

CT error is very difficult. The use of percentage restraint and variable percentage

characteristics make the relay quite insensitive to the effect of CT error. Nevertheless, it is

recommended that each application be referred to the manufacture together with all the

necessary data.

A disadvantage of this type of equipment is that the CT secondary leads must run to

relay panel.

7.(b) Current differential relaying with over voltage relays

Figure: bus protection using current differential relaying with over voltage relays

A type of high speed relaying equipment employing current differential relaying with

over voltage relay also eliminated the problem of current transformer saturation with this

equipment conventional exactly as for current differential relay over voltage rather than over

current relay are used.

Page 16: Power System1

In this equipment the impedance of over voltage relays coil is made to appear to the

circuit as resistance by virtue of a fall wave rectifier. The efficiency of this equipment is not

lowered as it would be if a series reactor were used.

The capacitance and inductance as shown in series with the rectifier circuit are in

series resonance at fundamental system frequency. The purpose of this is to make the relay

responsive to only the fundamental component of the CT secondary current so as to improve

the relay selectivity. This has the disadvantage of slowing the voltage relay response slightly,

but this is not serious in view of the high speed operation of an overcurrent relay element

now to be described.

As in fig an overcurrent relay unit in series with the voltage limiter provides high

speed operation for bus fault involving high magnitude current. As the overcurrent unit is

relied on only for high magnitude current it’s pickup can easily be made high enough to

avoide operation for external fault.

For the most possible result, all the CT should have the same rating and should be a

type like a bushing CT with a distributed secondary winding that gives little or no secondary

leakage reactance.

8. Different type of static relays

i. Electronic Relays

ii. Transistor Relays

iii. Transducer Relays

iv. Rectifier Bridge Relays

v. Hall effect Relays

vi. Gauss effect Relays

(i) Electronic Relays

- The two basic arrangement one as an amplitude comparator and another as a phase

comparator as shown in fig:

- In the former case, two a.c quantities to be compared are rectified and applied in

opposition in the control grid ckt of an electronic tube, so that operation occurs when one

quantity exceed the other by an amount depending on the bias.

- In the latter case, one a.c quantity can be connceted to the control grid of an

electronic tube; the another a.c quantity to the screen grid, so that operation occurs when two

quantities are in phase.

Page 17: Power System1

Advantages of an electronic relay

i. Low burden on C.Ts & P.Ts, since the operation power is from an auxiliary d.c

supply.

ii. Absence of mechanical inertia and bouncing contain

iii. Fast operation

iv. Low maintenance

Disadvantages of an electronic relay

i. Presence of incandescent filament and necessary low vtg power supply to heat them.

ii. Short life of the electronic valves.

iii. High power consumption

iv. Requirement of high tension supply

v. High cost of simple relay such as overcrt relays.

Transistor Relays

Page 18: Power System1

- The characteristics of modern transistor are such that they can replace the functional

element which are used in electromechanical relay to give necessary characteristics.

- Two basic arrangement of relays based on transistor comparators are shown in fig:

- In either of these ckt, crt of constant magnitude flow in the collector ckt only when

the input a.c quantities are simultaneously negative, a relay in the collector ckt will

pick up when the overlap angle exceeds a certain value.

Advantages of transistor relay

i. Quick response, long life, high resistance to shock & vibration

ii. Quick reset action

iii. No bearing friction or contact troubles

iv. Ease of providing amplification enable greater sensitivity to be obtained.

v. The low energy level required in measuring ckt.

vi. Use of printed to avoid wiring error and to facilitate rationalization of batch

production

Limitations

i. Variation of characteristics with temperature and age.

ii. Dependence of reliability on large number of small components and their electrical

connection.

iii. Low short time overload capacity.

Page 19: Power System1