Upload
morgan-mckenzie
View
215
Download
0
Tags:
Embed Size (px)
Citation preview
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Power Plus Training ServicesPower Plus Training ServicesAn introduction to our training programs
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Power Plus Training ServicesPower Plus Training Services Specializing in
nationwide “hands-on” electrical testing and safety training
Delivered at your facility, eliminating employee travel expenses
Instructors are NETA certified test technicians and trained in the facilitation of the learning process
All courses designed to meet OSHA and NFPA 70E requirements
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Power Plus Training ServicesPower Plus Training Services Courses available
– Industrial Electrical Safety
– NFPA 70E Electrical Safety
– Electrical Awareness for Emergency Responders
– Circuit Breaker Operation and Maintenance
– Transformer Operation and Maintenance
– Substation Safety and Operation
– Substation Maintenance
– NEC Training
– Electrical Theory
– Electrical Grounding Practices
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Power Plus Training ServicesPower Plus Training Services Customized training
– All courses may be customized to you plants specific equipment and procedures
– Student learn by doing “hands-on” labs on the actual equipment they will be applying the skills learned
Customers include:
– General Motors
– BASF
– Ford Motor Company
– ABB
– DaimlerChrysler
– US Coast Guard
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Electrical SafetyElectrical SafetyArc Flash Hazard Analysis
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Flash Hazard AnalysisFlash Hazard Analysis
The NFPA 70E states, “A Flash Hazard Analysis shall be done in order to protect personnel from the possibility of being injured by an arc flash. The analysis shall determine the Flash Protection Boundary and the personal protective equipment that people within the Flash Protection Boundary shall use.”
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Flash Hazard Analysis Flash Hazard Analysis The intensity level of an arc flash can be
calculated
A flash hazard analysis consists of 2 parts:
– Determining the flash hazard boundary
– Determining the incident energy level the worker would be exposed to
Boundary is based on the following:
– Amount of available fault current
– Distance of the electrode gap
– The clearing time of the protective device
Once the data is gathered, the flash protection boundary can be determined
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Dcb= (MVA*53*t)Example: (3*53*.1Sec)=3.99 Ft
Flash Hazard AnalysisFlash Hazard Analysis For systems that are 600V or less, the Flash
Protection Boundary shall be 4 feet, based on the product of clearing times of 6 cycles and the available bolted fault current of 50,000A or any combination not exceeding 300kA cycles
For clearing times and bolted fault currents other than 300kA cycles, or under engineering supervision, the Flash Protection Boundary shall be alternatively be permitted to be calculated in accordance with the following general formula:
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Flash Hazard AnalysisFlash Hazard Analysis Excel program
using NFPA 70E Equations
Download at www.epowerplus.com
Example:
– 3000kVA 480V transformer
– 6 cycle clearing time
DC=3.99 ft
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Flash Hazard Analysis Flash Hazard Analysis
The flash protection boundary determines at what distance from exposed live parts flash protection must be worn
Distance is usually based on not exceeding 1.2 cal/cm2 of heat energy on a persons skin
1.2 cal/cm2 will cause a 2nd degree burn of exposed skin in 0.1 second
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Flash Hazard AnalysisFlash Hazard AnalysisThe next step is
to determine the Incident Energy (EI) level that a worker would be exposed to if an arc flash were to occur.
The goal of this calculation is to determine the amount of heat energy a worker would be exposed to during an arc flash event
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Flash Hazard AnalysisFlash Hazard Analysis Excel program
using NFPA 70E Equations
Download at www.epowerplus.com
Example:
– 36kA available
– EI at 18”
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Flash Hazard AnalysisFlash Hazard Analysis
36kA will trip breaker in .07 seconds
Add breaker opening time (.06)
Arc duration would be about .13 sec
Given the following curve for a 1200A breaker
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Flash Hazard AnalysisFlash Hazard Analysis A 36 kA fault
with a 0.13 second clearing time at 18”
EI will be:
– 6.408 Cal/cm2 in open air
– 10.6607 Cal/cm2 in a cubic box
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Flash Hazard AnalysisFlash Hazard Analysis
13.68kA will trip breaker in .35 seconds
Add breaker opening time (.06)
Arc duration would be about .41 sec
At 38% IBF would be 13,680A (or 11.4x LT setting)
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Flash Hazard AnalysisFlash Hazard Analysis At 36kA and
.13 sec
Open Air was 6.408 Cal/cm2
Cubic box was 10.6607 Cal/cm2
Which is worse?
A 13.8 kA fault with a 0.41 second clearing time at 18”
EI will be:
– 8.205 Cal/cm2 in open air
– 17.9508 Cal/cm2 in a cubic box
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Flash Hazard AnalysisFlash Hazard Analysis The PPE necessary
to perform a task inside of the flash hazard boundary may be determined from the resultant Incident Energy from the flash hazard analysis.
The incident energy level determines the Hazard Risk Category (HRC) PPE rated for the available incident energy will prevent the onset of a second degree burn if an arc flash were to occur
Incident Energy Level
Hazard Risk Category
0-<4 cal/cm2 1
4-<8 cal/cm2 2
8-<25 cal/cm2 3
25-<40 cal/cm2 4
>40cal/cm2 Dangerous
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Electrical SafetyElectrical SafetySelection and use of Personal Protective Equipment
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Personal Protective EquipmentPersonal Protective Equipment
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
PPE Selection tablesPPE Selection tables
Task (Assumes equipment is energized, and work is done within the flash protection boundary)
Hazard/RiskCategory
V-RatedGloves
V-Rated Tools
Panel boards rated 240V and below - Notes 1 and 3 - - -
CB or fused switch operation with covers on 0 N N
CB or fused switch operation with covers off 0 N N
Work on energized parts, including voltage testing 1 Y Y
Remove/Install CB's or fused switches 1 Y Y
Removal of bolted covers (To expose bare, energized parts) 1 N N
Opening of hinged covers (To expose bare, energized parts) 0 N N
Find the task you will be performingFind the type of equipment you will be working on
Find the level of flash protection neededDetermine if gloves are neededDetermine if insulated tools are needed
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
PPE SelectionPPE Selection
Protective Clothing & Equipment
Protective System for Hazard / Risk Category
Hazard / Risk Category Number (-1) Note 3 0 1 2 3 4
Untreated Natural Fiber - - - - - -
T-shirt (short sleeve) X X X X
Shirt (long sleeve) X
Pants (long) X X X (Note 6)
X (Note 6) X X
Find your risk category
Determine the PPE needed
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Typical Protective ClothingTypical Protective Clothing
Hazard Risk Category 0
– Untreated Cotton long sleeve shirt and pants
– Safety Glasses
– PPE cal/cm2 -- N/A
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Typical Protective ClothingTypical Protective Clothing
Hazard Risk Category 1
– Long sleeve FR Shirt & Pants (Jeans are acceptable)
– Hard Hat
– Safety Glasses
PPE cal/cm2 -- ≥ 4.0
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Typical Protective ClothingTypical Protective Clothing Hazard Risk Category 2
– Cotton T-shirt plus FR shirt & FR Pants
– Leather Gloves and Shoes
– Hard Hat
– Safety Glasses
– Hearing protection
– Arc rated face shield or double layered switching hood
– PPE cal/cm2 -- ≥ 8.0
– * = Must use a double layered switching hood and hearing protection in addition to level 2 requirements
+ Or
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Typical Protective ClothingTypical Protective Clothing Hazard Risk Category 3
and 4– Cotton T-shirt and pants
– Leather Gloves and Shoes
– Hard Hat, Liner, Safety Glasses
– Double layered switching hood and hearing protection
– Multiple layers of FR clothing or switching suit to equal cal/cm2 requirements
PPE cal/cm2
– HRC 3 -- ≥ 25.0
– HRC 4 -- ≥ 40.0
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Safety GlovesSafety Gloves Employees shall
wear rubber insulating gloves where there is a danger of arm and hand injury from electrical shock and burns due to contact with live parts
Gloves used shall be of the appropriate voltage class
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Safety GlovesSafety Gloves Label on insulating equipment
contains the following information:
– Manufacturer
– ANSI/ASTM Reference
– Size (Gloves)
– Type
– Class
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Glove selectionGlove selection Glove size is
important to ensure a proper fit and dexterity
Size is inches around the palm of your hand
Types:
– Type 1 – Non-Ozone resistant (Natural rubber)
– Type 2 – Ozone resistant (Synthetic)
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Glove selectionGlove selectionMake sure you have the right glove for the
right job!
CLASSMAX USE VOLTAGE
A-C RETEST VOLTAGE
CLASS 00 500 2,500
CLASS 0 1,000 5,000
CLASS 1 7,500 10,000
CLASS 2 17,000 20,000
CLASS 3 26,500 30,000
CLASS 4 36,000 40,000
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Glove TestingGlove Testing Gloves are required to
be lab tested every six months
The tests include:
– Dielectric test at voltage on previous chart
– Air test
– Cleaning
– Visual inspection
(Courtesy Reed City
Power Line)
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Glove inspectionGlove inspection Gloves should be
inspected prior to each use
The inspection should include:Visual inspection checking for:
•Cracks
•Punctures
•Ozone damage
•Snags
•Embedded material
Air test
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Protective EyewearProtective Eyewear ANSI Z87.1
– Impact protection
– UV Attenuation
Will not withstand heat generated from arc flash
Must be tested for thermal Protection per ASTM 1959!
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Hard HatsHard Hats
Class Voltage Rating
Class (Prior to 1999)
G 2,200V A
E 20,000V B
C 0V C
Hard hats used for electrical shock protection must be rated
for the voltages present
Do not:– Drill holes for ventilation
– Paint
– Use excessive number of stickers (Check state OSHA regulation)
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Foot ProtectionFoot Protection Electrical workers shall
wear rubber soled shoes but they may not be used as primary electrical protection
Leather work shoes are recommended for all tasks and shall be used for incident energy exposure levels 4 cal/cm2 and higher
Where insulated footwear is used as protection against step and touch potential, dielectric overshoes shall be required
These overshoes follow under the same testing requirements as gloves
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Transformer Construction and Maintenance
Transformer Construction and Maintenance
Transformer Theory
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Transformer TheoryTransformer Theory William Stanley invented the transformer
in 1886
His basic design is still the principle by which all transformers are designed today
When current is passed through a conductor a magnetic field is induced
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Transformer TheoryTransformer Theory The direction of the field can be
determined by using the right hand rule for conductors
When an AC is passed through a conductor the field produced is constantly expanding and collapsing
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Transformer TheoryTransformer Theory When another conductor is placed in this
changing magnetic field, a voltage will be induced in the conductor
If a complete circuit exists on the secondary, current will flow through the circuit as shown below
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Transformer TheoryTransformer Theory A transformer can
be divided into three parts:
– Primary Windings
– Secondary Windings
– Core
The primary and secondary windings are linked by a common flux produced in the iron core
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Fact or Fiction?Fact or Fiction?
Fiction!
It will still work, but will be less efficient
“A transformer will not work without a core ”
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Power in the transformerPower in the transformer Transformers are
rated in volt-amps
EpIp = ESIS
What is the turns ratio?
If primary current was 25A, what would secondary current be?
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Transformer LossesTransformer Losses Exciting current is the current needed to set
up the magnetic flux in the windings and core
The losses from the excitation current is called core loss, which is subdivided into two categories:
– Eddy Current Losses: Losses from small circulating currents in the core
– Hysteresis Losses: Caused by the energy required to align the domains in the magnetic core material
The magnetic flux in the core and the current flowing in the windings generate heat, which is called copper loss, and is equal to the square of the current times the resistance of the windings
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Eddy current lossesEddy current losses Iron is a conductor of
electricity as well as being an excellent "conductor" of magnetic flux
There will be currents induced in the iron just as there are currents induced in the secondary windings from the alternating magnetic field
These induced currents tend to circulate through the cross-section of the core perpendicularly to the primary winding turns
The main strategy in mitigating these wasteful eddy currents in transformer cores is to form the iron core in sheets each sheet covered with an insulating varnish so that the core is divided up into thin slices
The result is very little width in the core for eddy currents to circulate in
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Hysteresis lossHysteresis loss
A: Because it doesn't know the words!
Q: Why do transformers hum?
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Hysteresis lossHysteresis loss
Here is a piece of ferromagnetic material showing each molecule as tiny magnetsWhen a magnetic field is applied they all line up
When the direction of the field reverses, they all flip around 180 degrees
This occurs 120 times per second (60Hz)
Each realignment causes a vibration
The vibration is heard as the familiar hum
A “B Flat” note is very close to 120 Hz
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Hysteresis lossHysteresis loss All ferromagnetic
materials tend to retain some degree of magnetization on a molecular level after exposure to an external magnetic field
This tendency to stay magnetized is called "hysteresis"
Hysteresis losses can be mitigated by choosing a core alloy with low hysteresis, as evidenced by a "thin" B/H hysteresis curve
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Effect of harmonicsEffect of harmonics Transformer energy losses tend
to worsen with increasing frequency
– The skin effect within winding conductors reduces the available cross-sectional area for electron flow, thereby increasing effective resistance as the frequency goes up
– Magnetic core losses are also exaggerated with higher frequencies, eddy currents and hysteresis effects becoming more severe
Modern power systems are exposed to high frequencies from harmonics produced by switching loads (I.E. VFD’s)
A K-Factor rated transformer is designed to handle these harmonics by utilizing a larger core
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Transformer Construction and Maintenance
Transformer Construction and Maintenance
Transformer inspections
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
InspectionsInspections Voltage: Primary and
Secondary voltage should be maintained within set limits
Load Current: The loading will determine the heat generated in the transformer. The heating determines the life expectancy so monitoring load current is a simple method of predicting failures. Load monitoring should be done on an hourly basis or by the use of data recording equipment
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
InspectionsInspections Temperature: The maximum
allowable temperature is the ambient temperature plus the rated maximum temperature rise. A common thumb rule for life expectancy of transformers is as follows:– Class “A” insulation - 8C
above max temp rating= ½ life expectancy
– Class “B” insulation - 12C above max temp rating= ½ life expectancy
Liquid level: Level loss may occur from leaks or evaporation of the fluid. Any liquid losses should be replaced immediately
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Inspections (Liquid Filled)Inspections (Liquid Filled)
External Inspection: This inspection includes checking the tank, radiators, auxiliary equipment, gaskets, and metal parts for corrosion and leaks
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Inspections (Liquid Filled)Inspections (Liquid Filled) Auxiliary equipment:
Fans, oil pumps, and cooling fins should be checked for proper flow and operation. Worn or damaged parts should be repaired or replaced
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Inspections (Dry Type)Inspections (Dry Type) Inspect fans for
proper operation by taking the mode selector switch to manual
Clean filters for proper air flow
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
InspectionsInspections Transformer liquid
Air, moisture, and heat are the most common contributors to the breakdown of the fluid
These contaminates react with the fluid and create sludge and acids, which in turn will damage the insulation
Samples should be taken on at least an annual basis and analyzed by an approved test lab that follows ASTM standards
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
InspectionsInspections More in-depth
inspections require the transformer to be shut down and placed in an electrically safe working condition
The following is a brief summary of the items to be inspected while the transformer is shut down
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
InspectionsInspections Protective devices:
The following devices should be inspected and tested on an annual basis
– Overcurrent phase and ground relays
– Differential relays
– Sudden pressure relays
– Under/Over voltage relays
– Alarms
– CT’s and associated wiring for relays
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
InspectionsInspections
Pressure relief device: Liquid filled transformers are equipped with pressure relief devices that are usually set to open at 10-15 psi
Inspections should include checking for leak around joints, diaphragm cracking, and gasket condition
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
AccessoriesAccessories Sudden pressure relays are designed to
respond to a rapid buildup of pressure in the 2 to 6 PSI range over the 0.02 to 6.0 second time band
Gas build-up can lead to possible explosions as seen here
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
InspectionsInspections
Ground Connections: The grounding straps should be inspected daily for damage and loose/corroded connections. The substation ground should be checked on an annual basis for proper continuity
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
InspectionsInspections Insulators:
Insulators should be inspected for tightness, dirt accumulation, water damage, and damaged surfaces
Lightning arrestors: Arrestors should be inspected for tightness, dirt accumulation, water damage, and damaged surfaces. Any dirt or deposits should be cleaned and all loose connections should be tightened
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Inspections (Dry type)Inspections (Dry type) Any dirt present should
be removed to permit circulation of air and to aid in the prevention of insulation failure
Compressed air (<25 Psi) and a vacuum cleaner should be used to remove dirt from the windings
All leads, terminations, bushings, and other surfaces should be wiped clean with a dry, lint free cloth
Liquid cleaners should not be used because they may deteriorate the insulation
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Inspections (Liquid filled)Inspections (Liquid filled) Internal inspection: this inspection
involves an internal investigation of the tank (liquid filled), windings, and core
This inspection is only done after the unit has been placed in an electrically safe working condition
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Circuit Breaker Construction and Maintenance
Circuit Breaker Construction and Maintenance
A guide to proper maintenance of Low Voltage power circuit breakers
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Circuit Breaker MaintenanceCircuit Breaker Maintenance Ensure the circuit
breaker is isolated from the power circuit
Always refer to the breaker's maintenance manual
In general, the three basic rules of electrical inspections apply to all circuit breakers:
– Keep it tight
– Keep it clean
– Keep it dry
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Contact InspectionContact Inspection The first step for the contact
inspection is to remove the arc chutes
The arc chutes should be inspected for damage, missing pieces, and cleanliness
Low-pressure air can be used to clean out the arc chute assemblies
After the chutes are removed the circuit breakers main and arcing contacts should be visually inspected for alignment and wear
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Contact InspectionContact Inspection Silver-plated contacts
normally require little maintenance but may be surface dressed to assure maximum contact at the mated surfaces. This should not be aggressive enough to remove the silver plating or change the shape of the contact surface
If contacts are pitted or eroded they must be reconditioned or replaced
Contact alignment may be checked visually by conducting a “Slow-close” procedure on the breaker
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
DisconnectsDisconnects Ensure that there are no
broken elements and the disconnects fit snugly together when joined
Disconnects should be lubricated to help them mate together smoothly when installing or removing the breaker from its cubicle
Excessive lubrication will attract dust and other contaminants, and eventually introduce further problems
Apply the lubricant generously then wipe off all the excess
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Operating MechanismOperating Mechanism This inspection ensures
cleanliness, nuts, and bolts are tight, and there is no physical damage
The operating mechanism should be lubricated according to the breaker's maintenance manual to ensure it operates freely through its entire stroke
Avoid lubricant on the arc chutes and other electrical parts that may get hot during operation
The operating mechanisms should be cycled several times to make sure that they are working smoothly and are free from binding
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Contact ResistanceContact Resistance One of the most
important test is the contact resistance measurement across the breakers closed contacts
High contact resistance will cause overheating and eventual failures
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Contact ResistanceContact Resistance Low resistance bridges
provide indication of the contact resistance in microhms
The test set should have at least a 10A output for accurate readings
A LVCB should be less than 100 micro-ohms
Values should never exceed 1.5 times the value of a new breaker or 1.5 times the lowest reading of one pole
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Insulation Resistance TestsInsulation Resistance Tests Insulation resistance
(IR) tests are commonly performed with a megohmmeter
Test results should only be interpreted for comparative purposes
Does not indicate the quality of the primary insulation system from the point of view of dielectric strength
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Custom TrainingCustom TrainingCustomized training on your plants equipment
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Utility feeds to Plant “X”Utility feeds to Plant “X”
The Utillity provides two 120 kV lines to the facility
These lines enter the outdoor switchyard on the east side of the plant near the powerhouse
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Plant “X” Primary DistributionPlant “X” Primary Distribution
In the outdoor switchyard two power transformers reduce the 120 kV from the utility to 13.2 kV
The main transformers are oil filled, fan cooled, and are rated for a max load of 24/32/40 MVA
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Plant “X” Primary DistributionPlant “X” Primary Distribution The two Utility
transformers distribute 13.2 kV to the primary substation
Secondary selective design consisting of:
– Two main 2000A breakers
– A 2000A tie breaker
– Eight feeder breakers
– Two main busses, 1000 and 2000
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Plant “X” Primary DistributionPlant “X” Primary Distribution
FDR 1004
Subs21C
22C 23C 24C
FDR 1003
Subs21A
22A 23A 24A
FDR 1002
Sub 8E
FDR 1001 P/H
Main Bus 1
FDR 2002 Sub 8D
FDR 2003
Subs21B
22B 23B 24B
FDR 2004 Subs 21D 22D 23D 24D
FDR 2001 P/H
Main Bus 2
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Plant “X” Primary DistributionPlant “X” Primary Distribution
Each breaker enclosure door contains its associated
– Relays
– Power monitoring
– Control circuits allowing for breaker operation with the door closed via a toggle switch mounted on the door
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Plant “X” Primary DistributionPlant “X” Primary Distribution
The circuit breakers in the primary substation are 15kV “General Electric Power Vac” Vacuum circuit breakers
The operation and maintenance of these breakers will be discussed later in this course
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Plant “X” Primary DistributionPlant “X” Primary Distribution The 13.2kV
substation in the powerhouse is a similar arrangement to the primary substation that was just discussed
Two main breakers feed busses 1 and 2 that each has 7 feeder breakers for distribution
Bus 1 and 2 are connected via a tie breaker.
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Plant “X” Primary DistributionPlant “X” Primary Distribution
Breakers are ITE/BBC 15HK air circuit breakers
Control power for these breakers is provided by a 125VDC-battery system located in the substation
FrontRear
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Plant “X” Primary DistributionPlant “X” Primary Distribution
This battery system needs to be kept on line at all times in order for the breakers to trip open under fault conditions
Battery system maintenance will be discussed in chapter 3
The battery is maintained on a 130V “Float charge” by the battery-charging unit mounted on the wall
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
Power Plus EngineeringPower Plus Engineering IBEW Local 58
NETA Certified Technicians
Complete Service of power distribution equipment
Engineering Services
Customized Training Courses Available including:– Substation Safety and Operation
– Substation Maintenance
– LV Circuit Breaker Maintenance
(248) 344-0200
www.epowerplus.com
28064 Center Oaks Court, Wixom, MI 48393-3343 ¤ (248) 344-0200 / Fax (248) 305-9105
www.epowerplus.com email:[email protected]
POWER PLUS Engineering is a professional full service electrical testing and maintenance firm here to solve all of your AC and DC equipment and system needs
A large number of Michigan, Ohio and Indiana customers rely on POWER PLUS expertise to maintain and repair their electrical distribution systems and emergency power equipment.
POWER PLUS was founded in 1985 and specializes in AC and DC electrical equipment, systems and training.
POWER PLUS is a “Full Member In Good Standing” of the International Electrical Testing Association (NETA), is signatory to IBEW Local 58 and long-time member of the Construction Association of Michigan (CAM).
We are pleased to present our Web site to you. Take a few moments to see some of our services we provide.
www.epowerplus.comwww.epowerplus.com Be sure to
visit our website for:
– Service info
– Training Info
– Useful tools
– Presentation samples
– Contact information