Plant Integrity Case Study CUI Jetty

Embed Size (px)

Citation preview

  • 7/25/2019 Plant Integrity Case Study CUI Jetty

    1/1

    Plant Integrity LtdGranta Park, Gt Abington, Cambridge CB21 6GP

    T:+44 (0) 1223 893994 F:+44 (0) 1223 893944

    [email protected]

    www.plantintegrity.com

    TechnicalBrief

    A TWI Group Company

    Corrosion Under Insulation(CUI)

    The Teletest Focus+ system is a Guided Wave NDTTechnique developed for screening pipe-work forareas of metal loss damage.

    It is a pulse-echo system aimed to inspect largevolumes of material from a single test point. The initialapplication was for the detection of corrosion underinsulation for petrochemical plant industry, but it hasevolved to be used widespread in other inspectionsituations where pipes or tubes are not accessible.Examples of this are lines that are buried, encased ina sleeve or elevated above the ground.

    Plant Integrity Ltd was requested by one of its clientsin Argentina to employ the Teletest Focus+ systemon two cryogenic jetty lines at 8 and 3 diameters.The inspection proved to be very successful with100% of both lines being inspected over a 2 weekperiod.

    Figure 1 Location of anomaly area highlighted in fig 3

    Each jetty line was approximately 2km in lengthincluding several expansion loops and pipe bridges.Several anomalies were identified during theinspection and follow up was conducted whilst theoperators were still on-site. The first anomalyidentified was located during the opening shot of theinspection; this was of upmost interest to the client asthe location was in a difficult to access area seen infigure 1.An anomaly classified as medium priority wasidentified approximately -3m from the tool position(see figure 3).

    Figure 2 corrosion detected at 180

    The area of interest was directly above water so anaccess platform had to be erected to allow follow upto take place at this location. Upon removal of theinsulation the inspection team identified externalcorrosion at the 180 position seen in figure 2. Thisarea of corrosion was approximately 1 meter in lengthand 35% wall loss.

    Figure 3 TL01~location of detected anomaly

    The A-map scan (see figure 3)was also used in the

    identification of this anomaly. The signal from theweld identified at approximately -13m from the toolposition does not display an axi-symmetric response.This echo response from the weld signal should bedisplayed as an even distribution of colourrepresenting uniform circumferential signal amplitude.The above gave the operator increased confidencethat the signal seen at -3m was in fact attributed to awall loss defect.

    For information on how we can support your pipelineintegrity management programme, please contact us byemail at [email protected] or by telephone at ourCambridge, UK headquarters on 0044 1223 893994.

    1 meter

    Anomaly

    Weld