    PL-300 units are digital based multifunction protection

    relays that incorporate simultaneously in a single unit a great

    number of protection functions that can be selected within

    a set of options to create a solution adapted to any user'sneeds.

    Apart from the protection functions, they incorporate a wide

    range of optional characteristics as listed below:

    Reclosing unit: three-phase and by minimum frequency Measurement

    Communication features Oscillography Events

    Fault reports

    Fault locator

    PL-300 unit includes up to two rear communication ports

    that allow:

    To link the units to a Protection and Control Integrated

    System, by means of various communication protocols To access the status, historical data, and settings

    information, locally and/or remotely through telephone

    communications

    PL-300 control features allow it to be used as a bay controlin M.V. in small installations, when including command exe-

    cution capabilities and automatisms.

    The innovations in PL-300 range of protection relays within

    TEAM ARTECHE protection and control units are:

    Unified rated currents (1A-5A)

    Scale background: 200A

    Multiprotocol communications

    Class 0,5 in I, V, and P measures

    More digital inputs and outputs

    IRIG-B synchronization input

    Greater capacity and resolution of events reports,

    faults reports, oscilloperturbographic recording and

    measurement historical

    Measurement of unit temperature

    Aluminium box

    Battery voltage measurement

    6 setting tables

    4 ANSI curves, 6 IEC/BSC curves, 1 definite time and

    2 user programmable curves

    The units are avai lable in the following mechanical

    constructions:

    PL-300 Horizontal case:

    PL-300 Vertical case:

    PL-300 Integrated in TCP:

    Includes the same protection functions as PL-300 and

    additionally incorporates enhanced control and local

    automation functions ofTCP units (seeTCP catalogue).

    It is applied as protection and control unit for medium andhigh voltage bays.

    2

    INTRODUCTION

  • 8/12/2019 PL-300 Multifunction Relay

    3/203

    FUNCTIONAL DESCRIPTION

    Phase overcurrent (3*50/51) and neutral overcurrent(50N/51N)

    Protects the installations against phase to phase and phase

    to earth faults, with instantaneous trips (2 levels) and timed

    trips (programmable curves ANSI and IEC/BSC, and user

    curves).

    Phase directional overcurrent (67) and neutral directionalovercurrent (67N)

    If the model includes directional overcurrent, the type of

    polarization for phase and neutral directional can be

    selected by setting:

    67 Quadrature polarization Sequence polarization

    67N: Polarization by V0

    Polarization by V0, I0 (under request)

    Sequence polarization

    There are models of PL-300 that include a second

    directional overcurrent unit.

    If the 67N unit is current polarized, the T9 transformer

    should measure the polarization current.

    The connection of units that polarize by V0 will vary upon

    models, this voltage can be connected to T4, T5, T9 or

    internally calculated.

    PROTECTION FUNCTIONS

  • 8/12/2019 PL-300 Multifunction Relay

    4/20

    Sensitive neutral overcurrent (50/51SN)

    Models with sensitive neutral unit are able to detect very

    resistive earth faults. For sensitive neutral measurement, it isnecessary to use a toroid transformer connected to

    transformer T5 or T4, depending on the model chosen.

    If the model has directional overcurrent, the type of directio-

    nal for this function can be chosen via setting:

    angular watimetric I * cos f

    I * sen f

    Isolated neutral overcurrent (67IN)

    The high sensitivity and the directionality of this function

    allows detecting earth faults for isolated neutral systems

    and very resistive earth faults. The isolated neutral current is

    measured using the same transformer as that used for thesensitive neutral current measurement (see figure above).

    Voltage controlled overcurrent (51V)

    Lowers the pickup level of the overcurrent unit depending

    on the voltage level. This reduces the tripping time in case

    of severe faults (with voltage fall).

    Cold Load Pickup

    Avoids undesired trips produced by overcurrents at

    connection time.

    Tap changer lock (50TCL)

    Enables an independent current level to be set which can

    be used for various automatisms, such as tap changer lock,

    to prevent the regulator from acting when the current is

    enough to damage the tap changer.

    Current unbalance (46)

    Protects the installation against unbalances in current as a

    result of anomalies in the power system or unbalanced

    loads.

    Broken conductor (46BC)

    Detects when a phase of the installation comes down and

    protects bays against this anomaly.

    Breaker failure (50BF)

    Detects failures in breaker actuation, providing information

    to other protection units so that these accelerate their trip.

    The PL-300 includes a three phase 50BF unit, and there are

    models that include a single phase unit, monitoring each

    phase separately

    Overvoltage (59), undervoltage (27) and voltageunbalance (47)

    There are models of PL-300 with the following voltage

    functions: overvoltage, undervoltage and voltageunbalance, that can be independently enabled or disabled

    according to customer needs.

    Overvoltage function acts against voltage increases that

    could endanger the isolation and security of the protected

    units.

    Undervoltage function protects, those loads connected to

    the line, which are sensitive to line voltage drops.

    Voltage unbalance function protects the installation against

    the harmful effects of voltage unbalances, such as

    excessive warming in motors, current unbalances, etc.

    Zero sequence overvoltage (59N)

    Protects against earth isolation failures in machines. Zero

    sequence voltage can be obtained through an open delta

    connection of the secondaries of three voltage transformers

    (see polarization by V0 of 67N) or calculated as the vectorial

    sum of the three phase simple voltages.

    Thermal image (49)

    Protect elements such as lines, transformers, etc, against

    thermal overloads, calculating the temperature according tothe present and recent load conditions of the protected

    device.

    Fuse failure (68FF)

    Detects if a fuse has blown up in the secondary circuit of the

    voltage transformers. While detecting this situation,

    functions 51V, 27 and 59N will remain locked.

    4

  • 8/12/2019 PL-300 Multifunction Relay

    5/20

    Frequency unit (81 O, U, R)

    Frequency units protect the Power System against loss of

    balance between generated and demanded power.

    There are models of PL-300 with the following frequency

    functions: overfrequency and/or underfrequency and

    frequency rate of change, that can be enabled or disabled

    independently via setting according to customer needs.

    There are 5 steps of frequency that can be programmed

    independently as overfrequency or underfrequency,

    allowing an underfrequency load shedding.

    The frequency rate of change unit has 4 steps, this allows

    the disconnection of loads before reaching undesiredfrequency levels.

    Power protection (32)

    There are models of PL-300 with the following power

    functions, that can be independently enabled or disabled

    via setting according to customer needs:

    Minimum active and apparent power (independent) Maximum active and apparent power (independent) Reverse power

    The maximum and minimum power (active and apparent)

    units protect against excessive increases and decreases ofthe generated power.

    The reverse power protection acts against motorization of

    the generator.

    Zones and pilot protection (85)

    There are models of PL-300 that communicating with other

    terminals allow the next pilot protection schemes: Permissive overreach

    Permissive underreach Directional locking Directional unlocking

    Additional schemes: ECO

    Inverse direction locking

    To carry out these schemes, the instantaneous units of 67

    and 67N have 3 zones with independent settings for each

    zone. The direction of zones 1 and 2 is forwards and the

    zone 3 can be forwards or backwards.

    Breaker monitoring (74TC/CC)

    Breaker supervision by pole. Statistic of number of

    breaker manoeuvres and breaker health monitoring bySkI2 counter

    Possibility of supervision of 4 coils

    Protection functions locking feature

    Each of the protection functions can be locked by a digital

    input or logic function (see programmable logic).

    Syncrocheck (25)

    It is used to supervise the closing of a breaker with voltage

    on both sides. The function enables the closing when theangle, frequency and magnitude in both sides comply with

    the set conditions. Synchrocheck function is made by

    comparing voltages of phase B in both sides of the breaker.

    The measurement of T7 is used against measurement of T9

    or T5 connected to phase B of the other side of the

    breaker:

    Recloser (79)

    PL-300 units include a three-phase recloser and by

    actuation of the underfrequency unit (for models with 81Uunit) which gives a reclosure possibility for each step of the

    81U unit.

    The recloser also includes the option to enable the

    sequence coordination function. Such sequence

    coordination is applied when a number of units is installed

    downstream and have a slow trip programmed with the last

    reclosure. This function avoids the fast trip of the units that

    are in a higher level, during the fast trip of the units that are

    in the lower side.

    High Current Lockout (HCL)

    Provides a second instantaneous overcurrent unit at a

    higher setting, so that its actuation does not produce

    automatic reclosing.

    AUTOMATISMS

    5

  • 8/12/2019 PL-300 Multifunction Relay

    6/20

    Programmable logic

    The user can configure up to 15 logic signals, that can be

    assigned to output relays, LEDs, or inputs for protectionfunctions blocking features.

    Logic selectivity functions

    Logic selectivity functions that lockout the trip, but not the

    pick-up of the instantaneous overcurrent and isolated neu-

    tral directional units, can be done.

    Special automatisms

    The unit is provided by the following special automatisms:

    Slack springs automatism: the unit watches the status ofan input assigned as "slack springs". If this input is

    active during a time longer than the one programmed in

    setting "spring slack time" the output "open spring

    motor" is generated, this input is used to trip the switch

    of the spring tightening motor's power supply Voltage presence: The automatism watches if the

    average compound voltage is within particular values

    and gives a control signal. When the average compound

    voltage exceeds the presence threshold, the bit for the

    control word is set to 1, and if it falls below the absence

    threshold, that bit is set to 0

    Close locking: If the circuit breaker is seen as closed, no

    closing order is allowed from digital input, command,pushbutton or recloser

    Open locking: If the circuit breaker is seen as open, no

    opening order is allowed from digital input, command or

    pushbutton

    6

    Measurements

    The unit measures the following network parameters: Current for each phase (I) Neutral current (I)

    Phase to ground voltage in each phase (kV) Average phase to ground voltage (kV) Phase to phase voltage for each two phases (kV)

    Average phase to phase voltage (kV)

    Active power, three-phase and in each phase (MW)

    Reactive power, three-phase and in each phase (MVAR) Apparent power (MVA)

    Power factor Active energy counter (positive and negative)

    Reactive energy counter (positive and negative)

    Frequency (Hz) Current maximeter and power, three-phase and in each

    phase

    Harmonics distortion factor in IA, IB,IC, and average

    (in %) Harmonics distortion factor in VA, VB, VC and average

    (in %)

    Additionally, the PL-300 presents: Unit temperature measurement Optionally: Battery voltage measurement. The battery

    voltage measurement is executed using the units power

    supply input

    Events recording

    The unit stores in non volatile memory the last 400 events,

    which can be retrieved from a PC, with the following data: Date and time of the event

    Descriptive text of the event Values of electrical parameters

    DATA ACQUISITION FUNCTIONS

  • 8/12/2019 PL-300 Multifunction Relay

    7/20

    Oscillograph data recorder

    All the units have an oscillograph data recorder with the next

    characteristics: Each record comprises the samples from 9 analog

    signals and the status of 32 selectable digital signals 32 samples per cycle It is saved a maximum of 1200 cycles, and the number

    of cycles per record is programmable (for example: if 60

    cycles are selected, there will be 20 records of 60

    cycles). The prefault is programmable by setting.

    40 records of 30 cycles, 20 records of 60 cycles or 10

    records of 120 cycles with programmable prefault, this

    can be chosen via setting

    Configurable pickup

    Records in non volatile memory The disturbances are collected and exported in COM-

    TRADE format

    Historical reports

    A queue of 4000 historical records is stored in thenon-volatile memory. Each record has currents, voltages

    and maximum and minimum powers (active, reactive and

    apparent), detected in a programmable time span.

    Fault records

    The last 20 faults are stored in the non volatile memory, with

    the following data: Date and time of the fault pickup, beggining and end.

    Prefault and fault values of electrical parameters Duration and type of fault Level of electrical parameters at the fault's ocurrence

    time

    Demand maximeter

    The unit stores the maximum current value, plus the time

    tag for the moment when it occurs.

    Fault locator (FL)

    There are models of PL-300 which have a fault locator unit.

    This unit processes the information collected for each fault

    and gives as a result of this calculation the distance to the

    fault point. The distance is given in Km, %, miles,... and it

    can be accesed via the display or the PC.

    Time synchronization

    Via communications Via demodulated IRIG-B input

    The unit has clock with backup battery.

    Setting tables

    The unit has 6 setting tables. The active table selection can

    be made through the keyboard/display, command from the

    protections console or digital input activation.

    7

  • 8/12/2019 PL-300 Multifunction Relay

    8/20

    Non-directional PL-300 family (figure 1):

    NB: 50/51 + 50/51N + 46 + 46BC + 50BF (3) +

    74TC/CC

    NC: NB model + 50/51SN + 49 + 51V + Cold Load

    Pickup + 50TCL + 68FF

    ND: NC model + 59 + 27 + 47 + 59N + 81O/U + 81R +

    25

    NE: ND model + FL

    Directional PL-300 family (figure 2):

    DB: 67 + 67N + 46 + 46BC + 50BF (3) + 74TC/CC

    DC: DB model + 67SN + 67IN + 49 + 51V + Cold Load

    Pickup + 50TCL + 68FF

    DD: DC model + 59 + 27 + 47 + 81O/U + 81R + 25

    DE: DD model + 2nd

    67/67N unit + 50BF ()

    DF: DE model + FL

    PL-300 for distributed generator interconnection family

    (figure 2):

    IB: 50/51 + 67N + 46 + 46BC + 50BF (3) + 74TC/CC

    + 68FF + 59 + 27 + 47 + 59N + 81O/U + 81R + 25 +

    32 + 79 + 79 (81U) + High Current Lockout

    IC: IB model + 49 + 51V + Cold Load Pickup + 50TCL

    + 2nd

    67/67N unit

    PL-300 for distribution centres family:

    CR: /51 + 50/51N + 46 + 46BC + 50BF (3) + 74TC/CC

    + 49 + 79 + High Current Lockout

    Figure 1

    Figure 2

    Figure 3

    8

    MODELS

    All models incorporate the following special automatisms: slack springs automatisms, voltage presence, open locking and

    close locking.

  • 8/12/2019 PL-300 Multifunction Relay

    9/209

    SETTING RANGES (6 tables)

    Setting Range StepTimed unit (A) 0.1-200 0.01Instanatenous unit (A) 0.1-200 0.01

    Phase and neutral overcurrent units (indep.)

    Setting Range Step

    Pickup (%) 1-200 1Timing (s) 0-60 0.01

    Minimum active and apparent power units (independent)

    Ajuste Rango Paso

    Timed unit (A) 0.005-10 0.001Instantaneous unit (A) 0.005-10 0.001

    Sensitive neutral overcurrent unit

    Setting Range Step

    Pickup (I2/I1) 0.1-0.5 0.01

    Definite time (s) 0.05-300 0.01

    Broken conductor unit

    Setting Range StepTimed pickup (A) 0.1-200 0.01Instantaneous pickup (A) 0.1-200 0.01

    Current unbalance unit

    Setting Range StepLow current (A) 0.005-1 0.001High current (A) 0.005-1 0.001Low voltage (V) 0.5-60 0.1High voltage (V) 0.5-60 0.1First trip timming (s) 0-60 0.01

    Isolated neutral overcurrent unit

    Setting Range Step

    Timed pickup (V2/V1) 0.1-0.5 0.01

    Definite time (s) 0-600 0.01Additional time (s) 0-60 0.01

    Voltage unbalance unit

    Setting Range Step

    Control voltage (V) 10-200 0.1

    Voltage controlled overcurrent unit

    Setting Range Step

    Nominal current (A) 0.2-100 0.1Alarm threshold (%) 80-100 1Heating ratio (min.) 3-60 1Cooling ratio (min.) 3-180 1

    Thermal image unit

    Setting Range Step

    Supervision frequency (Hz) 45-65 0.01Minimum current (A) 0-100 0.1df/dt pickup (Hz/s) 0.2-5 0.1Additional time (s) 0-2 0.01

    Frequency rate of change unit

    Setting Range Step

    HI-Set (%) 1-200 1Timing (s) 0-60 0.01LO-Set (%) 1-200 1Timing (s) 0-100 0.1

    Maximum active and apparent power units (independent)

    Setting Range Step

    HI-Set (%) 1-200 1

    Timing (s) 0-60 0.01LO-Set (%) 1-200 1Timing (s) 0-100 0.1

    Reverse power unit

    Setting Range Step

    Min. frequency conditions to reclose YES/NOMin. frequency value for reclosing (Hz) 45-65 0.01Reclosing time (s) 1-1000 1Security time (s) 1-300 1

    Minimum frequency recloser

    Setting Range StepNumber of closures 0-4 11st closure time for phase to phase faults (s) 0.05-100 0.012nd closure time for phase to phase faults (s) 1-600 13rd closure time for phase to phase faults (s) 1-600 14th closure time for phase to phase faults (s) 1-600 11st closure time for phase to earth faults (s) 0.05-90 0.12nd closure time for phase to earth faults (s) 1-600 13rd closure time for phase to earth faults (s) 1-600 14th closure time for phase to earth faults (s) 1-600 1Security time for phase to phase faults (s) 1-600 1Security time for phase to earth faults (s) 1-600 1Security time after manual closure (s) 1-600 1Dead time for Vref (s) 1-600 1

    Recloser

    Setting Range StepMinimum voltage side A (V) 10-200 1Minimum voltage side B (V) 10-200 1Enable "if not A and not B" YES/NOEnable "if not A and B" YES/NOEnable "if A and not B" YES/NOVoltage difference enable YES/NOVoltage difference (V) 2-90 1Frequency difference enable YES/NOFrequency difference (Hz) 0.05-2 0.01Angle difference enable YES/NO

    Angle difference () 5-50 1Checking time (s) 0-100 1

    Synchrocheck

    Setting Range Step

    Type of frequency Max./MinFrequency (Hz) 45-65 0.01Definite time (s) 0-60 0.01Minimum supervision voltage (V) 40-200 1

    Underfrequency and Overfrequency units

    Setting

    Curve type Definite timeInverse BSC

    Very Inverse BSCExtremely Inverse BSCInverse short time BSCInverse long time BSC

    Inverse ANSIVery Inverse ANSI

    Extremely Inverse ANSIModerately inverse time ANSIUser curve (USAR1 or USAR2)

    Relapse with disc emulation option

    Setting Range StepTime index 0.05-30 0.01Definite time (s) 0-600 0.01Inst. addit. time (s) 0-60 0.01

    Time characteristics

    Setting

    Type selection Permissive overreachPermissive underreach

    Directional lockDirectional unlock

    Setting Range StepRTP input dropout time 0-1.00 0.01Block additional time 0-1.00 0.01Loss of guard delay 0-0.20 0.01ECO enable YES/NOMinimum RTP delay for ECO 0-9.9 0.1Reverse directional lock enable YES/NOReverse directional lock definite time 0-9.9 0.1

    Pilot protection schemes

    Setting Range Step

    Phase angle 0-359 1Neutral angle 0-359 1Minimum polarization voltage (V) 1.0-15.0 0.1

    Directional unit

    Setting Range StepTimed unit (V) 10-200 0.1Instantaneous unit (V) 10-200 0.1

    Overvoltage and undervoltage units (independent)

    Setting Range StepTimed unit (V) 2-200 0.1Instantaneous unit (V) 2-200 0.1

    Zero sequence overvoltage unit

    Setting Range StepPhase restore (A) 0.1-200 0.01Neutral restore (A) 0.1-200 0.01Definite time (s) 0-60.00 0.01

    Breaker failure unit

    Setting Range StepActivation trip number 1-4 1Pickup (A) 0.1-200 0.01Additional time (s) 0-60 0.01

    Phase and neutral High current lockout units (independent)

    Note: All the units have an enable setting.

  • 8/12/2019 PL-300 Multifunction Relay

    10/20

    Power supply24-48 Vdc

    Range 18-60 Vdc Ripple over 48 Vdc 20 % over rated125-220 Vdc

    Range 86-280Vdc Ripple over 220 Vcc 20 % over ratedBurden 8W mn

    18W max

    Current circuitsThermal capacity for phase/neutral current (UNIFIED RATED CURRENT 5/1A)

    Continuous 20 A For 1 sec. 500 A For cycle 1250 A Burden for In = 5A

  • 8/12/2019 PL-300 Multifunction Relay

    11/20

    The PL-300 units allow the communication and dialogue

    with the user through the associated peripherals:

    Keyboard-display

    Featuring:

    2 line 16 character LCD with programmable language:

    spanish/english 16 key keyboard

    Optical signalling: 7 programmable red LEDs and 1 two-

    colour status LED 4 signalled push-buttons with programmable functiona-

    lity. The functionality of these push-buttons are chosen

    by setting:

    a- Deactivated

    b- Functionality programmable by the user

    c- Programmed as indicated below

    Breaker closure with signalled LED

    Breaker open with signalled LED

    Breaker control: Local/Remote with signalling LED

    Maneuver permission

    When you select the four push-buttons to have

    programmable functionality, the keys of the keyboard can

    also be programmed to carry out commands, which are set

    by the user.

    Allows:

    Displaying of inputs, measurements, date and time,

    statistical data and last fault Displaying and modification of active table, settings,

    inputs, outputs and LEDs allocation, except the

    programmable logic and the oscillograph data recorder

    Communications: Local and remote

    The units has:

    1 RS232 front serial port, for direct connection to a PC 1 or 2 rear serial outputs for connection to a PC, modem

    or Integrated Protection and Control System. The rear

    terminals can be: RS232, RS485, glass F.O. or plastic

    F.O.

    Rear port's programmable communication protocols

    The communications protocol for the first rear port (COM-1)

    is always Procome. The protocol of the second rear port

    (COM-2), If exists, is programmable.

    The user can choose via setting out of the next communi-

    cations protocols: Procome, DNP 3.0, MODBUS,IEC 870-5-101.

    TEAM ARTECHE uses the SIPCON Protections programm,

    developed for PCs running under WINDOWS. This

    programm allows clear and simple dialogue with the unit for

    access to the information stored in it and for setting as

    necessary.

    All the configuration accesses are password protected toprevent tampering by unauthorized personnel.

    The outstanding features of the SIPCON Protections

    programm include the following:

    Authomatic detection of the unit which it is in dialogue

    with

    Unit status display via status screens

    Presentation and modification of settings Filling and presentation of all information stored by the

    relay for its later study in higher levels: events, historical

    data, faults, etc.

    SIPCON Protections is compatible with the software used

    in TEAM ARTECHE's Integrated Protection and Control

    System, and can be incorporated into them as just one

    more functional module.

    11

    MAN-MACHINE INTERFACE

    SOFTWARE

  • 8/12/2019 PL-300 Multifunction Relay

    12/2012

    PIN TYPE TERMINALS

    Rear board example

    HorizontalModel

    Vertical Model

  • 8/12/2019 PL-300 Multifunction Relay

    13/2013

    CONNECTIONS DIAGRAMM PL-300 PIN TYPE TERMINALS

    Interconnection example

  • 8/12/2019 PL-300 Multifunction Relay

    14/2014

    CLOSED TERMINALS (for analog inputs)

    Rear board example

    Vertical Model

    HorizontalModel

  • 8/12/2019 PL-300 Multifunction Relay

    15/2015

    CONNECTIONS DIAGRAMM PL-300 CLOSED TERMINALS

    Interconnection example

  • 8/12/2019 PL-300 Multifunction Relay

    16/2016

    PL300 IN BOX DIMENSIONS

    HORIZONTAL

    VERTICAL

  • 8/12/2019 PL-300 Multifunction Relay

    17/2017

    PL300 IN TCP DIMENSIONS

    PL300 PIN TYPE TERMINALS IN TCP

  • 8/12/2019 PL-300 Multifunction Relay

    18/20

    Since it was founded,TEAM ARTECHE has committed itself

    to complying with the guideline laid out in its quality policy,

    oriented towards the continuous improvement of its

    products and services in each and every one of its activities,in order to obtain complete client satisfaction.

    The ISO 9001 international certificate shows that the

    desing, manufacturing and service provided by TEAM

    ARTECHE follow the most secure and stringent control and

    supervision procedures.

    Every unit manufactured byTEAM ARTECHE is designed to

    operate under severe electrical substation and industrial

    plant conditions, complying with the most exigent

    electromagnetic, environmental and mechanical tests, thus

    incorporating the CE mark of electromagnetic compliance.

    18

    QUALITY POLICY

    STANDARDS AND TESTS

    Electrical

    Immunity to electrostatic discharges IEC 61000-4-2 Class IV

    Immunity to fast transient bursts IEC 61000-4-4 Class IV

    Immunity to voltage pulses (surges) IEC 61000-4-5 Class IV

    Immunity to 1MHz damped wave IEC 61000-4-12 Class III

    Measurement of insulation resistance IEC-255-5

    Measurement of dielectric rigidity IEC-255-5 Class III

    Measurement of insulation with voltage pulses IEC 255-5 Class III

    Microcuts IEC 60870-2-1

    Electromagnetic

    Measurement of radiated electromagnetic interference EN55011 Class A, group 1

    Immunity to radiated radiofrequency fields IEC 61000-4-3 Class III

    Immunity to conducted radiofrequency signals IEC 61000-4-6 Class I II

    Immunity to 50Hz magnetic fields IEC 61000-4-8

    Mechanical

    Vibration IEC 255-21-1 Class I

    Shock and bump IEC 255-21-2 Class I

    Environmental

    Damp heat IEC 68-2-3 (+70C, 93% relative humidity)

    Dry heat IEC 68-2-2 (+85C)

    Cold IEC 68-2-1 (-40C)

    Change of temperature IEC 68-2-14 (-20/+70C, 2 of 4 hours cycle)

  • 8/12/2019 PL-300 Multifunction Relay

    19/20

    PL300 MODEL

    PL300 NB

    NC

    MODEL

    ND

    DBPL300

    DC

    DD

    IC

    IB

    DF

    CR

    NE

    Horizontal

    Vertical

    H

    V

    BOX TYPE

    POWER SUPPLY

    86-280 Vdc

    18-60 Vdc

    Z

    Y

    DIGITAL INPUTS VOLTAGE

    EXTENSION MODULE

    ANALOG INPUTS TERMINALS

    Closed terminals 2

    Range: 86-280 Vdc

    Range: 18-60 Vdc

    9 DIs (6 indepen.) + 7 DOs (3 indepen.)

    No module

    Z

    1

    Y

    0

    Pin type Standard terminals 1

    RS232 (COM-2) + RS232 (COM-1)

    GFO (COM-2) + RS232 (COM-1)

    RS485 (COM-2) + RS232 (COM-1)

    RS485

    PFO (COM-2) + PFO (COM-1)

    GFO (COM-2) + GFO (COM-1)

    RS232

    PFO

    REAR COMMUNICATION PORTS

    GFO A

    B

    C

    D

    E

    F

    I

    H

    G

    3

    2

    1

    SPECIAL FUNCTIONS AND AUTOMATISMS

    Battery voltage measurement and extended operating temperature

    79 + 79 (81U) + HCL + 85

    85

    79 + 79 (81U) + HCL

    No functions 0

    TTCP integrated

    DE

    Programmable Protocol

    Programmable Protocol

    Programmable Protocol

    Programmable Protocol

    Note 1

    Note 1

    Note 1

    Note 1

    Note 1

    Battery voltage measurement

    None

    Current polarized 67N

    0

    1

    No

    Yes

    0

    1

    Note 2

    Note 2

    PL300

    PL300

    Non directional

    Directional

    Interconnection

    Distribution center

    (only for directional PL-300 models)

    (only for directional PL-300 models)

    (included in models IB, IC and CR)

    2Extended operating temperature

    Battery voltage measurement and extended operating temp. 3

    If you want to have a printed manual with your relay, tell our sales departament.

    Both (only for models DD + current polarized 67N,

    V or I calculation

    V calculated

    I calculated

    None

    3

    2

    1

    0

    Specify also the language you want fot the manual (spanish or english).

    Note 3

    0

    N

    0 N

    TInternal communication for TCP

    DE + current polarized 67N, DF + current polarized 67N)

    Note 4

    Note 5

    Note 5

    19

    SELECTION TABLE

    Model NB I

    I calculated

    T4 T5 T9

    Model NC

    Model ND*

    Model ND*

    Model DC

    current polarized

    Model DB

    Model NE*

    Model DF*

    Model DD*

    Model DE*

    Model DD*

    Model CR

    Model IC

    Model IB

    Model DB +

    67N

    67N*current polarizedModel DC +

    67N*current polarizedModel DC +

    67N

    Model DD +current polarized

    67N

    Model DE +current polarized

    67N

    Model DF +current polarized

    67N*

    Model IB +current polarized

    67N*

    Model IB +current polarized

    67N*

    Model IC +current polarized

    Same transformer arrangement asmodel ND

    I

    V

    N

    SN

    0

    NI

    NI

    NI

    NI

    NI

    NI

    NI

    NI

    NI

    NI

    SNI

    SNI

    SNI

    SNI

    SNI

    SNI

    SNI

    SNI

    V0

    V0

    V0

    V0

    V0

    V0

    V0

    0I

    0I

    0I

    0I

    0I SYNCV

    SYNCV

    SYNCV

    SYNCV

    SYNCV

    SYNCV

    SYNCV

    V calculated

    I calculated

    I and V calculated

    I calculated

    V calculated

    I calculated

    V calculated

    V calculated

    0

    0

    0

    0

    0

    N

    N

    N

    N

    N

    Same transformer arrangement asmodel DD

    Same transformer arrangement asmodel DD + current polarized 67N

    Same transformer arrangement asmodel DD

    Same transformer arrangement asmodel IB + current polarized 67N

    model IBSame transformer arrangement as

    model DD + current polarized 67NSame transformer arrangement as

    0I VSYNC

    TRANSFORMER ARRANGEMENT

    Note 1: For models with 2 communications ports the communication protocol of the port COM-2 is programmable and the one of the port COM-1 is always Procome

    protocol.

    Note 2: The unit 79 (81U) is only for models with function 81U.

    Note 3: For models marked with an * in the transformer arrangement table.

    Note 4: Only for models with 67N and T9 = I0

    Note 5: When T box type is selected, the rear communication option to select must be T: Internal communication for TCP.

    Continuous improvement of its products i s TEAM ARTECHEs one of the

    main objetives, consequently, this catalogues information, can be modified

    without previous advise. To get a completer information, consult the manual or

    contanct our sales department.