PG&E’s Applied Technology Services’ Hot Water Technology Performance Laboratory Edwin Huestis, P.E. Senior Mechanical Engineer PG&E Applied Technology Services ACEEE Hot Water Forum February 23, 2016

PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

PG&E’s Applied Technology Services’ Hot Water Technology Performance

Laboratory

Edwin Huestis, P.E.

Senior Mechanical Engineer

PG&E Applied Technology Services

ACEEE Hot Water Forum

February 23, 2016

Page 2: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Presentation Objectives

• Describe the history of hot water testing at PG&E’s Applied Technology Services (ATS)

• Summarize the results of the last effort

• lab testing effort on Identify the opportunities for future research presented at the conclusion of the last study

• Describe the vision of PG&E’s Upgraded Hot Water Technology Performance Laboratory

• Identify how PG&E’s laboratory will be modified to support of commercial kitchen field performance characterization research

2

Page 3: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

PG&E Applied Technology Services (ATS)

3

• Multidisciplinary team of Engineers, Technologists, Technicians and Scientists

• Act as an internal PG&E consultant, also perform some 3rd Party work

Vibration AnalysesNon-Destructive ExaminationEnd use Equipment

Testing

Page 4: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

4

History of Hot Water Testing at ATS – Residential Water Heater Testing

• Started off supporting the development of ASHRAE standards

Page 5: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Residential Hot Water Draw Simulation – Flow Measurement and Control

5

Page 6: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Residential Lab Hot Water Draw Simulation – Flow Measurement and Control (Staged Volume Draws)

6

¾” Line Fed from EUT

Pressure Compensating

Valves

Remotely Actuated Isolation Valves

Cori

olis

Flo

w M

eter

To Drain

Page 7: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Field Characterization of Restaurant Hot Water Use (Completed by Fisher Nickel - FSTC)

• Fisher-Nickel conducted field monitoring at a quick service restaurant to gather a high resolution 24-hour “real world” hot water use profile

Page 8: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

8

END USES W/ AUTOMATED VALVESWATER HEATERUNDER TEST

RECIRCULATION LOOP

PG&E Applied Technology ServicesCommercial Water Heater Laboratory Configuration

• PG&E installed and fully instrumented and functional replication of the hot water system monitored in the field study. Tested various retrofit and RCx measures.

Page 9: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

9

PG&E Applied Technology ServicesCommercial Water Heater Laboratory Configuration (cont’d)

• Commercial and Residential Testing in same lab space

Page 10: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

10

Measuring Commercial Hot Water System Performance: System Delivery Efficiency vs. WH Thermal Efficiency

~ Output Energy/Input Energy

Page 11: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

11

Measuring Commercial Water Heater System Performance: System Delivery Efficiency vs. WH Thermal Efficiency

Page 12: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

12

Energy Performance Impact Summary: Standard Efficiency Tank-Type Water Heater - RCx and Retrofit Measures

Page 13: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

13

Energy Performance Impact: Stratification in High Efficiency Tank-Type Water Heater – Standby Loss & T.E.

Standby Loss - 1.28% - 670.0 Btu/h

Page 14: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

14

Energy Performance Impact: Stratification in Standard Efficiency Tank-Type Water Heater – Standby Loss & T.E.

Standby Loss - 2.58% - 1654.0 (Btu/h)

Page 15: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

15

Opportunities for Future Research – Distribution System Scenarios – PG&E CHWH

Page 16: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

16

PG&E Applied Technology ServicesHot Water Technology Laboratory Vision

• Include capabilities of past residential and commercial test systems

• Employ modular laboratory design, easily adaptable to changing test setups, specifically distribution system

• Design instrumentation plan and DAS system for versatility

• Automation of tests via National Instruments Labview DAS

• Continued focus maintaining high instrument accuracy and control of test variables

• Rely on industry for guidance and new ideas, also attempt to develop our own

Vision for PG&E’s Upgraded Hot Water Technology Laboratory

Page 17: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

PG&E Applied Technology ServicesImplementing the Hot Water Technology Laboratory Vision

17

Hot Water Distribution SystemCity Water

Tempering System

Chiller

Water Heater

Tempered City Water Loop Pump

TemperingTank

(Future) Residential/Other

Units

Commercial Units

Hot Water Supply

Hot Water Dem

and –Sim

ulation of End Uses

Page 18: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Regulating City Water Pressure

18

Page 19: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Conditioning City Water - Tempering System

19

Hot Water Tank

1.5 Ton Chiller

Mixing Tank

Page 20: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Conditioning City Water - Tempering System

20

Page 21: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Distribution System – Piping Rack

21

Page 22: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Hot Water Draw Simulation – Flow Measurement and Control (Constant, Staged and Variable Volume)

22

Page 23: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Hot Water Draw Simulation – Flow Measurement and Control (Constant, Staged and Variable Volume)

23

Flow Meters

2-Way Modulating

Valve

8 Si

mul

ated

End

Use

s

1

2

3

4

5

6

7

8

Constant Volumetric Flow

Control

Coriolis Mass Flow

Meter (Collects all

Flow For Comparison)

Solenoid Isolation

Valve

3-WayDiverter

Valve (Throttling vs.

Constant Volume)

*ATS Likely to add additional

end uses

Page 24: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Hot Water Draw Simulation – Flow Measurement and Control (Constant Volume Draws)

24

Flow Meter2-Way

Modulating Valve

Constant Volumetric Flow

Control

(Open)

3-Way Diverting

Valve

IsolationValve

To Drain

Single DrawFrom

Distribution System

Volumetric Flow between .2 – 3.0 gpm (smaller valves)

.7 – 20 (larger valves)

“Larger” Pressure Compensating Valve “Smaller” Pressure

Compensating Valve

Page 25: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Hot Water Draw Simulation – Flow Measurement and Control (Variable Volume Draws) (Not Implemented Yet)

25

Flow Meter2-Way

Modulating Valve

Bypassed Constant Volumetric Flow

Control

(Modulating)

3-Way Diverting

Valve

IsolationValve

To Drain

Single DrawFrom

Distribution System

Variable Volume Flow Draw

Flow

Equivalent Constant Volume Flow Draw

Flow

Flow

Equivalent Staged Volume Flow Draw

Page 26: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Temperature Measurement and Calibration

26

4-wire RTD’s Almost Exclusively Used

Isothermal Block for Temperature Calibration

Page 27: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Pressure Measurement and Calibration

27

Rosemount Pressure Transmitters for Natural Gas

Flow Compensation

Dead Weight Tester – Calibration Standard

*Omega pressure transmitters purchased for measuring pressure drop in piping network

Page 28: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Flow Measurement and Calibration

28

Coriolis Flow Calibration Standard

Coriolis Flow Meter

Diaphragm Meter w/ Pulsing Transmitter

Nutating Disc Hot Water Meter

Page 29: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

29

Opportunities for Future Research – Account for Human Factors

Page 30: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

Accounting for Human Factors – Temperature Feedback and Min Temperature Criteria

30

Flow Meter2-Way

Modulating Valve

Bypassed Constant Volumetric Flow

Control

(Modulating)

3-Way Diverting

Valve

IsolationValve

To Drain

Single DrawFrom

Distribution System

• Force solenoid valve to remain open until water reaches specified temperature, and for a specified duration/volume

Page 31: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

31

Summary of Test Conditions

Build Baseline and Optimized Distribution System on Rack• Run Tests using each of the following

• (2) Standard Efficiency Tankless Units (199,000 Btuh ea)

• (1) Condensing Tankless (250,000 Btuh)• (1) Standard Efficiency Tank (199,000 Btuh)• (1) Condensing Tank (199,000 Btuh)

• If possible, vary recirc return port location (upper/lower)

• Add insulation, program timeclock, aquastat, D’mandcirculation, modify drop dimensions

• Run a variety of flow profiles if time permits

Page 32: PG&E’s Applied Technology Services’ Hot Water …...2016/02/23  · Hot Water Technology Laboratory Vision •Include capabilities of past residential and commercial test systems

32

Thank You

Questions?

[email protected]