INRPHAR1 68 BLOCK BLK2H PHHPTOC1 50-1 BLOCK ENA_MULT OPERATE START PHIPTOC1 50-2 BLOCK ENA_MULT OPERATE START PHLPTOC1 51 BLOCK ENA_MULT OPERATE START EFHPTOC1 50N-1 BLOCK ENA_MULT OPERATE START EFIPTOC1 50N-2 BLOCK ENA_MULT OPERATE START EFLPTOC1 51N BLOCK ENA_MULT OPERATE START OR6 B1 B2 B3 B4 B5 B6 O TRPPTRC1 86 BLOCK OPERATE RST_LKOUT TRIP CL_LKOUT NOT IN OUT TCSSCBR1 95-1 BLOCK ALARM NOT IN OUT TCSSCBR2 95-2 BLOCK ALARM NOT IN OUT OR B1 B2 O CCBRBRF1 CBFP BLOCK START POSCLOSE CB_FAULT CB_FAULT_AL TRBU TRRET EFLPTOC2 51G BLOCK ENA_MULT OPERATE START OR6 B1 B2 B3 O OR B1 B2 O INRUSH 50-1_OPERATE 50-1_START 50-2_OPERATE 50-2_START 51_OPERATE 51_START 50N-1_OPERATE 50N-1_START 50N-2_OPERATE 50N-2_START 51N_OPERATE 51N_START 50-1_OPERATE 50-2_OPERATE 50N-1_OPERATE 50N-2_OPERATE 51_OPERATE 51N_OPERATE INRUSH INRUSH INRUSH INRUSH INRUSH INRUSH LOCKOUT OPTD LOCKOUT NOT OPTD TRIP CKT-1 FAULTY TRIP CKT-2 FAULTY TRIP CKT HEALTHY CBFP OPTD 51G_OPERATE 51G_START 51G_OPERATE PROTECTION TRIP PROTECTION TRIP PROTECTION TRIP 59_OPERATE CB ON 51,51N OPTED PROTECTION SHEET-1 A A B B C C D D E E 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 Main Application: MainApp, Page: 1 Rev. Modification Rel. date Created by Replacing Based on Project CPCL Responsible department ABB Ltd. CPCL.Substation.Voltage Level.Bay Technical reference Document kind Graphical Application Configuration Doc. designation IC_2_SYNF979 Created by Title REF615 INCOMER-2OC REF615 Document id. Approved by Rev. 0 Rel. date 9/25/2015 Lang. en 1 / 7

pdf

Embed Size (px)

Citation preview

Page 1: pdf

INRPHAR1

68

BLOCK BLK2H PHHPTOC1

50-1

BLOCKENA_MULT

OPERATESTART

PHIPTOC1

50-2

BLOCKENA_MULT

OPERATESTART

PHLPTOC1

51

BLOCKENA_MULT

OPERATESTART

EFHPTOC1

50N-1

BLOCKENA_MULT

OPERATESTART

EFIPTOC1

50N-2

BLOCKENA_MULT

OPERATESTART

EFLPTOC1

51N

BLOCKENA_MULT

OPERATESTART

OR6B1B2B3B4B5B6

O

TRPPTRC1

86

BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

NOTIN OUT

TCSSCBR1

95-1

BLOCK ALARM

NOTIN OUT

TCSSCBR2

95-2

BLOCK ALARM

NOTIN OUT

ORB1B2

O

CCBRBRF1

CBFP

BLOCKSTARTPOSCLOSECB_FAULT

CB_FAULT_ALTRBU

TRRET

EFLPTOC2

51G

BLOCKENA_MULT

OPERATESTART

OR6B1B2B3

O

ORB1B2

O

INRUSH50-1_OPERATE50-1_START

50-2_OPERATE50-2_START

51_OPERATE51_START

50N-1_OPERATE50N-1_START

50N-2_OPERATE50N-2_START

51N_OPERATE51N_START

50-1_OPERATE50-2_OPERATE

50N-1_OPERATE50N-2_OPERATE

51_OPERATE51N_OPERATEINRUSH

INRUSH

INRUSH

INRUSH

INRUSH

INRUSH

LOCKOUT OPTD

LOCKOUT NOT OPTD

TRIP CKT-1 FAULTY

TRIP CKT-2 FAULTYTRIP CKT HEALTHY

CBFP OPTD

51G_OPERATE51G_START

51G_OPERATE

PROTECTION TRIP

PROTECTION TRIP

PROTECTION TRIP

59_OPERATE

CB ON

51,51N OPTED

PROTECTION SHEET-1

A A

B B

C C

D D

E E

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

Main Application: MainApp, Page: 1

Rev. Modification Rel. date Created by

Replacing

Based on

ProjectCPCL

Responsible departmentABB Ltd.

CPCL.Substation.Voltage Level.Bay

Technical reference Document kindGraphical Application Configuration

Doc. designationIC_2_SYNF979

Created by Title

REF615 INCOMER-2OCREF615

Document id.

Approved by Rev.0

Rel. date9/25/2015

Lang.en

1 / 7

Page 2: pdf

SEQRFUF1

FUSE FAIL

BLOCKCB_CLOSEDDISCON_OPENMINCB_OPEN

FUSEF_3PHFUSEF_U

ORB1B2

OPHPTUV1

27

BLOCK OPERATESTART

PHPTOV1

59

BLOCK OPERATESTART

SECRSYN1

25

BLOCKCL_COMMANDBYPASS

SYNC_INPROSYNC_OK

CL_FAIL_ALCMD_FAIL_AL

LLDBLLLBDLLBDLDB

ORB1B2

O

ANDB1B2

O

ANDB1B2

O

ORB1B2

O

27_OPERATE27_START

59_OPERATE59_START

CB ON

LINE-B PT FAIL ALARM

LINE-B PT FUSE FAIL

VTG >80%

LINE HEALTHY

SYNC OK

BUS DEAD

PROTECTION SHEET-2

A A

B B

C C

D D

E E

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

Main Application: MainApp, Page: 2

Rev. Modification Rel. date Created by

Replacing

Based on

ProjectCPCL

Responsible departmentABB Ltd.

CPCL.Substation.Voltage Level.Bay

Technical reference Document kindGraphical Application Configuration

Doc. designationIC_2_SYNF979

Created by Title

REF615 INCOMER-2OCREF615

Document id.

Approved by Rev.0

Rel. date9/25/2015

Lang.en

2 / 7

Page 3: pdf

NOTIN OUT

NOTIN OUT

NOTIN OUT

NOTIN OUT

NOTIN OUT

CB IN TEST

CB ON

CB IN SERVICE

LOCAL CLOSE

LINE-B PT FAIL ALARM

BC ON & IN SERVICE

IC-1 ON & IN SERVICE

IC-2 & BC NO FAULT

AIM IN IND

AIM IN MANUAL

TSS ON IC-2

IC-1 UV

REMOTE CLOSE

CB OFF

LOCKOUT OPTD

TRIP CKT HEALTHY

BC OFF&SERV

IC-1 OFF&SERV TSS NOT ON IC-2

NO IC-1 UV

CB OPEN CMD O/P

27_START

CB CLOSE CMD O/P

51,51N OPTED

CB OFF

CB ON

X110 (BIO).X110-Input 1

X110 (BIO).X110-Input 2

X110 (BIO).X110-Input 3

X110 (BIO).X110-Input 4

X110 (BIO).X110-Input 5

X110 (BIO).X110-Input 6

X110 (BIO).X110-Input 7

X110 (BIO).X110-Input 8

X120 (AIM).X120-Input 1

X120 (AIM).X120-Input 2

X120 (AIM).X120-Input 3

X120 (AIM).X120-Input 4

X130 (AIM).X130-Input 1

X130 (AIM).X130-Input 2

X130 (AIM).X130-Input 3

X130 (AIM).X130-Input 4

X100 (PSM).X100-PO1

X100 (PSM).X100-PO2

X100 (PSM).X100-SO1

X100 (PSM).X100-SO2

X100 (PSM).X100-PO3

X100 (PSM).X100-PO4

X110 (BIO).X110-SO1

X110 (BIO).X110-SO2

X110 (BIO).X110-SO3

X110 (BIO).X110-SO4

BINARY INPUT & OUTPUT SHEET

A A

B B

C C

D D

E E

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

Main Application: MainApp, Page: 3

Rev. Modification Rel. date Created by

Replacing

Based on

ProjectCPCL

Responsible departmentABB Ltd.

CPCL.Substation.Voltage Level.Bay

Technical reference Document kindGraphical Application Configuration

Doc. designationIC_2_SYNF979

Created by Title

REF615 INCOMER-2OCREF615

Document id.

Approved by Rev.0

Rel. date9/25/2015

Lang.en

3 / 7

Page 4: pdf

LED1

LOCKOUT OPTD

OKALARMRESET

LED2

51G OPTD

OKALARMRESET

LED3

LINE UV

OKALARMRESET

LED4

OVER VTG

OKALARMRESET

LED5

LPT-A FUSE

OKALARMRESET

LED6

CBFP OPTD

OKALARMRESET

LED7

TCS FAULTY

OKALARMRESET

LED8

CB COND MONT

OKALARMRESET

LED9OKALARMRESET

LED10

SYNC CHECK OK

OKALARMRESET

LED11OKALARMRESET

ANDB1B2

OTRIP CKT-1 FAULTY

TRIP CKT-2 FAULTY

51G_OPERATE

27_OPERATE

59_OPERATE

LINE-B PT FUSE FAIL

CBFP OPTD

CB COND MONT ALARM

SYNC OK

51,51N OPTED

ALARM LED SHEET

A A

B B

C C

D D

E E

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

Main Application: MainApp, Page: 4

Rev. Modification Rel. date Created by

Replacing

Based on

ProjectCPCL

Responsible departmentABB Ltd.

CPCL.Substation.Voltage Level.Bay

Technical reference Document kindGraphical Application Configuration

Doc. designationIC_2_SYNF979

Created by Title

REF615 INCOMER-2OCREF615

Document id.

Approved by Rev.0

Rel. date9/25/2015

Lang.en

4 / 7

Page 5: pdf

CBXCBR1

BKR

POSOPENPOSCLOSEENA_OPENENA_CLOSEBLK_OPENBLK_CLOSEAU_OPENAU_CLOSEITL_BYPASS

SELECTEDEXE_OPEXE_CL

OPENPOSCLOSEPOS

OKPOSOPEN_ENAD

CLOSE_ENAD

DCSXSWI1

BKR

POSOPENPOSCLOSE

OPENPOSCLOSEPOS

OKPOS

SSCBR1

CBCM

BLOCKPOSOPENPOSCLOSEPRES_ALM_INPRES_LO_INSPR_CHR_STSPR_CHRRST_IPOWRST_CB_WEARRST_TRV_TRST_SPR_T

TRV_T_OP_ALMTRV_T_CL_ALMSPR_CHR_ALM

OPR_ALMOPR_LO

IPOW_ALMIPOW_LO

CB_LIFE_ALMMON_ALM

PRES_ALMPRES_LO

OPENPOSINVALIDPOSCLOSEPOS

AND6B1B2B3B4B5B6

O

ORB1B2

O

ORB1B2

O

AND6B1B2B3B4

O

AND6B1B2B3B4B5B6

O

ORB1B2

O

ANDB1B2

O

ORB1B2

O

ANDB1B2

O

ORB1B2

O

CB CLOSE CMD O/P

CB COND MONT ALARM

CB OFFCB ON

IC-2 & BC NO FAULTTRIP CKT HEALTHY

CB OFFLINE HEALTHY

CB IN TESTCB CLOSE ENA

CB IN TESTCB IN SERVICE

CB OFFCB ON

CB CLOSE ENA

IC-1 OFF&SERVBC OFF&SERV

BUS DEADAIM IN IND

TSS NOT ON IC-2AIM IN MANUAL

IC-1 ON & IN SERVICEBC ON & IN SERVICE

SYNC OK

CLOSE ENA IN IND/MAN

CLOSE ENA IN IND/MAN

CB IN SERVICE

LOCAL CLOSEREMOTE CLOSE

CB IN TESTLOCAL CLOSE

CB CLOSE CMD

CB IN SERVICE

CB OPEN CMD O/P

CB OPEN CMDCB CLOSE CMD

LOCKOUT NOT OPTD

LOCKOUT NOT OPTD

CONTROL SHEET-1CB CONTROL BLOCK

CB CLOSING INTERLOCK IN TEST/SERVICE

CB CLOSING INTERLOCK WHEN AIM IN IND/MAN

CB CLOSING CMD IN SERVICE/TEST POSITION

A A

B B

C C

D D

E E

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

Main Application: MainApp, Page: 5

Rev. Modification Rel. date Created by

Replacing

Based on

ProjectCPCL

Responsible departmentABB Ltd.

CPCL.Substation.Voltage Level.Bay

Technical reference Document kindGraphical Application Configuration

Doc. designationIC_2_SYNF979

Created by Title

REF615 INCOMER-2OCREF615

Document id.

Approved by Rev.0

Rel. date9/25/2015

Lang.en

5 / 7

Page 6: pdf

AND6B1B2B3B4

O

TONGAPC1IN1IN2IN3IN4IN5IN6IN7IN8

Q1Q2Q3Q4Q5Q6Q7Q8

AND6B1B2B3

O

ANDB1B2

O

NOTIN OUT

ANDB1B2

O

OR6B1B2B3

O

ANDB1B2

O

CB ONCB IN SERVICE

BC ON & IN SERVICEIC-1 ON & IN SERVICE

TSS ON IC-2AIM IN MANUAL

CB ONCB IN SERVICE

CB OPEN CMD

27_OPERATENO IC-1 UV

CONTROL SHEET-2

A A

B B

C C

D D

E E

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

Main Application: MainApp, Page: 6

Rev. Modification Rel. date Created by

Replacing

Based on

ProjectCPCL

Responsible departmentABB Ltd.

CPCL.Substation.Voltage Level.Bay

Technical reference Document kindGraphical Application Configuration

Doc. designationIC_2_SYNF979

Created by Title

REF615 INCOMER-2OCREF615

Document id.

Approved by Rev.0

Rel. date9/25/2015

Lang.en

6 / 7

Page 7: pdf

CMMXU1BLOCK HIGH_ALARM

HIGH_WARNLOW_WARN

LOW_ALARM

PEMMXU1RSTACM

RESCMMXU1BLOCK HIGH_ALARM

HIGH_WARN

RESVMMXU1BLOCK HIGH_ALARM

HIGH_WARN

VMMXU1BLOCK HIGH_ALARM

HIGH_WARNLOW_WARN

LOW_ALARM

CSMSQI1

FLTMSTA1BLOCK

FMMXU1

IL1TCTR1

RESTCTR1

RDREC1C2C3C4C5C6C7C8C9C10C11C12C13C14C15C16C17C18C19C20C21C22C23C24C25C26C27C28C29C30C31C32C33C34C35C36C37C38C39C40C41C42C43C44C45C46C47C48C49C50C51C52C53C54C55C56C57C58C59C60C61C62C63C64

TRIGGERED

UL1TVTR1

RESTVTR1

UL1TVTR2

VSMSQI1

INRUSH50-1_START50-2_START

50N-1_START50N-2_START

51_START51N_START

50-1_OPERATE50-2_OPERATE

50N-1_OPERATE50N-2_OPERATE

51_OPERATE51N_OPERATE

LOCKOUT OPTDTRIP CKT-1 FAULTYTRIP CKT-2 FAULTY

CB CLOSE CMD O/PCBFP OPTD

VTG >80%

27_START59_START

51G_START

27_OPERATE59_OPERATE

51G_OPERATE

CB OPEN CMD O/P

CB IN TESTCB ON

CB IN SERVICEAIM IN IND

AIM IN MANUALBC ON & IN SERVICEIC-2 & BC NO FAULT

IC-1 ON & IN SERVICEIC-1 UV

LINE-B PT FAIL ALARMREMOTE CLOSE

LOCAL CLOSETSS ON IC-2

MEASUREMENT & DR SHEET

A A

B B

C C

D D

E E

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

Main Application: MainApp, Page: 7

Rev. Modification Rel. date Created by

Replacing

Based on

ProjectCPCL

Responsible departmentABB Ltd.

CPCL.Substation.Voltage Level.Bay

Technical reference Document kindGraphical Application Configuration

Doc. designationIC_2_SYNF979

Created by Title

REF615 INCOMER-2OCREF615

Document id.

Approved by Rev.0

Rel. date9/25/2015

Lang.en

7 / 7