Upload
lamliem
View
215
Download
0
Embed Size (px)
Citation preview
Parts Manual Gas Floor Type Convection Steamer
Series: SteamCraft Model 24CGA10 1333 East 179th Street
Cleveland, Ohio 44110
Phone: (216) 481-4900 1-800-338-2204
Fax: (216) 481-3782 www.clevelandrange.com
CLEVELAND RANGE 24CGA10 SEQUENCE OF OPERATIONS
Mechanical Timer
1. To turn the unit on, depress the red on/off rocker switch.• 115 VAC is sent to the red indicator light.• 115 VAC is sent to normally open drain valve closing it.• 115 VAC is sent to H and N of the water level board• 115 VAC is sent to the timed/manual switches.• 115 VAC is sent to the heat standby timer which will energize the R5 relay 20 seconds
every 6 minutes to maintain heat while unit is idle
2. With the water level board energized and no water in the generator• After a 5 second delay 115 VAC is sent from the FILL terminal to the fill solenoid.• The fill solenoid opens and the generator fills through the drain valve.• The water fills to the low probe shorting it to ground• 115 VAC is sent from the HEAT terminal to the 24 VAC heat circuit transformer.•
3. When the timed/manual switch is in the timed position and time is on the timer for the topcabinet only• 115 VAC is sent from the timer to the coil of the R6 relay.• The R6 relay energizes• R6B contacts close sending 115 VAC to the timer motor.• R6A contacts close sending 115 VAC through the door switch (optional) to the steam
solenoid, condensate solenoid and R1 relay.• R1 is energized closing the R1 contacts.• 24 VAC is sent from the 24VAC transformer to the normally open contacts of R2.• 24 VAC is sent from the 24VAC transformer to the R4 coil.
• R4 is energized and the R4 contacts are closed.• 24 VAC is sent to one side of the ignition module.• 24 VAC is sent to the R3 relay coil
• R3 is energized and the R3 contacts are closed.• 115 VAC is sent through the now closed R4 contacts to the normally open steam
relief valve closing it.• 115 VAC is sent to the fan motor.• The fan motor is energized and the air prover switch closes.• 24 VAC is sent through the normally closed highlimit and the now closed air prover
switch to the other side of the ignition module.
4. With 24 VAC to both sides of the ignition module.• Spark is sent to the igniter.• 24VAC is sent to the pilot coil on the gas valve and gas is sent to the pilot.• When flame is generated and 1.0 micro amps DC is detected, 24 VAC is sent to the main
coil of the gas valve igniting the main burner on low flame.
• Steam is energized and sent to the cooking compartment. • When the mechanical timer times down a buzzer will sound and the timer will open
removing 115 VAC from the heat circuit. 5. When the timed/manual switch is in the timed position and time is on the timer for the
bottom cabinet only • 115 VAC is sent from the timer to the coil of the R7 relay. • The R7 relay energizes • R7B contacts close sending 115 VAC to the timer motor. • R7A contacts close sending 115 VAC through the door switch (optional) to the steam
solenoid, condensate solenoid and R2 relay. • R2 is energized closing the R2 contacts. • 24 VAC is sent from the 24VAC transformer to the normally open contacts of R1. • 24 VAC is sent from the 24VAC transformer to the R4 coil.
• R4 is energized and the R4 contacts are closed. • 24 VAC is sent to one side of the ignition module. • 24 VAC is sent to the R3 relay coil.
• R3 is energized and the R3 contacts are closed. • 115 VAC is sent through the now closed R4 contacts to the normally open steam
relief valve closing it. • 115 VAC is sent to the fan motor. • The fan motor is energized and the air prover switch closes sending 24 VAC to the
other side of the ignition module. 6. With 24 VAC to both sides of the ignition module.
• Spark is sent to the igniter. • 24VAC is sent to the pilot coil on the gas valve and gas is sent to the pilot. • When flame is generated and 1.0 micro amps DC is detected, 24 VAC is sent to the main
coil of the gas valve igniting the main burner on low flame. • Steam is energized and sent to the cooking compartment. • When the timer times down, the closed contact will open removing 115 VAC from the
heat circuit. • 115 VAC will be sent through the now closed contacts to the 3-second timer. • For 3 seconds 115 VAC will be sent to the buzzer and it will buzzzzzz.
7. When the timed/manual switch is in the timed position and time is on the timer for both
cabinets • 115 VAC is sent from the timer through the door switch (optional) to both steam
solenoids, both condensate solenoids and both relays. • Both relays are energized closing the relay contacts.
• 24 VAC is sent from the 24VAC transformer through the R1 and R2 contacts to the high coil on the gas valve.
• 24 VAC is sent from the 24VAC transformer to the R4 coil. • R4 is energized and the R4 contacts are closed.
• 24 VAC is sent to one side of the ignition module.
• 24 VAC is sent to the R3 relay coil. • R3 is energized and the R3 contacts are closed.
• 115 VAC is sent through the now closed R4 contacts to the normally open steam relief valve closing it.
• 115 VAC is sent to the fan motor. • The fan motor is energized and the air prover switch closes sending 24 VAC to the
other side of the ignition module. 8. With 24 VAC to both sides of the ignition module.
• Spark is sent to the igniter. • 24VAC is sent to the pilot coil on the gas valve and gas is sent to the pilot. • When flame is generated and 1.0 micro amps DC is detected 24 VAC is sent to the main
coil of the gas valve igniting the main burner on high flame (the high coil was energized in step 7).
• Steam is energized and sent to the cooking compartments. • When the timers time down the buzzers will sound and each timer will open removing
115 VAC from the heat circuit. 9. When the water level reaches the high probe then 115 VAC is removed form the FILL
terminal and the fill solenoid is turned off. 10. After the water level drops below the high probe for 5 seconds 115 VAC is sent to the FILL
terminal again. 11. 115 VAC is turned of by depressing the red on/off rocker switch.
• 115 VAC is removed from the timer and heating circuits. • 115 VAC is removed from the normally open drain valve allowing the steamer to drain. • 115 VAC is sent to the 3-minute timer.
• The fill solenoid is energized for 3 minutes flushing the drain.
STEAM VALVE
GND
SP
GND
24V
MV/PV
L105974 M
C
HI
GASVALVE
24V
TRANSFORMER
HEAT STANDBY TIMER
R5 COIL2
R2
IGNITOR
R5
R4
1
R1
R1 R2
3
PRESS SWITCH
R4 COIL
CONTROL MODULE MV
PV
R3 COIL AIR PROVER
SECONDARY 24V
PRIMARY 115V
HIGH LIMITRESET SWITCH
STEAM RELIEF VALVE
FAN MOTOR
R3 R4
2 WIRE, 115 VACTB
POWER SWITCH
3 MIN TIMER 32
1
DESCALETIMER
BLK
8
2
7
34
65
1
R1 COIL
CONDENSER VALVE
HI
WATERBOARD
HN XL
HEATFILL
C
DESCALE INDICATOR
POWER ONR
FILL VALVE
NO
L
NO
AL
& RESET SWITCH
WHT
STEAMCRAFT 10 GAS - MECHANICAL CONTROLN
L1CUSTOMERCONNECTION
TO PROBES
3
2
CBLOWDOWN
OPTIONTIMER 1
R3
NC
DRAIN VALVEUPPER
R6
UPPER MOTORIZED TIMER
R6ANC
MOTOR
C NO
NO SWITCH(SCS OPT)
C DOOR
3
2
1
BUZZER
MANUALTIMEDMANUAL
NOC
R6B3 SEC TIMER
TIMED
(SCS OPT)SWITCH
CR7A
LOWER MOTORIZED TIMER
NC NO
TIMED
C
MANUAL
MOTOR
C NO
MANUAL
NO
R7B
DOOR R2 COIL
STEAM VALVE
CONDENSER VALVE
3 SEC TIMER
1
3
TIMED
2R7BUZZER
P105974 M
RED
WH
T/R
EDW
HT/
YEL
1PRP
WHT
253
2
24
GR
AW
HT/
GR
A
ORN
BLU
WH
T
BLK
RED
YEL
OR
N
20
25 26 27 28
22 21
24 23
107241 - WATERBOARD105788 - AIR PROVER SWITCH 105693 - GAS CONTROL MODULE 105784 - PILOT107239 - PROBE ASSEMBLY 105785 - RELAY ( R3, R4 ), 24V 03524 - RELAY ( R1, R2 ) 120V 22199 - STEAM RELIEF SOLENOID 105695 - FAN105990 - TERMINAL STRIP 20478 - 3 MIN TIMER105966 - RELAY ( R5 ) 120V 106580 - HEAT STANDBY TIMER 22218 - WATER SOLENOIDS 22221 - DRAIN VALVE106541 - BLOWDOWN TIMER
16
WH
T/O
RN 19
17 18
14 15
13
19994 - DESCALE IND / RESET SW 108880 - DOOR SW ( SCS ) MAGNETIC 22193 - COMP STEAM SOLENOID
26
9 106911 - DESCALE TIMER 10 105782 - GAS VALVE ( NAT )
1057821 - GAS VALVE ( LP ) 11 20528 - TRANSFORMER 12 439091 - TERMINAL BLOCK
CO
ND
TOP
7 6
8
3 20477 - 3 SEC TIMER4 41350 - BUZZER5 19993 - POWER SWITCH
2 1
PARTS LIST110198 - MOTORIZED TIMER 104224 - TIMED / MANUAL SWITCH
( OPTIONAL )
18 91 135
3
21
INTERMITTENT
28
26
WH
T/BR
N
BO
TBRN
CO
ND
8
5
BLOWDOWN
19 12
9
4
1
14
13
BLK
8
5
8
31
8
5
124 14
19 9
BLK
1 13
144 12
18
124 14
91 13
RE
DR
ED
13
14
FILLBLU
22
GRN
27
27
GRN
191848
REF
15
RED
RE
D
12
9
BRN
PRP
YEL
BLK
30
WHT/BLK
8
YEL
LT/BLU
CONNECTIONCUSTOMER 12
WHT
WHT
GRA
WHT
BLK
WHT 15
24v
ORN
WHT/ORN
WHT/YEL
YEL
GR
N16
BR
N
TAN
20 RE
D
REDBRN
LT BLUTAN
19PR
P
HI V
OLT
WHT/GRA
RE
D
41
23
8 4
41
85
PR
P
WHTLT BLU
19
14 12
1491312
TAN
LT/BLU
TAN
56
7
58 4
1RE
D
5 1
YEL
YEL
98
58 4
1
LT B
LU
18 1314
912
13 9
LT B
LU
YEL
LT B
LU
18 1314
912
YEL
OR
N
231
WH
T 3
2
BLK
MECHANICAL TIMER
YEL BLK
YELWHT
REDP
RP
RE
D
C
10
14
YEL
YEL
LT BLU
BLK
BR
N
YEL
BRNWHT
29
RED
BLK
BRN
WHT/RED
BLK
XL
HEAT NHFILL
ORN
BLU
WHT
GRN
13 HI
C
BLKRED
17 21
STEAMCRAFT 10 - GAS
RED
6
TANTAN
WHT
LT/B
LU
WH
T/R
ED
W / OPTIONALREMOVED
DOOR SWITCH ( SCS )WHT/BLK
4
3
WHT/RED
16587
43 2
9
RED
ORN
BLK
BLK
RE
D
YEL
WH
T/Y
EL
GR
A
WH
TW
HT/
GR
A
BLKWHT
WH
T
RE
D
BLU
RE
D
BLK
BLK
7
WHT
DOOR SWITCH ( SCS )
5
GRA
WHTWHT/GRA Y
ELW
HT
8
REMOVED W / OPTIONAL
RE
D
BLU
ORN
7
ORN
HI
MP
11
BRN
YEL
WHT/RED
WHT/YEL
RE
D
22
WH
TB
LK
WH
T/B
LK
WH
T/R
ED
WH
TB
LK
RE
D
RE
D
WH
T
WH
T
WHT
RE
D
BLK
LT BLU
1
NC
C NO
32 R7
123
2
ORN/BLK
WHT/BLK
PN
K
LT BLU
OR
N
LT BLULT BLU
W/B
LU
OR
N
1 NO
LT BLU
C
LT BLU
ORN/BLK
2 32
NC
R6WHT/BLK
W/B
LU LT BLU
PN
K
43 2 1
3
LT BLU
WHT/BLKRE
D
29 108995 - HIGH LIMIT RESET SWITCH 30 106144 - IGNITION ASSY 31 222231 - FILL VALVE32 105966 - RELAY ( R6) 120V
W/B
LU
BLK B
LK
BLK B
LK
W/B
LU
Replace the on/off rocker
switch
Yes
Connect powerto steamer.
NoIs the red light on? Is there power to
the steamer?
Is there water inthe sight glass?
Yes
SeeSteamer won't
fill.
No
Has the steamgenerator ignited?
Yes
No
Does the steamersteam in manual
mode?
Yes
Replacethe timer
Yes
Is there power tothe Timed/Manual
switch?No
Repair orreplace thewiring to the
switch
Is there powerfrom the Timed/Manual switch?
Yes
Replace theswitch
No
Does the steamerhave the optional
door switch?
Yes
Replace thedoor switch
Is there 120 VACaccross the coil of
the steamsolenoid.?
No
PROBLEM:24CGA10
Steam cabinet won't
steam with time onthe timer and time/manual switch in
the timed position
Yes
No
SeeSteamer
generatorwon't ignite
No
Steam cabinetwon't steam
Does the steamcabinet steamwhen the door
switch isbypassed?
Yes
Yes
No
Replace thesteam solenoid
Repair or replace the
wiring to the steamsolenoid
No
Steam generatorwon't fill.
Is there powerto the
steamer?
Yes
Supply power tothe steamer.
No
Is there waterto the
steamer?
Supply cold waterto the steamer.
No
Yes
Is there 120 VACbetween the H and Non the water board?
Replace the on/offrocker switch .
No
Yes
Is there 120 VAC
between Fill andN on the water
board?
Yes
Remove the wire from the HIterminal on the waterboard. Is there 120
VAC between Fill andN?
NoReplace the water
boardNo
Is there debris on theHI probe in the
probe assy?
Yes
Replace the wireto the Hi probe.
Clean the probesor replace theprobe assy.
No
Yes
Is there120 VAC acrossthe coil of the fill
solenoid?
Yes
Is water leaving
the fillsolenoid?
Replace the wiringto the fill solenoid.
No
Yes
Replace the fillsolenoid
No
Is there 120 VAC across
the coil of thedrain valve?
Yes
Does the steamer have
the optionalintermittent
blowdown timer?
NoReplace wiring todrain solenoid.
No
Isthere 120 VAC
between terminals2&3 on the timer?
Is waterdraining from
the generator?
Replace the drainvalve.
Yes
Replace theintermittent
blowdown timer.
Yes
Yes
Replace the wiringto the intermittentblowdown timer .
No
No
PROBLEM:24CGA10
Steamgeneratorwon't fill
If water is leavingthe fill solenoidand not draining
from the generatorwhere is it going?check for leaks..
Yes
Is there 120 VACbetween the
terminals Heat andN on the waterlevel board with
the the low probesubmerged?
Is there 120 VACbetween Heat and N
terminals on the waterlevel board with ajumper between
terminal XL and C?
NoClean or
replace theprobe assy.
Replace waterlevel board.
No
Yes
Yes
Is the red light on?Is there power to
the steamer?Connect powerto the steamer
No No
Replace theon/off switch
Is there water inthe sight glass?
YesYes
Yes
SeeSteamer won't
fillNo
PROBLEM:24CGA10
Steam generatorwon't ignite
Steam generatorwon't ignite
Is there 24 VACon ignition
transformer?
Replace theigniton module.
No
With the Topcabinet in the
manual position, isthere 120 VAC to
the fan?
Yes
Is there 120 VACto the coil of
cabinet relay R1?No
Replace theTimed/Manual
switch.No
Is there 24 VAC tothe R4 coil?
Yes
With the bottomcabinet in the
manual position, isthere 120 VAC to
the fan?
Is there 120 VACto the cabinet relay
R2 coil?
Yes
NoYes
Replace thecabinet relay(R1or R2).
No
Is there 24 VAC tothe R3 coil?
Yes
Replace the R4relay.
No
Does the fan turn?Yes
Replace thetimed/manual
switch.No
Replace thefan.
No
Is there 24 VAC tothe gas valve?
Yes
With the high limittemporarily by
passed is there 24VAC to the ignition
module?
No
Replace thehigh limit.
Yes
Adjust orreplace the airprover switch.
No
Replace the R3relay
Yes
Is there 24 VAC tothe PV and MV/PV
terminals on theGas valve and
spark to the igniterfor 90 seconds?
Yes
Replace theignition module
No
Is the pilot valveopening?
Yes
Replace thegas valve.
No
Is there gas to thesteamer?
Yes
Supply gas tothe steamer
No
Due to the construction of the
burner box it is best toreplace the ignitor,
ignition cable and sensor(ground wire ) at the
same time.
Yes
PROBLEM:24CGA10
Electronic timer displays "PAUS" and won't count down
START
Is steam heatingthe cooking
cabinetabove 192degrees (the set
temp of thethermo-switch)?
Does the timercount down whenthe thermo-switch
is bypassed?
Yes
See Steamer
won't steamNo
Replace theelectronic timer
NoReplace the
thermo-switchYes
PROBLEM:24CGA10
Steam leaks around the door.
START
Is COLD watersupplied to the
steamer?
Supply coldwater (35-60PSI) to thesteamer.
No
Is the door gasketphysicallydamaged?
Yes
Turn over thegasket orreplace it.
Yes
Is the door out ofalignment?
No
Replace thedoor bearings
and pins.
Yes
Is the drainobstructed?
No
Remove theobstruction
Yes
Is there 120 VACacross the coil ofthe condensate
solenoid?
No
Replace thewiring to thecondensate
solenoid.
No
Is the solenoidopening?
Yes
Replace thecondensate
solenoid.No
Replace thecondensate spray
nozzle
Yes
Steamerwon'tstop
steaming
PROBLEM:24CGA10
Steamer won't stop steaming withdoor open
Is the timed/manual switchin the timed positionwith no time on the
timer?
Steamer will steamconstantly in the
manual position. Putthe timed/manualswitch in the timed
position with no time onthe timer.
No
Does the steamerhave the optional
door switch?
Yes
Adjust or replacethe door switch.
Yes
Does steamer continue to steam with
both wires removedfrom terminal 1 on the
heat standby timer?
No
Replace the heatstandby timer.
Yes
Is there 120 VAC to the
coil of thecontacter?
No
Replace the timer.
Yes
Is there an amp
draw at theelement?
No
Replace thecontactor
Yes
When power isremoved from theelement steam is
still made forapproximately 10seconds. This is
normal.
No
Problem:24CGA10
Steamer won't preheat
Steamer won'tpreheat
Is the timed/manual
switch in the timed postionwith time on it or in the
manual postion?
See Problem:steamer won't
steam.
Yes
This steamer isnot equiped with a
preheatthermostat. Thetimed manual
switch must be inmanual or timemust be on the
timer.
No
PROBLEM:24CGA10 Generator over--
pressurizes (relief valvedischarges constantly)
Generator over-pressurizes
Is discharge fromrelief valve cold?
See Problem:SteamerFloods
Yes
No
Does generatorover-pressurizewith door open
(and optional doorswitch bypassed)?
Is condensatesolenoid operating
properly?No
Replacecondensate
solenoid.
No
Is the condensate spraynozzle spraying a coneof cold water down the
drain?
Yes
Replace spraynozzle
Check drain forany obstructions
and correctinstallation.
No
Yes
Does the generator over-pressurizeonly when both cabinets have beenrunning and are then shut down?
Yes
Replace thenormally openrelief solenoid
Does generator over-pressurize whenthe steam supply hoses have been
disconnected from the steammanifolds? Warning: Steam is
hot!!
No
Descalegenerator
Yes Replace thesteam
solenoids
No
Problem: 24CGA10 Steamer Floods (Water is entering cabinet through the steam nozzles)
Steamer Floods
Is 120 VAC to thefill solenoid with
water touching thetop probe?
Replace the fillsolenoid.
No
Is there 120 VACto the fill solenoid
with the wireremoved from
terminal 1 on the 3min. timer?
Yes
Replace the 3minute timer.
No
Is there 120 VAC to the fillsolenoid with a jumper
placed from the HI terminalto the C terminal on the
water level board?
Yes
Replace thewater level
board.
Yes
Clean or replace theprobe housing
No
Is gas pressurecorrect (Natural:
2.0" Low and 3.5"high. L.P.: 4.2"low, 10" high)?
Adjust orreplace the gas
valveNo
Yes
Yes
Descaling Procedure-SteamCraft Ultra and Gemini Series
1. Turn the unit OFF and open thedoors:
This will drain and rinse the generator for about3 minutes.
2. Turn the unit power back On:The generator will begin to refill with water.
3. Select Timed with the Timed/Manualswitch:
DO NOT start the timer, since you do not wantto heat the water during descaling. Leave thedoors open.
4. Remove descaling port cap and addwith the specified amount ofDISSLOVE: (See chart above)
Do this while the unit is refilling. The generatorscan take-up to 8 minutes to refill.
5. After refill has stopped, add extra tapwater into the descaling port untilliquid is seen entering the cookingcabinet. Note: Ultra 10 gas will have liquidcoming out of the drain,
Adding extra water when descaling will raise thedescaling solution higher than the normal fill level,allowing the DISSOLVE to work on sensors andsurfaces above the water line
6. Let the descaler soak in generator forapproximately one hour:
7. After one hour, turn the unit powerOff: This will drain and rinse the generatorfor about 3 minutes.
8. After the 3-minute drain cyclecompletes, turn the unit back ON. Afterthe filling has stopped, add water untilliquid enters the cooking compartment (ordrain for the ultra 10 gas), and then turnthe unit OFF. This will drain and flush anyresidue from the water level controlassembly. Replace descaling cap.
9. After the 3 minute drain cyclecompletes, Turn the unit ON and setthe Timer for 20 minutes: Make sure theTime/Manual switch is in the timed settingand the doors are closed.
10. When the timer times out (after 20minutes) turn the power Off:This will drain and rinse the generator forabout 3 minutes.
This ends the descaling procedure. You cannow turn the unit back on and resume normalstartup and cooking operations.
How Much DISSOLVE to UseModel DissolveUltra 3 1/2 Gallon
Ultra 5 1 Gallon
Ultra 10 (Elec.) 1 Gallon (ea.)
Ultra 10 (Gas) 1½ Gallon
Gemini 6 & 10 1 Gallon (ea.)
Note: Some SteamCraft Ultra models (theelectric powered Ultra 10 and Gemini 6 and 10,for example) have two generators and twodescaling ports. Both units should be descaledat the same time, using this procedure