33
MAHLUM 09 21 16 UMPQUA COMMUNITY COLLEGE GYPSUM BOARD ASSEMBLIES SNYDER HALL REPLACEMENT © 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 1 OF 12 ADDENDUM 2 | Issue Date: 17 MAY 2017 PART 1 GENERAL 1.1 SECTION INCLUDES A. Performance criteria for gypsum board assemblies. B. Cementitious backing board. C. Gypsum wallboard. D. Joint treatment and accessories. E. Acoustic (sound-dampening) wall and ceiling board. F. Impact Resistant Gypsum Board System. G. Rated Assembly Markings and Identification 1.2 RELATED REQUIREMENTS A. Section 01 61 16 - Volatile Organic Compound (VOC) Content Restrictions. B. Section 06 10 00 - Rough Carpentry: Building framing ,wood blocking product and execution requirements. C. Section 07 21 00 - Thermal Insulation: Acoustic insulation. D. Section 07 92 00 - Joint Sealants: Sealing acoustical gaps in construction other than gypsum board or plaster work. E. Section 09 30 00 - Tiling: Cementitious backing board. 1.3 REFERENCE STANDARDS A. AISI S100-12 - North American Specification for the Design of Cold-Formed Steel Structural Members; American Iron and Steel Institute; 2012. B. ANSI A108.11 - American National Standard for Interior Installation of Cementitious Backer Units; 2010 (Revised). C. ANSI A118.9 - American National Standard Specifications for Test Methods and Specifications for Cementitious Backer Units; 1999 (Reaffirmed 2010). D. ASTM A653/A653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process; 2015. E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM C475/C475M - Standard Specification for Joint Compound and Joint Tape for Finishing Gypsum Board; 2015. G. ASTM C514 - Standard Specification for Nails for the Application of Gypsum Board; 2004 (Reapproved 2014). H. ASTM C557 - Standard Specification for Adhesives for Fastening Gypsum Wallboard to Wood Framing; 2003 (Reapproved 2009).

PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM 09 21 16 UMPQUA COMMUNITY COLLEGE GYPSUM BOARD ASSEMBLIES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 1 OF 12

ADDENDUM 2 | Issue Date: 17 MAY 2017

PART 1 GENERAL

1.1 SECTION INCLUDES

A. Performance criteria for gypsum board assemblies.

B. Cementitious backing board.

C. Gypsum wallboard.

D. Joint treatment and accessories.

E. Acoustic (sound-dampening) wall and ceiling board.

F. Impact Resistant Gypsum Board System.

G. Rated Assembly Markings and Identification

1.2 RELATED REQUIREMENTS

A. Section 01 61 16 - Volatile Organic Compound (VOC) Content Restrictions.

B. Section 06 10 00 - Rough Carpentry: Building framing ,wood blocking product and execution requirements.

C. Section 07 21 00 - Thermal Insulation: Acoustic insulation.

D. Section 07 92 00 - Joint Sealants: Sealing acoustical gaps in construction other than gypsum board or plaster work.

E. Section 09 30 00 - Tiling: Cementitious backing board.

1.3 REFERENCE STANDARDS

A. AISI S100-12 - North American Specification for the Design of Cold-Formed Steel Structural Members; American Iron and Steel Institute; 2012.

B. ANSI A108.11 - American National Standard for Interior Installation of Cementitious Backer Units; 2010 (Revised).

C. ANSI A118.9 - American National Standard Specifications for Test Methods and Specifications for Cementitious Backer Units; 1999 (Reaffirmed 2010).

D. ASTM A653/A653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process; 2015.

E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014.

F. ASTM C475/C475M - Standard Specification for Joint Compound and Joint Tape for Finishing Gypsum Board; 2015.

G. ASTM C514 - Standard Specification for Nails for the Application of Gypsum Board; 2004 (Reapproved 2014).

H. ASTM C557 - Standard Specification for Adhesives for Fastening Gypsum Wallboard to Wood Framing; 2003 (Reapproved 2009).

Page 2: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM 09 21 16 UMPQUA COMMUNITY COLLEGE GYPSUM BOARD ASSEMBLIES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 2 OF 12

ADDENDUM 2 | Issue Date: 17 MAY 2017

I. ASTM C645 - Standard Specification for Nonstructural Steel Framing Members; 2014.

J. ASTM C665 - Standard Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing; 2012.

K. ASTM C754 - Standard Specification for Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products; 2015.

L. ASTM C840 - Standard Specification for Application and Finishing of Gypsum Board; 2013.

M. ASTM C1002 - Standard Specification for Steel Self-Piercing Tapping Screws for Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs; 2014.

N. ASTM C1047 - Standard Specification for Accessories For Gypsum Wallboard and Gypsum Veneer Base; 2014a.

O. ASTM C1325 - Specification for Non-Asbestos Fiber-Mat Reinforced Cementitious Backer Units; 2014.

P. ASTM C1396/C1396M - Standard Specification for Gypsum Board; 2014.

Q. ASTM C1629/C1629M - Standard Classification for Abuse-Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels; 2015.

R. ASTM C1658/C1658M - Standard Specification for Glass Mat Gypsum Panels; 2013.

S. ASTM D3273 - Standard Test Method for Resistance to Growth of Mold on the Surface of Interior Coatings in an Environmental Chamber; 2012.

T. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials; 2015a.

U. ASTM E90 - Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements; 2009.

V. ASTM E413 - Classification for Rating Sound Insulation; 2010.

W. GA-216 - Application and Finishing of Gypsum Board; 2013.

X. GA-224 - Installation of Predecorated Gypsum Board; Gypsum Association; 2008.

Y. GA-226 - Application of Gypsum Board to Form Curved Surfaces; Gypsum Association; 2008.

Z. GA-600 - Fire Resistance Design Manual; 2015.

AA. UL (FRD) - Fire Resistance Directory; current edition.

1.4 SUBMITTALS

A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.

B. Shop Drawings: Indicate special details associated with fireproofing and acoustic seals.

C. Product Data: Provide data on gypsum board, accessories, and joint finishing system.

D. Product Data: Provide manufacturer's data on partition head to structure connectors, showing compliance with requirements.

Page 3: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM 09 21 16 UMPQUA COMMUNITY COLLEGE GYPSUM BOARD ASSEMBLIES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 3 OF 12

ADDENDUM 2 | Issue Date: 17 MAY 2017

E. Test Reports: For stud framing products that do not comply with ASTM C645 or ASTM C754, provide independent laboratory reports showing maximum stud heights at required spacings and deflections.

F. Samples: Submit two samples of gypsum board finished with proposed texture application, 12 by 12 inches in size, illustrating finish color and texture.

1.5 QUALITY ASSURANCE

A. Installer Qualifications: Company specializing in performing gypsum board installation and finishing , with minimum five years of experience.

B. Fire-Test-Response Characteristics: For gypsum board assemblies with fire-resistance ratings, provide materials and construction identical to those tested in assembly indicated according to ASTM E 119 by an independent testing and inspecting agency acceptable to authorities having jurisdiction. 1. Fire-Resistance-Rated Assemblies: Indicated by design designations from UL's "Fire

Resistance Directory." GA-600,or "Fire Resistance Design Manual." <Insert listing organization and publication.

C. Sound Transmission Characteristics: For gypsum board assemblies with STC ratings, provide materials and construction identical to those tested in assembly indicated according to ASTM E 90 and classified according to ASTM E 413 by a qualified independent testing agency. 1. STC-Rated Assemblies: Indicated by design designations from GA-600, "Fire

Resistance Design Manual."

D. Single-Source Responsibility: Obtain each type of gypsum board and related joint treatment materials from a single manufacturer.

E. Structural Performance Characteristics: Provide gypsum wallboard systems engineered to withstand the following lateral design loadings (air pressures), applied transiently and cyclically, for maximum heights of partitions required, within the following deflection limits, verified by pre-testing for deflection characteristics: 1. Lateral Loading: 5 psf for interior partitions. 2. Deflection Limit: 1/240 of partition height, unless noted otherwise. 3. Deflection Limit, Ceramic Tile Finish: 1/360 of partition height.

PART 2 PRODUCTS

2.1 GYPSUM BOARD ASSEMBLIES

A. Provide completed assemblies complying with ASTM C840 and GA-216. 1. See PART 3 for finishing requirements.

B. Interior Partitions , Indicated as Acoustic: Provide completed assemblies with the following characteristics: 1. Acoustic Attenuation: STC of 50-54 calculated in accordance with ASTM E413, based

on tests conducted in accordance with ASTM E90.

C. Marking and Identification 1. Fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions or any other

wall required to have protected openings or penetrations shall be effectively and permanently identified with signs or stenciling. Such identification shall:

Page 4: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM 09 21 16 UMPQUA COMMUNITY COLLEGE GYPSUM BOARD ASSEMBLIES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 4 OF 12

ADDENDUM 2 | Issue Date: 17 MAY 2017

a. Be located in accessible concealed floor, floor-ceiling or attic spaces. b. Be located within 15 feet of the end of each wall and at intervals not exceeding 30

feet measure horzontally along the wall or partition c. Include lettering not less than 3 inches in height with a minimum 3/8 inch stroke in a

contrasting color incorporating the suggested wording 1) FIRE AND/OR SMOKE BARRIER - PROTECT ALL OPENINGS

2) or other wording.

2.2 METAL FRAMING MATERIALS

A. Manufacturers - Metal Framing, Connectors, and Accessories: 1. Bostwick Steel Framing 2. Cemco; Viper-Studs, www.cemco.com 3. National Gypsum Company www.nationalgypsum.com 4. The Steel Network, Inc: www.SteelNetwork.com. 5. SCAFCO Steel Stud Mfg. Co. www.scafco.com. 6. Steeler inc.; www.steeler.com 7. United States Gypsum Co. www.usg.com 8. Substitutions: See Section 01 60 00 - Product Requirements.

B. Non-Loadbearing Framing System Components: ASTM C645; galvanized sheet steel, of size and properties necessary to comply with ASTM C754 for the spacing indicated, with maximum deflection of wall framing of L/120 at 5 psf. 1. Resilient Furring Channels: 1/2 inch depth, for attachment to substrate through one

leg only. a. Products:

1) Same manufacturer as other framing materials. 2) Substitutions: See Section 01 60 00 - Product Requirements.

C. Ceiling Hangers: Type and size as specified in ASTM C754 for spacing required.

2.3 BOARD MATERIALS

A. Manufacturers - Gypsum-Based Board: 1. CertainTeed Corporation : www.certainteed.com. 2. Georgia-Pacific Gypsum : www.gpgypsum.com. 3. National Gypsum Company : www.nationalgypsum.com. 4. USG Corporation : www.usg.com. 5. ______. 6. Substitutions: See Section 01 60 00 - Product Requirements.

B. Gypsum Wallboard: Paper-faced gypsum panels as defined in ASTM C1396/C1396M; sizes to minimize joints in place; ends square cut. 1. Application: Use for vertical surfaces, ceilings, and soffits, unless otherwise indicated. 2. Thickness: 5/8 inch 3. Edges: Tapered.

C. Mold Resistant Wallboard: Gypsum wallboard especially formulated for mold and mildew resistance either encased in a mold/mildew resistant paper or without paper exterior. Score of 10, when tested in accordance with ASTM D3273. 1. Mold-resistant board is required whenever board is being installed before the building is

enclosed and conditioned.

Page 5: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM 09 21 16 UMPQUA COMMUNITY COLLEGE GYPSUM BOARD ASSEMBLIES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 5 OF 12

ADDENDUM 2 | Issue Date: 17 MAY 2017

2. Application: Interior sides of all exterior walls, and other locations as indicated on the drawings.

3. Core Type: Regular and Type X at fire rated assemblies. 4. Thickness: 5/8 inch 5. Edges: Tapered.

D. At Assemblies Indicated with Fire-Rating: Use type required by indicated tested assembly; if no tested assembly is indicated, use Type X board, UL or WH listed. 1. Thickness: 5/8 inch. 2. Edges: Tapered.

E. Water-Resistant Gypsum Backing Board: ASTM C 1396/C 1396M; ends square cut. 1. Application: At wet areas, such as kitchen walls, preparation sinks and mop sinks

locations. 2. Core Type: Regular and Type X at fire assemblies. 3. Thickness: 5/8 inch. 4. Edges: Tapered.

F. Impact Resistant Wallboard: 1. Application: All hallways and ciurculation areas up to 4'-0" above finish floor.. 2. Surface Abrasion: Level 3, minimum, when tested in accordance with ASTM

C1629/C1629M. 3. Indentation: Level 1, minimum, when tested in accordance with ASTM

C1629/C1629M. 4. Soft Body Impact: Level 3, minimum, when tested in accordance with ASTM

C1629/C1629M. 5. Hard Body Impact: Level 2, minimum, when tested in accordance with ASTM

C1629/C1629M. 6. Mold Resistance: Score of 10, when tested in accordance with ASTM D3273. 7. Paper-Faced Type: Gypsum wallboard as defined in ASTM C1396/C1396M. 8. Type: Fire resistance rated Type X, UL or WH listed. 9. Thickness: 5/8 inch. 10. Edges: Tapered. 11. Products:

a. National Gypsum Company; Gold Bond HI-Impact XP Gypsum Board. b. Substitutions: See Section 01 60 00 - Product Requirements.

G. Backing Board For Wet Areas: One of the following products: 1. Application: Surfaces behind tile in wet areas including toilet areas and exterior veneer

stone walls. 2. Mold Resistance: Score of 10, when tested in accordance with ASTM D3273. 3. ANSI Cement-Based Board: Non-gypsum-based; aggregated Portland cement panels

with glass fiber mesh embedded in front and back surfaces complying with ANSI A118.9 or ASTM C1325. a. Thickness: 1/2 inch. b. Products:

1) National Gypsum Company; PermaBase Cement Board: www.nationalgypsum.com.

2) USG Corporation : www.usg.com. 3) Substitutions: See Section 01 60 00 - Product Requirements.

Page 6: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM 09 21 16 UMPQUA COMMUNITY COLLEGE GYPSUM BOARD ASSEMBLIES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 6 OF 12

ADDENDUM 2 | Issue Date: 17 MAY 2017

H. Ceiling Board: Special sag resistant gypsum ceiling board as defined in ASTM C1396/C1396M; sizes to minimize joints in place; ends square cut. 1. Application: Ceilings, unless otherwise indicated. 2. Thickness: 1/2 inch. 3. Edges: Tapered. 4. Products:

a. Georgia-Pacific Gypsum; ToughRock Span 24 Ceiling Board. b. Substitutions: See Section 01 60 00 - Product Requirements.

I. Acoustical Sound Dampening Wall and Ceiling Board: Two layers of heavy paper faced, high density gypsum board separated by a viscoelastic polymer layer and capable of achieving STC rating of 50 or more in typical stud wall assemblies as calculated in accordance with ASTM E413 and when tested in accordance with ASTM E90. 1. Thickness: 5/8 inch. 2. Long Edges: Tapered. 3. Mold Resistance: Score of 10, when tested in accordance with ASTM D3273. 4. Products:

a. National Gypsum Company; Gold Bond SoundBreak XP Gypsum Board: www.nationalgypsum.com.

b. Substitutions: See Section 01 60 00 - Product Requirements.

J. Exterior Soffit Board: Exterior gypsum soffit board as defined in ASTM C1396/C1396M; sizes to minimize joints in place; ends square cut. 1. Application: As noted in drawings, unless otherwise indicated. 2. At Assemblies Indicated with Fire-Rating: Use type required by indicated tested

assembly; if no tested assembly is indicated, use Type X. 3. Types: Regular and Type X, in locations indicated. 4. Type X Thickness: 5/8 inch. 5. Edges: Tapered. 6. Products:

a. American Gypsum Company; Exterior Soffit Gypsum Wallboard Type X. b. Substitutions: See Section 01 60 00 - Product Requirements.

2.4 ACCESSORIES

A. Acoustic Insulation: 1; preformed glass fiber, friction fit type, unfaced. Thickness: Full stud cavity. 1. Manufacturers:

a. CertainTeed Corporation: www.certainteed.com. b. Johns Manville Corporation: www.jm.com. c. Owens Corning Corporation ; EcoTouch PINK FIBERGLAS Insulation:

www.ocbuildingspec.com. d. Black Acoustic Insulation: Owens Corning Corp; SelectSound Black Acoustic

Blanket: www.owenscorning.com. e. Owens Corning Corp: www.owenscorning.com. f. Knauf Insulation: www.knaufinsulation.com

B. Acoustic Sealant: Acrylic emulsion latex or water-based elastomeric sealant; do not use solvent-based non-curing butyl sealant. 1. Products:

a. Franklin International, Inc.; Titebond GREENchoice Professional Acoustical Smoke and Sound Sealant: www.titebond.com/sle.

Page 7: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM 09 21 16 UMPQUA COMMUNITY COLLEGE GYPSUM BOARD ASSEMBLIES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 7 OF 12

ADDENDUM 2 | Issue Date: 17 MAY 2017

b. Substitutions: See Section 01 60 00 - Product Requirements.

C. Acoustic Sealant: As specified in Section 07 90 05.

D. Beads, Joint Accessories, and Other Trim: ASTM C1047, galvanized steel, unless noted otherwise. 1. Rigid Corner Beads: Low profile, for 90 degree outside corners and archways. 2. Other types: As detailed or required for finished appearance. 3. Special Shapes: In addition to conventional corner bead and control joints, provide

U-bead, L-bead, and LC-bead at exposed panel edges. a. Products:

1) Trim-Tex, Inc. : www.trim-tex.com. 2) Phillips Manufacturing Co: www.phillipsmfg.com. 3) Substitutions: See Section 01 60 00 - Product Requirements.

4. Expansion Joints: Hidden Expansion Joint. a. Products:

1) Trim-Tex, Inc. ; Magic Corner Expansion Bead: www.trim-tex.com.

E. Joint Materials: ASTM C475/C475M and as recommended by gypsum board manufacturer for project conditions. 1. Joint Compound for Interior Gypsum Wallboard: For each coat use formulation that is

compatible with other compounds applied on previous or for successive coats. a. Prefilling: At open joints and damaged surface areas, use setting-type taping

compound. b. Embedding and First Coat: For embedding tape and first coat on joints, fasteners,

and trim flanges, use setting-type taping compound. 1) Use setting-type compound for installing paper-faced metal trim accessories.

c. Fill Coat: For second coat, use drying-type, all-purpose compound. d. Finish Coat: For third coat, use drying-type, all-purpose compound. e. Skim Coat: For final coat of Level 5 finish, use drying-type, all-purpose compound.

2. Tape: 2 inch wide, coated glass fiber tape for joints and corners , except as otherwise indicated.

3. Tape: 2 inch wide, creased paper tape for joints and corners , except as otherwise indicated.

4. Ready-mixed vinyl-based joint compound. 5. Powder-type vinyl-based joint compound.

F. High Build Drywall Surfacer: Vinyl acrylic latex-based coating for spray application, designed to take the place of skim coating and separate paint primer in achieving Level 5 finish or to preparate Impact-Rated Gypsum Wallboard. 1. Product: Builders Solution Interior Surfacer manufactured by Sherwin Williams. 2. Product: Tuff-Hide manufactured by U.S. Gypsum Corporation. 3. Substitutions: See Section 01 60 00 - Product Requirements.

G. Nails for Attachment to Wood Members: ASTM C514.

H. Staples For Attachment of Base Ply of Two-Ply Assembly to Wood Members: Flattened galvanized wire type as specified in ASTM C840.

I. Anchorage to Substrate: Tie wire, nails, screws, and other metal supports, of type and size to suit application; to rigidly secure materials in place.

J. Adhesive for Attachment to Wood, ASTM C557:

Page 8: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM 09 21 16 UMPQUA COMMUNITY COLLEGE GYPSUM BOARD ASSEMBLIES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 8 OF 12

ADDENDUM 2 | Issue Date: 17 MAY 2017

1. Products: a. Franklin International, Inc. ; Titebond PROvantage Professional Drywall Adhesive:

www.titebond.com/sle. b. Substitutions: See Section 01 60 00 - Product Requirements.

K. Fire/Smoke Assembly Marking: 1. At rated wall assemblies, contractor to provide proper marking and identification as

noted in this section; contractor's choice (stencil, or tape) 2. Approved tape manufacturer: M&I Tape: www.mnitape.com

PART 3 EXECUTION

3.1 EXAMINATION

A. Verify that project conditions are appropriate for work of this section to commence.

B. Examine areas and substrates, with Installer present, and including welded hollow-metal frames, cast-in anchors, and structural framing, for compliance with requirements and other conditions affecting performance. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Temporary Climate control will be used to maintain dry bulb temperatures between 55 and 80 degrees F and relative humidity at less than 50% during installation, taping and curing of joint compound. 1. Refer to Division 1 Section “Temporary Facilities and Controls” for temporary climate

control requirements.

B. Suspended Ceilings: Coordinate installation of ceiling suspension systems with installation of overhead structure to ensure that inserts and other provisions for anchorages to building structure have been installed to receive ceiling hangers at spacing required to support ceilings and that hangers will develop their full strength. 1. Furnish concrete inserts and other devises indicated to other trades for installation in

advance of time needed for coordination and construction.

3.3 FRAMING INSTALLATION

A. Acoustic Furring: Install resilient channels at maximum 24 inches on center. Locate joints over framing members.

B. Blocking: Install wood blocking for support of: 1. Framed openings. 2. Wall mounted cabinets. 3. Plumbing fixtures. 4. Toilet partitions. 5. Toilet accessories. 6. Wall mounted door hardware. 7. Digital Monitors. 8. Markerboards 9. Other wall-mounted accessories indicated on the drawings that require support.

Page 9: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM 09 21 16 UMPQUA COMMUNITY COLLEGE GYPSUM BOARD ASSEMBLIES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 9 OF 12

ADDENDUM 2 | Issue Date: 17 MAY 2017

3.4 ACOUSTIC ACCESSORIES INSTALLATION

A. Acoustic Insulation: Place tightly within spaces, around cut openings, behind and around electrical and mechanical items within partitions, and tight to items passing through partitions. 1. Tape black acoustic insulation joints with same color, and as recommended by

insulation manufacturer. Joints shall be located behind wall and ceiling finishes such that they are not visible.

B. STC-Rated Assemblies: Seal construction at perimeters, behind control and expansion joints, and at openings and penetrations with a continuous bead of acoustical sealant. Install acoustical sealant at both faces of partitions at perimeters and through penetrations. Comply with ASTM C 919 and manufacturer's written recommendations for locating edge trim and closing off sound-flanking paths around or through gypsum board assemblies, including sealing partitions above acoustical ceilings.

C. Acoustic Sealant: Install in accordance with manufacturer's instructions. 1. Place one bead continuously on substrate before installation of perimeter framing

members. 2. Place continuous bead at perimeter of each layer of gypsum board. 3. Seal around all penetrations by conduit, pipe, ducts, and rough-in boxes, except where

firestopping is provided.

3.5 BOARD INSTALLATION

A. Comply with ASTM C840, GA-216, and manufacturer's instructions. Install to minimize butt end joints, especially in highly visible locations.

B. Water-Resistant Gypsum Backing Board: Install at showers, tubs, and where indicated. Install with 1/4-inch (6.4-mm) gap where panels abut other construction or penetrations.

C. Single-Layer Non-Rated: Install gypsum board perpendicular to framing, with ends and edges occurring over firm bearing. 1. Exception: Tapered edges to receive joint treatment at right angles to framing.

D. Double-Layer Non-Rated: Use gypsum board for first layer, placed parallel to framing or furring members, with ends and edges occurring over firm bearing. Place second layer perpendicular to framing or furring members. Offset joints of second layer from joints of first layer.

E. Exterior Soffits: Install exterior soffit board perpendicular to framing, with staggered end joints over framing members or other solid backing. 1. Seal joints, cut edges, and holes with water resistant sealant.

F. Cementitious Backing Board: Install over wood framing members and rain screen clips where indicated, in accordance with ANSI A108.11 and manufacturer's instructions.

G. Installation on Metal Framing and Wood Framing: Use screws for attachment of all gypsum board .

H. Installation on Wood Framing: For rated assemblies, comply with requirements of listing authority. For non-rated assemblies, install as follows: 1. Single-Layer Applications: Screw attachment. 2. Double-Layer Application: Install base layer using screws or nails. Install face layer

using adhesive.

Page 10: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM 09 21 16 UMPQUA COMMUNITY COLLEGE GYPSUM BOARD ASSEMBLIES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 10 OF 12

ADDENDUM 2 | Issue Date: 17 MAY 2017

I. Tile Backing Panels: 1. Water-Resistant Gypsum Backing Board: Comply with manufacturer's written

installation instructions and install at locations indicated to recieve tile. Install with 1/4 inch (6.4 mm) gap where panels abut other construction or penetrations.

2. Where tile backing panels abut other types of panels in the same plane, shim surfaces to produce a uniform plane across panel surfaces.

3.6 INSTALLATION OF TRIM AND ACCESSORIES

A. Control Joints: Place control joints consistent with lines of building spaces and as indicated but a minimum of: 1. Not more than 30 feet apart on walls and ceilings over 50 feet long. 2. At exterior soffits, not more than 30 feet apart in both directions.

B. Corner Beads: Install at external corners, using longest practical lengths.

C. Edge Trim: Install at locations where gypsum board abuts dissimilar materials .

3.7 JOINT TREATMENT

A. Glass Mat Faced Gypsum Board and Exterior Glass Mat Faced Sheathing: Use fiberglass joint tape, bedded and finished with chemical hardening type joint compound.

B. Paper Faced Gypsum Board: Use paper joint tape, bedded with ready-mixed vinyl-based joint compound and finished with ready-mixed vinyl-based joint compound.

C. Finish gypsum board in accordance with levels defined in ASTM C840, as follows: 1. Level 5: Walls and ceilings to receive semi-gloss or gloss paint finish and other areas

specifically indicated. 2. Level 4: Walls and ceilings to receive paint finish or wall coverings, unless otherwise

indicated. 3. Level 3: Walls to receive textured wall finish. 4. Level 2: In utility areas, behind cabinetry, and on backing board to receive tile finish. 5. Level 1: Wall areas above finished ceilings, whether or not accessible in the

completed construction. 6. Level 0: Temporary partitions.

D. Tape, fill, and sand exposed joints, edges, and corners to produce smooth surface ready to receive finishes. 1. Feather coats of joint compound so that camber is maximum 1/32 inch. 2. Taping, filling, and sanding is not required at surfaces behind adhesive applied ceramic

tile and fixed cabinetry. 3. Taping, filling and sanding is not required at base layer of double layer applications.

E. Where Level 5 finish is indicated, spray apply high build drywall surfacer over entire surface after joints have been properly treated; achieve a flat and tool-mark free finish.

F. Where Impact-Rated Gypsum Wallboard is specified, spary apply high build drywall surfacer over entire surface after joints have been properly treated; achieve a flat and tool-mark free finish.

G. Fill and finish joints and corners of cementitious backing board as recommended by manufacturer.

Page 11: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM 09 21 16 UMPQUA COMMUNITY COLLEGE GYPSUM BOARD ASSEMBLIES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 11 OF 12

ADDENDUM 2 | Issue Date: 17 MAY 2017

3.8 TOLERANCES

A. Maximum Variation of Finished Gypsum Board Surface from True Flatness: 1/8 inch in 10 feet in any direction.

END OF SECTION

Page 12: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM 09 21 16 UMPQUA COMMUNITY COLLEGE GYPSUM BOARD ASSEMBLIES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 12 OF 12

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 13: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 23 09 50 UMPQUA COMMUNITY COLLEGE SEQUENCE OF OPERATIONS FOR HVAC DDC SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 1 OF 11

PART 1 - GENERAL

1.01 SECTION INCLUDES A. Description of Control Sequences

1.02 WORK INCLUDED

A. The control system will consist of all necessary devices and software to provide the sequences

of operation described herein.

B. Provide custom engineered BAS operating software to perform control sequences specified. Sequence of operations describes major control functions, but does not limit Contractor's responsibility to provide a fully operational automatic control system. Contractor shall provide additional control functions not specifically described herein including time delays, control deadbands, equipment interlocks, equipment sequencing, alarm notification, control functions recommended by equipment manufacturers, or as otherwise required.

1.03 SUBMITTALS

A. Provide submittals for products listed in the Product Table below in accordance with Section

23 05 00 – General HVAC Provisions. Submittal requirements indicated by column number designation as follows: 1. Materials List 2. Catalog Data 3. Product Data 4. Performance Data 5. Wiring Diagrams 6. Shop Drawings 7. Installation Instructions 8. Special Requirement listed herein.

PRODUCT TABLE 1 2 3 4 5 6 7 8

All Products This Section X

B. Special Requirements: Provide a complete written sequence of operations for each system

or subsystem under all modes of operation. Where Contractor proposes any variation to the sequence of operation described hereunder, the Contractor shall specifically highlight the change and describe the reason for the revision.

1.04 DESIGN REQUIREMENTS A. All safety control circuits interlocked with motor starters or VFDs shall be hardwired and shall

function in all operating modes (Automatic, Hand, and Manual Bypass).

B. Control setpoints and parameters listed in control sequences are initial values. Adjust setpoints and control parameters as directed by Engineer to achieved desired environment conditions, optimum system performance, and as recommended by TAB contractor.

C. Control setpoints shall be adjustable from the Operator Workstation without modification of control programming or use of proprietary software. All setpoints which are necessary for normal operation and optimization of system performance as required by Owner shall be adjustable, and shall include, but not limited to: time schedules; temperature, pressure, humidity, and CO2 setpoints, time delay settings, safety sequence setpoints, and alarming parameters.

D. Where BAS network communications are provided to networkable control systems or equipment, Contractor shall configure accessible points for control, monitoring, and alarm as

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 14: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 23 09 50 UMPQUA COMMUNITY COLLEGE SEQUENCE OF OPERATIONS FOR HVAC DDC SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 2 OF 11

required to provide specified sequences and as directed by the Owner’s Authorized Representative for trending and monitoring.

E. All cascade control sequences and closed control loops shall have proportional-integral action and derivative capability, except where approved otherwise.

F. Provide BAS alarm functions and configuration as detailed in plans and specifications, and as directed by Owner’s Authorized Representative. Alarm functions may include: 1. Visual display on workstation graphic 2. Audible alarm at workstation computer 3. Listing in workstation alarm log 4. “Pop-up” alarm notification at workstation computer 5. Dial-out alarm to Owner’s security staff or alarm monitoring service.

PART 2 - PRODUCTS

2.01 HEATING WATER SYSTEM (B-1, HWP-1, HWP-2)

A. General: Replacement Science Building boiler will serve both Science and Snyder Halls. The

boiler system utilizes a primary/secondary configuration. Pumps are constant volume, parallel operation Boiler and boiler pump operation are controlled by packaged boiler controls and by a Boiler Management Panel (BMP) furnished by the boiler manufacturer.

B. Boiler Management Panel (BMP): A central boiler controller will control boiler staging and related functions. The BMP may be either an independent field mounted controller or may be integrated into the controller of an individual boiler. 1. Boiler Plant Enable/Disable:

a. Enable boiler plant if any of the following conditions exist: 1) Outside air temperature is below 40°F. 2) Outside air temperature is below 65°F, any heating water valve is more than 15%

open, and a least one air handler is on. 2. Disable boiler plant if any of the following conditions are true 3. Disable when outside air temperature is above 65oF. 4. All heating coil valves are closed for 10 minutes 5. All air handlers are off.

C. Heating Water Pump Operation: Heating water pumps operate subject to individual on-off-auto switch at motor starters as follows. 1. Auto Position: Operate pumps subject to BAS control sequences whenever Boiler Plant

is enabled. 2. On Position: Override automatic control and start pump. Safety control sequences

enabled. 3. Off Position: Pump off.

D. Heating Water Pump Control: 1. Pumps operate whenever boiler plant is enabled.

E. Boiler Control 1. BAS will send an enable command to the BMP two minutes after the Boiler Plant is

enabled. 2. Once enabled, the BMP shall be enabled for a minimum of 20 minutes. 3. BAS to provide heating water supply temperature setpoint to BMP. 4. Start-up Setpoint: If the outside air temperature is less than 50oF, maintain heating water

setpoint at 140oF for a startup period. Reset startup duration based on outside air temperature. Reset the duration from 0 when the outside air temperature is 50oF to 3 hours when the outside air temperature is 30oF. Setpoints adjustable at workstation heating water system graphic display screen.

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 15: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 23 09 50 UMPQUA COMMUNITY COLLEGE SEQUENCE OF OPERATIONS FOR HVAC DDC SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 3 OF 11

5. Operating Setpoint: After the start-up duration has expired, reset heating water supply temperature setpoint subject to outside air temperature. Initial setpoints shall be 180oF at 30oF and 120oF at 65oF. Setpoints adjustable at workstation heating water system graphic display screen.

6. Boiler package control system and BMP to operate boilers and modulate boiler firing to maintain heating water temperature setpoint. Refer to 23 52 16 – Condensing Boilers.

7. BAS contractor to installed BMP supply temperature transmitter furnished with BMP. BAS contractor to provide communications wiring connection between BAS and BMP.

8. Safety/Emergency Control, Monitoring and Alarming a. Provide emergency stop button at entry to boiler room. Activation will disconnect all

power from boilers and water heaters in accordance with ASME, CSD-1. b. Heating Water System Failure: If the heating water supply temperature is more than

10oF below setpoint for more than 10 minutes, activate Critical Heating Water System Alarm. Maintain alarm until acknowledged by operator. Activate alarm if heating water system is enabled and after a 30-minute start-up delay to allow for system warm-up.

c. Boiler Alarm: Monitor boiler alarm contacts. Display alarm on workstation graphic display.

d. Pump Alarm Mode: If a pump is commanded “on” and the status after a 30 second delay indicates that the pump is off, activate a critical alarm. Maintain alarm until acknowledged by operator.

2.02 HEATING WATER SYSTEM (HWP-3)

A. General: New Science Building boiler will serve both Science and Snyder Halls. The heating

water system utilizes a primary/secondary configuration. Snyder hall is served by a variable flow secondary loop through buried piping. Single pump, HWP-3, is located in existing Science building attic, operates to maintain differential pressure setpoint within Snyder Hall. Maintain 10 psi ΔP on dp transmitter.

B. Heating Water Pump Operation: Heating water pump operates subject to individual on-off-auto switch at VFD as follows. 1. Auto Position: Operate pump subject to BAS control sequences whenever Boiler Plant is

enabled. 2. On Position: Override automatic control and start pump. Safety control sequences

enabled. 3. Off Position: Pump off.

C. Heating Water Pump Control: 1. Start pump on call for heating. Call for heating occurs whenever:

a. Outside air temperature is below 65°F, any heating water valve is more than 15% open, and a least one air handler is on

D. Input/Output Points List 1. Provide all control points required to perform the automatic control sequence described

above, which as a minimum shall include all points listed below. Where BAS points are obtained from packaged equipment, the equipment connection is listed following the point description.

BAS Points List

Equipment Connection

Digital Inputs

HWP-3 status

Digital Outputs

HWP-3 start/stop

Analog Inputs

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 16: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 23 09 50 UMPQUA COMMUNITY COLLEGE SEQUENCE OF OPERATIONS FOR HVAC DDC SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 4 OF 11

Heating water differential pressure

Analog Outputs

HWP-3 speed

2.03 CHILLED WATER SYSTEM

A. General: Existing Science Building chiller will serve both Science and Snyder Halls. The

chilled water system utilizes a primary/secondary configuration. Snyder hall is served by a variable flow secondary loop through buried piping. Single pump, CWP-2, is located in existing Science building attic, operates to maintain differential pressure setpoint within Snyder Hall. Maintain 10 psi ΔP on dp transmitter.

B. Input/Output Points List 1. Provide all control points required to perform the automatic control sequence described

above, which as a minimum shall include all points listed below. Where BAS points are obtained from packaged equipment, the equipment connection is listed following the point description.

BAS Points List

Equipment Connection

Digital Inputs

CWP-2 status

Digital Outputs

CWP-2 start/stop

Analog Inputs

Chilled water differential pressure

Analog Outputs

CWP-2 speed

2.04 DOMESTIC WATER HEATING SYSTEM

A. Pump Control:

1. Operate DWP-1 during occupied periods as defined by BAS occupied mode time schedule whenever the return water temperature is less than 115oF

2. Safety Control, Monitoring, and Alarming: 3. Pump Alarm Mode: If a pump is commanded “on” and the status after a 30 second delay

indicates that the pump is off, activate a critical alarm. Maintain alarm until acknowledged by operator.

B. Input/Output Points List 1. Provide all control points required to perform the automatic control sequence described

above, which as a minimum shall include all points listed below. Where BAS points are obtained from packaged equipment, the equipment connection is listed following the point description.

BAS Points List

Equipment Connection

Digital Inputs

DWP-1 status

Digital Outputs

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 17: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 23 09 50 UMPQUA COMMUNITY COLLEGE SEQUENCE OF OPERATIONS FOR HVAC DDC SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 5 OF 11

DWP-1 start/stop

Analog Inputs

Domestic hot water return temperature

2.05 AIR HANDLING SYSTEMS, AHU-1 & AHU-2

A. General: Variable volume air handling systems, supply fan, return fan, hot water preheat coil,

and chilled water cooling coil. Outside airflow monitor station measures ventilation air quantity.

B. Time Control: Provide optimum start routine to control system operating modes. 1. Occupied Mode: Provide time schedule to define occupied times for each day of the

week and holidays. 2. Warm-up and Cool Down Modes:

a. Provide optimum start routine to calculate system warm-up/cool down duration subject to outside air temperature and space temperatures so that all spaces are at occupied temperature at the occupied start time. Optimum start routines shall use a sophisticated algorithm that monitors historical system performance to accurately predict start-up duration and shall be capable to achieving occupied space temperature in all spaces within 2°F, unless the start-up duration exceeds the maximum start-up duration setpoint. Maximum start-up duration shall be adjustable and initially set to 2 hours.

C. Unoccupied Mode:

1. Mode Control: Enable during unoccupied period in accordance with Time Control, unless Night Low Limit Mode or Night High Limit is enabled.

2. Fan Operation: Fans off. 3. Damper Control: Close outside air and exhaust air dampers and open return air damper. 4. Control Valves: Closed.

D. Night Low Limit Mode: 1. Mode Control: Enable during unoccupied period if space temperature is below 58oF.

Disable when space temperature is above 62ºF. 2. Fan Operation: Fans on. 3. Fan Speed: Operate in accordance with Fan Speed Control. Limit fan speed to maximum

of 42 hz. 4. Damper Control: Close outside air and exhaust air dampers and open return air damper. 5. Discharge Air Temperature Control:

a. Modulate heating coil control valve to maintain discharge air temperature setpoint of 65ºF.

b. Chilled water valve closed.

E. Night High Limit Mode: 1. Mode Control:

a. Enable during unoccupied periods if any space temperature is above 85oF and the outside air temperature is below 65oF.

b. Disable when all space temperatures are below 80ºF. 2. Fan Operation: Fans on. 3. Fan Speed: Operate in accordance with Fan Speed Control. Limit fan speed to maximum

of 42 hz. 4. Damper Control: Operate in accordance with Discharge Air Temperature Control. 5. Discharge Air Temperature Control:

a. Operate in accordance with Discharge Air Temperature Control. b. Discharge air temperature setpoint 55ºF. c. Chilled water valve closed.

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 18: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 23 09 50 UMPQUA COMMUNITY COLLEGE SEQUENCE OF OPERATIONS FOR HVAC DDC SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 6 OF 11

F. Warm-up/Cool-down Mode: 1. Mode Control: Enable between fan start time and occupancy time in accordance with

Time Control. 2. Fan Operation: Fan on. 3. Fan Speed: Operate in accordance with Fan Speed Control. 4. Damper Control: Operate in accordance with Discharge Air Temperature Control. 5. Discharge Air Temperature Control: 6. Discharge Air Temperature Setpoint and Control:

a. Operate in accordance with Discharge Air Temperature Setpoint and Discharge Air Temperature Control.

b. Chilled water valve closed.

G. Occupied Mode: 1. Mode Control: Enable during occupied period in accordance with Time Control. 2. Fan Operation: Fan on. 3. Fan Speed: Operate in accordance with Fan Speed Control. 4. Damper Control: Operate in accordance with Discharge Air Temperature Control. 5. Discharge Air Temperature Setpoint and Control: Operate in accordance with Discharge

Air Temperature Setpoint and Discharge Air Temperature Control.

H. Motor Control: Operate subject to individual On-Off-Auto switch at motor controller as follows: 1. Auto Position: Operate motor subject to BAS control signal. 2. On Position: Override automatic control and start motor. Safety control sequences

enabled. 3. Off Position: Motor off.

I. Fan Speed Control: 1. Supply Fan: Modulate supply fan speed control to maintain duct static pressure setpoint.

Static pressure setpoint determined by balancing contractor. Sensor locations: a. AHU-1: b. AHU-2:

2. Control discharge air pressure setpoint to maintain the associated terminal unit damper with the greatest open position at 90% cooling loop output. Discharge air pressure setpoint shall be maximum of 1.25 inches’ water column and minimum of 0.30 inches water column.

3. Return Fan: Modulate return fan speed so that the return airflow is equal to the supply airflow minus the total exhaust airflow rate. Building exhaust rate shall be determined from exhaust fan status and airflow measurements.

J. Discharge Air Temperature Setpoint:

1. Modulate discharge air temperature setpoint to maintain space with the greatest cooling demand at 90% cooling loop output. Discharge air temperature setpoint shall be maximum of 68oF and minimum of 55oF.

K. Discharge Air Temperature Control:

1. Modulate outside air dampers and cooling valve in sequence to maintain discharge air temperature setpoint.

2. Maintain a minimum outside air damper position to provide ventilation in accordance with Demand Control Ventilation.

3. Whenever the outside air temperature is greater than the return air temperature minus 2oF, limit maximum outside damper position to maintain ventilation in accordance with Demand Control Ventilation.

4. Outside/relief air and return air dampers shall operate in unison with return damper having an inverse signal from outside/relief air damper.

5. Modulate return/relief air dampers to maintain a constant mixed air plenum pressure. The pressure setpoint shall be equal to the pressure drop from the outdoors to the mixed air plenum when the air handler is operating at design airflow with outside air dampers fully

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 19: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 23 09 50 UMPQUA COMMUNITY COLLEGE SEQUENCE OF OPERATIONS FOR HVAC DDC SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 7 OF 11

open and return air damper full closed plus 0.2 inches w.c.. Pressure setpoint determined by TAB contractor.

6. Modulate heating coil control valve to maintain a minimum supply air temperature of 55oF.

L. Demand Control Ventilation (DCV): 1. Modulate outside air damper minimum position to maintain DCV airflow setpoint. 2. DCV Airflow Setpoint: Modulate setpoint to maintain the following conditions.

a. Maximum supply air CO2 level of 850 ppm. b. Maximum space CO2 level of 1200 ppm.

3. Limit DCV setpoint range between a “Upper Limit” and “Lower Limit” as follows: a. Upper Limit: Minimum outside airflow rate as scheduled on the Drawings. b. Lower Limit: 20% of minimum outside airflow rate as scheduled on the Drawings.

M. Safety/Emergency Control, Monitoring and Alarming

1. Fire Alarm: Shut off fan when the building fire alarm is activated. When alarm signal ends, resume normal operating condition.

2. Smoke Detection: Stop fans when ductwork mounted smoke detector(s) are activated. Electrically interlock to motor controller. Maintain alarm until acknowledged by building operator.

3. Freeze Protection (hardware): Activate freeze protection alarm when supply temperature is less than 36ºF. Stop fans. Associated valves and dampers set to unoccupied mode position. Electrically interlock to fan starter. Manual reset.

4. Freeze Protection (software): Activate freeze protection alarm when supply temperature is less than 40ºF. Stop fans. Associated valves and dampers set to unoccupied mode position, except modulate heating coil control valve to maintain coil leaving air temperature of 60ºF. Automatically attempt re-start three (adjustable) times. If unit stops following third attempt, set and maintain alarms until acknowledged by operator.

5. High Duct Static Pressure: Stop fans and provide high supply duct static pressure alarm when duct pressure exceeds 4.0 inches w.c. Associated valves and dampers set to normal off position. Electrically interlock with supply fan starter. Automatically attempt re-start three (adjustable) times. If unit stops following third attempt, set and maintain alarms until acknowledged by operator.

6. Low Duct Static Pressure: Stop fans and provide low mixed air plenum pressure alarm when plenum pressure is less than –1.0 inches w.c. Associated valves and dampers set to normal off position. Electrically interlock with supply fan starter. Automatically attempt re-start three (adjustable) times. If unit stops following third attempt, set and maintain alarms until acknowledged by operator.

7. Fan Alarm Mode: If fan is commanded “on” and fan status after a 30 second delay indicates that the fan is off, provide a critical alarm. Automatically attempt re-start three (adjustable) times. If unit stops following third attempt, set and maintain alarms until acknowledged by operator.

N. Input / Output Points List:

1. Provide all control points required to perform the automatic control sequence described above, which as a minimum shall include all points listed below. a. Point Communication: All points listed are to be hardwired to BAS controllers, except

where point is identified as being communicated over a BAS network. C = BAS Network Communication.

b. Point Source: All point values shall be obtained from field-mounted control devices, except where the point is identified as being obtained from an equipment control panel. See Drawing Legend or equipment schedules for designation of equipment control panel abbreviation.

BAS Points List

Point Communication

Point Source

Digital Inputs

Supply fan status

Return fan status

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 20: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 23 09 50 UMPQUA COMMUNITY COLLEGE SEQUENCE OF OPERATIONS FOR HVAC DDC SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 8 OF 11

Building fire alarm notification FAP

High duct pressure

Low duct pressure

Freeze protection switch

Digital Outputs

Supply fan start/stop VFD

Return fan start/stop VFD

Analog Inputs

Supply air temperature

Supply fan speed C VFD

Supply fan airflow

Supply duct static pressure

Supply air CO2

Return air temperature

Return fan speed C VFD

Return fan airflow

Mixed air temperature

Mixed air pressure

Outside airflow

Analog Outputs

Supply fan speed VFD

Return fan speed VFD

Heating coil control valve

Chilled water coil control valve

Outside air dampers

Return / relief air damper

2.06 TERMINAL UNITS, AHU-1 & AHU-2

A. Period of Operation

1. Operate terminal unit subject to supply fan status and operating mode. 2. If supply fan on-off-auto switch is positioned on, operate terminal units in occupied period

mode.

B. Unoccupied Period Control: Close terminal unit air damper and reheat valve.

C. Warm-up Mode Control and Night-Low-Limit Control. 1. Modulate damper to maintain maximum heating airflow setpoint. 2. Modulate heating valve to maintain occupied heating temperature setpoint.

D. Night High Limit Mode:

1. Modulate damper to maintain occupied cooling temperature setpoint. 2. Close heating valve.

E. Occupied Mode Control (Temperature Control Only):

1. Cooling Mode: Reheat valve closed. Modulate air damper to maintain occupied cooling space temperature setpoint. At maximum cooling demand, modulate air damper to maintain maximum cooling airflow setpoint. As cooling demand decreases, reduce primary airflow. With no cooling or heating demand, modulate primary air damper to maintain minimum cooling airflow setpoint with reheat valve closed.

2. Heating Mode: Modulate reheat coil control valve to maintain space temperature setpoint. Modulate air damper to maintain minimum cooling airflow setpoint.

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 21: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 23 09 50 UMPQUA COMMUNITY COLLEGE SEQUENCE OF OPERATIONS FOR HVAC DDC SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 9 OF 11

3. Terminal Units: All, except as otherwise noted.

F. Occupied Mode Control (Temperature Control, Occupancy Control): Control terminal units as follows during scheduled occupied periods. Room in-use and not-in-use modes determined by lighting occupancy sensor. 1. Room In-use, Cooling Mode: Reheat valve closed. Modulate air damper to maintain

occupied cooling space temperature setpoint. At maximum cooling demand, modulate air damper to maintain maximum cooling airflow setpoint. As cooling demand decreases, reduce primary airflow. With no cooling or heating demand, modulate primary air damper to maintain minimum cooling airflow setpoint with reheat valve closed.

2. Room In-Use, Heating Mode: Modulate reheat coil control valve to maintain space temperature setpoint. Modulate air damper to maintain minimum cooling airflow setpoint. As heating demand increases, modulate air damper up to maximum scheduled heating airflow.

3. Room Not-In-Use, Cooling Mode: Same as “Room In-Use, Cooling Mode” except increase cooling space temperature setpoint by 2oF.

4. Room Not-In-Use, Heating Mode: Primary air damper closed. Open heating valve and modulate air damper to maintain maximum heating setpoint when space temperature is 2oF below the occupied space heating setpoint.

G. Occupied Mode Control (Temperature Control, Occupancy Control, Demand Based Ventilation Control: Control terminal units as follows during scheduled occupied periods. Room in-use and not-in-use modes determined by space occupancy sensor input, as indicated on Terminal Unit schedule on Drawings. 1. Room In-use, Cooling Mode: Reheat valve closed. Modulate air damper to maintain

occupied cooling space temperature setpoint. At maximum cooling demand, modulate air damper to maintain maximum cooling airflow setpoint. As cooling demand decreases, reduce primary airflow. With no cooling or heating demand, modulate primary air damper to maintain minimum cooling airflow setpoint with reheat valve closed.

2. Room In-Use, Heating Mode: Modulate reheat coil control valve to maintain space temperature setpoint. Modulate air damper to maintain minimum cooling airflow setpoint. As heating demand increases, modulate air damper up to maximum scheduled heating airflow.

3. Room Not-In-Use, Cooling Mode: Same as “Room In-Use, Cooling Mode” except increase cooling space temperature setpoint by 1oF.

4. Room Not-In-Use, Heating Mode: Same as “Room In-Use, Heating Mode” except increase decrease heating space temperature setpoint by 1oF.

5. Between minimum terminal unit flow and 50% of the maximum cooling cfm setpoint to maintain CO2 setpoint of 1200 ppm.

H. Input / Output Points List: 1. Provide all control points required to perform the automatic control sequence described

above, which as a minimum shall include all points listed below. 2. Point Communication: All points listed are to be hardwired to BAS controllers, except

where point is identified as being communicated over a BAS network. C = BAS Network Communication

3. Point Source: All point values shall be obtained from field-mounted control devices, except where the point is identified as being obtained from an equipment control panel. See Drawing Legend or equipment schedules for designation of equipment control panel abbreviation.

BAS Points List

Point Communication

Point Source

Digital Inputs

Space occupancy (where required)

Digital Outputs

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 22: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 23 09 50 UMPQUA COMMUNITY COLLEGE SEQUENCE OF OPERATIONS FOR HVAC DDC SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 10 OF 11

None

Analog Inputs

Space temperature

Space CO2 (where required)

Primary air flow

Discharge air temperature

Analog Outputs

Primary air damper

Heating water valve

Bacnet Communications

Occupancy status C

2.07 UNIT HEATERS, UH-1

A. Space Temperature Control: Start unit heater fan and open heating water control valve when

space temperature is below 60°F. For spaces with multiple unit heaters, control heating water valves and fans in unison.

B. Input/Output Points List

1. Provide all control points required to perform the automatic control sequence described above, which as a minimum shall include all points listed below. Where BAS points are obtained from packaged equipment, the equipment connection is listed following the point description.

BAS Points List

Point Communication

Point Source

Digital Outputs

Fan start/stop

Heating water control valve

Analog Inputs

Space temperature

2.08 EXHAUST FANS

A. General: Exhaust fans interlocked with associated air handling system. BAS opens automatic

isolation damper prior to starting fan, and closes damper after stopping fan for fan systems as indicated below. Fan operation monitored with CT switch, unless otherwise indicated. 1. Interlock with air distribution system or equipment. 2. Operation: Exhaust fan operates whenever associated system is in Occupied Mode. 3. Shutoff Damper: Open damper when fan is on, and close damper when fan is off. 4. Unit: EF-1, AHU-1

B. Space temperature control.

1. Operation: Operate fan whenever associated space temperature is above temperature setpoint of 78°F.

2. Unit: EF-2.

C. Input / Output Points List 1. Provide all control points required to perform the automatic control sequence described

above, which as a minimum shall include all points listed below. Where BAS points are obtained from packaged equipment, the equipment connection is listed following the point description.

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 23: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 23 09 50 UMPQUA COMMUNITY COLLEGE SEQUENCE OF OPERATIONS FOR HVAC DDC SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 11 OF 11

BAS Points List

Point Communication

Point Source

Digital Inputs

EF-1 fan status

EF-2 fan status

Digital Outputs

EF-1 fan start/stop

EF-1 damper open/closed

EF-2 fan start/stop

Analog Input

IT Closet space temperature

PART 3 - EXECUTION

3.01 INSTALLATION

A. Install complete control system including all components, devices, and accessories required

to perform desired sequence of operation. END OF SECTION

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 24: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 26 51 13 UMPQUA COMMUNITY COLLEGE INTERIOR LIGHTING FIXTURES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 1 OF 3

PART 1 - GENERAL

1.01 SECTION INCLUDES

A. This Section includes supply and installation of luminaires, supports and accessories; and supply of plaster frames, trim rings and backboxes for plaster, tile, drywall or concrete ceilings.

1.02 REFERENCE STANDARDS

A. National Electrical Manufacturer's Association (NEMA)

1. NEMA LE1: Fluorescent Luminaires

1.03 COORDINATION

A. Confirm compatibility and interface of other materials with luminaire and ceiling system. Report discrepancies to the Engineer/Architect, and defer ordering until clarified.

B. Supply plaster frames, trim rings and backboxes to other trades.

C. Coordinate with Division 23 to avoid conflicts between luminaires, supports, fittings, and mechanical equipment.

PART 2 - PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. Refer to LUMINAIRE SCHEDULE.

2.02 RECESSED LUMINAIRES

A. Supply recessed luminaire complete with trim type required for ceiling system installed. Before ordering, confirm ceiling construction details and architectural finish for each area.

2.03 PENDANTS/CABLE HANGERS

A. Swivel sockets permitting normal fixture motion and self-adjustment. Adjustable to provide fixture height alignment.

B. One piece, white finish, with matching canopies.

C. Fixtures shall be factory counter-weighted and balanced to provide level hanging. Weights shall not be visible.

D. Cable hangers shall be adjustable for a minimum of 24”.

2.04 LED LUMINAIRES

A. General:

1. LED light fixtures shall be in accordance with IES, NFPA, UL as shown on the Drawings and as specified.

2. LED light fixtures shall be Reduction of Hazardous Substances (RoHS) compliant.

3. LED drivers shall include the following features unless otherwise indicated:

a. Minimum Efficiency: 85% at full load.

b. Minimum Operating Ambient Temperature: -20°C (-4°F).

c. Input Voltage: 120-277V (±10%) at 60 Hz.

d. Integral short circuit, open circuit, and overload protection.

e. Power Factor: ≥ 0.95.

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 25: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 26 51 13 UMPQUA COMMUNITY COLLEGE INTERIOR LIGHTING FIXTURES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 2 OF 3

f. Total Harmonic Distortion: ≤ 20%.

g. 4-wire (0-10VDC voltage controlled) dimming driver.

i. Capable of dimming from 100% to 5% light output and step to 0%. Driver shall respond similarly when raising from 0% to 100%.

h. Driver shall be free from objectionable flicker as measured by flicker index (ANSI/IES RP-16-10).

4. LED modules shall include the following features unless otherwise indicated:

a. Comply with IES LM-79 and LM-80 requirements.

b. Minimum CRI 80 and color temperature 4000˚ K unless otherwise specified in LUMINAIRE SCHEDULE.

c. Minimum Rated Life: 50,000 hours per IES L70.

d. Light output lumens as indicated in the LUMINAIRE SCHEDULE.

B. LED Downlights:

1. Housing, LED driver, and LED module shall be products of the same manufacturer.

C. LED Troffers:

1. LED drivers, modules, and reflector shall be accessible, serviceable, and replaceable from below the ceiling.

2. Housing, LED driver, and LED module shall be products of the same manufacturer.

2.05 CORRELATED COLOR TEMPERATURE (CCT) & COLOR RENDERING INDEX (CRI)

A. Refer to LUMINAIRE SCHEDULE.

PART 3 - EXECUTION

3.01 COORDINATION

A. Refer to Reflected Ceiling Plans for exact locations with respect to ceiling construction.

B. Consult Finish Schedule for ceiling and wall construction and finish.

C. Prior to ordering lighting fixtures, coordinate style of mounting with ceiling construction and trim details for ceiling system finally selected.

3.02 SURFACE MOUNTING

A. Attach with means that will draw fixtures snugly to finished surface without bending or tipping. Twist-on clips with studs not allowed on exposed "T" grid ceilings, except where specified. Support from channel above ceiling framing members with bolt at each corner of fixture.

3.03 PENDANTS

A. Support from structure per paragraph titled “SUPPORT”.

B. Provide steel, stranded safety cable between fixture and structure to support fixture in the event of a pendant breakage.

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 26: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 26 51 13 UMPQUA COMMUNITY COLLEGE INTERIOR LIGHTING FIXTURES SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 3 OF 3

3.04 SUPPORT

A. Suspended ceiling:

1. Positively attach all light fixtures to the suspended ceiling system. The attachment device shall have a capacity of 150% of the lighting fixture weight acting in any direction.

2. Support grid with No. 12 minimum gage hangers attached to the grid members within 3 inches of the corner of each fixture, attached to structure above.

3. Attach two No. 12 minimum hangers from the fixture housing to the structure above. These wires may be slack.

4. Where suspended fixtures do not align with grid, provide “bridging” above grid and support from structure.

5. Support pendent-hung lighting fixtures directly from the structure above with No. 9 minimum wire or approved alternate support.

B. Support all other fixtures from structure by method rated at least five times support weight.

3.05 ACCESS

A. Recessed fixtures shall have code accessible supply. Use reach-through type fixtures in non-accessible ceilings or other suitable means. Coordinate with ceiling installer.

3.06 FIRE RATED CEILINGS

A. Where a ceiling carries a fire rating, recessed fixtures shall carry UL rating for use in protective enclosures. Coordinate installation of protective enclosures to provide sufficient air space for heat dissipation. 3-inch minimum all around.

3.07 CLEAN-UP

A. At time of acceptance, fixtures and lenses shall be clean, with visible labels removed. Touch-up any blemishes.

B. Remove ballast leakage and dispose of cleaning materials in accordance with EPA regulations.

3.08 FIXTURES AS RACEWAYS

A. Code Reference: NEC 410-31

B. Through-Wiring: In continuous rows of fluorescent lighting, a connection to a single point in the row indicates that the branch circuit conductors are to be routed through the fixture wiring compartments and a connection made to each ballast.

3.10 EXTRA STOCK

A. Provide extra replacement LED driver for each fixture type in project. Quantity: 10%. Where a fraction occurs, round up to next larger integer.

END OF SECTION

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 27: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 27 20 00 UMPQUA COMMUNITY COLLEGE VOICE, DATA AND FIBER OPTIC WIRING SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 1 OF 7

PART 1 - GENERAL

1.01 SECTION INCLUDES

A. Furnish and install all materials required for the installation of a Corning Fiber Cables system. Owner will provide all patch cords, cross connect and networking equipment.

B. Furnish and install all labor and materials required for the installation of a voice backbone cabling distribution system. The system is intended to provide for distribution of traditional analog and digital dial tone.

C. Furnish and install all labor and materials required for the installation of a PANDUIT® category 6E cabling system. This horizontal cabling system will provide connectivity from each station outlets.

D. Unless otherwise noted, Owner will provide all patch cords, cross-connects, networking equipment, telephone and monitoring equipment. Close coordination with the Owner will be required.

E. Work described in this section includes all open relay racks in all IDF rooms, all overhead ladder racking for cable routing and support inside all IDF rooms.

1.02 QUALITY ASSURANCE

A. Do all work in accordance with the guidelines published in EIA/TIA standard 568 and 569. Where conflicts exist, the plans and specifications shall take precedence. All manufacturer installation instructions shall be followed.

B. The install system for optic fiber shall be covered by Corning Cable System Corning Extended Warranty Program.

C. The contractor shall have completed Panduit product and installation training. ADD-1 All workers involved in the installation and termination of cable shall have at least two years of experience. No less than 33% of the workers on the job shall have attended a vendor sponsored training program covering installation and termination of cable.

D. Horizontal cabling system shall be provided with a one year system warranty to guarantee end-to-end high performance cabling systems that meet application requirements. The guarantee shall include cable and connectivity components and have one point of contact for all cabling issues. The system shall be warranted for a period of at least one (1) year and will include all labor and materials to correct any defect during warranty period.

1.03 GUARANTEE

A. Guarantee all work against faulty and improper material and workmanship for a minimum period of one (1) year from the date of final written acceptance by Owner, except where guarantee or warranties for longer terms are specified herein.

B. Upon notification of a problem, the warranty provider shall furnish within 48 hours and at no cost to Owner, such labor and materials as are needed to restore system to proper operation.

PART 2 - PRODUCTS

2.01 CATEGORY 6E HORIZONTAL CABLING

A. Category 6e unshielded twisted pair cable: any manufacturer extra headroom.

B. Category 6 Station Jacks: Panduit mini-com TX56 jacks color to match electrical outlet color.

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 28: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 27 20 00 UMPQUA COMMUNITY COLLEGE VOICE, DATA AND FIBER OPTIC WIRING SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 2 OF 7

C. Single gang device plates: Panduit mini-com CFPnXX classic series device plates or CFPnSY for stainless steel device plates, number of jack positions as required. Match color and style of electrical trim.

D. Modular furniture device plates: Panduit mini-com appropriate for modular furniture yet to be selected. This is a coordination issue. Bid shall include modular furniture device plates.

2.02 FIBER OPTIC CABLE

A. All fiber cables shall be of an all dielectric construction.

B. Outdoor Fiber Cable Package

1. Cable must be warranted by the Corning for use in outdoor applications and listed for use in applications requiring a UL listing of CMR or OFNR.

2. Cable must utilize loose buffer tube construction with no more than 12 fibers per buffer tube.

3. Cable must be water blocked, either with construction flooded or gel free with water swellable yarns and tapes.

C. Indoor Fiber Cable Package

1. Cable must fire rated for use in the space it is installed.

2. Individual fiber subunits shall consist of 900 micron tight buffer.

D. Multi Mode Fiber

1. 62.5 micro multi mode fiber cable: Corning 62.5µm/125µm. Attenuation: 3.0 dB/km @ 850 nm; 1.5 dB/km @ 1300 nm. Minimum effective modal bandwidth: 200/500 Mhz/km.

2. Fiber Cassettes: Corning CCH-CS

3. Multi mode ST fiber panels: Corning CCH-CP12-15T 12-fiber ST Panels

4. Multi mode ST connectors: Corning 95-101-52-SP or 3M 6105-B 62.5 micron anaerobic-cure connectors.

E. Single Mode Fiber

1. Cable: Corning SMF28 single mode fiber

2. Finer Cassettes: Corning CCH-CS.

3. 12-Fiber Single Mode Panels Corning CCH-CP12-59

4. 6-Fiber Single mode SC fiber modules pre-loaded with six factory SC/UPC pigtails: Corning CCH-RM06-3C-P03RH

5. 12-Fiber Single mode SC fiber modules pre-loaded with twelve factory SC/UPS pigtails: Corning CCH-RM12-3C-P03RH.

6. Splice Trays: Corning M67-048 tray for 12 single fiber heat shrink fusion splices.

PART 3 - EXECUTION

3.01 GENERAL INSTALLATION

A. The Contractor shall furnish and install all cabling in accordance with these specifications, Manufacturer installation specifications shall take precedence if there is a conflict with this section.

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 29: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 27 20 00 UMPQUA COMMUNITY COLLEGE VOICE, DATA AND FIBER OPTIC WIRING SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 3 OF 7

B. Install each cable as an uninterrupted conductor section between the designated termination points, unless otherwise directed by the cable installation specifications. There shall be no splices or mechanical coupler installed between the cable points of origin and termination except as shown on Drawings and/or specifications.

C. Contractor is responsible for insuring that cable jacket is suitable for the environment in which it is placed, i.e., CM, CMR, CMP rated. Unless otherwise noted on the Drawings, all cable should be assumed to be rated CMR.

D. All cable shall be attached to building structure except as noted below, at intervals not to exceed 5 feet.

E. At the same time cable is pulled into a cable pathway, also install a pull string of appropriate size to facilitate future cable pulls along those pathways.

F. Install “J-hooks” or reusable “o-rings” for horizontal cable support. Coordinate location of support hardware to avoid conflicts with other trades.

G. Provide firestopping at all locations where cables penetrate fire rated surfaces. Materials and methods used shall be acceptable to the code authority having jurisdiction and shall maintain the fire integrity of the wall, floor, or ceiling.

H. Contractor shall closely coordinate and work with the Owner on the construction of racking and panels and termination and routing of the cabling in the telecommunications room, and into the open relay racks.

3.02 HORIZONTAL CATEGORY 6E CABLE INSTALLATION

A. For each data outlet shown in drawing provide 4x4 inch by 2-inch-deep cast Feralloy single or double gang cover threaded hubs. Provide a one inch conduit from box into ceiling space.

B. Unless otherwise specified, each station outlet shall consist of four (4) category 6e cables. Four port device plates shall be loaded with four jacks.

C. No installed category 6e cable shall exceed 90 meters in length.

D. All cables shall be terminated in station jacks, no direct RJ-45 or RJ-11 connections are allowed.

E. Cabling shall be installed with a 3-foot slack loop placed as near to the station outlet as possible. Often this slack loop will be in the space above a drop ceiling where conduit is stubbed from the outlet box.

F. Installation of communications cabling into floor boxes shall be coordinated with the electrical subcontractor. Provide and install appropriate device plates for mounting the jacks in the electrical contractor installed floor boxes.

G. Unless otherwise noted below, the category 6e cabling shall be terminated in category 6e jacks that are mounted into category 6e patch panels. All cables run to a single station device plate shall be terminated on sequential jacks in the patch panels.

3.03 WIRELESS ACCESS POINT CATEGORY 5E CABLE INSTALLATION

A. Please refer to specifications outlined in the above horizontal category 5e cable installation section.

B. Unless otherwise specified, each wireless access station outlet shall consist of four (4) category 5e cables.

C. Where the wireless access point station termination point is above the drop ceiling, the station outlet shall be terminated in a fourport surface housing that is attached to the building structure or basket tray.

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 30: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 27 20 00 UMPQUA COMMUNITY COLLEGE VOICE, DATA AND FIBER OPTIC WIRING SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 4 OF 7

D. Where the wireless access point station termination is on a wall, it shall be mounted in a standard four port single gang device plate.

E. The wireless access point category 5e cabling shall be terminated on the category 5e patch panel system. ADD-1

3.04 FIBER OPTIC CABLE INSTALLATION

A. Manufacturer instructions shall be carefully followed during the installation of fiber optic cable. Particular attention should be paid to pulling tension and bend radius.

B. At least 30ft of slack cable shall be coiled neatly and mounted to the telecommunications backboards using Velcro tie wraps in at each termination point.

C. Each cable shall be individually attached to the respective fiber enclosure by mechanical means. The cables strength member shall be securely attached the cable strain relief bracket in the enclosure.

D. Fiber optic splicing/distribution shall be placed at the top of the left-most rack or cabinet in the IDF when viewed from the front of the rack or cabinet unless otherwise noted on the drawings or in this specification.

E. Indoor Fiber Cable

1. Where routed through tray system, all indoor fiber cable shall be installed in plenum rated inner duct.

2. Inner duct is not required where cable is installed in conduit and that conduit does not contain any other than fiber optic cables. In conduits that are populated with other cabling, inner duct shall be provided and installed.

F. Outdoor Fiber Cable

1. Each intermediate vault shall have 80ft of slack cable coiled and stored neatly.

2. Fanout kits shall be installed on all buffer tubes containing multi mode fiber.

3. Fanout kits are not required for single mode fiber.

G. Multi Mode Fiber Cable

1. Multi mode fiber cable shall be terminated with ST anaerobic-cure connectors.

2. Fiber shall be hand or machine polished according to Corning instructions.

3. Terminated fiber shall be mounted in standard color code order into ST bulkhead panels mounted in the fiber optic enclosures.

H. Single Mode Fiber Cable

1. Single mode fiber cable shall be terminated by fusion splicing factory SC/UPC pigtails modules onto the backbone cabling.

2. The fiber count in the SC/UPC pigtail modules shall be matched to the fiber count in the cabling being terminated.

a. If a cable has 6 single mode fibers, then a 6-fiber pigtail module shall be used to terminate that cable.

b. If a cable has 12 or multiples of 12 single mode fibers, then 12-fiber pigtail modules shall be used to terminate that cable.

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 31: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 27 20 00 UMPQUA COMMUNITY COLLEGE VOICE, DATA AND FIBER OPTIC WIRING SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 5 OF 7

3. Fiber slack of buffer tubes or indoor fiber sub-units shall be neatly coiled within the fiber splice enclosure. No slack loops of buffer tubes shall be allowed in the cabinet or on the relay rack.

4. Each fiber cable shall be stripped to expose the 6 or 12-fiber sub units or buffer tubes upon entering the fiber splice enclosure and the sub units or buffer tubes routed to the splice tray.

5. A maximum of 12 strands of fiber shall be spliced in each tray and no more than one cable shall be spliced in a tray, which means that some trays will only contain 6 splices.

3.05 IDENTIFICATION

A. Horizontal Category 6e Cable Identification

1. Each category 6e cable shall be assigned a unique cable ID that is constructed out of the following:

a. The three-digit building number.

b. The IDF identification that the cable terminates in.

c. The 4-digit cable number. Each cable pulled to IDF A (telecom closet) shall be numbered sequentially starting at 001 and increasing for each cable pulled to that IDF.

2. For example, the label for the 92nd cable run to IDF A in building 16 shall have cable ID 016A0092. Coordinate with owner for designated building number.

B. Device Plate Identification

1. Each device plate shall be labeled as follows:

a. At the top of the device plate, the building number and IDF letter (for example, every device plate with conductors run to IDF B in building 16 shall have 016A at the top of the device plate).

b. Under each individual jack, the 4-digit cable number.

2. All jacks in a single device plate must have sequential cable numbers.

3. Device plate labeling shall be typewritten label tape with industrial strength adhesive.

4. For cables that are not terminated in device plate or surface mount box, identify with a label equivalent to horizontal cable identification.

C. Patch Panel Identification (Horizontal Category 6e)

1. Each group of four sequential jacks representing a typical device plate in the category 6e panels must be labeled with the room number that the device plate resides in. This room number must be the permanent room numbers assigned by the Owner, not the construction room numbers. The room designation shall be placed above the jacks in the panel.

2. Below each jack in every patch panel, the 4-digit cable number representing that jack. All cable numbers in all patch panels must be sequential.

3. Label shall be typewritten label tape, 3/8-inch-wide with industrial strength adhesive.

3.06 TERMINATION HARDWARE

A. Quantities of termination blocks, racks, splice enclosures, and patch panels, etc. shown on Drawings are illustrative only and are meant to indicate the general configuration of the work. The Contractor is responsible for providing the correct quantities of termination

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 32: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 27 20 00 UMPQUA COMMUNITY COLLEGE VOICE, DATA AND FIBER OPTIC WIRING SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 6 OF 7

hardware required to terminate, patch, cross connect, etc. the volume of cable described herein and shown on the Drawings. Rack quantities shall be no less than what is shown on the Drawings.

B. At all times during the construction, the Contractor shall protect the equipment from damage and theft. Equipment shall not be installed until such time as other trades have completed their work in the area.

3.07 TELECOMM ROOMS

A. Contractor is responsible for providing earthquake bracing and support for all racks installed in telecommunications rooms.

B. Each relay rack must have front facing vertical wire management chases installed on each side of the rack.

3.08 CROSS-CONNECT

A. Perform all cross-connects and patching.

B. Furnish cross connect cables and perform all necessary cross-connect and patches as indicated in these specifications. Utilize cross-connect wire, and 25 pair cable as necessary. Cut all cross-connect wire to length, leaving enough slack to form a “3-finger loop”. After completion of work, dress patch cords and cross-connect wire in cable management apparatus. Do not tie-wrap cross-connect wires into bundles. The Contractor is responsible for all cross-connect schedules and documentation to the Owner/Consultant on completion of project. Patch cables shall be same brand as the patch panel jacks.

C. Telecommunication entrance room: Cross-connect all pairs of the “voice” station cable to the “voice” backbone.

3.09 GROUNDING

A. All metallic cable tray, ladder rack, raceways, cable sheath/armor, enclosures, and equipment racks and other conductive surfaces shall be properly bonded to the grounding system. All paint and other coatings shall be removed at all contact surfaces to ensure proper ground.

B. Furnish and install an insulated #6 copper ground wire from all telecommunication rooms to the main building electrical ground point in the main electrical room. Drawing notes indicating a larger size shall take precedence.

C. Ground all cable shields, ducts, connector panels and grounding blocks.

D. All grounding shall be in compliance with the NEC code Article 800, Article 250, as well as EIA/TIA standard 607.

3.10 CABLE TESTING

A. Copper:

1. Visually inspect all cables, cable reels, and shipping cartoons to detect cable damage incurred during shipping and transport. Return visibly damaged items to the manufacturer.

2. Conduct cable testing as described below upon completion of installation. Test fully completed systems only. Piecemeal testing is not acceptable, except by prior written approval from the Architect.

3. After terminating both ends, but before any cross connects are installed, test all UTP voice and data stations cables for attenuation and for near-end cross talk (NEXT) to 100 Mhz. Test all UTP backbone, distribution and patch cable for cable pair/conductor

ADDENDUM 2 | Issue Date: 17 MAY 2017

Page 33: PART 1 GENERAL SECTION INCLUDES 1.2 RELATED …...E. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes; 2014. F. ASTM

MAHLUM SECTION 27 20 00 UMPQUA COMMUNITY COLLEGE VOICE, DATA AND FIBER OPTIC WIRING SNYDER HALL REPLACEMENT

© 2017 Mahlum 100% CONSTRUCTION DOCUMENTS I Issue Date: 21 APRIL 2017 PAGE 7 OF 7

continuity, ground fault, proper cross-connect, shorts, loose connectors, and crossed pairs.

4. Remove all defective cables from pathways system. Do not abandon cables in place.

B. Fiber:

1. Visually inspect all fiber, fiber reels, and shipping cartons to detect cable damage incurred during shipping and transport. Return visibly damaged items to the manufacturer.

2. Conduct fiber testing as described below upon completion of installation. Test fully completed systems only. Piecemeal testing is not acceptable, except by prior written approval from the Architect.

3. After installation of connectors, visually inspect each fiber end-face at 10x magnification. Refinish fibers with visible defects and/or variations in the core area.

4. Perform end-to-end, bi-directional attenuation (loss) test for each fiber strand at 850 nm and 1300nm wave lengths. Conduct tests in accordance with EIA/TIA-526-14, method B and with test instrument manufacturers printed instructions test equipment must have calibration certificate.

5. Demonstrate that measured link loss does not exceed the “worst case” allowable loss, which is the sum of: the connectors loss (based on the number of mated connector pairs at the EIA/TIA-568 maximum allowable loss of 3.75 db/km @ 850nm and 1.5dB/km @ 1300nm).

6. Strands whose measured attenuation falls outside the acceptable range shall be subject to further inspection and testing to determine the nature of the fault. At a minimum, an OTDR shall be used to determine the true loss for each connector pair, the exact length of the fiber, and to identify the presence of any core damage.

7. Faults related to connectorization shall be corrected, and the fiber re-tested as stated in the paragraph above until acceptable attenuation measurements are recorded.

8. Where defects are found to be inherent in the fiber itself, fiber must be removed and replaced. Also, replace any cable having fewer than the manufacturers guarantee number of serviceable fibers.

9. Remove all defective cables from pathways system. Do not abandon cables in place.

10. The Architect reserves the right to observe the conduct of any or all portions of the testing process.

11. All test results and corrective procedures are to be documented and submitted to the Owner within fourteen (14) working days of test completion.

3.11 ACCEPTANCE

A. Upon receipt of the Contractor’s documentation of cable testing, the Architect will review the installation and may request a retest using contractor equipment and labor, of up to 5% of the cable/wires installed.

END OF SECTION

ADDENDUM 2 | Issue Date: 17 MAY 2017