Upload
others
View
6
Download
0
Embed Size (px)
Citation preview
Parameterization of Reactive Power Characteristics for Distributed
Generators: Field Experience and Recommendations
M. Kraiczy1, G. Lammert2, T. Stetz1, S. Gehler2, G. Arnold1, M. Braun1, 2, S. Schmidt3, H. Homeyer4, U. Zickler5, F. Sommerwerk5,
C. Elbs6
(1) Fraunhofer IWES, Königstor 59, 34119 Kassel, Germany
Phone +49(0)561/7294-268, Fax +49(0)561/7294-400, E-Mail: [email protected]
(2) University of Kassel, Kassel, Germany
(3) Bayernwerk AG, Regensburg, Germany
(4) Avacon AG, Salzgitter, Germany
(5) TEN Thüringer Energienetze GmbH, Erfurt, Germany
(6) Vorarlberger Energienetze GmbH, Bregenz, Austria
Abstract This paper presents recommendations for an effective commissioning and operation of distributed generators (DGs),
focussing on the aspect of reactive power control for static voltage support. Error-sensitive tasks in the process chain
from commissioning to operation are revealed, based on first-hand field experience of major German and Austrian dis-
tribution grid operators. The evaluation shows that the share of DGs, which currently cannot be operated in compliance
with the requirements of relevant grid codes and guidelines, is noticeable. The issues and challenges related to grid code
compliant DG operation are multilateral. For example the parameterization of reactive power controllers turned out to
be an error-sensitive task, due to the diversity of manufacturer-specific GUIs and the lack of clear parameter definitions.
Different, typical DG parameterization errors are categorized and measurement examples from the field are presented.
Furthermore, the impact of non-grid code compliant parameterizations of DGs on the distribution grid operation is dis-
cussed. As a consequence, the authors recommend founding a European, industry-driven working group for defining
binding parameter definitions and further commissioning standards.
1 Introduction
Reactive power control by distributed generators (DGs)
has been identified as an effective measure for maintain-
ing service voltages of distribution grids within its limita-
tion. Recent studies showed that reactive power control
by DGs can be used by the distribution grid operator
(DSO) for static voltage support and hence for avoiding
or delaying extensive grid reinforcement measures (e.g.
[1], [2]). As of today, reactive power control capabilities
are generally required from DGs in accordance to several
European and national grid codes (see Section 2). This
paper presents field experience on reactive power control
by DGs from the perspective of major German and Aus-
trian distribution grid operators, focussing on non-grid
code compliant DG operation and their origins. The au-
thors neither question the positive effect of decentralized
reactive power provision on the grid voltage nor its ap-
plicability in the field. On the contrary, by revealing typi-
cal error-sensitive tasks, the authors would like to con-
tribute to improve the general acceptance of decentralized
reactive power provision by DGs.
The aim of this paper is to improve the reader’s awareness
for various challenges that might occur during the design,
parameterization and operation process of DGs, which
can pave the way for non-grid code compliant DG reac-
tive power provision. In this context the paper addresses
the following aspects:
Introduction to the present DG commissioning process
according to the present regulatory framework and the
practical parameterization of a DG’s reactive power
controller
Discussion of different error-sensitive tasks within the
DG design, parameterization and operation process
Discussion of consequences of a non-grid code com-
pliant DG operation for the grid operation
Recommendations for an improved utilization of de-
centralized reactive provision
First, an overview on the regulatory framework for DG
reactive power provision with the focus on the German
and Austrian distribution grid is presented in Section 2.
The error types of a non-grid code compliant DG parame-
terization are categorized and measurement samples from
the field are presented in Section 3. The consequences of
a non-grid code compliant DG operation for the grid op-
eration are analysed and discussed in Section 4. In Section
5, the potential of an improved utilization of decentralized
reactive power provision is discussed and recommenda-
tions are derived. Finally, the conclusions are presented.
2 Regulatory framework and prac-
tical implementation of DG reac-
tive power control
This Section gives a brief overview on the regulatory
framework of DG reactive power provision (Section 2.1)
and the DG commissioning process (Section 2.2). In Sec-
© 2015 Power Engineering Society in the VDE (ETG) .
ETG-Fb. 147: International ETG Congress 2015
tion 2.3 typical error sources in the DG design, parameter-
ization and operation process are discussed.
2.1 DG reactive power provision
The regulatory framework for DG reactive power control
comprises general technical guidelines and grid codes,
which specify general reactive power requirements for
DGs. Table 1 gives an overview on such currently appli-
cable grid codes and guidelines. These general require-
ments are usually complemented by specifications on pa-
rameter settings (e.g., for cosϕ(P)- or Q(U)-
characteristics), defined by the technical guidelines of the
respective DSOs (e.g. [8] - [11]). Due to the heterogene-
ous structure of distribution grids and the different grid
operation philosophies of DSOs, the specifications for
DGs reactive power control can vary significantly be-
tween DSOs. Figure 1 exemplary shows different reactive
power control characteristics, as currently required by
chosen German DSOs. The characteristics can differ re-
garding the absolute set values (e.g. Q, U, P, and cosϕ),
the number of set points, the dead-band or a hysteresis
function. Furthermore, the required dynamic behaviour of
DG reactive power control can differ (e.g. response time).
Figure 1 Examples of different Q(U) characteristics for MV
DGs (left) and different cosϕ(P) characteristics for LV DGs
(right); examples according DSO 1 [8], DSO 2 [9], DSO 3 [10],
DSO 4 [11] and VDE-AR-N 4105 [4]
2.2 Commissioning process of DGs
The commissioning procedure varies between voltage
levels, DSO, DG type, the date of commissioning and the
country. This Section gives a brief overview on the DG
commissioning process according to the presently applied
general grid codes and guidelines in Germany. Figure 2
shows an example of the timeline and relevant certificates
and verifications for the DG interconnection with the pub-
lic MV grid in Germany. Different certificates and proofs
have to be delivered to the respective DSO for the DG in-
terconnection with the public grid. The certificates are
verified by independent accredited certification authori-
ties and are based on laboratory tests and verified simula-
tion models of the DG unit/plant. Detailed information’s
about the DG certification procedure in Germany are giv-
en in the FGW technical guidelines [12], [13]. Different
types of DG certificates are required for the DG intercon-
nection with the public grid:
The unit certificate specifies the electrical properties
and proofs the conformity of single DG units (e.g.
photovoltaic (PV) inverter) with the respective guide-
line. The certificate is required for high voltage (HV)
DGs [5] and medium voltage (MV) DGs [3].
The plant certificate also includes the internal DG
plant components (e.g. plant transformer, cables) and
proofs the conformity of the entire DG plant at the
network connection point (NCP) with the respective
guideline. The certificate is required for HV DG [5]
and large MV DG (with a maximum apparent connec-
tion power SA > 1 MVA or line length from the NCP
to the generation unit(s) > 2 km) [3]
Application DG unit
Network compatibility
test
Network connectionacceptance
Network connection
contract
Unit Certificate
Plant certificate
DG owner/ installer
DSO
DG installation
DG Start-upDG parameterization
DG functional test
Conformity declaration
Initial start-up records
May request additional proofs or functional test for reactive
power control of DG
DG grid operation
t
Figure 2 Illustrative timeline with relevant verification and cer-
tificates for the interconnection of a MV DG in Germany
The DG parameterization and functional test in the field is
not part of these certificates. The parameterization of DG
reactive power control in the field is usually performed by
the DG installation company or another specialist compa-
ny. In some cases, the DG reactive power control is pre-
defined by the DG manufacturer using a standard reactive
power characteristic. For the initial start-up of the DG
unit/plant a conformity declaration is required. The con-
formity declaration determines that the DG unit/plant is
designed and configured according to the relevant certifi-
cates and guidelines, which consider the requirements of
the respective DSO. The FGW technical guideline Part 8
(FGW TR8) [13] specifies the certification procedure of
DG units/plants in the extra high voltage, high voltage
and medium voltage level. According [13] the conformity
declaration has to be ratified by an accredited certification
authority, an independent expert or a specialised company
with knowledge of the DG unit/plant. According the new
VDE-AR-N 4120 [5] the conformity declaration in the
HV level has to be ratified by an accredited certification
authority. In the LV level the conformity declaration is
usually provided by the DG manufacturer. However this
conformity declaration in the LV level does not necessari-
ly include the requirements of the respective DSOs. The
necessity of functional test of the DG reactive power con-
trol also depends on the voltage level of the interconnec-
tion. At HV level, the new VDE-AR-N 4120 [5] defines
functional tests of the DG reactive power control in the
field. At MV level, the respective DSO may define func-
tional tests of DG reactive power control in the field (e.g.
[14]). At LV level, functional tests of DG reactive power
control are usually not applied.
This Section gives a brief overview of the DG commis-
sioning process in the presently applied grid codes and
guidelines in Germany. For DG units/plants, which were
installed in the past years in Germany, the commission
process may differ significantly.
Grid Code Scope Control Modes Reactive Power Capability* Dynamics*
VDE-AR-N 4120
(01/2015) [5]
High voltage
(HV) (Germany)
Qfix, Q(U), Q(P),
cosϕfix, remote con-
trol
Different operating ranges
specified by the DSO
Q(U): response time between
5 s to 60 s
Qremote and Q(P): settling time
max. 4 min
BDEW Technical
Guideline MV DG
(06/2008) [3]
Medium voltage
(MV) (Germany) Qfix, Q(U), cosϕfix,
cosϕ(P), remote
control
cosϕ = 0.95underexcited to
0.95overexcited
cosϕ(P): target value with-
in 10 s
Q(U): target value within 10 s
to 60 s
TOR D4 (09/2013)
[6]
Medium voltage
and low voltage
(LV) (Austria)
Qfix, Q(U), cosϕfix,
cosϕ(P), remote
control (MV DG)
MV DG: see BDEW Tech-
nical Guideline MV
LV DG: see VDE AR-N-4105
-
VDE AR-N-4105
(08/2011) [4]
Low voltage (LV)
(Germany) cosϕfix,
cosϕ(P), Q(U)**
cosϕ = 0.95/0.9underexcited to
0.95/0.9overexcited
cosϕ(P): target value with-
in 10 s
DIN EN 50438
(06/2014) [7]
Low voltage DG
with IN ≤ 16A per
Phase (Europe)
Q(U), cosϕfix,
cosϕ(P)
cosϕ = 0.9underexcited to
0.9overexcited
Q(U): First order filter, time
constant: 3 s to 60 s.
Table 1: Overview of selected general grid codes and guidelines for DG interconnection with the public grid (* requirements partly
simplified; **in VDE AR-N-4105: Q(U) noted as a possible future characteristic)
2.3 Typical error sources of DG reactive
power provision during commission-
ing and operation
The implementation of DG reactive power control ac-
cording to the relevant grid codes and guidelines faces
various challenges in the field. These challenges are:
Large number of different DG types and manufac-
turers: high diversity of user interfaces for the pa-
rameterization of DG reactive power control
Large number of DSOs (e.g. in Germany approxi-
mately 850): the settings of the DG reactive power
control can vary significantly between the DSOs
(see for example Figure 1)
Large number of DG planning, installation and op-
eration companies with a different technical back-
ground
Full verification of the DG reactive power control
in the field is time consuming and sometimes dif-
ficult (e.g. test of Q(U)-functionality).
The typical error sources are separated between errors in
the DG parameterization process and errors in the DG
design process or during grid operation.
2.3.1 DG parameterization process
The diversity of manufacturer dependent user interfaces
is one major source for reactive power parameterization
errors. The following list gives an example for the di-
versity of parameter values, needed to configure the
Q(U) characteristic of LV PV inverters from different
manufacturers (see also [15]):
Voltage:
o Input value in [V]
o Input value in [%] or [p.u.]
Reactive power:
o Sign of reactive power not standardized
o Input value in [%] of Smax
o Input value in [%] of Qmax
o Input value in [%] of Pmax
o Input value in [kvar]
Reactive power per phase
Total reactive power
o Input value maximum cosϕ
Dynamic behaviour:
o Sometimes no setting options available
o Often no precise instruction
This list illustrates that the manual configuration of the
DG reactive power control can be very challenging in
the field. Therefore, DG installation companies have to
be trained for the relevant guidelines and for different
DG types to avoid parameterization errors in the field.
Furthermore, it is required, that the DG manufacturer
comprehensively describes the procedure for the DG
reactive power configuration. Other sources of error in
the DG parameterization process are:
Application of an outdated guideline
Misinterpretation of the relevant guidelines
Takeover of a pre-defined DG standard configura-
tion (e.g. standard cosϕ(P) characteristic according
VDE-AR-N 4105), which is not required by the re-
spective DSO
Inattention in the DG parameterization process
2.3.2 DG design process or grid operation
Error sources in the DG reactive power provision can
also occur in the DG design process or during the DG
grid operation. Examples of errors sources are:
The DG unit is technically not capable of provid-
ing the required reactive power characteristic (es-
pecially for existing DGs without unit certificate)
The impedances of the DG plant components are
not sufficiently considered during the planning or
operation of the DG plant (especially for existing
DG without plant certificate)
The requested reactive power is provided at con-
nection terminals of the DG units and not at NCP
of the entire DG plant
Interactions with other DG plant components (e.g.
intrinsic protection devices of DG unit)
Failure of DG unit/plant components (e.g. com-
munication devices)
The described error sources are described more in detail
and with specific examples in the next Section.
3 Field experience – DG reactive
power control
Section 3.1 shows different examples of a non-requested
DG reactive provision in the field. The results are based
on measurement samples from different DSOs. The rel-
evance and the validity of the findings are discussed in
Section 3.2.
3.1 Examples of a non-requested DG reac-
tive power provision in the field
In this Section the examples are separated between the
errors in the DG parameterization process and the errors
in the DG design process or during grid operation. Fur-
thermore, an example of the dynamic behaviour of a DG
Q(U) characteristic is analysed in detail.
3.1.1 Error in the DG parameterization process
Different examples of a wrong reactive power configu-
ration have been observed in the field:
No reactive power control applied (cosϕ of 1 in-
stead of required reactive power control)
Wrong control characteristic applied (e.g. cosϕ(P)
instead of a required Q(U)-characteristic)
Wrong set values of the reactive power control ap-
plied (e.g. cosϕ of 0.9 instead of cosϕ of 0.95)
Sign error of the reactive power control (e.g. over-
excited instead of an under-excited operation)
Figure 3 shows a sample measurement, recorded at the
NCP of a MV wind turbine. The wind turbine applies a
fixed power factor of 0.9 (under-excited). However, the
DSO required a fixed power factor of 0.95 (under-
excited), in accordance to the German MV grid code
[3].
Partially, the DG user interfaces do not specify the sign
of reactive power (see also Section 2.3) and sometimes
this is not even indicated in the documentation. This as-
pect can lead to a sign error of the DG reactive power
control (e.g. over-excited instead of under-excited be-
haviour). Figure 4 shows an example of a sign error,
recorded from a MV biogas plant. During operation, a
fixed power factor of 0.95 (under-excited) is requested
by the DSO (red line). However, the DG is operating
with a fixed power factor of 0.95 (over-excited).
Figure 3 Example for wrong set values of the reactive power
control (MV wind turbine, Pmax=800 kW, initial start-up
06/2009)
Figure 4 Example of a direction error of DG reactive power
control ( MV biogas plant, Pmax = 1,2 MW)
3.1.2 Error in the DG design process or during
grid operation
In this category, the DG unit/plant is technically not ca-
pable of providing the required reactive power charac-
teristic at the NCP. The sources of error are multilateral
(see Section 2.3.2). Figure 5 shows an example of an
inaccurate performance of a cosϕ(P)-characteristic of a
MV PV plant at the NCP. The reason for this inaccurate
performance remains vague, it might be caused by tech-
nical constrains of the PV inverters.
Figure 6 illustrates the challenge of a grid code compli-
ant reactive power provision of large DG plants. The
requirements of the DG reactive power provision are
specified for the NCP in the HV [5] and MV grid [3]. In
the LV grid the requirements are specified for the con-
nection terminals of the DG unit [4]. The plant equip-
ment (cables, transformers etc.) can lead to a mismatch
between the operation points of the single DG units and
the operation points of the entire DG plant at the NCP
(Figure 6, bottom). A simple adoption of the required
control characteristic by the DG units, without consider-
ation of the DG plant equipment, will lead to insuffi-
cient results in many cases [16]. Different solutions for
this behaviour are analysed in [16].
Figure 5 Example of an inaccurate performance of a cosϕ(P)-
characteristic (MV PV plant, Pmax = 354 kW, initial start-up
03/2010)
LV plantimpedance
MV plantimpedance
Plant transformer
Public MV grid
NCP
DG unitDG plant
=
~
PV inverters
=
~
Inverter connection pointNetwork connection point
Reacitve power [p.u.]
Aci
tve
po
wer
[p
.u.]
0.2
0.4
0.6
0.8
1.0
0 0.2 0.4-0.4 -0.2
Figure 6 Example of MV PV plant (top) and the typical PQ
operating range (bottom) at the Inverter and the NCP (genera-
tor reference-arrow system) (own diagram based on [16])
In some cases a tripping of the overvoltage protection of
DG units has been observed in the field, whereat the
voltage at the NCP was within the specified limits. The
protection devices even trip before the DG reactive
power provision (e.g. Q(U)-characteristic) is fully acti-
vated. The intrinsic protection of the DG unit can trip
because of relevant internal DG plant impedance and
high voltages at DG unit connection terminals. Howev-
er, the intrinsic protection should not undermine the re-
quirements of the relevant guidelines (at MV-level
[21]).
In the HV and MV grid the reactive power provision of
the DG units/plants can be adjusted by the DSO via re-
mote control (see Section 2.1). However, in a noticeable
number of cases a failure in the communication system
of the DG unit/plant avoids a remote control by the
DSO.
In other examples the DG units/plants shows a non-
compliant DG reactive power control after a firmware
update by the DG manufacturer, whereat the update
overwrite the tested and verified DG configurations.
Furthermore, problems have been observed after the ex-
change of DG plant components (e.g. PV inverters),
whereat the DG parameterization and tests were not ad-
equately repeated by the DG installation company.
3.1.3 Detailed example - dynamic behaviour of
a Q(U) characteristic
The configuration of the dynamic behavior of the Q(U)
characteristic is an error-sensitive task, which concerns
the DG design, parameterization and operation process.
The dynamic behavior is limited by technical constrains
of the DG unit/plant (e.g. measurement dead-time, con-
trol cycles). Section 2.3 shows that in the DG user inter-
face sometimes no dynamic setting options are available
or that the configuration is not precisely instructed.
In several studies (e.g. [17] - [19]) the stability of a
closed loop voltage control (Q(U)-characteristic) by DG
systems is analyzed. The stability of the Q(U)-control
depends on the NCP characteristics (short-circuit power,
R/X-ratio) and the settings of the Q(U)-controller (gain,
measurement dead-time, filter settings). For a secure
and stable operation of a Q(U)-characteristic a first or-
der filter (PT1-behaviour) with a sufficient time con-
stant is suggested in [18] and [19]. However, most gen-
eral grid codes and guidelines do not define the step re-
sponse sufficiently. For example, the German MV
guideline describes the required dynamic behaviour of
reactive power settings as “adjustable between 10 sec-
onds and 1 minute for the Q(U)-characteristic“ [3]. The
EN 50438 is already more precise as it describes the re-
quired dynamic behaviour of the Q(U)-characteristic
with a first order filter and a time constant between
τ = 3 s to τ = 60 s (see Table 1). However, important
parameters, such as the actual voltage measurement val-
ue (3 phase, 1 phase, average values or actual values
etc.) and the maximum dead-time T between voltage
measurement and the change of the operation point need
to be defined, too.
For a stable operation of the Q(U)-characteristic the
time constant τ of the reactive power control should be
sufficiently larger than the dead-time T of the reactive
power control [18]. A detailed description of the stabil-
ity analysis of the Q(U)-characteristics is given in [18].
Figure 7 shows the Q(U)- step responses resulting from
an a) unfavourable plant design and controller-
parameterization (left, extreme dead-time between
measurement and change of operation point, very high
gain, no filtering) and b) a more reasonable implementa-
tion. According to recent studies (e.g. [18], [19]), the
dynamic behavior of the first PV system (Figure 7, left)
can be inappropriate for the voltage stability within the
distribution grid. The second PV system (Figure 7,
right) instead clearly shows the recommended dynamic
behavior using a first order filter with a relevant time
constant τ whilst having a relatively small dead-time T.
Figure 7 Example of an unrecommended Q(U) step response
(left, MV PV, Pmax=665 kW, initial start-up 08/2011) and a
recommed Q(U) step response (right, MV PV, Pmax=621 kW,
initial start-up 07/2010).
3.2 Discussion of the given examples
Section 3 discusses different examples of a non-grid
code compliant DG reactive power control in the field.
The results are based on measurement samples from dif-
ferent DSOs. The frequency and relevance of the errors
differs per voltage level, DG type, DSO, region and date
of the initial start-up of the plant. Although the follow-
ing statistics cannot be considered as representative,
they clearly show that a non- grid code compliant DG
unit/plant operation might occur if the plants functional-
ity is not thoroughly checked during commissioning
and/or after reconfigurations. The base population co-
vers 186 DG systems (HV DG and MV DG) from with-
in the service of one particular DSO. The test is per-
formed via remote control by the DSO. The DSO re-
quests an active power curtailment and a reactive power
target value by the DG unit/plant. The measurements
reveal that:
84 DGs show requested behaviour
62 DGs show deficits
40 DGs with failure in the communication
(no tests possible)
For approximately 30 % of the 62 DG systems with def-
icits, an error with the reactive power control was ob-
served. Other frequently observed deficits concern the
active power curtailment or incorrect measurements by
the DG units/plants.
4 Impact of DG parameterization
errors on grid operation
This Section gives an overview of the consequences of
DG parameterization errors for the operation of distribu-
tion grids. The consequences cover different topics,
such as:
Voltage quality
Loading of grid assets and losses
Protection system
4.1 Voltage quality
The aim of reactive power provision by DGs is to sup-
port the voltage in the distribution grid and to keep the
grid voltage within specified limits, which are defined
in DIN EN 50160 [20] for Germany. However, DG pa-
rameterization errors could lead to unpredictable grid
voltages, which worsen the voltage quality of the distri-
bution grid. The worst case scenario for the voltage
quality would be a direction error of the DG reactive
power provision (see Section 3.1.1).
Furthermore, a parameterization error of a closed loop
voltage control (e.g. Q(U) characteristic) could lead to
reactive power and voltage oscillations in the grid.
Therefore recent studies [18], [19] suggest a first order
filter with a sufficient time constant for the Q(U) char-
acteristics (see also Section 3.1.3). In addition, it is con-
ceivable that a sign error of the Q(U) or cosϕ(U) char-
acteristic (see Section 3.1.1) could lead to reactive pow-
er and voltage oscillations in parallel operation with
other voltage regulators or reactive power compensa-
tors.
4.2 Loading of grid assets and losses
In cases, where the reactive power output of DGs is
larger than originally planned by the DSO or the DG
plant designer/operator, the DG parameterization error
can lead to an overloading of grid or DG plant assets.
Due to the increased reactive power flow, the losses of
these components can also increase.
4.3 Protection system
DG parameterization errors may also have an impact on
the protection coordination of the power system. A
wrong parameterization can lead to interferences with
the voltage protection, especially the under and over
voltage function. Due to a wrong parameterization of
DG, e.g., sign error of reactive power provision (see
Section 3.1.1), the voltage protection might trip. This
can lead to disconnection of DGs, consumers or other
grid components. A DG parameterization error can also
lead to interferences with the distance protection. In
case, the DG reactive power provision is larger than ex-
pected, the measured current and voltage values of the
distance protection can lead to an impedance value,
which lies within the protection zone and leads to a trip-
ping signal of the protection system as seen in Figure 8.
Thus, a wrong parameterization might lead to a discon-
nection of lines, busbars or other grid components.
Sreal
Expected Operation Zone of DG
R
XProtectionZone Operation
Zone
R
XProtectionZone
OperationZone
Operation Zone of DG larger then expected
Figure 8: Example: Impact of a DG parameterization error on
the distance protection
5 Improved utilization of decen-
tralized reactive power provision
In an energy system, with increasingly adopted system
responsibility by distributed resources, it is mandatory,
that the DGs operate predictable and according the rele-
vant guidelines and grid codes. The aim of this paper is
to raise the awareness of error-sensitive tasks in the DG
design, parameterization and operation process for DG
plant designers, DG manufacturers, DG installation
companies, DSOs and other relevant parties. The previ-
ous chapters show, that the issues and challenges related
to grid code compliant DG operation are multilateral.
Table 2 shows several ideas for an improved utilization
of decentralized reactive power provision. The ideas in
Table 2 should be discussed by experts of the relevant
parties (e.g. DG plant designer, DSOs, DG manufactur-
er, DG installers). Therefore, an implementation of an
industry-driven working group with the focus on a non-
grid code compliant DG operation is recommended. The
working group can analyse the frequency and relevance
of non-grid code compliant DG operations on a repre-
sentative database and can define binding parameter
definitions and further commissioning standards.
6 Conclusion and outlook
This paper contributes field experience of DG reactive
power control in the German and Austrian distribution
grid and addresses error-sensitive tasks in the DG de-
sign, parameterization and operation process. The au-
thors neither question the positive effect of decentral-
ized reactive power provision on the grid voltage nor its
applicability in the field. However, the paper reveals
that the share of DGs, which currently cannot be operat-
ed in full compliance with the requirements of relevant
grid codes and guidelines, is noticeable. The paper dis-
cussed typical errors sources and shows measurement
samples of non-grid code compliant DG operations in
the field. Furthermore, the impact of a non-grid code
compliant DG operation on the grid operation is dis-
cussed. The examples reveal that a non-grid code com-
pliant DG operation can affect a secure DG plant or grid
operation, which can increase the outage time of DGs,
consumers or grid segments. Finally, an improved utili-
zation of decentralized reactive power provision is dis-
cussed. The paper recommends the implementation of
an industry-driven working group for defining binding
parameter definitions and further commissioning stand-
ards.
Guidelines, grid codes, standards
Further standardization of DG parameterization (e.g. communication interfaces1, input values of DG configuration)
Detailed definition of the required measurement values (e.g. 3 phase, 1 phase, average values or actual values) and
the dynamic behavior of the DG control (esp. Q(U), cosϕ(U)-characteristic)
Clarification of responsibilities, rights and obligations of the relevant parties in case of a non-grid code compliant
DG operation
Certification of DG
DG certification should remain an essential part of the DG commissioning process
Comprehensive analysis of a non-grid code compliant DG operation in the field and a reflection with the DG certi-
fication may identify further improvement potential in the DG certification process
Parameterization of DG
Comprehensive documentation and demonstrative examples2 of the DG configuration by the DG manufacturer
Training programs for DG installation companies about DG configuration for different DG types and guidelines
Long term goal: Automated and/ or semi-automated DG parameterization according variable requirements in the
smart grid
DG start-up and conformity declaration
Further standardization of DG start-up and functional test (e.g. definition of DG standard test procedures)
Discussion and clarification of the qualifications of the responsible person for the conformity declaration
Long term goal: Automated and/ or semi-automated test procedures
Repetitive inspections in DG operation
Firmware updates, exchange of DG components, failure in DG components can cause parameterization errors dur-
ing DG operation and may require repetitive inspections
Discussion and clarification of the regulatory framework for repetitive inspections
Long term goal: Automated and/or semi-automated repetitive inspections Table 2: Ideas for an improved utilization of decentralized reactive power provision
1 Standardized DG unit/plant communication interfaces can simplify the DG configuration and the DG test procedure and can enable an automatic
adoption of the DG unit/ plant configuration due to variable requirements in the smart grid, e.g. standards for DG plug & play (http://sunspec.org) 2 Examples of demonstrative videos of the DG configuration are given by Vorarlberg Netz (http://www.vorarlbergnetz.at/inhalt/at/1163.htm)
Acknowledgement
The authors thank the German Federal Ministry for Economic Affairs and Energy
and the “Forschungszentrum Jülich GmbH
(PTJ)” for the support within the frame-work of the project “HiPePV2” (FKZ:
0325785) and “SmartGridModels” (FKZ:
0325616). The authors are solely responsi-ble for the content of this publication.
References
[1] Deutsche Energie-Agentur GmbH (dena): dena –
Verteilnetzstudie: Ausbau- und Innovationsbedarf
der Stromverteilnetze in Deutschland bis 2030,
Deutsche Energie-Agentur GmbH, Berlin, 2012
[2] Stetz T., Diwold K., Kraiczy M., Geibel D., Schmidt
S., Braun M.: Techno-Economic Assessment Ap-
proach for Autonomous Voltage Control Strategies
in Low Voltage Grids, IEEE Transactions on Smart
Grid TSG-00387-2013, 2014
[3] German association of energy and water industries
(BDEW): Technical Guideline for the Connection
and Parallel Operation of Generator Connected to
the Medium Voltage Network 2008.
[4] German association for electrical, electronic & in-
formation technologies (VDE): Guideline for the
Connection and Parallel Operation of Generation
Units at Low Voltage Level VDE-AR-N 4105, 2011.
[5] German association for electrical, electronic & in-
formation technologies (VDE): Technical require-
ments for the connection and operation of customer
installations to the high voltage network (TAB high
voltage) VDE-AR-N 4120, 2015
[6] Energie-Control Austria: Technische und organisa-
torische Regeln für Betreiber und Benutzer von Net-
zen – Hauptabschnitt D4: Parallelbetrieb von Erzeu-
gungsanlagen mit Verteilernetzen TOR-D4, Wien,
2013
[7] European Committee for Electrotechnical Standardi-
zation (CENELEC): Requirements for micro-
generating plants to be connected in parallel with
public low-voltage distribution networks EN 50438,
2014
[8] LEW-Verteilnetz GmbH: Anschlussbedingungen
Mittelspannung, Augsburg, [Online] Available:
http://www.lew-verteilnetz.de
[9] Bayernwerk AG: Technische Richtlinie Erzeu-
gungsanlagen am Mittelspannungsnetz der Bayern-
werk AG, [Online] Available: https://www.bayern-
werk.de
[10] Netze BW GmbH: Technische Richtlinie Erzeu-
gungsanlagen am Mittelspannungsnetz der Netze
BW GmbH, 2013, [Online] Available:
https://www.netze-bw.de
[11] SWU Netze GmbH: Technische Anschlussbedin-
gungen der SWU-Netze GmbH für Erzeugungsanla-
gen im Netzparallelbetrieb, 2012, [Online] Availab-
le: http://www.ulm-netze.de
[12] Fördergesellschaft Windenenergie und andere
Erneuerbare Energien (FGW): Technical Guidelines
for Power Generation Units, Part 4 – Demands on
Modelling and Validating Simulation Models of the
Electrical Characteristics of Power Generating Units
and Systems, Revision 7, Berlin, 2014
[13] Fördergesellschaft Windenenergie und andere
Erneuerbare Energien (FGW): Technical Guidelines
for Power Generation Units and Farms, Part 8 - Cer-
tification of the Electrical Characteristics of Power
Generating Units and Farms in the Medium-, High-
and Highest-voltage Grid, Revision 6, Berlin, 2013
[14] Bayernwerk AG: Informationen zur Einreichung von
EZA-Konformitätserklärungen für Erzeugungsanla-
gen mit Anschluss am Mittelspannungnetz der Bay-
ernwerk AG, Version 1.5, 2015, , [Online] Availab-
le:
https://www.bayernwerk.de/cps/rde/xbcr/bayernwer
k/2015-02-
01_Information_zur_Einreichung_von_EZA-KE.pdf
[15] Elbs C.: Einführung der Q(U)-Regelung bei Vorarl-
bergnetz und Weiterverteilern, 2014, [Online]
Available:
http://www.vorarlbergnetz.at/downloads/at/2014-06-
06_PV-Wechselrichter_ELBS.pdf
[16] Mende D., Schwarz J., Schmidt S., Premm D. et al.:
Reactive power control of PV plants to increase the
grid hosting capacity, 28. European PV Solar Energy
Conference and Exhibition, Paris, 2013
[17] Elbs C., Nenning R., Pardatscher R., Witzmann R.:
Einsatz der Q(U)-Regelung bei der Vorarlberger
Energienetze GmbH – Endbericht, 2014, [Online]
Available:
http://mediatum.ub.tum.de/doc/1228066/1228066.pd
f
[18] Andrén F., Bletterie B., Kadam S., Kotsampopoulos,
Bucher C.: On the Stability of Local Voltage Control
in Distribution Networks with a High Penetration of
Inverter-Based Generation, DOI
10.1109/TIE.2014.2345347, IEEE Transactions on
Industrial Electronics
[19] Schacht D., Patzack S., Vennegeerts H., Bock C.,
Schmidt S.: Auslegung einer Q(U)-Regelung an Er-
zeugungsanlagen unter Berücksichtigung von Stabi-
litätsaspekten, Zukünftige Stromnetze für Erneuer-
bare Energien, Berlin, 2015
[20] DIN EN 50160: Voltage characteristics of electricity
supplied by public distribution networks, 2011
[21] German association of energy and water industries
(BDEW): Rules and transitional periods for specific
requirements complementary to the technical guide-
line: Generating plants connected to the medium-
voltage network - Guideline for generating plants
connection to and parallel operation with the medi-
um-voltage network, 2013, [Online] Available:
https://www.bdew.de/internet.nsf/id/A2A0475F2FA
E8F44C12578300047C92F/$file/4.%20Erg%C3%A
4nzung%20BDEW-MSR%20final_englisch.pdf